HomeMy WebLinkAboutOED - Earthworks - AB Lot 9 - Manual J (11.11.20)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 1 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Load Short Form 03/05/2019Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) WEST AHU 2583 33099 29772 413 1400 EAST AHU 2053 22308 19151 278 840 (Unconditioned)921 0 0 0 0 ENTIRE BUILDING 5556 55407 48923 691 2240 Other equip loads 0 0 Equip. @ 1.00 RSM 48923 Latent cooling 13043 TOTALS 5556 55407 61966 691 2240 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 2 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Load Short Form 03/05/2019Date:EAST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Trane Trade Trade TRANE Model Cond 4TTR6030J1 AHRI ref Coil TEM6A0B30H21++TDR AHRI ref 8626669 Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input kW4.8 Sensible cooling Btuh23652 Heating output Btuh16378 Latent cooling Btuh5548 Temperature rise °F54 Total cooling Btuh29200 Actual air flow cfm278 Actual air flow cfm840 Air flow factor cfm/Btuh0.012 Air flow factor cfm/Btuh0.044 Static pressure in H2O0.65 Static pressure in H2O0.65 Space thermostat Load sensible heat ratio 0.80 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) CLUB ROOM 272 3479 4044 43 177 MECH 35 0 0 0 0 MASTER BEDRM 409 6612 5893 82 258 HIS WIC 138 274 224 3 10 HIS BATH 106 993 768 12 34 HER WIC 156 1461 949 18 42 HER BATH 204 1563 1483 19 65 BEDRM 2 255 4190 3686 52 162 HER WC 37 56 46 1 2 BEDRM 2 BATH 77 999 701 12 31 BEDRM 2 WIC 47 885 417 11 18 MASTER HALL 90 0 0 0 0 PWDR 54 1006 495 13 22 HALL CLST 27 399 178 5 8 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 3 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N BEDRM HALL 148 390 267 5 12 EAST AHU 2053 22308 19151 278 840 Other equip loads 0 1195 Equip. @ 1.00 RSM 20346 Latent cooling 5079 TOTALS 2053 22308 25425 278 840 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 4 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Load Short Form 03/05/2019Date:WEST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Trane Trade Trade TRANE Model Cond 4TTR6048J1 AHRI ref Coil TEM6A0D48H41++TDR AHRI ref 8631424 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW7.7 Sensible cooling Btuh36400 Heating output Btuh26273 Latent cooling Btuh9100 Temperature rise °F58 Total cooling Btuh45500 Actual air flow cfm413 Actual air flow cfm1400 Air flow factor cfm/Btuh0.012 Air flow factor cfm/Btuh0.047 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.80 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bonus Room 283 7240 4260 90 200 Bath 4 57 1047 830 13 39 Cabana 51 1444 955 18 45 kitchen 240 1961 4037 24 190 Bath 3 72 1772 1186 22 56 PANTRY 28 83 91 1 4 OPEN AREA 284 0 0 0 0 UTILITY RM 120 2201 2014 27 95 GARAGE HALL 113 1169 751 15 35 DINING 228 3104 3011 39 142 GREAT ROOM 540 4942 5541 62 261 FOYER 100 1710 1085 21 51 BREAKFAST 227 4525 3852 56 181 WIC BDRM 3 18 23 19 0 1 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 5 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N BEDRM 3 223 1877 2141 23 101 WEST AHU 2583 33099 29772 413 1400 Other equip loads 0 1877 Equip. @ 1.00 RSM 31649 Latent cooling 7964 TOTALS 2583 33099 39613 413 1400 Bold/italic values have been manually overridden 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 1 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Load Multizone Summary Report 03/05/2019Date: CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Infiltration Summary Heating Cooling ZONE NAME Volume ACH AVF HTM Volume ACH AVF HTM ft³cfm Btuh/ft²ft³cfm Btuh/ft² 0.5 57 0.15 23009 1.8 106 0.28 23009EAST AHU 0.5 81 0.15 32146 1.8 151 0.28 32146WEST AHU 0 0 0 0 0 0 0 0(Unconditioned) ENTIRE BUILDING 55155 0.28 257 1.8 55155 0.15 138 0.5 Load and AVF Summary ROOM NAME Area Htg load Clg load Htg AVF Clg AVF ft²Btuh Btuh cfm cfm 177 43 4044 3479 272CLUB ROOM 0 0 0 0 35MECH 258 82 5893 6612 409MASTER BEDRM 10 3 224 274 138HIS WIC 34 12 768 993 106HIS BATH 42 18 949 1461 156HER WIC 65 19 1483 1563 204HER BATH 162 52 3686 4190 255BEDRM 2 2 1 46 56 37HER WC 31 12 701 999 77BEDRM 2 BATH 18 11 417 885 47BEDRM 2 WIC 0 0 0 0 90MASTER HALL 22 13 495 1006 54PWDR 8 5 178 399 27HALL CLST 12 5 267 390 148BEDRM HALL 840 278 19151 22308 2053EAST AHU 200 90 4260 7240 283Bonus Room 39 13 830 1047 57Bath 4 45 18 955 1444 51Cabana 190 24 4037 1961 