HomeMy WebLinkAboutEnergy Calculation Form & Manual J's (2) f _ I Project Summary Job: o - Wrightsoft° � � By: Dec 15,zols Entire House QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,-FL 34946 Phone:772-466-6799 Fax:772466-6796 Email:QUICKCALCS@AOL.COM ® • • • For: FERSCH RESIDENCE SOUTHWIND TRAIL, FORT PIERCE, FL 34951 N otes: . besi6n infoftation. Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19374 Btuh Structure 13058 Btuh Ducts 3458 Btuh Ducts 4992 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh y Piping 0 Btuh Equipment load 22832 Btuh Use manufacturers data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 17147 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure' 2988 Btuh Ducts 1317. Btuh Heating Cool ingg Central vent(0 cfm) 0 Btuh Area(ftz) 1640 1640 Equipment latent load 4305 Btuh Volume(ft3) 15712 15712 Air changes/hour 0.38 0.20 Equipment total load 21451 Btuh Equiv.AVF (cfm) 100 52 Req. total capacity at 0.70 SHR 2.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1624AJlNA AHRI ref Coil RH1T2417STANJA AHRI ref 7940891 Efficiency 100 EFF' Efficiency 13.0 EER, 16 SEER Heating input, 6.2 ,kW Sensible cooling 16800 Btuh Heating output 21131 Btuh'. Latent cooling 7200 Btuh Temperature rise 24 °F, Total cooling 24000 Btuh Actual air flow 800 cfm Actual air flow 800 cfm Air flow factor 0.035 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ A=, wrightsoft" 2W -D'o- 11:1 L38 Right-Suite®Universal 2017 17.0.08'RSU08101 EADocumnets\Wrightsoft HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W F. -V wrightsoft° Right-J®Worksheet Job: Entire House Date: Dec 15,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name Entire House BEDROOM 3 2 Exposed wall 176.0 ft 25.0 ft 3 Room height 9.6 ft 8.0 ft heat/cool 4 Room dimensions 12.0 x 13.0 ft 5 Room area 1640.0 ft' 156.0 ft' Ty Construction U-value Or HTM Area (W) Load Area (ft 2) Load number (Btuh/fV-°F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 W. _......13A1tocs-.' - 0;143 n'. ._.,_4 00 ._2.19._._. �.21,6. .216___.:__865 .._._473. 0.'.:_ _. :0._._ 0 13A-ocs 0.143 a 4.00 2.19 584 481 1927 1053 104 89 356 195 2 glazing,clr low-e 0.450 a 12.60 24.89 45 3 567 1120 15 1 189 373 11D0 0.390 a 10.92 10.34 17 17 186 176 0 0 0 0 11 11GO 0.540 a 15.12 14:31 41 41 617 584 0 0 0 0 .-_ _ _. _ 473 _, -96 916_ _._ 8650 43 sr. _40D 1 __._384 , 210 13A-4ocs 0.143 w 4.00 2.19 584 489 1956 1069 0 0 0 0 2 glazing,cir low-e 0.450 w 12.60 24.89 75 5 945 1866 0 0 0 0 10.92..._ 10_34_ 20 ._.20. .223 211,___.. _ 0-- _ _.0...-_.____._0 0 __.,0:9Q i_-_224_. .1640 __1.640_. 1469__ ..,3674 . .. 156--___._156-------_140. ...___349 F_. ..._.. 22A-tPh. . _._._...._.. . _.._1.358._ r._ . __38.p2 .. 0.00._. . .1640 _.,. _.. .176 . _..6692 0_ .., 1`�,_. .. ..25 951... .. .0 • ..... . ....... ... -.. _.