HomeMy WebLinkAboutIR Spirits Energy Calc SSFlorida Building Code, Sixth Edition (2017) - Energy Conservation EnergyGauge Summit® Fla/Com-2017, Effective Date: Dec 31, 2017 ASHRAE 90.1-2013 - Energy Cost Budget Option Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist The full compliance report generated by the software that contains the project summary, compliance summary, certifications and detailed component compliance reports. The compliance report must include the full input report generated by the software as contigous part of the compliance report. Boxes appropriately checked in the Mandatory Section of the complaince report. WARNING: INPUT REPORT NOT GENERATED. To include input report in final submission, go to the Project Form, Settings Tab and check the box - "Append Input Report to Compliance Output Report" Then rerun your calculation EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 1 of 17 PROJECT SUMMARY Short Desc:IRS Description:2020-0275 Owner:- Address1:3200 N. KINGS HWY.City:FORT PIERCE Address2:-State:FLORIDA Zip:34951 Type:Retail Class:New Finished building Jurisdiction:FORT PIERCE, ST LUCIE COUNTY, FL (661100) Conditioned Area:9662 SF Conditioned & UnConditioned Area:9662 SF No of Stories:1 Area entered from Plans 0 SF Permit No:0 Max Tonnage 10 If different, write in:______________________ EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 2 of 17 ResultCriteriaDesignComponent Compliance Summary Gross Energy Cost (in $) 9,809.0 14,420.0 PASSED LIGHTING CONTROLS PASSES EXTERNAL LIGHTING No Entry HVAC SYSTEM PASSES PLANT No Entry WATER HEATING SYSTEMS PASSES PIPING SYSTEMS No Entry Met all required compliance from Check List?Yes/No/NA IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 3 of 17 CERTIFICATIONS I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________ Building Official: __________________ Date: _________________ Date: __________________ I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________ Date: __________________ If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________ Reg No: __________________ Electrical Designer: BRAD BROWN Reg No: 58232 Lighting Designer: BRAD BROWN Reg No: 58232 Mechanical Designer: BRAD BROWN Reg No: 58232 Plumbing Designer: BRAD BROWN Reg No: 58232 (*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 4 of 17 Project: IRS Title: 2020-0275 Type: Retail (WEA File: FL_ST_LUCIE_CO_INTL.tm3) 612.00 $9,809 612.00 179316 $9,809 44.30 12984 $710 63.80 18693 $1,023 0.10 28 $2 327.10 95839 $5,242 29.90 8756 $479 146.80 43016 $2,353 904.60 $14,420 904.60 265066 $14,420 158.10 46319 $2,520 63.80 18693 $1,017 0.10 28 $2 462.10 135396 $7,366 22.40 6574 $358 198.10 58056 $3,158 Total ELECTRICITY(MBtu/kWh/$) AREA LIGHTS MISC EQUIPMT PUMPS & MISC SPACE COOL SPACE HEAT VENT FANS 2) Baseline1) Proposed Building End Uses Credits Applied: None Passing Criteria = 14420 Design (including any credits) = 9809 Passing requires Proposed Building cost to be at most 100% of Baseline cost. This Proposed Building is at 68% PASSES EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 5 of 17 CLP (W) Area or Length or No. of Units (Sqft or ft) Allowance (W/Unit) CategoryDescription External Lighting Compliance ELPA (W) Tradable? None Project: IRS Title: 2020-0275 Type: Retail (WEA File: FL_ST_LUCIE_CO_INTL.tm3) ComplianceDesign CP Min CP DescriptionAcronym Lighting Controls Compliance Ashrae ID Area (sq.ft) 25,001 Sales Area 459 12 PASSESZONE 1 16 Office - Open Plan 1,106 12 PASSESZONE 2 31,001 Workshop 4,190 22 PASSESZONE 3 31,001 Workshop 3,907 22 PASSESZONE 4 PASSES EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 6 of 17 Project: IRS Title: 2020-0275 Type: Retail (WEA File: FL_ST_LUCIE_CO_INTL.tm3) System Report Compliance AHU 1 ZONE 1 Constant Volume Air Cooled Split System < 65000 Btu/hr Component Category Capacity Design Eff Eff Criteria Design IPLV IPLV Criteria Comp- liance No. of Units 1 Cooling System Air Conditioners Air Cooled Split System < 65000 Btu/h Cooling Capacity 18000 16.00 13.00 8.00 PASSES Heating System Electric Furnace 17105 1.00 1.00 PASSES Air Handling System -Supply Air Handler (Supply) - Constant Volume 600 0.80 0.82 Not Required AHU 2 ZONE 2 Constant Volume Air Cooled Split System < 65000 Btu/hr Component Category Capacity Design Eff Eff Criteria Design IPLV IPLV Criteria Comp- liance No. of Units 1 Cooling System Air Conditioners Air Cooled Split System < 65000 Btu/h Cooling Capacity 34100 16.00 13.00 8.00 PASSES Heating System Electric Furnace 27292 1.00 1.00 PASSES Air Handling System -Supply Air Handler (Supply) - Constant Volume 1200 0.80 0.82 Not Required RTU 1 ZONE 3 Constant Volume Packaged System--902 Component Category Capacity Design Eff Eff Criteria Design IPLV IPLV Criteria Comp- liance No. of Units 1 Cooling System Air Conditioners Air Cooled 65000 to 135000 Btu/h Cooling Capacity 103600 12.20 11.20 12.9012.90 PASSES Heating System Electric Furnace 266136 1.00 1.00 PASSES Air Handling System -Supply Air Handler (Supply) - Constant Volume 3400 0.80 0.82 Not Required EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 7 of 17 RTU 2 ZONE 4 Constant Volume Packaged System--902 Component Category Capacity Design Eff Eff Criteria Design IPLV IPLV Criteria Comp- liance No. of Units 1 Cooling System Air Conditioners Air Cooled 65000 to 135000 Btu/h Cooling Capacity 119500 12.00 11.20 12.9012.90 PASSES Heating System Electric Furnace 266136 1.00 1.00 PASSES Air Handling System -Supply Air Handler (Supply) - Constant Volume 4000 0.80 0.82 Not Required PASSES Comp liance CategoryMin IPLV Min Eff Design IPLV Design Eff SizeInstalled No Description Plant Compliance None Project: IRS Title: 2020-0275 Type: Retail (WEA File: FL_ST_LUCIE_CO_INTL.tm3) Comp liance Design Loss Design Eff Max Loss Min EffCategoryTypeDescription Water Heater Compliance Water Heater 1 Electric water heater <= 12 [kW] 0.960.96 PASSES PASSES EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 8 of 17 Piping System Compliance Category Pipe Dia [inches] Ins Cond [Btu-in/hr .SF.F] Operating Temp [F] Is Runout? Ins Thick [in] Compl- iance Req Ins Thick [in] None EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 9 of 17 Topic Section Component Description Yes N/A Exempt Mandatory Requirements (as applicable)Mandatory requirements compiled by US Department of Energy and Pacific Northwest National Laboratory. Adopted with permission 1. To be checked by Designer or Engineer Insulation 5.8.1.2 Envelope Below-grade wall insulation installed per manufacturer’s instructions. Insulation 5.8.1.2 Envelope Slab edge insulation installed per manufacturerâ €™s instructions. Insulation 5.5.3.5 Envelope Slab edge insulation depth/length. Insulation 6.4.4.1.5 Envelope Bottom surface of floor structures incorporating radiant heating insulated to >=R-3.5. Fenestration 5.5.3.6 Envelope U-factor of opaque doors associated with the building thermal envelope meets requirements. SYSTEM_SPECIFIC 6.5.1, 6.5.1.1, 6.5.1.3, 6.5.1.4 Mechanical Air economizers provided where required (and not exempted), meet the requirements for design capacity, control signal, ventilation controls, high-limit shut-off, integrated economizer control, and provide a means to relieve excess outside air during operation. SYSTEM_SPECIFIC 6.5.1, 6.5.1.2, 6.5.1.3 Mechanical Water economizers provided where required, meet the requirements for design capacity, maximum pressure drop and integrated economizer control. SYSTEM_SPECIFIC 6.5.1.5 Mechanical Economizer operation will not increase heating energy use during normal operation. SYSTEM_SPECIFIC 6.5.2.2.1 Mechanical Three-pipe hydronic systems using a common return for hot and chilled water are not used. SYSTEM_SPECIFIC 6.5.2.2.3 Mechanical Hydronic heat pump systems connected to a common water loop meet heat rejection and heat addition requirements. SYSTEM_SPECIFIC 6.5.1.6 Mechanical Water economizer specified on hydronic cooling and humidification systems designed to maintain inside humidity at >35 ºF dewpoint if an economizer is required. SYSTEM_SPECIFIC 6.5.3.1.1 Mechanical HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp. SYSTEM_SPECIFIC 6.5.3.1.2 Mechanical HVAC fan motors not larger than the first available motor size greater than the bhp. HVAC 6.5.6.1 Mechanical Exhaust air energy recovery on systems meeting Tables 6.5.6.1-1, and 6.5.6.1-2. SYSTEM_SPECIFIC 7.4.2 Mechanical Service water heating equipment meets efficiency requirements. SYSTEM_SPECIFIC 7.5.2 Mechanical Service water heating equipment used for space heating complies with the service water heating equipment requirements. Insulation 5.8.1.2 Envelope Above-grade wall insulation installed per manufacturer’s instructions. Insulation 5.8.1.2 Envelope Floor insulation installed per manufacturer’s instructions. Controls 10.4.3 Mechanical Elevators are designed with the proper lighting, ventilation power, and standby mode. SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7a Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7b Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7c Mechanical Heat Rejection Equipment: Minimum Efficiency RequirementTable 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7d Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 10 of 17 SYSTEM_SPECIFIC 6.5.5.3 Mechanical Centrifugal fan open-circuit cooling towers having combined rated capacity >= 1100 gpm meets minimum efficiency requirement: Table 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7e Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7f Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7g Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7. SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7h Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 SYSTEM_SPECIFIC 6.4.1.1, 6.8.1-7i Mechanical Heat Rejection Equipment: Minimum Efficiency Requirement Table 6.8.1-7 SYSTEM_SPECIFIC 7.5.3 Mechanical Gas-fired water-heating equipment installed in new