240kitchen 56 22 1186 1772 72Bath 3 4 1 91 83 28PANTRY 0 0 0 0 284OPEN AREA 95 27 2014 2201 120UTILITY RM 35 15 751 1169 113GARAGE HALL 142 39 3011 3104 228DINING 261 62 5541 4942 540GREAT ROOM 51 21 1085 1710 100FOYER 181 56 3852 4525 227BREAKFAST 1 0 19 23 18WIC BDRM 3 101 23 2141 1877 223BEDRM 3 1400 413 29772 33099 2583WEST AHU 0 0 0 0 668GARAGE 0 0 0 0 253GOLF GAR. Bold/italic values have been manually overridden 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 2 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 0 0 0 0 921(Unconditioned) ENTIRE BUILDING 5556 55407 48923 691 2240 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 1 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Building Analysis 03/05/2019Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 21.5118882.3Walls 16.893268.6Glazing 0.740510.5Doors 10.658821.1Ceilings 17.597181.71.7Floors 13.876361.4Infiltration 19.010551Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.055407Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 19.896671.8Walls 29.31434413.2Glazing 0.944011.4Doors 10.651850.9Ceilings 000Floors 4.823480.4Infiltration 17.18379Ducts 00Ventilation 17.58560Internal gains 00Blower 0Adjustments 100.048923Total Latent Cooling Load = 13043 Btuh Overall U-value = 0.099 Btuh/ft²-°F Data entries checked. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 2 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Building Analysis 03/05/2019Date:EAST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 23.652652.9Walls 14.532278.8Glazing 000Doors 11.726051.3Ceilings 18.440972.02.0Floors 14.131441.8Infiltration 17.83971Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.022308Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Blower % of loadBtuhBtuh/ft²Component 21.142952.4Walls 28.1572115.6Glazing 000Doors 11.322961.1Ceilings 000Floors 4.89670.5Infiltration 15.53152Ducts 00Ventilation 13.42720Internal gains 5.91195Blower 0Adjustments 100.020346Total Latent Cooling Load = 5079 Btuh Overall U-value = 0.090 Btuh/ft²-°F Data entries checked. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 3 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Building Analysis 03/05/2019Date:WEST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 20.066233.0Walls 18.460998.5Glazing 1.240510.5Doors 9.932771.3Ceilings 17.056212.22.2Floors 13.644921.8Infiltration 19.96580Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.033099Total Cooling Walls Glazing Other CeilingsInfiltration Ducts Internal Gains Blower % of loadBtuhBtuh/ft²Component 17.053712.4Walls 27.2862412.0Glazing 1.444011.4Doors 9.128891.1Ceilings 000Floors 4.413820.5Infiltration 16.55227Ducts 00Ventilation 18.55840Internal gains 5.91877Blower 0Adjustments 100.031649Total Latent Cooling Load = 7964 Btuh Overall U-value = 0.100 Btuh/ft²-°F WARNING: window to floor area ratio = 27.8% - more than 25%. Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 1 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Project Summary 03/05/2019Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor:648 Tulip Ln., Vero Beach, FL 32963 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh44856 Structure Btuh40545 Ducts Btuh10551 Ducts Btuh8379Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 Humidification Btuh0Blower Btuh0 Piping Btuh0Equipment load Btuh55407 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh48923 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh7960 Ducts Btuh5083Central vent (0 cfm) Btuh0 CoolingHeating46354635Area (ft²) Equipment latent load Btuh13043 5515555155Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh61966 Equiv. AVF (cfm) 138257 Req. total capacity at 0.70 SHR ton5.8 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTrade n/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 2 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Project Summary 03/05/2019Date:EAST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor:648 Tulip Ln., Vero Beach, FL 32963 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18338 Structure Btuh15999 Ducts Btuh3971 Ducts Btuh3152Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0Blower Btuh1195 Piping Btuh0Equipment load Btuh22308 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh20346 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3089 Ducts Btuh1990Central vent (0 