Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutSES Foam r
ICC EVALUATION • • - - • - e s • Trusted,.
C SERVICE
ICC-ES Report ESR-3315'
:11 • .•• 1 • d',08/201,0
This ropaft is suoiedld,ienewal 08/2018
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
SECTION:07 2100—THERMAL INSULATION
REPORT HOLDER: . ;
SES FOAM
4008 LOUETTA ROAD;#538
SPRING,TEXAS 77388-4405
EVALUATION SUBJECT:
SUCRASEALTM 0.5 AND SES FOAM 0.5 LB SPRAY:
SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION
-r
ICC ICC ICC a �'
c
PMG LIS'lED
Look for the trusted marks of Conformity! :_
"2014 Recipient of Prestigious Western States Seismic Policy Council AxIugs
:®�
WSSPC Award in Excellence" CODE'COUN{AL
� � A Subsidiary of CooEcout�cie
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not g`c"""a"°d
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or aCPO. C
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report. �C99Fr"N ,�,eamccN
Copyright© 2016 ICC Evaluation Service, LLC.All rights reserved.
U
11 'ICC
.-$;_
SERVICE
Widely
IMES Evaluation Report ESR-3376
Reissued August 2016
This report is subject to renewal August 2018.
www.1cc-es.org 1 (800)423-6587 1 (562)699-0543 A Subsidiary of the International Code Council®
DIVISION: 07 00 00—THERMAL AND MOISTURE crawl spaces when installed as described in Section 4.4.
PROTECTION Under the IRC, the insulation may be used as air-
Section:07 21 00—Thermal Insulation impermeable insulation when installed as described in
Section 3.4. SES Foam 0.5 lb Spray is identical to
REPORT HOLDER: SucrasealTA° 0.5. Wherever SucrasealTM 0.5 is mentioned,
the same property applies to SES Foam 0.5 lb Spray.
SES FOAM 4008 LOUETTA ROAD,#538 3.0 DESCRIPTION
SPRING,TEXAS 77388-4405 3.1 General:
(713)239=0252 SucrasealTM 0.5 spray foam insulation is a two-
www.sesfoam.com component, open cell, one-to-one-by-volume spray-
EVALUATION SUBJECT: applied polyurethane foam system with a nominal density
of 0.5 pcf(8.0 kg/m ). The insulation's liquid components
SUCRASEALTm 0.5 AND SES FOAM 0.5 LB SPRAY: are supplied in'nominally 55-gallon drums, labeled as "A"
SPRAY-APPLIED POLYURETHANE FOAM PLASTIC component or "B" component. The insulation components
INSULATION have a shelf life of six months when stored in unopened
containers at temperatures between 70°F (21°C) and 90°F
1.0 EVALUATION SCOPE (32-C).
The attributes of the insulation have been verified as
1.1 Compliance with the following codes: conforming to the provisions of ICC 700-2008 Section
■ 2012 and 2009 International Building Code®(IBC) 703.2.1.1.1(c) as an air impermeable insulation. Note that
decisions on compliance for those areas rest with the user
■ 2012 and 2009 International Residential Codee(IRC) of this report. The user is advised of the project-specific
■ 2012 and 2009 International Energy Conservation provisions that may be contingent upon meeting specific
® conditions, and the verification of those conditions is
Code (IECC) outside the scope of this report. These codes or standards
E. Other Codes(see Section 8.0) often provide supplemental information as guidance.
Properties evaluated: 3.2 Surface-burning Characteristics:
■ Surface-burning characteristics At a maximum thickness of 4 inches (102 mm) and a
nominal density of 0.5 pcf, the insulation has a flame-
■ Physical properties spread index of 25 or less and a smoke-developed index of
450 or less when tested in accordance with ASTM E84.
■ Thermal resistance(R-values) Thicknesses for wall cavities and ceiling cavities are not
■ Air permeability limited when the insulation is covered with a minimum
/z-inch-thick (12.7 mm) gypsum board installed in
■ Exterior walls in Types I-IV construction accordance with the applicable code.
1.2 Evaluation to the following green standard: 3.3 Thermal Resistance(R-values):
■ 2008 ICC 700 National Green Building Standard TM ([CC The insulation has thermal resistance(R-values)at a mean
700-2008) temperature of 75°F(24°C)as shown in Table 1.
