OED - Earthworks - AB Lot 20 - Manual J (12.17.20)
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Load Short Form 01/06/2020Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach, St Lucie County, FL 34949 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 1st Flr AHU 1521 21573 20819 368 1000 2nd Flr AHU 1048 16394 17978 231 1000 ENTIRE BUILDING 2568 37967 38797 599 2000 Other equip loads 0 0 Equip. @ 1.00 RSM 38797 Latent cooling 12216 TOTALS 2568 37967 51013 599 2000 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Load Short Form 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach, St Lucie County, FL 34949 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade Trade TRANE Model Cond 4TTR6030J1 AHRI ref Coil TEM8A0B30V31++TDR AHRI ref 10149819 Efficiency 100 EFF Efficiency 14.0 EER, 16.3 SEER Heating input kW7.7 Sensible cooling Btuh23490 Heating output Btuh26273 Latent cooling Btuh5510 Temperature rise °F65 Total cooling Btuh29000 Actual air flow cfm368 Actual air flow cfm1000 Air flow factor cfm/Btuh0.017 Air flow factor cfm/Btuh0.048 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.81 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Dining 120 3674 3426 63 165 Master Bdrm 330 5763 5718 98 275 Master WIC 57 923 412 16 20 Kitchen 268 607 2163 10 104 Master Bath 117 878 1318 15 63 WC Rm 15 72 51 1 2 Laundry 55 1121 1486 19 71 G Hall 23 0 0 0 0 Foyer 150 2342 996 40 48 Study 222 4873 4373 83 210 Bath 4 84 1320 875 23 42 1st flr stairs 79 0 0 0 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 1st Flr AHU 1521 21573 20819 368 1000 Other equip loads 0 0 Equip. @ 1.00 RSM 20819 Latent cooling 4843 TOTALS 1521 21573 25662 368 1000 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 4 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Load Short Form 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach, St Lucie County, FL 34949 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade Trade TRANE Model Cond 4TTR6030J1 AHRI ref Coil TEM8A0B30V31++TDR AHRI ref 10149819 Efficiency 100 EFF Efficiency 14.0 EER, 16.3 SEER Heating input kW4.8 Sensible cooling Btuh20880 Heating output Btuh16378 Latent cooling Btuh8120 Temperature rise °F65 Total cooling Btuh29000 Actual air flow cfm231 Actual air flow cfm1000 Air flow factor cfm/Btuh0.014 Air flow factor cfm/Btuh0.056 Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 0.72 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bedrm 3 WIC 45 565 421 8 23 2nd Flr Stairs 0 0 0 0 0 Loft 247 3277 3601 46 200 2nd flr hall 49 0 0 0 0 Bath 3 47 531 576 7 32 Bath 2 51 535 579 8 32 Bedroom 2 209 2246 2863 32 159 Bedroom 3 144 2131 2095 30 117 Family 256 3305 4409 47 245 FAMILY RM CLG.0 3803 3434 54 191 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 5 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 2nd Flr AHU 1048 16394 17978 231 1000 Other equip loads 0 1195 Equip. @ 1.00 RSM 19172 Latent cooling 7373 TOTALS 1048 16394 26546 231 1000 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Building Analysis 01/06/2020Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach, St Lucie County, FL 34949 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 22.585522.7Walls 18.5702211.4Glazing 0.620910.5Doors 7.026771.3Ceilings 16.462313.03.0Floors 16.562531.8Infiltration 18.57023Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.037967Total Cooling Walls Glazing OtherCeilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 18.672162.3Walls 33.41296021.0Glazing 0.622711.4Doors 7.830081.4Ceilings 0.31170.1Floors 4.718390.5Infiltration 12.34759Ducts 00Ventilation 22.38670Internal gains 00Blower 0Adjustments 100.038797Total Latent Cooling Load = 12216 Btuh Overall U-value = 0.138 Btuh/ft²-°F ERROR: negative wall area in Bedroom 3 - check windows. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Building Analysis 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach, St Lucie County, FL 34949 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 21.345882.8Walls 17.3374212.2Glazing 1.020910.5Doors 5.311541.4Ceilings 24.352473.53.5Floors 13.428931.8Infiltration 17.33741Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.021573Total Cooling Walls Glazing OtherCeilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 18.237902.3Walls 34.2712723.2Glazing 1.122711.4Doors 5.611651.5Ceilings 000Floors 4.18510.5Infiltration 11.42369Ducts 00Ventilation 25.45290Internal gains 00Blower 0Adjustments 100.020819Total Latent Cooling Load = 4843 Btuh Overall U-value = 0.172 Btuh/ft²-°F Data entries checked. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Building Analysis 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach, St Lucie County, FL 34949 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 24.239642.6Walls 20.0328110.6Glazing 000Doors 9.315231.2Ceilings 6.09841.71.7Floors 20.533601.8Infiltration 20.03282Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.016394Total Cooling Walls Glazing CeilingsOtherInfiltration Ducts Internal Gains Blower % of loadBtuhBtuh/ft²Component 17.934262.2Walls 30.4583318.9Glazing 000Doors 9.618431.4Ceilings 0.61170.2Floors 5.29880.5Infiltration 12.52390Ducts 00Ventilation 17.63380Internal gains 6.21195Blower 0Adjustments 100.019172Total Latent Cooling Load = 7373 Btuh Overall U-value = 0.100 Btuh/ft²-°F WARNING: window to floor area ratio = 29.4% - more than 25%. ERROR: negative wall area in Bedroom 2 - check windows. Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Project Summary 01/06/2020Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach, St Lucie County, FL 34949 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh30944 Structure Btuh34038 Ducts Btuh7023 Ducts Btuh4759Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 Humidification Btuh0Blower Btuh0 Piping Btuh0Equipment load Btuh37967 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh38797 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh5953 Ducts Btuh6263Central vent (0 cfm) Btuh0 CoolingHeating25682568Area (ft²) Equipment latent load Btuh12216 3084530845Volume (ft³)Air changes/hour 0.210.41 Equipment Total Load (Sen+Lat)Btuh51013 Equiv. AVF (cfm) 108211 Req. total capacity at 0.70 SHR ton4.6 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTrade n/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Project Summary 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach, St Lucie County, FL 34949 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh17832 Structure Btuh18450 Ducts Btuh3741 Ducts Btuh2369Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0Blower Btuh0 Piping Btuh0Equipment load Btuh21573 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh20819 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2614 Ducts Btuh2229Central vent (0 cfm) Btuh0 CoolingHeating (none)15211521Area (ft²) Equipment latent load Btuh4843 1520515205Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh25662 Equiv. AVF (cfm) 5098 Req. total capacity at 0.81 SHR ton2.1 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTrade Trade TRANE Model Cond 4TTR6030J1AHRI ref Coil TEM8A0B30V31++TDR AHRI ref 10149819Efficiency 100 EFF Efficiency 14.0 EER, 16.3 SEER Heating input kW7.7 Sensible cooling Btuh23490Heating output Btuh26273 Latent cooling Btuh5510 Temperature rise °F65 Total cooling Btuh29000Actual air flow cfm368 Actual air flow cfm1000 Air flow factor cfm/Btuh0.017 Air flow factor cfm/Btuh0.048Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.81 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Dec-17 16:20:35 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...tom Home MEP\Avalon Custom HVAC calcs EXP.N.rup Calc = MJ8 Front Door faces: N 191242Job:Project Summary 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach, St Lucie County, FL 34949 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh13112 Structure Btuh15588 Ducts Btuh3282 Ducts Btuh2390Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0Blower Btuh1195 Piping Btuh0Equipment load Btuh16394 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh19172 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3339 Ducts Btuh4034Central vent (0 cfm) Btuh0 CoolingHeating (none)10481048Area (ft²) Equipment latent load Btuh7373 1564015640Volume (ft³)Air changes/hour 0.220.43 Equipment Total Load (Sen+Lat)Btuh26546 Equiv. AVF (cfm) 58113 Req. total capacity at 0.72 SHR ton2.2 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTrade Trade TRANE Model Cond 4TTR6030J1AHRI ref Coil TEM8A0B30V31++TDR AHRI ref 10149819Efficiency 100 EFF Efficiency 14.0 EER, 16.3 SEER Heating input kW4.8 Sensible cooling Btuh20880Heating output Btuh16378 Latent cooling Btuh8120 Temperature rise °F65 Total cooling Btuh29000Actual air flow cfm231 Actual air flow cfm1000 Air flow factor cfm/Btuh0.014 Air flow factor cfm/Btuh0.056Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 0.72 Job #: 191242 Performed by CJH for: Gelcorp. Industries Avalon by the Beach Custom Home Avalon by the Beach St Lucie County, FL 34949 The EARTHWORKS Group 7410 S US Hwy 1 Suite 104 Port St Lucie, FL 34952 Scale: 1 : 101 Page 1 Right-Suite® Universal 2019 19.0.21 RSU25986 2020-Dec-17 16:21:34 ...alon Custom HVAC calcs EXP.N.rup N Level 1 Family Kitchen Dinin g Master Bdrm Master WIC Master Bath WC Rm LaundryG Hall Garage Fo yer Study Bath 4 1st flr stairs Job #: 191242 Performed by CJH for: Gelcorp. Industries Avalon by the Beach Custom Home Avalon by the Beach St Lucie County, FL 34949 The EARTHWORKS Group 7410 S US Hwy 1 Suite 104 Port St Lucie, FL 34952 Scale: 1 : 101 Page 2 Right-Suite® Universal 2019 19.0.21 RSU25986 2020-Dec-17 16:21:34 ...alon Custom HVAC calcs EXP.N.rup N 2ND Flr Bedroom 3 Bedrm 3 WIC 2nd Flr Stairs Loft 2nd flr hall Bath 3 Bath 2 Bedroom 2 FAMILY RM CLG.