buildings: where a singular piece of water-heating equipment >= 1,000 kBtu/h serves the entire building, thermal efficiency must be >= 90 Et. Where multiple pieces of water-heating equipment serve the building with combined rating is >= 1,000 kBtu/h, the combined input-capacity-weighted-average thermal efficiency , thermal efficiency must be >= 90 Et. Exclude input rating of equipment in individual dwelling units and equipment <= 100 kBtu/h. 2. To be checked by Plan Reviewer Plan Review 4.2.2, 5.4.3.1.1, 5.7 Envelope Plans and/or specifications provide all information with which compliance can be determined for the building envelope and document where exceptions to the standard are claimed. Plan Review 4.2.2, 6.4.4.2.1, 6.7.2 Mechanical Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical systems and equipment and document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks. Plan Review 4.2.2, 7.7.1, 10.4.2 Mechanical Plans, specifications, and/or calculations provide all information with which compliance can be determined for the service water heating systems and equipment and document where exceptions to the standard are claimed. Hot water system sized per manufacturer's sizing guide. Plan Review 4.2.2, 8.4.1.1, 8.4.1.2, 8.7 Project Plans, specifications, and/or calculations provide all information with which compliance can be determined for the electrical systems and equipment and document where exceptions are claimed. Feeder connectors sized in accordance with approved plans and branch circuits sized for maximum drop of 3%. Plan Review 4.2.2, 9.4.3, 9.7 Interior Lighting Plans, specifications, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Plan Review 9.7 Exterior Lighting Plans, specifications, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Insulation 5.8.1.7.3 Envelope Insulation in contact with the ground has <=0.3% water absorption rate per ASTM C272. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 11 of 17 Air Leakage 5.4.3.4 Envelope Vestibules are installed where building entrances separate conditioned space from the exterior, and meet exterior envelope requirements. Doors have self-closing devices, and are >=7 ft apart (>= 16 ft apart for adjoinging floor area >= 40000 sq.ft.). Vestibule floor area <=7 50 sq.ft. or 2 percent of the adjoining conditioned floor area. HVAC 6.4.3.4.4 Mechanical Ventilation fans >0.75 hp have automatic controls to shut off fan when not required. HVAC 6.4.3.8 Mechanical Demand control ventilation provided for spaces >500 ft2 and >25 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating outside air damper control, or design airflow >3,000 cfm. HVAC 6.4.4.1.4 Mechanical Thermally ineffective panel surfaces of sensible heating panels have insulation >= R-3.5. HVAC 6.5.2.3 Mechanical Dehumidification controls provided to prevent reheating, recooling, mixing of hot and cold airstreams or concurrent heating and cooling of the same airstream. SYSTEM_SPECIFIC 6.5.3.1.3 Mechanical Fans have efficiency grade (FEG) >= 67. The total efficiency of the fan at the design point of operation <= 15% of maximum total efficiency of the fan. SYSTEM_SPECIFIC 6.5.3.5 Mechanical Motors for fans >= 1/12 hp and < 1 hp are electronically-commutated motors or have a minimum motor efficiency of 70%. These motors are also speed adjustable for either balancing or remote control. SYSTEM_SPECIFIC 6.4.3.10 Mechanical DDC system installed and capable of providing control logic including monitoring zone and system demand for fan pressure, pump pressure, heating, and cooling; transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers; automatically detecting and alerting system operator when zones and systems excessively drive the reset logic; allow operator removal of zone(s) from the reset algorithm; AND capable of trending and graphically displaying input and output points. SYSTEM_SPECIFIC 6.5.3.2.3 Mechanical Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Controls provide: zone damper monitoring or indicator of static pressure need; autodetection, alarm, and operator override of zones excessively triggering reset logic. SYSTEM_SPECIFIC 6.5.3.3 Mechanical Multiple zone VAV systems with DDC of individual zone boxes have static pressure setpoint reset controls. SYSTEM_SPECIFIC 6.5.3.4 Mechanical Multiple zone HVAC systems have supply air temperature reset controls. SYSTEM_SPECIFIC 6.5.4.1 Mechanical System turndown requirement met through multiple single-input boilers, one or more modulating boilers, or a combination of single-input and modulating boilers. Boiler input between 1.0 MBtu/h and 5 MBtu/h has 3:1 turndown ratio, boiler input between 5.0 MBtu/h and 10 MBtu/h has 4:1 turndown ratio, boiler input > 10.0 MBtu/h has 5:1 turndown ratio. HVAC 6.5.4.2 Mechanical HVAC pumping systems >10 hp designed for variable fluid flow. SYSTEM_SPECIFIC 6.5.4.3, 6.5.4.3.1, 6.5.4.3.2 Mechanical Fluid flow shutdown in pumping systems to multiple chillers or boilers when systems are shut down. SYSTEM_SPECIFIC 6.5.4.4 Mechanical Temperature reset by representative building loads in pumping systems >10 hp for chiller and boiler systems >300,000 Btu/h. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 12 of 17 SYSTEM_SPECIFIC 6.5.4.5.2 Mechanical Hydronic heat pumps and water-cooled unitary air conditioners with pump systems >5 hp have controls or devices to reduce pump motor demand. SYSTEM_SPECIFIC 6.5.4.6 Mechanical Chilled-water and condenser water piping sized according to design flow rate and total annual hours of operation (Table 6.5.4.6). SYSTEM_SPECIFIC 6.5.5.2.1 Mechanical Fan systems with motors >=7.5 hp associated with heat rejection equipment to have capability to operate at 2/3 of full-speed and auto speed controls to control the leaving fluid temperature or condensing temp/pressure of heat rejection device. SYSTEM_SPECIFIC 6.5.5.2.2 Mechanical Multicell heat rejection equipment with variable-speed fan drives installed that operate the maximum number of fans allowed that comply with manufacturers specs and control all fans to the same fan speed required for the instantaneous cooling duty. SYSTEM_SPECIFIC 6.5.5.2.3 Mechanical NA HVAC 6.5.7.1.1 Mechanical Kitchen hoods >5,000 cfm have make up air >=50% of exhaust air volume. HVAC 6.5.7.1.1 Mechanical Kitchen hoods >5,000 cfm have make up air >=50% of exhaust air volume. SYSTEM_SPECIFIC 6.5.7.1.2 Mechanical Conditioned supply air to space with a kitchen hood shall not exceed the greater of a) supply flow required to meet space heating or cooling, or b) hood exhaust flow minus the available air transfer from available spaces. SYSTEM_SPECIFIC 6.5.7.1.3 Mechanical Kitchen hoods with a total exhaust airflow rate >5000 cfm meet replacement air, ventilation system, or energy recovery requirements shown in Table 6.5.7.1.3. SYSTEM_SPECIFIC 6.5.7.1.4 Mechanical Kitchen hoods with a total exhaust airflow rate >5000 cfm meet replacement air, ventilation system, or energy recovery requirements. HVAC 6.5.7.2 Mechanical Fume hoods exhaust systems >=5,000 cfm have VAV hood exhaust and supply systems, direct make-up air or heat recovery. HVAC 6.5.8.1 Mechanical Unenclosed spaces that are heated use only radiant heat. SYSTEM_SPECIFIC 7.5.1 Mechanical Combined space and water heating system not allowed unless standby loss less than calculated maximum. AHJ has approved or combined connected load <150 kBtu/h. Controls 8.4.2 Project At least 50% of all 125 volt 15- and 20-Amp receptacles are controlled by an automatic control device. Other Equipment 10.4.1 Mechanical Electric motors meet requirements where applicable. HVAC 6.4.3.3.2 Mechanical Setback controls allow automatic restart and temporary operation as required for maintenance. SYSTEM_SPECIFIC 6.4.3.3.3 Mechanical Systems with setback controls and DDC include optimum start controls. Optimum start algorithm considers mass radiant slab floor temperature. SYSTEM_SPECIFIC 6.4.3.3.4 Mechanical Zone isolation devices and controls. Wattage 9.4.2 Exterior Lighting Exterior lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts. 3. To be checked by Inspector Insulation 5.8.1.7 Envelope Exterior insulation protected against damage, sunlight, moisture, wind, landscaping and equipment maintenance activities. HVAC 6.4.3.7 Mechanical Freeze protection and snow/ice melting system sensors for future connection to controls. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 13 of 17 Air Leakage 5.4.3.1 Envelope Continuous air barrier is wrapped, sealed, caulked, gasketed, and/or taped in an approved manner, except in semiheated spaces in climate zones 1-6. Air Leakage 5.4.3.2 Envelope Factory-built and site-assembled fenestration and doors are labeled or certified as meeting air leakage requirements. Fenestration 5.8.2.1, 5.8.2.3, 5.8.2.4, 5.8.2.5 Envelope Fenestration products rated (U-factor, SHGC, and VT) in accordance with NFRC or energy code defaults are used. Fenestration 5.8.2.2 Envelope Fenestration and door products are labeled, or a signed and dated certificate listing the U-factor, SHGC, VT, and air leakage rate has been provided by the manufacturer. SYSTEM_SPECIFIC 7.4.4.1 Mechanical Temperature controls installed on service water heating systems (<=120ºF to maximum temperature for intended use). SYSTEM_SPECIFIC 7.4.4.2 Mechanical Automatic time switches installed to automatically switch off the recirculating hot-water system or heat trace. SYSTEM_SPECIFIC 7.4.6 Mechanical Heat traps installed on non-circulating storage water tanks. HVAC 6.4.1.4, 6.4.1.5 Mechanical HVAC equipment efficiency verified. Non-NAECA HVAC equipment labeled as meeting 90.1. SYSTEM_SPECIFIC 6.4.1.5.2 Mechanical PTAC and PTHP with sleeves 16 in. by 42 in. labeled for replacement only. HVAC 6.4.3.4.1 Mechanical Stair and elevator shaft vents have motorized dampers that automatically close. HVAC 6.4.3.4.2, 6.4.3.4.3 Mechanical Outdoor air and exhaust systems have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Check