Attributes verified: 3.4 Air Permeability:
■ See Section 3.1 The insulation, at a minimum thickness of 3 inches
(76 mm), is considered air-impermeable in accordance
2.0 USES with IRC Section R202, based on testing in accordance
with ASTM E283.
SucrasealTM 0.5 spray polyurethane foam plastic insulation 3.5 DC 316 Fireproof Paint:
is used as a nonstructural thermal insulating material in
buildings of Type I, II, III, IV and V(IBC) construction, and DC 315 Fireproof Paint is manufactured by International
in dwellings built under the IRC. The insulation is for use in Fireproof Technology, Inc., and is a water-based coating
wall cavities and floor/ceiling assemblies, and in attics and supplied in 5-gallon (19 L) pails and 55-gallon (208 L)
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed MRS
as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as
to any finding or other matter in this report,or as to any product covered by the report. 0
Copyright©2016 ICC Evaluation Service,LLC. All rights reserved. Page 1 of 4
ESR-3376 I Most Widely Accepted and Trusted Page 2 of 4
drums and has a shelf life of six months when stored in a coating. The coating is applied in one or more coats with
factory-sealed container at temperatures between 50oF brush, roller or airless spray equipment.
(10°C)and 90°F(32°C). 4.3.2.2 Application with FireShell®F10E:The thickness
3.6 FireShell®F10E: of the foam plastic applied to the underside of roof
2, and is a water- sheathing and to vertical wall surfaces must not exceed
FireShell®F10E is manufactured by TPR
based coating supplied in 5-gallon (19 L) pails and 11 /2 inches (292 mm). The foam plastic must be covered
55-gallon (208L) drums and has a shelf life of one year on all surfaces with FireShell® F10E at a minimum
when stored in a factory-sealed container at temperatures thickness of 20.0 mils (0.51 mm) wet film thickness
above 45°F(7°C). [14 mils (0.36 mm) dry film thickness] with a minimum
application rate of 1.25 gal/100 ft2. The coating must be
4.0 INSTALLATION applied over the SucrasealTM 0.5 insulation in accordance
4.1 General: with the coating manufacturer's published instructions and
TM this report. Surfaces to be coated must be dry, clean and
Sucraseal 0.5 spray insulation must be installed in free of dirt, loose debris and other substances that could
accordance with the manufacturer's published installation interfere with adhesion of the coating. The coating is
instructions and this report. A copy of the manufacturer's applied in one or more coats with brush, roller or airless
published installation instructions must be available at all spray equipment.
times on the jobsite during installation.
4.2 Application: 4.4 Attics and Crawl Spaces:
The insulation is spray-applied at the jobsite using a 4.4.1 Application with a Prescriptive Ignition Barrier:
volumetric positive displacement pump as identified in the When SucrasealTM 0.5 spray is installed within attics and
SucrasealTM 0.5 spray application manual. The insulation crawl spaces, where.entry is made only for service of
components must be stored at temperatures between utilities, an ignition barrier must be installed in accordance
70°F (21°C) and 90°F (32°C) for several days before with IBC Section 2603.4.1.6 or IRC Section R316.5.3 or
application. The insulation must not be used in areas that R316.5.4, as applicable, except when the installation is in
have maximum in-service temperatures greater than 180°F accordance with Section 4.4.2 or Section 4.4.3. The
(82°C). The insulation must not be used in electrical outlet ignition barrier must be consistent with the requirements
or junction boxes or in contact with water (e.g., rain, for the type of construction required by the applicable
condensation, ice, snow) or soil. The substrate must be code, and must be installed in a manner so that the foam
free of moisture, frost or ice, loose scales, rust, oil, grease plastic insulation is not exposed. SucrasealTM 0.5 spray
or other surface contaminants. The insulation can be insulation at a minimum thickness of 3 inches (76 mm)
installed in one pass to the maximum thickness. The may be installed in unvented attics in accordance with
spray-applied foam insulation must be protected from 2012 IRC Section R806.5 (2009 IRC Section R806.4), as
i weather during and after installation. applicable.