__._....... _ _- 6 c)AED excursion 397 -37 Envelope loss/gain 16312 11094 2020 1090 12 a) Infiltration 3062 863 383 108 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1100 0 Subtotal(lines 6 to 13) 119374 13058 2403 11198 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 194 98 14 Subtotal 19374 13058 2597 1296 15 Duct loads 118% 38% 3458 4992 18% 38% 464 495 Total room load 22832 18049 3060 1791 Air required(cfm) 800 800 107 79 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2016-Dec-15 11:03:38 .4C�P Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\FERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W wrightsoft Right-J®Worksheet Job: Entire House Date: Dec 15,zols • By: QUICK CALCS, INC. 317 STLUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax:772466-6796 Email:QUICKCALCS@AOL.COM 1 Room name CLST 3 CLST 2 2 Exposed wall 2.0 ft 2.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 2.0 x 9.0 ft 2.0 x 9.0 ft 5 Room area 18.0 ftz 18.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz-°F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NOS Heat Cool Gross N/P/S Heat Cool _ W_. . . _ . . .__ 6 ,W 13A-0ocs.._., __. _.. ...._ ._0143 _..r_._.._4 00.._ _219 _, .-:.0__.: ._ 0 __-6,_.,w,.__ _0 _ .-. __ __._.0. i V1113A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.450 a 12.60 24.89 .0 0 0 0 0 0 0 0 11DO 0.390 a 10.92 10.34 0 0 0 0 0 0 0 0 11GO 0.540 a 15.12 14.31 0 0 0 0 0 0 0 0 0,143 ,s._. ___400 -2.19 __....16 _ ..__ 16 64-•--.. 35 M._.__ _16- __._..16 :_ 64 . _ .:'_35 Vl/ 13A-0acs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.450 w 12.60 24.89 0 0 0 0 0 0 0 0 11 DO _ 0,390. w, 10.92 ----.0,., 0 ..._ 0 0 _. 9 0 _. 0 C__.,. 161k30md.....,.. . . ___..0.032, 0.9,0_._.__,224._.. .<18_._ .__18 _ _ .•16 _ _.. ._.40 :. _18_.._ _..18 _. 16. __.._._ 40. .F...._._ 22A-tah ._ ._. 1358 r.....,_.38.02 0.00. _._,. ,18.,__,�.__2_._._.__:_76 _------18 __._._._.2 ._. .. ...._76 6 c)AED excursion -31 -3 Envelope loss/gain 156 72 156 72 12 a) Infiltration 31 9 31 9 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 187 81 187 81 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -187 -81 -187 -81 14 Subtotal 0 0 0 0 15 Duct loads 1 18% 38%1 0 0 18% 38% 0 0 Total room load 0 0 0 0 Air required(cfm) 0 0 1 10 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft' 2016-Dec-1511:03:38 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 2 E:\Documnets\Wrighlsoft HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W -r- wrightsoft' Right-J®Worksheet Job: Entire House Date: Dec 15,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@\OL.COM 1 Room name BEDROOM 2 LAUNDRYCLST 2 Exposed wall 24.0 ft 2.0 ft 3 Room height 6.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 136.0 ft 11.0 x 2.0 ft 5 Room area 136.0 ftz 22.0 ft' TY Construction U-value Or HTM Area (ft-) Load Area (ft-) Load number (Btuh/ft?°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool _... _ _ _ ._6 .W. _ . 13A119cs _. _.._ , _:0.143.. n .. .4 00...,_ 2,19 .....0_. ___� ._0 _. ..,.,:.0 . ..._.__ 0._._. . ;0.__ 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.450 a 12.60 24.89 0 0 0 0 0 0 0 0 11DO 0.390 a 10.92 10.34 0 0 0 0 0 0 0 0 11 ��-DDD 11G0 0.540 a 15.12 14.31 0 0 0 0 0 0 0 0 W_..__ 13A�ocs.. .:_. ____ .