gravity dampers where allowed. HVAC 6.4.3.4.5 Mechanical Enclosed parking garage ventilation has automatic contaminant detection and capacity to stage or modulate fans to 50% or less of design capacity. HVAC 6.5.3.2.1 Mechanical DX cooling systems >= 75 kBtu/h (>= 65 kBtu/h effective 1/2016) and chilled-water and evaporative cooling fan motor hp >= ¼ designed to vary indoor fan airflow as a function of load and comply with operational requirements. HVAC 6.4.4.1.1 Mechanical Insulation exposed to weather protected from damage. Insulation outside of the conditioned space and associated with cooling systems is vapor retardant. HVAC 6.4.4.1.2 Mechanical HVAC ducts and plenums insulated. Where ducts or plenums are installed in or under a slab, verification may need to occur during Foundation Inspection. HVAC 6.4.4.1.3 Mechanical HVAC piping insulation thickness. Where piping is installed in or under a slab, verification may need to occur during Foundation Inspection. HVAC 6.4.4.2.1 Mechanical Ducts and plenums sealed based on static pressure and location. SYSTEM_SPECIFIC 6.4.4.2.2 Mechanical Ductwork operating >3 in. water column requires air leakage testing. SYSTEM_SPECIFIC 6.5.2.1 Mechanical Zone controls can limit simultaneous heating and cooling and sequence heating and cooling to each zone. SYSTEM_SPECIFIC 6.5.2.2.2 Mechanical Two-pipe hydronic systems using a common distribution system have controls to allow a deadband >=15 ºF, allow operation in one mode for at least 4 hrs before changeover, and have rest controls to limit heating and cooling supply temperature to <=30 ºF. HVAC 6.5.2.4.1 Mechanical Humidifiers with airstream mounted preheating jackets have preheat auto-shutoff value set to activate when humidification is not required. HVAC 6.5.2.4.2 Mechanical Humidification system dispersion tube hot surfaces in the airstreams of ducts or air-handling units insulated >= R-0.5. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 14 of 17 SYSTEM_SPECIFIC 6.5.3.2.2 Mechanical VAV fans have static pressure sensors positioned so setpoint <=1.2 in. w.c. design pressure. SYSTEM_SPECIFIC 6.5.4.5.1 Mechanical Two-position automatic valve interlocked to shut off water flow when hydronic heat pump with pumping system >10 hp is off. SYSTEM_SPECIFIC 6.5.6.2 Mechanical Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. HVAC 6.5.7.1.5 Mechanical Approved field test used to evaluate design air flow rates and demonstrate proper capture and containment of kitchen exhaust systems. SYSTEM_SPECIFIC 6.5.9 Mechanical Hot gas bypass limited to: <=240 kBtu/h – 15% >240 kBtu/h – 10% HVAC 6.4.3.9 Mechanical Heating for vestibules and air curtains include automatic controls that shut off the heating system when outdoor air temperatures > 45F. Vestibule heating systems controlled by a thermostat in the vestibule with setpoint <= 60F. Controls 6.5.10 Mechanical Doors separating conditioned space from the outdoors have controls that disable/reset heating and cooling system when open. Controls 9.4.1.1 Interior Lighting Automatic control requirements prescribed in Table 9.6.1, for the appropriate space type, are installed. Mandatory lighting controls (labeled as 'REQ') and optional choice controls (labeled as 'ADD1' and 'ADD2') are implemented. Controls 9.4.1.1 Interior Lighting Independent lighting controls installed per approved lighting plans and all manual controls readily accessible and visible to occupants. Controls 9.4.1.2 Interior Lighting Parking garage lighting is equipped with required lighting controls and daylight transition zone lighting. Controls 9.4.1.1f Interior Lighting Daylight areas under skylights and roof monitors that have more than 150 W combined input power for general lighting are controlled by photocontrols. Controls 9.4.1.4 Exterior Lighting Automatic lighting controls for exterior lighting installed. Controls 9.4.1.3 Interior Lighting Separate lighting control devices for specific uses installed per approved lighting plans. Wattage 9.6.2 Interior Lighting Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting. Wattage 9.6.4 Interior Lighting Where space LPD requirements are adjusted based on room cavity ratios, dimensions are consistent with approved plans. Insulation 5.5.3.1 Envelope Roof R-value. For some ceiling systems, verification may need to occur during Framing Inspection. Insulation 5.8.1.2, 5.8.1.3 Envelope Roof insulation installed per manufacturer’s instructions. Blown or poured loose-fill insulation is installed only where the roof slope is <=3 in 12. Insulation 5.8.1.1 Envelope Building envelope insulation is labeled with R-value or insulation certificate has been provided listing R-value and other relevant data. Insulation 5.8.1.9 Envelope Building envelope insulation extends over the full area of the component at the proposed rated R or U value. Insulation 5.8.1.4 Envelope Eaves are baffled to deflect air to above the insulation. Insulation 5.8.1.5 Envelope Insulation is installed in substantial contact with the inside surface separating conditioned space from unconditional space. Insulation 5.8.1.6 Envelope Recessed equipment installed in building envelope assemblies does not compress the adjacent insulation. Insulation 5.8.1.7.1 Envelope Attics and mechanical rooms have insulation protected where adjacent to attic or equipment access. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 15 of 17 Insulation 5.8.1.7.2 Envelope Foundation vents do not interfere with insulation. Insulation 5.8.1.8 Envelope Insulation intended to meet the roof insulation requirements cannot be installed on top of a suspended ceiling. Mark this requirement compliant if insulation is installed accordingly. SYSTEM_SPECIFIC 6.4.3.1.1 Mechanical Heating and cooling to each zone is controlled by a thermostat control. HVAC 6.4.3.1.2 Mechanical Thermostatic controls have a 5 °F deadband. HVAC 6.4.3.2 Mechanical Temperature controls have setpoint overlap restrictions. HVAC 6.4.3.3.1 Mechanical HVAC systems equipped with at least one automatic shutdown control. SYSTEM_SPECIFIC 6.4.3.5 Mechanical Heat pump controls prevent supplemental electric resistance heat from coming on when not needed. HVAC 6.4.3.6 Mechanical When humidification and dehumidification are provided to a zone, simultaneous operation is prohibited. Humidity control prohibits the use of fossil fuel or electricity to produce RH > 30% in the warmest zone humidified and RH < 60% in the coldest zone dehumidified. HVAC 6.4.3.6 Mechanical When humidification and dehumidification are provided to a zone, simultaneous operation is prohibited. Humidity control prohibits the use of fossil fuel or electricity to produce RH > 30% in the warmest zone humidified and RH < 60% in the coldest zone dehumidified. SYSTEM_SPECIFIC 7.4.4.3 Mechanical Public lavatory faucet water temperature <=110 °F. SYSTEM_SPECIFIC 7.4.4.4 Mechanical Controls are installed that limit the operation of a recirculation pump installed to maintain temperature of a storage tank. SYSTEM_SPECIFIC 7.4.5.1 Mechanical Pool heaters are equipped with on/off switch and no continuously burning pilot light. SYSTEM_SPECIFIC 7.4.5.2 Mechanical Pool covers are provided for heated pools and pools heated to >90°F have a cover >=R-12. SYSTEM_SPECIFIC 7.4.5.3 Mechanical Time switches are installed on all pool heaters and pumps. Wattage 9.2.2.3 Interior Lighting Interior installed lamp and fixture lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts. SYSTEM_SPECIFIC 7.4.3 Mechanical All piping in circulating system insulated SYSTEM_SPECIFIC 7.4.3 Mechanical First 8 ft of outlet piping is insulated SYSTEM_SPECIFIC 7.4.3 Mechanical All heat traced or externally heated piping insulated 4. To be checked by Inspector at Project Completion and Prior to Issuance of Certificate of Occupancy Plan Review 6.7.2.4 Mechanical Detailed instructions for HVAC systems commissioning included on the plans or specifications for projects >=50,000 ft2. Plan Review 6.7.2.4 Mechanical Detailed instructions for HVAC systems commissioning included on the plans or specifications for projects >=50,000 ft2. Post Construction 6.7.2.1 Mechanical Furnished HVAC as-built drawings submitted within 90 days of system acceptance. Post Construction 6.7.2.2 Mechanical Furnished O&M manuals for HVAC systems within 90 days of system acceptance. Post Construction 6.7.2.3 Mechanical An air and/or hydronic system balancing report is provided for HVAC systems serving zones >5,000 ft2 of conditioned area. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 16 of 17 HVAC 6.7.2.4 Mechanical HVAC control systems have been tested to ensure proper operation, calibration and adjustment of controls. Post Construction 8.7.1 Interior Lighting Furnished as-built drawings for electric power systems within 30 days of system acceptance. Post Construction 8.7.2 Interior Lighting Furnished O&M instructions for systems and equipment to the building owner or designated representative. EnergyGauge Summit® Fla/Com-2017. TAM 2017-1.0 Compliant Software. Effective Date: Dec 31, 2017 Florida Building Code, Sixth Edition (2017) - Energy Conservation ASHRAE 90.1-2013 - Energy Cost Budget Option 11/17/2020 Page 17 of 17 EnergyGauge Summit® v6.10INPUT DATA REPORTIRSProject Name:3200 N. KINGS HWY.Address:--Owner:FLORIDAState:Zip:RetailBuilding Type:New Finished buildingBuilding Classification:1No.of Stories:Orientation:9662GrossArea: Project Information349510 Deg Clockwise. Walls & Windows willbe rotated accordingly2020-0275Project Title:SFType DescriptionAcronymZonesArea[sf] Multiplier Total Area[sf]NoZONE 1 Zone 1 CONDITIONED 459.0 1 459.01ZONE 2 Zone 2 CONDITIONED 1106.0 1 1106.02ZONE 3 Zone 3 CONDITIONED 4190.0 1 4190.03ZONE 4 Zone 4 CONDITIONED 3907.0 1 3907.04111/17/2020 EnergyGauge Summit® v6.10 Width[ft]Depth[ft] DescriptionSpacesAcronymHeight[ft]NoMultiplierTotal Area[sf]Total Volume[cf]TypeZONE 1In Zone: ZONE 1 10.00 45.90 9.00ZONE 11 459.0 4131.0Sales Area1ZONE 2In