4.3 Thermal Barrier: 4.4.2 Application without a Prescriptive Ignition
Barrier: Where the spray-applied insulation is installed in
4.3.1 Application with a Prescriptive Thermal Barrier: accordance with this section or Section 4.4.3, the following
SucrasealTM 0.5 spray insulation must be separated from conditions apply:
the interior of the building by an approved thermal barrier
of 1/2-inch-thick (12.7 mm) gypsum wallboard or an a) Entry to the attic or crawl space is to service utilities,
equivalent 15-minute thermal barrier complying with, and and no storage is permitted.
installed in accordance with, IBC Section 2603.4 or IRC b) There are no interconnected attic or crawl space
Section R316.4, as applicable, except when the installation
is in accordance with Section 4.3.2.Within an attic or crawl areas.
space, installation must be in accordance with Section 4.4. c) Air in the attic or crawl space is not circulated to other
4.3.2 Application without a Prescriptive Thermal parts of the building.
Barrier:The prescriptive 15-minute thermal barrier may be d) Attic ventilation is provided when required by IBC
omitted when installation is in accordance with this section. Section 1203.2 or IRC Section R806, except when
The insulation and coating may be spray-applied to the air-impermeable insulation is permitted in unvented
interior facing of walls and the underside of roof sheathing attics in accordance with 2012 IRC Section R806.5 or
or roof rafters, and in crawl spaces, and may be left 2009 IRC Section R806.4. Under-floor (crawl space)
exposed as an interior finish without a prescribed ventilation is provided when required by IBC Section
15-minute thermal barrier or prescribed ignition barrier 1203.3 or IRC Section R408.1,as applicable.
when the installation is in accordance with either Sections
4.3.2.1 or 4.3.2.2. e) Combustion air is provided in accordance with
4.3.2.1 Application with DC 315 Fireproof Paint: The International Mechanical Code®Section 701.
thickness of the foam plastic applied to the underside of In attics, the insulation may be spray-applied to the
roof sheathing and to vertical wall surfaces must not underside of roof sheathing or roof rafters, and/or vertical
exceed 111/2 inches (292 mm). The foam plastic must be surfaces, and in crawl spaces the insulation may be spray-
covered on all surfaces with DC 315 Fireproof Paint at a applied to the underside of floors and/or vertical surfaces
minimum thickness of 18.0 mils (0.47 mm) wet film as described in this section. The thickness of the foam
thickness [12 mils (0.30 mm) dry film thickness] with a plastic applied to the underside of the top of the space
minimum application rate of 1.12 gal/100 fe. The coating must not exceed 12 inches(305 mm).The thickness of the
must be applied over the SucrasealTM 0.5 insulation in foam plastic applied to vertical surfaces must not exceed
accordance with the coating manufacturer's published 111/2 inches (292 mm). The foam plastic may be installed
instructions and this report. Surfaces to be coated must be without a covering or coating. The insulation may be
dry, clean and free of dirt, loose debris and other installed in unvented attics in accordance with 2012 IRC
substances that could interfere with adhesion of the Section R806.5 (2009 IRC Section R806.4). The ignition
ESR-3375 I Most Widely Accepted and Trusted Page 3 of 4
barrier in accordance with IBC Section 2603.4.1.6 or IRC 6.0 EVIDENCE SUBMITTED
Section R316.5.3 may be omitted. 6.1 Data in accordance with the ICC-ES Acceptance
4.4.3 Use on Attic Floors: SucrasealTM 0.5 spray Criteria for Spray-applied Foam Plastic Insulation
insulation may be installed exposed at a maximum (AC377), dated November 2012 (editorially corrected
thickness of 111/2 inches (292 mm) between joists in attic April 2013), including reports of tests in accordance
floors. The ignition barrier in accordance with.IBC Section with Appendix X of AC377.
2603.4.1.6 or IRC Section R316.5.3 may be omitted. The 6.2 Reports of room corner fire-testing in accordance with
insulation must be separated from the interior of the NFPA 286.
building by an approved thermal barrier.
4.5 Exterior Walls of Type 1,11,111 and IV Construction: 6.3 Report of air permeance testing in accordance with
ASTM E283.