____t)143--s_ _.4OQ..:_..219__,.,. _t38_._w _.m88 _.. ..,._352__ _._193_- 00 �_.0.._____m,_0 W: 13A-4ocs 0.143 w 4.00 2.19 104 89 356 195 16 16 64 35 TG 2 glazing,clr low-e 0.450 w 12.60 24.89 15 1 189 373 0 0 0 0 11DO 0.390w 10.92 10.34_ 0 0 0 -., ,'0. 0 0 _.._ 0 0 C p m _....._.16A 30md - .____,._ .._ 0.032_, _..._ _0,90_:._- 2.24 _. 136 -__v_._.136_____.`__122__,__305,....._.._ 22 .._.__22_:._ _20.__.___A9 F_ 22A-tph _. .. ._ 1.358 _.. ._. ._. 38.02._ 0.00 ._ ..._,1.36 v_ _24- 913 -_. 0 . .... 22 . ..... -2__.... _ 76 __ .._.. ..0 6 c)AED excursion 127 -4 Envelope loss/gain 1932 1192 160 80 12 a). Infiltration 367 104 31 9 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 2300 1296 190 89 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 289 142 -190 -89 14 Subtotal 2589 1438 0 0 15 Duct loads 18% 38% 462 550 18% 38% 0 0 Total room load 3051 1988 0 0 Air required(cfm) 107 88 1 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightt50ft" 2016-Dec-1511:03:38 ACCA Right-Suite®Universal 2017 17.0.08 RSU08101 Page 3 EADocumnetslWrightsoft HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W -rF wrrightsoft, Right-J®Worksheet Date: Entire House Date: Dec 15,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772.466-6796 Email:QUICKCALCS@\OL.COM 1 Room name LAUNDRYROOM BATH 2 2 Exposed wall 6.0 ft 8.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 11.0 x 6.0 ft 1.0 x 82.0 ft 5 Room area 66.0 ft' 82.0 ft' Ty Construction 1-1-value Or HTM Area (ft) Load Area (ftz) Load number (BtutVI't'°F) (BtutVft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W . .13A4ocs. >r_ ._- 0043 p 4.00., _.219._. .:_ .0 __-,_. .0 ,_ 0 _ _'_0_____.___..0 . -0 0. "+ 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 64 47 188 103 2 glazing,clr low-e 0.450 a 12.60 24.89 0 0 0 0 0 0 0 0 11DO 0.390 a 10.92 10.34 0 0 0 0 17 17 186 176 11 11GO 0.540 a 15.12 14.31 0 0 0 0 0 0 0 0 0.143'.._s_ :_.._400:. _ 219...__ _. 0 - __0..... 0 .0 _0 13A-4ocs 0.143 w 4.00 219 48 33 132 72 0 0 0 0 2 glazing,clr low-e 0.450 w 12.60 24.89 15 1 189 373 0 0 0 0 11D0 _.. 0.390 w 10.92,_.._10_34 9_ _.0 .__. .0 __ _._0_... .. _Q._ .. 9-.._._._ 0. _ 0. C......__. 10A,30md.,_, _ .,_.._. ___.,:_0.032,:.. _.0.90........._224 - _.-_.__66,--,.. 66 59._____ 148... _82 __._._._82. 73 . 184 F. 22A-tph._._..,_ _.._ _ ..1.358..._- ._ .38.02. ____0.00_ ._66 _ _6.__6_._._ ..228 ._:._ .0 . 82 _81. 304 - 0 6 c)AED excursion 149 -20 Envelope loss/gain 608 743 751 442 12 a) Infiltration 92 26 122 35 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 700 769 874 476 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 106 70 18 43 14 Subtotal 806 839 892 619 15 Duct loads 18% 38%1 144 321 18% 38% 159 198 Total room load 950 1160 1051 718 Air required(cfm) 1 1 33 51 37 32 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsOft" 2016-Dec-1511:03:38 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 4 EADocumnetslWrightsoft HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W - -wrightsoft" Right-J®Worksheet °b Entire House Date: Dec 15,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772.466-6796 Email:QUICKCALCS ,AOL.COM 1 Room name LINEN KITCHEN 2 Exposed wall 0 It 10.0 ft 3 Room height 8.0 ft heat/cool 12.0 It heat/cool 4 Room dimensions 7.0 x 2.0 ft 12.0 x 10.0 ft 5 Room area 14.0 ftz 120.