Zone: ZONE 2 10.00 110.60 9.00ZONE 21 1106.0 9954.0Office - Open Plan1ZONE 3In Zone: ZONE 3 10.00 419.00 9.00ZONE 31 4190.0 37710.0Workshop1ZONE 4In Zone: ZON 4 10.00 390.70 9.00ZONE 41 3907.0 35163.0Workshop1Control TypePower[W] TypeLightingNo.ofCtrl ptsNo Category No. ofLuminairesWatts perLuminaireIn Zone: ZONE 1In Space: ZONE 11 LED 219 Occupancy sensor without Daylighting2General Lighting 6 37In Zone: ZONE 2In Space: ZONE 21 LED 438 Occupancy sensor without Daylighting2General Lighting 12 37In Zone: ZONE 3In Space: ZONE 31 LED 2049 Occupancy sensor without Daylighting2General Lighting 9 228In Zone: ZONE 4In Space: ZONE 41 LED 1366 Occupancy sensor without Daylighting2General Lighting 6 228211/17/2020 EnergyGauge Summit® v6.10 OrientationNoWalls (Walls will be rotated clockwise by building rotation value) Description Width[ft]H (Effec)[ft]MultiplierArea[sf]Conductance[Btu/hr. sf. F]Dens.[lb/cf]Heat Capacity[Btu/sf.F]R-Value[h.sf.F/Btu]TypeIn Zone: No UOrientationWindows (Windows will be rotated clockwise by building rotation value)Description[Btu/hr sf F]SHGCShadedVis.TraW[ft]H (Effec)[ft]Multiplier [sf]Total AreaIn Zone:In Wall:DoorsNo Description Area[sf]MultiplierH (Effec)[ft]Width[ft]Shaded? Cond.[Btu/hr. sf. F]Dens.[lb/cf]Heat Cap.[Btu/sf. F]R-Value[h.sf.F/Btu]TypeIn Zone: In Wall: RoofsNo Description Width[ft]Tilt[deg]Area[sf]MultiplierH (Effec)[ft]Type Cond.[Btu/hr. Sf. F]Dens.[lb/cf]Heat Cap[Btu/sf. F]R-Value[h.sf.F/Btu]In Zone: 311/17/2020 EnergyGauge Summit® v6.10 UType DescriptionNoSkylightsSHGC[Btu/hr sf F]Vis.Trans W[ft]H (Effec)[ft]Area[Sf]Multiplier Total Area[Sf]In Zone:In Roof:FloorsNo Description Area[sf]MultiplierH (Effec)[ft]Width[ft]Type Cond.[Btu/hr. sf. F]Dens.[lb/cf]Heat Cap.[Btu/sf. F]R-Value[h.sf.F/Btu]In Zone: ZONE 11 ZONE 1 121.80 1218.0110.001 ft. soil, concrete floor, carpet and rubber pad0.2681 34.00 113.33 3.73In Zone: ZONE 21 ZONE 2 110.60 1106.0110.001 ft. soil, concrete floor, carpet and rubber pad0.2681 34.00 113.33 3.73In Zone: ZONE 31 ZONE 3 419.00 4190.0110.001 ft. soil, concrete floor, carpet and rubber pad0.2681 34.00 113.33 3.73In Zone: ZONE 41 ZONE 4 390.70 3907.0110.001 ft. soil, concrete floor, carpet and rubber pad0.2681 34.00 113.33 3.73SystemsAHU 1 ZONE 1 Constant Volume Air Cooled Split System < 65000 Btu/hrComponent Category Capacity EfficiencyIPLV1No. Of Units411/17/2020 EnergyGauge Summit® v6.10 1 Cooling System 18000.00 16.00 8.002 Heating System 17105.00 1.003 Air Handling System -Supply 600.00 0.80AHU 2 ZONE 2 Constant Volume Air Cooled Split System < 65000 Btu/hrComponent Category Capacity Efficiency IPLV1No. Of Units1 Cooling System 34100.00 16.00 8.002 Heating System 27292.00 1.003 Air Handling System -Supply 1200.00 0.80RTU 1 ZONE 3 Constant Volume Packaged System--902Component Category Capacity Efficiency IPLV1No. Of Units1 Cooling System 103600.00 12.20 12.902 Heating System 266136.00 1.003 Air Handling System -Supply 3400.00 0.80RTU 2 ZONE 4 Constant Volume Packaged System--902Component Category Capacity Efficiency IPLV1No. Of Units1 Cooling System 119500.00 12.00 12.902 Heating System 266136.00 1.003 Air Handling System -Supply 4000.00 0.80Eff.Inst.NoSizeCategory EquipmentIPLVPlant511/17/2020 EnergyGauge Summit® v6.10 LossEfficiencyI/P Rt.Cap.UnitCapacityW-Heater DescriptionWater Heaters1 Electric water heater 30 [Gal] 5 [kW] 0.9600 [Ef] [Btu/h]WattageArea/Len/No. of unitsCategory Description[sf/ft/No] [W]Ext-LightingNo. ofLuminairesWatts perLuminaireControl TypeInsulationThickness[in]Nomonal pipeDiameter[in] Insulation Conductivity[ Btu-in/h.sf.F]Operating Temperature[F]TypePipingIs Runout?NoVLTSHGCGlassConductance[Btu/h.sf.F]No. ofPanesGlass TypeFenestration UsedName611/17/2020 EnergyGauge Summit® v6.10 RValue[h.sf.F/Btu]SpecificHeat[Btu/lb.F]Density[lb/cf]Conductivity[Btu/h.ft.F]Thickness[ft]DescriptionAcronymMat NoMaterials UsedOnly R-Value Used178 Matl178 CARPET W/RUBBER PAD 1.2300Yes265 Matl265 Soil, 1 ft 1.0000 0.5000 100.00 0.20002.0000No48 Matl48 6 in. Heavyweight concrete 0.5000 1.0000 140.00 0.20000.5000NoConstructs Used1057 1 ft. soil, concrete floor, carpet and rubber pad0.27 34.00 113.33 3.7No NameConductance [Btu/h.sf.F]Heat Capacity[Btu/sf.F]Density[lb/cf]RValue[h.sf.F/Btu]Layer MaterialNo.Material Thickness[ft]FramingFactorNoSimple ConstructNoMasslessConstruct1 265 Soil, 1 ft 1.0000 0.0002 48 6 in. Heavyweight concrete 0.5000 0.0003 178 CARPET W/RUBBER PAD 0.000711/17/2020 EnergyGauge Summit® v6.10 Air System Sizing Summary for AHU 1 Project Name: INDIAN RIVER SPIRIT 2020-0275 04/28/2020 Prepared by: Kamm Consulting 09:23AM Air System Information Air System Name AHU 1 Equipment Class SPLT AHU Air System Type SZCAV Number of zones 1 Floor Area 459.0 ft² Location FORT PIERCE, Florida Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads Central Cooling Coil Sizing Data Total coil load 1.2 Tons Total coil load 14.1 MBH Sensible coil load 11.7 MBH Coil CFM at Oct 1500 594 CFM Max block CFM 594 CFM Sum of peak zone CFM 594 CFM Sensible heat ratio 0.825 ft²/Ton 389.5 BTU/(hr·ft²) 30.8 Water flow @ 10.0 °F rise N/A Load occurs at Oct 1500 OA DB / WB 87.0 / 76.0 °F Entering DB / WB 74.6 / 63.5 °F Leaving DB / WB 56.4 / 55.4 °F Coil ADP 54.4 °F Bypass Factor 0.100 Resulting RH 53 % Design supply temp. 55.