4.5.1 General:When used on walls of Type I, 11, III and IV 6.4 Report of potential heat testing in accordance with
exterior wall construction, the SucrasealTM 0.5 spray- NFPA 259.
applied foam insulation must comply with Section
2603.5 of the IBC and this section. The potential heat 6.5 Report of fire propagation testing in accordance with
of SucrasealTM 0.5 spray-applied foam insulation is NFPA 285.
466 Btu/ftz(5.26 MJ/mZ) per inch of thickness when tested 6.6 Engineering evaluation extending NFPA 285 testing
in accordance with NFPA 259. to various exterior wall constructions.
4.5.2 Specific Wall Assemblies: Wall assemblies must 7.0 IDENTIFICATION
be as described in Table 2.
Components of the SucrasealTM 0.5 spray polyurethane
5.0 CONDITIONS OF USE foam plastic insulation are identified with the
The SucrasealTM 0.5 spray polyurethane foam plastic manufacturer's name (SES Foam) and address; the date
insulation described in this report complies with, or is a of manufacture or the lot number; the product trade name
suitable alternative to what is specified in, those codes (Sucraseal'rm 0.5); the mixing instructions; the density; the
listed in Section 1.0 of this report, subject to the following flame-spread and smoke-developed indices; and the
conditions: evaluation report number(ESR-3375).
5.1 The insulation must be installed in accordance with 8.0 OTHER CODES
the manufacturer's published installation instructions, In addition to the codes referenced in. Section 1.0, the
this evaluation report and the applicable code. If there products in the report were evaluated for compliance with
are any conflicts between the manufacturer's the requirements of the following codes:
published installation instructions and this report, this
report governs. ■ 2006 International Building Code®
5.2 The insulation must be separated from the interior of 0 2006 International Residential Code®
the building by an approved 15-minute thermal ■ 2006 International Energy Conservation Code®
barrier, as described in Section 4.3.1, except when
the installation is in accordance with Section 4.3.2. The products comply with the above mentioned codes as
Installation in an attic or crawl space must be as described in Sections 2.0 through 7.0 of this report, with
described in Section 4.4. revisions as noted below:
5.3 The insulation must not exceed the thicknesses noted • Application with and without a Prescriptive Thermal
in Sections 3.2,4.3, and 4.4. Barrier: See Section 4.3, except the approved thermal
barrier must be installed in accordance with Section
5.4 The insulation must be protected from exposure to the R314.4 of the 2006 IRC.
weather during and after application.
■ Application with a Prescriptive Ignition Barrier: See
5.5 The insulation must be applied by contractors certified Section 4.4.1, except an ignition barrier must be
by SES Foam. installed in accordance with Section R314.5.3 or
5.6 Use of the insulation in areas where the probability of R314.5.4 of the 2006 IRC.
termite infestation is "very heavy' must be in ■ Application without'a Prescriptive Ignition Barrier:
accordance with 2012 IBC Section 2603.9 (2009 IBC See Section 4.4.2, except that combustion air is
Section 2603.8)or IRC Section R318.4, as applicable. provided in accordance with Sections 701 and 703 of
5.7 Jobsite certification and labeling of the insulation must the 2006 IECC.
comply with IRC Sections N1101.4 and N1101.4.1 ■ Protection against Termites:,See Section 5.6, except
and IECC Sections R303.1.1 and 303.1.1.1, as use of the insulation in areas where the probability of
applicable. termite infestation if"very heavy" must be in accordance
5.8 When use is on exterior wall of buildings of Type I, 11, with Section R320.5 of the 2006 IRC.
III or IV construction, construction must be as ■ Jobsite Certification and Labeling: See Section 5.7,
described in Section 4.5 and Table 2. except jobsite certification and labeling must comply
5.9 A vapor retarder must be installed in accordance with with Sections 102.1.1 and 102.1.1.1, as applicable, of
the requirements of the applicable code. the 2006 IECC.
5.10 SucrasealTM 0.5 spray polyurethane foam plastic
insulation is produced in St. Louis, Missouri, under a
quality-control program with inspections by ICC-ES.
ESR-3375 I Most Widely Accepted and Trusted Page 4 of 4
TABLE 1—THERMAL RESISTANCE(R-VALUES'.2)
THICKNESS(inches) R-VALUE(°F•ft2•h/Btu)
1 4.0
2 7.6
3 11
3.5 13
4 15
5 19
6 22
7 26
8 30
9 33
10 37
11 41
12 44
For SI: 1 inch=25.4 mm,1°F•ft2•h/Btu=0.176 110K•m2/W.