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ft) Load number (BtuhffFz OF) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-0ocs: ,- _._.__. _..,m_0 143 n 4 00. 2.19 -_,0 .,._,.,_ 0 .__,.-._ .0 0 0 13A-4ocs 0.143 a 4,00 2.19 0 0 0 0 120 105 426 230 2 glazing,clr low-e 0.450 a 12.60 24.89 0 0 0 0 15 1 189 373 11DO 0.390 a 10.92 10.34 0 0 0 0 0 0 0 0 11 11GO, 0.540 a 15,12 14.31 0 0 0 0 0 0 0 0 W........ _13A4ac._.._., 0,143 _s -A00. 2.19 0 .,.. .: ._0 _ - 0 0 0 .__. ._.. 0 __0__0 _.-_._'_0 Ut/ 13A-4ocs 0.143 w 4'00 219 0 0 0 0 0 0 0 0 �L-Gp 2 glazing,clr low-e 0.450 w 12.60 24.89 0 0 0 0 0 0 0 0 11 D0 _-. 0.390 w.--_ 10.92_ 10.34 0 _._. 0 0 _ 0 0 0. _0. C _-.,_. 16A-30md _,_0.032 0.90!_ .229.._--_ 14 ._ ._14 __.,._13_ . .31 „ . 12f1 .___120 .- --_1.08_ ____.269. F. 22A-tPh- ..._...... _.-,1.358,r... .-__38.02 _0.00........... - 14_..._..._ 0. _._ 9.._ _. ..0 .;.._._120 _._. _10 .._ _. 380 . -. , O 6 c)AED excursion -1 -33 Envelope loss/gain 13 30 1097 839 12 a) Infiltration 0 0 230 65 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 200 Subtotal(lines 6 to 13) 13 30 1327 1103 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -13 -30 5 13 14 Subtotal 0 0 1332 1117 151 Duct loads 1 18% 38% 0 0 18% 38%1 2381 427 Total room load 0 0 1570 1543 Air required(cfm) 0 0 1 55 68 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wvrightsoft- 2016-Dec-15 11:03:38 ACCk Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 5 EADocumnets\Wrightsoft HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W -r- wrightsoft, Right-J®Worksheet Job: Entire House Date: Dec 15,2016 QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772466-6796 Email:QUICKCALCS AOL.COM 1 Room name DINING LNING ROOM 2 Exposed wall 14.0 ft 24.0 ft 3 Room height 12.0 ft heat/cool 12.0 ft heaUcool 4 Room dimensions 12.0 x 14.0 ft 15.0 x 24.0 ft ft 5 Room area 168.0 ' 360.0 ft2 Ty Construction U-value Or HTM Area (1112) Load Area (W) Load • number (13tuh1 *F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool - Gross N/PIS Heat Cool Gross N/P/S Heat Cool 6 :W _ 1.A-4ocs_....,,. _:0;:143._ n_ -AA, 219_. _ .9 ._: 0 m;.. 0 .,: . ...0_ 0_._.__._._0 13A-4ocs 0.143 e 4.00 2.19 168 127 509 278 0 0 0 0 2 glazing,clr low-e 0.450 a 12.60 24.89 0 0 0 0 0 0 0 0 11DO 0.390 a 10.92 10.34 0 0 0 0 0 0 0 0 11 11G0. ._._ . _. .- --_._0.540 e._ 15.12 14.31 __.._ 41 41 617.__. _.584 _ _0._.__ _0'__ _-_ _.....0 W ._.,, 13A-4ocs....._ .__.. _._._0.143__.s. _4.00 219 0 0 0 _. 0._ ._ --. 0 _ .0 ____ 0 .....__. '0 t13A4ocs 0.143 w 4.00 219 0 0 0 0 288 238 951 520 2 glazing,cir low-e 0.450 w 12.60 24.89 0 0 0 0 30 2 378 747 11DO_._._. 0.390 w 10.92_ 10,34 0 0 _0_, 0__._ _20 . _20 223 211 16A-30md: ___. ._- _ ._.0.032!._._ . _..0.90. ,;:_.2.24 __' _168 __168 151 . -_ . 376 _.__.360.__. __. 360 . ._..._323. ._ __ ._806. F._._ .. 22Atoh 1,358__..-._ . _38.02 .__.._0.00168 _; 14 532_..._._._._.0__ _._...360__.___._24.._.._ ___913 _ _._.... 0. 