SCOPE OF WORK:
Install new Metal Roof(Extreme Metal Fabricators, LLC "5-V Crimp"FL #17022.1) at above .
referenced address over new underlayment, and existing plywood sheathing.
DESIGN CRITERIA:
FBC 2014
ASCE7-10
PROJECT DATA:
BUILDING HIEGHT= 10'-0"
A=3'
MEAN ROOF HIEGHT=<20'
ROOF ANGLE=4:12
SHAPE=PITCHED GABLE
ADJUSTMENT FACTOR= 1.00
IMPROTANCE FACTOR= 1.00
WIND VELOCITY V ult= 165MPH
WIND VELOCITY_V asd= 128 MPH
EXPOSURE=D
ENCLOSURE CLASS =ENCLOSED BUILDING
INTERNAL PRESSURE COEFFICIENT=-0.18
APPLIED UPLIFT DESIGN PRESSURES PER ASCE(PSF):
ZONE 1 (Field) =-40.3
t c7 kat r
ZONE 2 (Perimeter/Ridge) _-68.0
ZONE 3 Corners =-99.8 c x'`F* t'Paul Welch Inc.
y :t kdI
� Pag Welch P T. Reg.No. 29945
16, 2017
10851 S Ocean Dr. 17 Jensen Beach,FL 1 of 3
r
METAL ROOFING ATTACHMENT REQUIREMENTS:
Metal roofing to be attached with corrosion resistant Hex-Head wood screws#10 z 1
minimum with weather sealing washers(minimum 3/16"penetration through deck). Fasteners
shall be placed through the panel ribs at 12"on center across panel width and spacing along the
ribs as follows:
ZONE :l (Field):FASTENER SPACING= W O.C.
ZONE 2(Perimeter/Ridge):FASTENER SPACING= 16"O.C.
ZONE 3 (Comers):FASTENER SPACING=8" O.C.
NOTE:PROVIDE LAP SEALANT FOR ALL ROOF PANEL LAPS FOR ROOF
SLOPES UNDER 3 VERT. :12 HORZ.
Design up1lrt'Pfessure for attachment as per above:
Product Design Pressure: Zones 1 &2: -93.5PSF/Zone 3: -101PSF
Therefore O.K.
UNDERLAYMENT:
Underlayment shall be in accordance with manufacturer's guidelines,FBC 1507.4.5.1,and FBC
15074.5.2.Underlayment shall be Approved 30#Roofing Felt.
DECK INSTALLATION:
Re-nail all plywood sheathing(15/32"thick minimum)with 8D ring-shank nails at 4"O.C.
perimeter and 6"O.C. field for all zones.
All work to be in compliance with product approval (FL# 17022.1),manufacturer's
specifications, and the Florida Building Code 2014.
u htxSti,� �� ,aa
',+ `' ;Paul Welch Inc.
.`Pau1�We1cPIE�deg.No.29945
L 1
MdJtS46,-2017
10851 S Ocean Dr. 17 Jensen Beach,FL %ft 2 of 3
A ' 3 1-00-2�✓
s
;
ii
J f' '. - ! f
04
6vrl
1
Ole
/Owo'
.G�cdb
ROOF ZONE PLAN
A=3' nr" q
Q,Q,0=ZONE DESIGNA770N, PICAL)
NOTE: PROVIDE LAP SEALANT FOR ALL ROOFttPA i �LAP&TOR:ROOF
�, .4r✓'Wwd,t� ., .r
SLOPES UNDER 3 VERT. :12 HORZ. ��
5"d•�"� a w °°ram�'+�± 'ti. F •" r' r <;2p7
r YJT`T�7
y+�< r
Y'^
, ;� t, �u �Vlch'E E�Reg No.29945
^_� ,i1Vlaxc�l6, 017
10851 S Ocean Dr. 17 Jensen Beach FL