'R-values are calculated based on tested K values at 1-and 3.5-inch thicknesses.
2R-values greater than 10 are rounded to the nearest whole number.
TABLE 2—NFPA 285 COMPLYING EXTERIOR WALL ASSEMBLIES
WALL COMPONENT MATERIALS
1—Concrete wall
2—Concrete Masonry wall
Base wall system—Use either 3—1.layer of 5/8-inch thick Type X gypsum wallboard installed on the interior side of minimum 3 5/8 inch
1,2,or 3 deep minimum 20 gauge thick steel studs spaced a maximum of 24-inch on center.Lateral bracing
installed minimum every 4 ft.vertically or as required.Wall stud cavities shall be filled at each floor line with
minimum 4 Ib/ft'mineral-fiber insulation friction fit between steel wall studs.
Resilient Channel—For use 1—None
with Base Wall System 3 above 2—Double leg"hat"shaped steel resilient channel installed perpendicular to the wall studs(interior side
—Use either 1 or 2 only)and spaced a maximum of 24-inches on center between steel studs and Type X gypsum wallboard.
Entire perimeter of window opening to be framed with resilient channel.
Perimeter Fire Barrier System Perimeter fire barrier system complying with Section 715.4 of the 2012 IBC shall be installed to fill the void
between the edge of the concrete floor slab and the interior surface of the exterior wall assembly.
Full wall stud cavity depth or less of SucraSeaP 0.5 spray-applied foam plastic insulation applied using
Wall Stud Cavity Insulation exterior gypsum sheathing as the substrate and covering the width of the cavity and the inside of the steel
wall stud framing flange.
Exterior sheathing—For Base '/,-inch thick T e X exterior
Wall System 3 above YP type gypsum sheathing complying with ASTM C1177.
1—Any non-combustible exterior wall covering material
Exterior Wall Covering—Use 2—Any non-combustible exterior wall covering system with a combustible WRB that has successfully been
either 1,2,or 3 tested in accordance with NFPA 285.
(see Note 1 below) 3—Metal Composite Material(MCM)Mitsubishi Plastic Composites America,Inc.,Alpolic/fr wall panels
(see ICC-ES ESR-2653)or Alcoa Architectural Products Reynobond FR 6-mm panels(see ICC-ES ESR-
3435)where there is no exterior insulation in the cavity behind the panels.
Flashing of window,door and As an option,flash around window,door and other exterior penetrations with limited amounts of maximum
other exterior wall penetrations. 12-inch wide acrylic,asphalt or butyl-based flashing tape or liquid applied membrane material.
For SI: 1 inch=25.4 mm;1 pcf=16.0 kg/m'.
Note 3: Exterior wall coverings shall be installed in accordance with the manufacturer's installation requirements and must comply with the
applicable provisions of IBC Chapter 14 and IRC Chapter 7.
e
ICC EVALUATION
SERVICE
Most Widely Accepted . .
IMES Evaluation Report ESR-3375 FBC Supplement
Reissued August 2016
Revised August 17, 2016
This report is subject to renewal August 2018.
www.icc-es.org 1 (800)423-6587 1 (562)699-0543 A Subsidiary of the International Code Council°
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
Section:07 21 00—Thermal Insulation
REPORT HOLDER:
SES FOAM
4008 LOUETTA ROAD,#538
SPRING,TEXAS 77388-4405
(713)239-0252
www.sesfoam.com
EVALUATION SUBJECT:
SUCRASEALTM 0.6 AND SES FOAM 0.5 LB SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that SucraSeal 0.5 spray polyurethane foam plastic
insulation, recognized in ICC-ES master evaluation report ESR-3375, has also been evaluated for compliance with the codes
noted below.
Applicable code editions:
■ 2014 Florida Building Code—Building
■ 2014 Florida Building Code—Residential
2.0 CONCLUSIONS
The SucraSeal 0.5 spray polyurethane foam plastic insulation (also known as SES Foam 0.5 lb Spray), described in
Sections 2.0 through 7.0 of the master evaluation report ESR-3375, complies with the Florida Building Code—Building and
the Florida Building Code—Residential, provided the design and installation are in accordance with the 2012 'International
Building Codee (IBC) and 2012 International Residential Codee (IRC) provisions noted in the master report under the
following condition:.