6 c)AED excursion -54 213 Envelope loss/gain 1809 1184 2787 2497 12 a) Infiltration 322 91 551 155 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 900 Subtotal(lines 6 to 13) 2131 1275 3338 3552 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 7 17 14 Subtotal 2131 1275 3346 3570 15 Duct loads 18% 38% 380 487 18% 38% 597 1365 Total room load 2511 1762 3943 4934 Air required(cfm) 1 88 78 138 219 Calculations approved byACCA to meet all requirements of Manuai J 8th Ed. 411_ vvrighitSoft"' 2016-Dec-15 11:03:38 Right-Suite@ Universal 2017 17.0.08 RSUD8101 Page 6 ACCA E:IDocumnetslWrightsoft HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W -�wrightsoft, Right-J®Worksheet Date: Entire House Bate: Dec 15,zo,s By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS ,AOL.COM 1 Room name HALL MASTER WIC 2 Exposed wall 0 ft 6.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 4.0 x 12.0 ft 11.0 x 6.0 ft 5 Room area 48.0 ft2 66.0 ft2 Ty Construction Ll-value Or HTM Area (ft2) Load Area (W) Load number (Btuh/ft'�-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VJ 13A�ocs _ :,_ 0:143. .n�._. _4 00 .....219 _. .., ..0 0 0 _- . _. 0. .... s�..0.. 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.450 a 12.60 24.89 0 0 0 0 0 0 0 0 11DO 0.390 a 10.92 10.34 0 0 0 0 0 0 0 0 11 11GO 0.540 a 15.12 14.31 0 0 0 0 0 0 0 0 W__ _13A-4ocs __:.. ___:0,143'_,.s ._.. 4.00___'2.19 .._ ____0 n._ 0 _ .._..w 0.. - 0 . _0 __ 0 _� _0. . _. ...0 T:f-D 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 48 48 192 105 2 glazing,clr low-e 0.450 w 12.60 24.89 0 0 0 0 0 0 0 0 11130 0.390 w_ 10.92__ 10.34. 0 0 0 0 0 _ 0 _0. 0 ,16A 30md_.;__q_ . ___ ___,0;032 _ _..._ _0.90 _.2 24; , -,_..._____48 _:__43 __. ---108_ _66 - _66 F- 22A-tph_ 1.358 38.02 ._ .0.00 __.- ..48 _. ..0 . _.,.0 . _ - 0 66 .r__...._6 . _ .. 228 .0 6 c)AED excursion 4 -11 Envelope loss/gain 43 103 479 241 12 a) Infiltration 0 0 92 26 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 43 103 571 267 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -43 -103 0 0 14 Subtotal 0 0 571 267 15 Duct loads 118% 38% 0 0 18% 38% 102 102 Total room load 0 0 673 370 Air required(cfm) 0 0 24 16 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightso$t- 2016-Dec-15 11:03:38 ^ � Right-Suite®Universal 2017 17.0.08 RSU08101 Page 7 E:1Documnets\Wrightsott HVACIFERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W - -wrightsoft` Right-JO Worksheet Job: Entire House Date: Dec 15,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS aAOL.COM 1 Room name MASTER BEDROOM' MASTER BATH 2 Exposed wall 32.0 ft 21.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 16.0 x 16.0 ft 11.0 x 10.0 ft 5 Room area 256.0 ftz 110.0 ft2 Ty Construction U-value Or HTM Area (ft-) Load Area (f?) Load number (Btuh/ft?°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 :W. .-. 1*4662 glazing,g,clr low-e _ ...,r>0.143 e Y 12.00 22.89 _.19 128 ..._._:_113 452 .... 247 373 _0. ..._.800 _ a_.350 �90. 11D0 0.390 a 10.92 10.34 0 0 0 0 0 0 0 0 11 11GO 0.540 e__ 15.12 14.31 0 0 0 _ 0 0._ 0 _._ 0 ....0. W,_.. :_13A4ocs� _ a _ 0°143_ S-w.:. 