HomeMy WebLinkAboutConstruction PlansAMERICAST GENERATOR CONCRETE PAD
tilt
` GENERATOR
N
_I= y'l0
_ Ty
PAD
THICKNESS
PPO BEN
ISOMETRIC VIEW
PAD DIMENSIONS: GENERATOR TABLE:
CONCRETE PAD
GENERATOR -
S
CONCRETE PAD
ROA1
MASTE
I
GROU
GENERATOR UNIT BY
SEPARATE SUBMITTAL
(SEE SCHEDULE FOR
MINIMUM WEIGHT
REQUIRED)
54"LENGTH
PLAN VIEW
(ON -GRADE APPLICATIONS ONLY)
�Nff
AMERICAST
.bf1w31Ix1&bnwCwl•
FEDT"6204== L10ENIKE 09"M0163
SNL PW=mAve, FonKum n 3012
m. 7MV"-19U Fmr. M-461A
FAnII:
HVHZ OR NON-HVHZ
COUNTY
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
I
C
D
II
C
I D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf,
186 MPH
46.80 Psf
56.80 Psf
BRAND & MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
10 KW
25.00 "
48.00 "
29.0011
387 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac 005872 & OOS884
14 KW
25.00 "
48.00 "
29.00 "
439 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
46.00 "
29.00 "
513 Ibs
47.44 Psf
Generac 006721
16 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00 "
48.00 "
29.00 "
455 Ibs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00 "
48.00 "
29.00 "
421 Ibs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00 "
48.00 "
29.00 "
451 Ibs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
29.00 "
516 Ibs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00 "
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP C 170 MPH & G 156 MPH
GE04038215KW
15KW
33.00"
48.00"
30.50"
484lbs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE 040378 17KW
17 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 Ibs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507 Ibs
41.43 Psf jEXP
C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00 "
31.60 "
562 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75 "
49.00 "
31.60 "
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
406 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00'.
448 Ibs
47.44 Psf
Generac 007042 & 7043
22 KW
25.00 "
48.00 "
29.00"
466 Ibs 1
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #SO SS 316 SELF -DRILLING
SCREWS
TO GENERATOR
q (SEE GENERATOR SPECS)
F F GENERATOR
(SEE CONCRETE PAD
L9 w SCHEDULE FOR
_ = I DIMENSION WEIGHT
REQUI4"
} -32" WIDTH- }54" LENGTH
SIDE VIEW
FRONT VIEW
GENERATOR
Gordon DiBattisto PE
RECElk t 82328 CIA 9885
NOV 21 2019
Permitting Department
ST.LUCIE COUNTY St. Lucie County
PLAN REVIEW
BLDG:
WIND DESIGN REQUIREMENTS:
DATE:
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017))
ELE
-GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Vult = 186 mph -
DATE/ -241
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
PLUMB:
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
DATE
0.85
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
MECH:
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56
Ib/ft2
DATE:
FORCE COEFFICIENT Cf = 1.44
WIND PRESSURE:
ANCHOR TO PAD SCHEDULE:
SUBSTRATE I DESCRIPTION
CONCRETE: (2)-3/8"0 TITEN HD
(6000 PSI OR EQUIVALENT,
MIN.) 2-3/4" FULL EMBED
0 CONCRETE, 3" MIN.
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
P = qh G Cf = 56.80 Ib/ft2 (ASD)
GENERAL NOTES
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
SIXTH EDITION (2017).
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE
DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
ASSEMBLY AS SHOWN.
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
STATED HEREIN.
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
CLEARANCE. A MINIMUM DISTANCE FROM UNIT TO PAD EDGE IS SPECIFIED.
S. CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
6. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
NOTES:
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
1. ANCHOR QUANTITY PER LONG SIDE
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
2. EMBEDMENT AND EDGE DISTANCE
7• RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
EXCLUDES FINISHES, IF
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
APPLICABLE.
B. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
3. ENSURE MINIMUM EDGE DISTANCE
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
AS NOTED IN ANCHOR SCHEDULE.
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
4. ENSURE MINIMUM SPACING TO
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
ANY ADJACENT ANCHORS.
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
5. FOLLOW MANUFACTURER'S
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
INSTALLATION INSTRUCTIONS TO
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
INSTALL ANCHORS.
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
%a" SIMPSON TITEN HD,
SEE ANCHOR SCHEDULE
2"x3"x3/B" GALV. STEEL -
WASHER
RUBBER VIBRATION PAD -
%" THICK GALVANIZED
WASHER& RUBBER
VIBRATION PAD
Z
CONCRETE PAD -
6,000 PSI
LIGHTWEIGHT
CONCRETE PAD
X
CONCRETE MIX I
6,000 PSI
`
LIGHTWEIGHT
MASTERFIBER MAC 100
CONCRETE MIX
& ROAD MESH
NOTES:
FOAM CORE
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
a WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
,{I DEVIATIONS OF THIS PLAN.
®WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
® RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
CJPROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR.
il. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
12. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
PROJECT SITE. INFORMATION CONTAINED HEREIN IS BASED ON
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
,.I - REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
/ 1 INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
jCERTIFICATION.
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
OR AFFIRMATIONS ARE INTENDED.
2" SCAN HERE: ABOUT THIS DOCUMENT I
ENGINEER -CERTIFIED ORIGINALS, VARIATIONS
& MORE INFORMATION CAN BE FOUND BY
VISITING ENGI SM1,NGRESSCOM/STORE
IORUSIOR NG
THE WEB ADDRESS FOUND HERE >
i
THIS DOCUMENT NOT VALID WITHOUT OR, GO TO
ORIGINAL ENGINEER CERTIFICATION 1CALCIO/173961d
W19
OF AUTH
.NATURE ON SHEET 1, THIS
=ET IS PART OF A DIGITALLY
iNED FILE, SHALL REMAIN IN
;TTAL FORMAT, & PRINTED
PIES OF THIS DOCUMENT
E NOT CONSIDERED SIGNET
D SEALED. IF THERE IS NO
;ITAL SIGNATURE ON SHEET 1
THIS SHEET DOES NOT
VTAIN AN ENGINEER'S
:GINAL SIGNATURE & SEAL,
u O
oN
Z 't
't 0
�p W M MY2
v
111 ►~-I M o L,.n O Ln
Wol °L1L 'XNON
W111 O 2�UiHx
Z ><U x<
c�aa W
�Q W owU` U
W W 0 N_ m LU W U
O� J w
U W `J-O0
�U"�wz
UlwaxLU
�W w
TH �
C
C.
0 FW O - Of f~
Z
Q � In o
Y - _
U kof-I (z
E a °i GOEn o
LU M ~a ^ g CD
o p v 0.In
z
In
Y tY
W
rl N CO
CW7 < o
of
O
Li
c9
zQ�
U-
III to
U
0LL
W$ �'M
=
3 00
055:5
0
0�0r
w �
�zw
Fzow�
N
wo a
=ioo�a
K W
y
Q DO
J O]
�izw
N C)$
COPYRIGHT ENGINEERING EXPRESS
17-3961.1
SCALE: NITS UNLESS NOTED