Installation must meet the requirements of Sections 1403.8 and 2603.9 of the Florida Building Code—Building and
Sections R318.7 and R318.8 of the Florida Building Code—Residential, as applicable.
Use of Sucraseal 0.5/SES Foam 0.5 lb spray-applied polyurethane foam plastic insulation has also been found to be in
compliance with the High-Velocity Hurricane Zone provisions of the Florida Building Code—Building and the Florida Building
Code—Residential.
For products falling under Florida Rule 9N-3, verification that the report holder's quality-assurance program is audited by a
quality-assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report, reissued August 2016.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed ��„
as an endorsement of the subleci of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as _A
to any finding or other mailer in this repot!,or as to any product covered by the repot!. nW rx 4 ��
Copyright 0 2016 ICC Evaluation Service,LLC. All rights reserved. Page 1 of 1
l tICC EVALUATION
c
c SERVICE
ICC-ES Evaluation Report ESR-3375 Seal and Insulate with
ENERGY STWSupplement
Reissued August 2016
This report is subject to renewal August 2018.
www.icc-es.org 1 (800)423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council°
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
Section:07 21 00—Thermal Insulation
REPORT HOLDER:
SES FOAM
4008 LOUETTA ROAD,#538
SPRING,TEXAS 77388-4405
.(713)239-0252
www.sesfoam.com
EVALUATION SUBJECT:
SUCRASEAL7m 0.5 AND SES FOAM 0.5 LB SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC-
INSULATION
1.0 EVALUATION SCOPE
Conformance to the following:
Seal and Insulate with ENERGY STAR® Program—Definitions and Testing Requirements for Residential Insulation,
Version 1.0
Properties evaluated:
■ Thermal resistance
■ Surface-burning characteristics
2.0 PURPOSE OF THIS SUPPLEMENT
This supplement is issued to certify that the insulation products described in Sections 2.0 through 8.0 of the master report
ESR-3375 have been reviewed for compliance with the requirements of the Seal and Insulate with ENERGY STAR®
Program, as set forth in the document Definitions and Testing Requirements for Residential Insulation, Version 1.0. The
insulation product covered by this supplement is defined as"Spray or Pour Foam Insulation."
The requirements for testing laboratory qualification and product sampling, as well as the specific material and test
standards and editions used in this evaluation, are as set forth in the applicable documentation noted in Section 6.0 of the
master evaluation report.
3.0 DEFINITIONS
The following definitions are from Definitions and Testing Requirements for Residential Insulation, Version 1.0, and are
applicable to the subject of this report.
3.1 General Definitions:
Insulation: Any material mainly used to slow down heat flow. It may be mineral or organic, fibrous, cellular, or reflective
(aluminum foil). It may be in rigid,semi-rigid,flexible,or loose-fill form.
3.2 Insulation Product Definitions:
Spray or Pour Foam Insulation:A thermal insulating material that is sprayed or poured(as a gel or foamy liquid)into place,
and expands or sets into a cellular foam and cures at the point of installation through a chemical reaction. Foamed materials
include,but are not limited to polyurethane, polyisocyanu rate, phenolic, and cementitious insulation.
3.3 Insulation Performance Definitions:
R-value:The inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a
unit temperature difference between the two surfaces, under steady state conditions, per unit area. For the purposes of the
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not spectf cally addressed,nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as poi►
to any finding or other matter in this report,or as to any product covered by the report. ma uV
Copyright©2016 ICC Evaluation Service,LLC. All rights reserved. Pagel of 6
ESR-3375 I Most Widely Accepted and Trusted Page 2 of 6
Seal and Insulate with ENERGY STAR®program, Imperial units will only be accepted[(h-ft2-°F)/Btu].
Smoke-Development Index: The characteristic of a material to emit'smoke when exposed to flame or fire compared to red
oak and inorganic cement.
Flame-Spread Index: The characteristic of a material to resist the spreading of flames when exposed to flame or fire
compared to red oak and inorganic cement.