4.00 ,.. _2.19 w . - ;0 _: 0 .-_.mz.,..0_.' _ .0 �< ._ 0 _ 0_`: `_.__!0 V)/ 13A4ocs 0.143 w 4.00 219 0 0 0 0 80 65 260 142 (L�_p 2 glazing,cir low-e 0,450 w 12.60 24.89 0 0 0 0 15 1 189 373 11D0 0.390 w 10.92_ 10.34 0 _0 _ 0 0 0 .0 _0 0 u16A 30md ':� ._ _._0032 _ __..0 9Q .._2 24:m �256.. 256__. ..�229 � .573__-;._. 110_ _�10 ___ _99_ Fa_.. 22A tph _.. _ . 1.358 _r . . 38.02 �0.00 256 a 32 1217 ,.. ,..0 110> 21. _ 799 0 - .r,. ,.. _ 6 c)AED excursion -53 132 Envelope loss/gain 2600 1421 1699 1087 12 a) Infiltration 490 138 322 91 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 3090 1560 2020 1177 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3090 1560 2020 1177 151 Duct loads 1 18% 38%1 552 596 18% 38% 361 450 Total room load 3642 2156 2381 1627 Air required(cfm) 1281 96 83 72 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsmft" 2016-Dec-1511:03:38 Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 8 �� E:\Documnets\Wrightsoft HVACWERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W Duct System Summary - -� � � Date:e: Dec 15,2016 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax:772466-6796 'Email:QUICKCALCS a(�OL.COM ■ • • • For: FERSCH RESIDENCE SOUTHWIND TRAIL, FORT PIERCE, FL 34951 Heating Cooling External static pressure 1.00 in'H2O 1.00 in H2O ' Pressure losses - 0 in.H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply/return available pressure 0.500/0.500 in H2O . 0.500/0.500 in H2O Lowest friction rate 1.600 in/100ft 1,000 in/100ft Actual air flow 800 cfm 800 cfm Total effective length(TEL) 173 ft 54 e � i • Design Htg Clg Design ' Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln(ft) Trunk BATH 2 h 1051 37 32 1.000 4.0 Ox 0 VIFx 11.8 115.0 st4 BEDROOM 2 h 3051 107 •88 1,000 5.0 Ox0 VIFx 10.4 115.0 SO BEDROOM 3 h 3060 107 79 1.000 ' 5.0 Ox.0 VIFx 11.0 115.0 st1 DINING h 2511 88 78 1.000 . 5.0 Ox0 VIFx 24.6 115.0 st2 KITCHEN C 1543 55 68 1.000 4.0 Ox 0 VIFx 23.4 115.0 st2 LAUNDRY ROOM C 1160 33 �51 1.000 4.0 Ox 0 VIFx 13.4 115.0 st1 LIVING ROOM C 2467 69 109 1.000 5.0 Ox0 VIFx 20.2 115.0 st2 LIVING ROOM-A C 2467 69 109 1.000 5.0 Ox 0 VIFx 21.8 115.0 " st2 MASTER BATH h 2381 83 72 1.000 5.0 Ox 0 VIFx 37.9 135.0 st3 • MASTER BEDROOM h 3642 128 96 1.000 6.0 Ox0 VIFx 34.3 135,0 st3 MASTER WIC h 673 24 16 1.000 4.0 Ox0 VIFx 37.2 135.0 st3 4 Y ® • • Trunk Htg Clg, Design Veloc Diam H x W Duct Name Type (Cfm) (Cfm) FR (fpm) (in) (in) Material Trunk st3 Peak AVF 235 184 1.000 878 7.0 0 x 0 VInIFIX st2 st1 Peak AVF 284 251:• 1.000 814 8.0 0 x 0 VinIFIX st2 Peak AVF 516 549 1.000 832 11.0 0 x 0 VinlFlx Bold(italic values have been manually overridden 2016-Dec-15 11:03:39 ,41. - - wrightsoft5 Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 1 + �* E:\Documnets\Wrightsoft HVAC\FERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) ` (in) Opening(in) Matl Trunk rb1 ox0 800 800 0 0 0 0 Ox 0 VIFx . .� Wry htsoft' 2016-Dec-1511:03:39 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 2 " ✓�✓� E:\DocumnetslWrightsoft WACTERSCH RESIDENCE.rup Calc=MJ8 Front Door faces: W