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F Central Heating Coil Sizing Data Max coil load 5.7 MBH Coil CFM at Des Htg 594 CFM Max coil CFM 594 CFM Water flow @ 20.0 °F drop N/A Load occurs at Des Htg BTU/(hr·ft²) 12.3 Ent. DB / Lvg DB 66.8 / 75.7 °F Supply Fan Sizing Data Actual max CFM 594 CFM Standard CFM 594 CFM Actual max CFM/ft² 1.29 CFM/ft² Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg Outdoor Ventilation Air Data Design airflow CFM 63 CFM CFM/ft² 0.14 CFM/ft² CFM/person 62.58 CFM/person Hourly Analysis Program v5.01 Page 1 of 4 Air System Sizing Summary for AHU 2 Project Name: INDIAN RIVER SPIRIT 2020-0275 04/28/2020 Prepared by: Kamm Consulting 09:23AM Air System Information Air System Name AHU 2 Equipment Class SPLT AHU Air System Type SZCAV Number of zones 1 Floor Area 1106.0 ft² Location FORT PIERCE, Florida Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads Central Cooling Coil Sizing Data Total coil load 3.0 Tons Total coil load 35.8 MBH Sensible coil load 29.9 MBH Coil CFM at Jun 1500 1593 CFM Max block CFM 1593 CFM Sum of peak zone CFM 1593 CFM Sensible heat ratio 0.834 ft²/Ton 370.4 BTU/(hr·ft²) 32.4 Water flow @ 10.0 °F rise N/A Load occurs at Jun 1500 OA DB / WB 90.0 / 78.0 °F Entering DB / WB 73.8 / 63.2 °F Leaving DB / WB 56.5 / 55.5 °F Coil ADP 54.5 °F Bypass Factor 0.100 Resulting RH 55 % Design supply temp. 55.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F Central Heating Coil Sizing Data Max coil load 11.8 MBH Coil CFM at May 0600 1593 CFM Max coil CFM 1593 CFM Water flow @ 20.0 °F drop N/A Load occurs at May 0600 BTU/(hr·ft²) 10.6 Ent. DB / Lvg DB 56.3 / 63.2 °F Supply Fan Sizing Data Actual max CFM 1593 CFM Standard CFM 1592 CFM Actual max CFM/ft² 1.44 CFM/ft² Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg Outdoor Ventilation Air Data Design airflow CFM 76 CFM CFM/ft² 0.07 CFM/ft² CFM/person 38.18 CFM/person Hourly Analysis Program v5.01 Page 2 of 4 Air System Sizing Summary for RTU 1 Project Name: INDIAN RIVER SPIRIT 2020-0275 04/28/2020 Prepared by: Kamm Consulting 09:23AM Air System Information Air System Name RTU 1 Equipment Class PKG ROOF Air System Type SZCAV Number of zones 1 Floor Area 3907.0 ft² Location FORT PIERCE, Florida Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads Central Cooling Coil Sizing Data Total coil load 8.3 Tons Total coil load 100.2 MBH Sensible coil load 77.8 MBH Coil CFM at Jun 1500 3298 CFM Max block CFM 3298 CFM Sum of peak zone CFM 3298 CFM Sensible heat ratio 0.777 ft²/Ton 468.0 BTU/(hr·ft²) 25.6 Water flow @ 10.0 °F rise N/A Load occurs at Jun 1500 OA DB / WB 90.0 / 78.0 °F Entering DB / WB 78.3 / 65.4 °F Leaving DB / WB 56.4 / 55.2 °F Coil ADP 54.0 °F Bypass Factor 0.100 Resulting RH 47 % Design supply temp. 55.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F Central Heating Coil Sizing Data Max coil load 33.3 MBH Coil CFM at Des Htg 3298 CFM Max coil CFM 3298 CFM Water flow @ 20.0 °F drop N/A Load occurs at Des Htg BTU/(hr·ft²) 8.5 Ent. DB / Lvg DB 65.7 / 75.0 °F Supply Fan Sizing Data Actual max CFM 3298 CFM Standard CFM 3296 CFM Actual max CFM/ft² 0.84 CFM/ft² Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg Outdoor Ventilation Air Data Design airflow CFM 506 CFM CFM/ft² 0.13 CFM/ft² CFM/person 101.27 CFM/person Hourly Analysis Program v5.01 Page 3 of 4 Air System Sizing Summary for RTU 2 Project Name: INDIAN RIVER SPIRIT 2020-0275 04/28/2020 Prepared by: Kamm Consulting 09:23AM Air System Information Air System Name RTU 2 Equipment Class PKG ROOF Air System Type SZCAV Number of zones 1 Floor Area 4190.0 ft² Location FORT PIERCE, Florida Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads Central Cooling Coil Sizing Data Total coil load 9.9 Tons Total coil load 119.2 MBH Sensible coil load 87.2 MBH Coil CFM at Jul 1400 3678 CFM Max block CFM 3678 CFM Sum of peak zone CFM 3678 CFM Sensible heat ratio 0.731 ft²/Ton 421.7 BTU/(hr·ft²) 28.5 Water flow @ 10.0 °F rise N/A Load occurs at Jul 1400 OA DB / WB 90.6 / 77.9 °F Entering DB / WB 78.3 / 66.1 °F Leaving DB / WB 56.4 / 55.3 °F Coil ADP 53.9 °F Bypass Factor 0.100 Resulting RH 50 % Design supply temp. 55.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F Central Heating Coil Sizing Data Max coil load 30.3 MBH Coil CFM at Des Htg 3678 CFM Max coil CFM 3678 CFM Water flow @ 20.0 °F drop N/A Load occurs at Des Htg BTU/(hr·ft²) 7.2 Ent. DB / Lvg DB 66.0 / 73.6 °F Supply Fan Sizing Data Actual max CFM 3678 CFM Standard CFM 3675 CFM Actual max CFM/ft² 0.88 CFM/ft² Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg Outdoor Ventilation Air Data Design airflow CFM 540 CFM CFM/ft² 0.13 CFM/ft² CFM/person 108.06 CFM/person Hourly Analysis Program v5.01 Page 4 of 4