3.4 Thermal Resistance:
The insulation has the thermal resistance R-values as noted in Table 1 of ESR-3375, based upon testing.
3.5 Installation:
3.5.1 General: The installation of the insulation must be in accordance with the requirements set forth in Sections 4.0 and
5.0(as applicable)of ESR-3375.The insulation is manufactured on-site by spray polyurethane foam applicators meeting the
qualification requirements of SES Foam. The following information on personal protective equipment and ventilation
requirements is reprinted from the SES Foam published installation instructions:
"F. SAFETY
3. PERSONAL PROTECTIVE EQUIPMENT(PPE):
a. Skin:Wear gloves, coveralls, apron and boots as necessary to prevent contact of liquid components or partially-cured
SPF with skin.When handling liquid components,gloves should be made of nitrile, neoprene, butyl or PVC.
b. Eyes: Protect eyes while handling liquid components or spraying with safety goggles or safety goggles and a face
shield. During spray application,eye protection may be provided by a full-face or hood respirator.
c. Respiration: Firms engaged in the application of SES Foam systems must have a written respiratory protection
program for employees engaged in handling or applying SES Foam materials. Depending on the situation, respiratory
protection may include dust masks, air-purifying respirators (APR), powered air-purifying respirators (PAPR), or
supplied-air respirators(SAR).
4. VENTILATION: Provide ventilation and other engineering controls to exhaust vapors from work areas and to protect
building occupants and other trades."
3.6.2 Occupancy Time after Installation: The re-entry or re-occupancy time shall be in accordance' with the
manufacturer's installation instructions,which state the following:
"G. RE-ENTRY
SucrasealTM 0.5 reacts and cures within seconds of application. Re-entry times will vary depending on factors including
ventilation. Typically, ventilation is continued for 24 hours following the conclusion of spray application and re-entry may
occur at that time."
3.5.3 Figures:The figures shown represent general installations of the insulation in the following applications: above-grade
wall, below-grade wall, vented and unvented crawl space, unvented cathedral ceiling, and vented and unvented attic.These
figures are for illustration purposes and are not to be construed or used as construction documents.
This supplement expires concurrently with the master report, reissued August 2016.
ESR-3375 Most Widely Accepted and Trusted Page 3 of 6
°00 Og00 OOa. UO Opo 00 00 C0 op o4C Q
O 0°Op G1 000�0000 °�O°Op O00p O0a0OOQ O00p O 00p0
0 00 .00 00 0 O06 O°° 00 OO O00 000 O
€ \p00000°00 Oki
'00000 00000000Oo0a000000000000000 °
00
000p 00O Cy O000 - 0000000
o O o0 oc o oe
I Q0000O00
i p000a OO
o°°o o o°0 o Interior Partition
03 0000°0
?0 000000
j 0 00a00 - Interior Finished Surface
°o 000000 a (1/2-inch Sheetrock)
op° 0p°
00000000
00000
0 o 000
i0000�000 SUCRASEAL7M0.5or
0.00 0 SES Foam 0.5 lb Spray
0�0000 '00 .
f O/000 Ooo
{ o n o°a°o, Exterior Sheathing
0000000
_. i 10s° o°y,.n°o
SUCRASEAJMo.5 ABOVE GRADE WALL INSULATION SES 05-1 062914
SES FOAM 0.5 LB SPRAY
ESR-3375 I Most Widely Accepted and Trusted Page 4 of 6
Masonry Block V J
Interior Finish Surface
0Y., ryry� tl)24noh Shestrock)
2•x 4•Studs
SUCRASEAI�m0.5br
o / SES Foam 0.5 lb Spray
fo.
o.
