Loading...
HomeMy WebLinkAboutEngineering PILO A ENGINEERING & TESTING., INC. Phone: (8.66)-781-6889•Fax:_(866)'784-8550 `r•ww.floridaengineeringandtesting.com 250 S.W.13"'Avenue Pompano Beach,FL 33069 DATE: 2/16/17 JOB ORDER#: 17-624 CLIENT: All Area Roofing ADDRESS: 3921 S. US Highway 1 Fort Pierce,Florida 34982 PROJECT: Horbacz Residence 26 Gauge 5V Crimp Roof Panel ADDRESS: 63 Flores Del Norte Fort Pierce, Florida FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS Project Information: Mean Height= 15' Max. Exposure: C Basic/Ultimate Wind Speed: V„It=170 mph Length= 62' Category: II Nominal Wind Speed: Vasd=Vi1t*40.6 Width= 25' Slope: 2.4/12= 11° (asd=allowable strength design) Parapet Wall: N/A Residential K,= 0.85, Kzt= 1.0, Kd= 0.85 Design Calculations: Velocity Pressure: q= 0.00256*KZKztKdV2 Velocity Pressure (u1t): q=0.00256(0.85)(1.0)(0.85)(170)2] =53.45 psf Velocity Pressure (asd): q=0.00256(0.85)(1.0)(0.85)(170*40.6)2] = 32.07 psf Width of Pressure Coefficient: 0.1(25') = 2.5' 0.4(15') = 6.0' } use: 3'0" Effective Wind Area: <1 Of 2 External Pressure Coefficient: Internal Pressure Coefficient: 1) GCP 1 = -0.9 1) GCP; = 0.18 2) GCP2 = -1.7 3) GCP3 = -2.6 Design Pressures Based on Vasd: 1) Field P1 = 32.07*[(-0.9)—(0.18)] _-34.6 psf 2) Perimeter P2 = 32.07*[(-1.7)—(0.18)] _-60.3 psf 3) Corners P3 = 32.07*[(-2.6)—(0.18)] _-89.2 psf 1 10C '%-% Qicality��, L� Y.1murance Page 2,2/16/17,Job Orde*-624 All Area Roofing FLO A • Horbacz Residence-26 Gauge 5V Crimp Roof Panel 63 Flores Del Norte; Fort Pierce,FL: Attachment Requirements: Based on the requirements of Florida Product Approval # 11651.12, Table A with maximum design pressures of -108.5psf; the following are our recommended fastening patterns to attach the Gulf Coast Supply 26 ga. 5V Crimp Roof Panel to the minimum 15/32" thick plywood decking utilizing #9-15xl.5" fastener with sealing washing to provide a minimum 1/4" fastener penetration through plywood in the following fastener patterns and these fastener row spacings: Area Field,Perimeter& Corners Maximum Total Uplift Design Pressure -108.5psf Fastener Pattern Panel Ribs (12" o.c.) Fastener Pattern Spacing 12" O.C. *NOTE: Due to roof slope less than 3:12, lap sealant must be used in all panel side laps Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less than a = 3'0" (Zone 2: Perimeter (including along ridges) is a 3'0" wide strip, Zone 3: Corners are 3'0" x 3'0") Contractor to verify that the fastening patterns meet manufacturer's requirements for issuance of a warranty (as applicable). All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and Florida Building Code 2014 Edition. Wind load calculations based on ASCE 7-10, FBC 2014 and information provided by client. Client is responsible for verifying existing conditions as it pertains to the above provided product approval. All work shall be inspected by our field engineer (or authorized representative) or a building department inspector to verify compliance with specifications. Sincerely;..: M�Qe�eCrrf` r `Mark A:,09iano P--E Fl`oricla Engneeriiig_c Testing, Inc. -.al.-Florid a Re o 482b2 . Cer t leate,of Aut`horizat_ion No. 6923 � a. 5