cfm) Btuh0 CoolingHeating (none)20532053Area (ft²) Equipment latent load Btuh5079 2300923009Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh25425 Equiv. AVF (cfm) 57106 Req. total capacity at 0.81 SHR ton2.1 Heating Equipment Summary Cooling Equipment Summary Make Make TraneTrade Trade TRANE Model Cond 4TTR6030J1AHRI ref Coil TEM6A0B30H21++TDR AHRI ref 8626669Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input kW4.8 Sensible cooling Btuh23652Heating output Btuh16378 Latent cooling Btuh5548 Temperature rise °F54 Total cooling Btuh29200Actual air flow cfm278 Actual air flow cfm840 Air flow factor cfm/Btuh0.012 Air flow factor cfm/Btuh0.044Static pressure in H2O0.65 Static pressure in H2O0.65 Space thermostat Load sensible heat ratio 0.80 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 3 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:Project Summary 03/05/2019Date:WEST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor:648 Tulip Ln., Vero Beach, FL 32963 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh26518 Structure Btuh24545 Ducts Btuh6580 Ducts Btuh5227Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0Blower Btuh1877 Piping Btuh0Equipment load Btuh33099 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh31649 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh4871 Ducts Btuh3093Central vent (0 cfm) Btuh0 CoolingHeating (none)25832583Area (ft²) Equipment latent load Btuh7964 3214632146Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh39613 Equiv. AVF (cfm) 81151 Req. total capacity at 0.80 SHR ton3.3 Heating Equipment Summary Cooling Equipment Summary Make Make TraneTrade Trade TRANE Model Cond 4TTR6048J1AHRI ref Coil TEM6A0D48H41++TDR AHRI ref 8631424Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW7.7 Sensible cooling Btuh36400Heating output Btuh26273 Latent cooling Btuh9100 Temperature rise °F58 Total cooling Btuh45500Actual air flow cfm413 Actual air flow cfm1400 Air flow factor cfm/Btuh0.012 Air flow factor cfm/Btuh0.047Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.80 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 1 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:AED Assessment 03/05/2019Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) )L(15-Daily range (°F) 78-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 24.9%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 2 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:AED Assessment 03/05/2019Date:EAST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) )L(15-Daily range (°F) 78-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 26.7%. Zone has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh 2019-Mar-18 16:09:26 Right-Suite® Universal 2019 19.0.03 RSU25986 Page 3 ...91036.GelCorp\HVAC Calcs\Tulip Drive.energy.rup Calc = MJ8 Front Door faces: N 191036Job:AED Assessment 03/05/2019Date:WEST AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelman ResidenceFor: 648 Tulip Ln., Vero Beach, FL 32963 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) )L(15-Daily range (°F) 78-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 23.7%. Zone has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Job #: 191036 Performed by CJH for: Gelman Residence 648 Tulip Ln. Vero Beach, FL 32963 The EARTHWORKS Group 7410 S US Hwy 1 Suite 104 Port St Lucie, FL 34952 Scale: 1 : 164 Page 1 Right-Suite® Universal 2019 19.0.03 RSU25986 2019-Mar-18 16:11:42 ...VAC Calcs\Tulip Drive.energy.rup N Level 1 Bath 4 Bonus Room Cabana kitchen Bath 3 PANTRY BREAKFAST OPEN ARE A UTILITY RM GARAGE GARAGE HALL DINING GREAT ROOM FOYER CLUB ROOM MECH MASTER BEDRM HIS WIC HIS BATH HER WIC HER BATH BEDRM 2 HER WC BEDRM 2 BATH BEDRM 2 WIC MASTER HALL PWDR HALL CLST BEDRM HALL GOLF GAR. WIC BDRM 3 BEDRM 3 22 cfm 10 cfm 42 cfm 65 cfm 4 cfm 130 cfm 39 cfm 142 cfm 130 cfm 2 cfm 211 cfm Sup Riser 14 x 14 177 cfm 129 cfm 129 cfm 34 cfm 31 cfm 18 cfm 8 cfm 162 cfm Ret Riser 16 x 14 177 cfm 411 cfm 8 " 10 " 4 " 6 " 4 " 7 "5 " 95 cfm 35 cfm 10 x 12 12 x 14 Sup Riser 16 x 16 Ret Riser 19 x 16 51 cfm 56 cfm 421 cfm 95 cfm 8 " 8 " 4 " 16 x 16 8 x 104 " 5 " 100 cfm 14 x 14 6 "5 " 181 cfm 7 " 4 " 5 " 822 cfm 4 " 9 "41 cfm 12 " 12 cfm 19 x 16 14 " 12 "10 x 14 8 " 5 " 9 " 100 cfm 7 " 7 " 10 x 1010 x 10 7 " 95 cfm 7 " 6 " 8 " 4 " 14 " 45 cfm 8 " 157 cfm 9 " 101 cfm 8 " 4 " 1 cfm 16 x 14 14 x 14