SUCRASEALTM0.5 BELOW GRADE WALL INSULATION SES 05 2 062914
SES FOAM 0.5 LB SPRAY Insulation on Interior Side of Wall)
Baffle to provide
air space between Thermal
insulation and 19of Barrier*
deck. (as required
by local code)
irl .605
bV0°VVO°a° °A°tlaD°AG� JAG°°b°AJb°OVbaP°Da°a0
a0oa0VOVOVOVA°oaoV°`CC 0°0 OCOObp000°000
�,J l
Y'
V"4 U U
%%% °40UOOOA 1
/ °OOG p°oV
otloA ° a SUCRASEA1.7"i 0.5 or
G°ApO�O�A SES Foam 0.5 lb Spray
OOVO°OV0
I00°0000
°OVO0000
ODO00°00
VDVDnOV9
°yOOD°Da0
O 0 O O
tla°DOUOOD
ba00 D°O
baCDDDQD
UOU°a0
Vented Soffit Aoatluoao
°oaf°tl°tl
D a a atl
`.a°°°otlotl
o°OuaaQa° 'Where attic entry is for the
Ooa O°04
SES Foam 0.5 lb Spray a serviced utilities only_thermal
a°oOO° o
o°a�°,A°a° and'.igniton barrier on,the attic
O°°V�y00000
� D atla°a°j side of the spray foam surface
may be omitted.
SUCRASEALT 0.5 VENTED ATTIC:FLOOR f SOFFIT SES 05-3 062914
SES FOAM 0.5 LB SPRAY
ESR-3375 I Most Widely Accepted and Trusted Page 5 of 6
A O
ego; Subfloor SUCRASEAL 0.5 or
SES Foam 0.5 lb Spray
Go°o`
o,°°,o°°°oyog°go°°°OAgogogore°°°°g°°gogog°o°A°°og°og
PLO° O°og0°o Ao o O °O°Agg
Header
g4og`gtly�bg0 Ay�, .C �jy�°
ggA;°g°g°g4 / t
Opg°°Ogg�O�0A4° 4
o°u44000[
Sill
% Joistr Floor Cross Section
Thermal Barrier*
(as required by
1=xterior Grade X local code)
\/4\//\�
6"Min
Footer-.-,,., Vapor Barrier
*Where crawispace entry is for the
s'4 :•< \\/\�j\\\/ service of utilities only,thermal
and igniton barrier on the crawispace
side of the spray foam surface
may be omitted.
SUCRASEAPO.5 CRAWLSPACE:VENTED SES 05-4 062914
SES FOAM 0.5 LB SPRAY
Subfloor
1 gggg
Ig
Header— `Agg�Oogg°�/
8°g°
°gog
.Sill °Oo°`°gg tO15t
gn
gA�gg
° g I
°gg Thermal Barrier*
egoggg — (as required by
Exterior Grade ggg , local code)
SUCRASEAI!'0.5 or
Z ga°go SES Foam 0.5 lb Spray
q ,
T
Footers` 6"Min Vapor Barrier
�'- " •: Y /l.�// f/l� *Where crawispace entry is for the
service of utilities only,thermal
and igniton barrier on the crawispace
side of the spray foam surface
may be omitted.
SES FOAM
0.5 0.5
LB CRAWLSPACE:UNVENTED SES 655
SES FOAM 0.5 LB SPRAY 062914
ESR-3375 Most Widely Accepted and Trusted Page 6 of 6
Note:In cold climates,embed
metal connector plates in spray foam
to prevent winter-time condensation.
SUCRASEALV 0.5 or %° °
SES Foam 0.5 Ib Spray
O°O
°4. U°U
Roof Sheathing
b
000
O
-O°O
OOO�Oap00° nn�- I
Truss Top Cord 1
Rafter
nn
�0
L0° nnnnnn
ti. nnnn nnnn
'o° n nnnnnn
Thermal Barrier'
(as required by local code)
Note:Local building code may
require the use of a vapor retarder
In cold climate zones. `Where attic entry is for the
Ceiling/Thermal Barrier service of utilities only,thermal
as required by local building code. and igniton Barrier on the attic
side of the spray foam surface
may be omitted.
SES FOAM
0.5 LB0. UNVENTED ATTIC/INSULATED ROOF DECK SES 05-6 062914.
SES FOAM 0.5 LB SPRAY
SUCRASEALTM 0.5 or �` O O O ey
SES Foam 0.5 lb Spray O O O C O O
to specified thickness. �x
0 0 � 0 0 0
O OO
Roof Sheathing O 0 0 0 0 0
O O0000
���_ Thermal Barrier as
Rafter / 0 0 0 0 / required by code.
O
Note:The local building code
may require the installation of
a vapor barrier in cold climate
zones.
SUCRASEAP 0.5 CATHEDRAL CEILING SES 05-7
SES FOAM 0.5 LB SPRAY 062914