Loading...
HomeMy WebLinkAboutEnergy Calculation Form & Manual J's (2) FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: %.330 " Permit Number: FT.PIERCE,FL, MAR+IATORY REQUIREMENTS See individual code sections for full details. ❑ -=401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law ,a,�JSection 553.9085,Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. ❑ R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. 0 R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3.Interior doors,if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and 6.Supply and return registers,if installed at the time of the test,shall be fully open. 0 R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. 0 R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or AAMANVDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. 0 R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. ❑ R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.2.2 Sealing(Mandatory)AII ducts,air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99,Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(2513a)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 4/26/2017 1:20 PM EnergyGauge@ USA-FlaRes2014 -Section R405.4.1 Com Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) ❑ R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ "^vR403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105•F(41°C) 'or below 55°F(13°C)shall be insulated to a minimum of R-3., R403.3.1 Protection of piping insulation. ❑ R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. ❑ R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. ❑ R403.4.4 Water heater efficiencies(Mandatory). 0 R403.4.4.1 Storage water heater temperature controls • R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38'C to 60°C). • R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. 0 R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation,Commercial Provisions,for the type of equipment.installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. Ji R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water 4� heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. 0 R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 4/26/2017 1:20 PM EnergyGaugeO USA-FlaRes2014 -Section R405.4.1 Com Page 2 of 3 FORD R405-2014 MANDATORY REQUIREMENTS - (Continued) 0 R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal, rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. J1 Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer, in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. 0 R403.6.1.2 Heating equipment capacity . R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. . R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. 0 R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems,supplied through energy service to the building,shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40`F. ❑ I; R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. 0 R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2,Standard Rating Conditions-LOW Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. 0 R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps ac cording to a preset schedule shall be installed on all heaters and pumps.Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. O R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or solar energy source computed over an operating season. ❑ RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. 0 R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights ❑ R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. 0 R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space,R-10 is allowed. 4/26/2017 1:20 PM EnergyGaugeO USA-FlaRes2014 -Section R405.4.1 Com Page 3 of 3 FORM R405�-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: RENAR SCH ARTZBERG , �} Builder Name: RENAR HOMES Street: 9230 kj_WkA_,� Permit Office: ST LUCIE COUNTY !3 City,State,Zip: FT. PIERCE,FL, Permit Number: 1 7,93-6-3 7 J Owner: Jurisdiction: 661000 Design Location: FL, Fort Pierce COMPONENT CRITERIA CHECK Air barrier-and thermal barrier A continuous-air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings,drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and.the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/doorjambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. '('Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces.. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated,and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls,or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 4/26/2017 1:20 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 Residential System Sizing Calculation Summary /� xj Project Title: rC�t RENAR SCHWARTZBERG FT. PIERCE, FL 4/26/2017 Location for weather data: Fort Pierce, FL - Defaults: Latitude(27.48) Altitude(25 ft.) Temp Range(L) Humidi data: Interior RH 50% Outdoor wet bulb 78F Humidity difference 62 r. Winter design temperature(TMY3 99%) 40 F Summer-design temperature(TMY3 99%) 91 F Winter setpoint 70 F Summer setpoint 75 F Winter temperature difference 30 'F Summer temperature difference 16 F Total heating load calculation 29893 Btuh Total cooling load calculation 32889 Btuh Submitted heating capacity %of calc Btuh Submitted cooling capacity %of calc Btuh Total.(Electric Heat Pump) 113.7 34000 Sensible(SHR=0.75) 112.1 26700 Heat Pump+Auxiliary(O.OkW) 113.7 34000 , Latent 98.2 8900 Total Electric Heat Pump) 108.2 35600 WINTER CALCULATIONS Winter Heating Load for 1763 sqft Load component Load Window total 191 sqft 5486 Btuh Walls(tE.3%) Ceilirgsf5.��l Wall total 1276 sqft 5479 Btuh Door total 38 sqft 521 Btuh t:indo;r(lo".445; Ceiling total 1763 sqft 1684 Btuh Floor total 1763 sqft 6655 'Btuh Infiltration 218 cfm 7191 Btuh l Duct loss 2876 Btuh F�oors(2z3°al Subtotal 29893 Btuh Cuctsi4,3`.5: Ventilation 0 cfm 0 Btuh TOTAL HEAT LOSS 29893 Btuh Doors(1 T°fiS SUMMER CALCULATIONS Infil.(24.M Summer Cooling Load for 1763 s ft Load component Load Window total 191 sqft 8418 Btuh Wall total 1276 sqft 2922 Btuh Geilings(73°ii Door total 38 sqft 539 Btuh - Ceiling total 1763 sqft 2527 Btuh ya ng c%j �in�dovis(Mr-3s) Floor total 0 Btuh Infiltration 164 - cfm 2876 Btuh Ooors[1,i 95i Internal gain 3040 Btuh Duct gain 3500 Btuh Sens.Ventilation 0 cfm 0 Btuh Blower Load 0 Btuh Latentint(4.5 Total sensible gain 23822 Btuh Latent gain(ducts) 578 Btuh Latent gain(infiltration) 6890 Btuh Infil.(2?.7g6i t Into Gslni�?5h Latent gain(ventilation) 0 Btuh Latent gain(internal/occupants/other) 1600 Btuhs(12.4°ti; Total latent gain 9068 Btuh TOTAL HEAT GAIN 32889 Btuh EnergyGaugeO Sy em 'z' 8th Edition PREPARED BY: x r :ti w DATE: EnergyGauge®/USRCZB v5.1 -1-ra,mnzing Calculations a SL-,qru,';Luni�m ser Residential Load - Room by Room Component Detail's Project Title: IPZL� RENAR SCHWARTZBERG FT. PIERCE, FL 4/26/2017 Reference City: Fort Pierce, FL Temperature Difference: 16.OF(TMY3 99%) Humidity difference: 62gr. This calculation is for Worst Case.The house has been rotated 270 degrees. Component Loads for Room#1 Main> 5 Type* Overhang Window Area(sqft) HTM Load Window Panes SHGC U-"InSh IS Ornt Len Hgt Gross Shaded Unshaded Shaded Unshaded 1 1 NFRC 0.42,0.96 No No SW 1.3ft 0.5ft 8.0 3.7 4.3 24 45 283 Btuh 2 1 NFRC 0.42,0.96 No No SW 1.3ft 0.5ft 45.0 16.6 28.4 24 45 1679 Btuh 3 1 NFRC 0.42,0.96 No No SW 1.3ft 0.5ft 40.0 11.1 28.9 24 45 1569 Btuh 4 1 NFRC 0.42,0.96 No No NW 1.3ft 0.5ft 22.5 0.0 22.5 24 44 991 Btuh 5 1 NFRC 0.42,0.96 No No NE 1.3ft 0.5ft 30.0 0.0 30.0 24 44 1821 Btuh 6 1 NFRC 0.42,0.96 No No SE 1.3ft 0.5ft 45.0 16.6 28.4 24 45 1679 Btuh Window Total 191 (sqft) 7522 Btuh Walls Type LI-Value R-Value Area(sqft) HTM Load L Cav/Sheath 1 Concrete Blk,Hollow-Ext 0.15 4.1/0.0 331.0 2.4 790 Btuh 2 Concrete Blk,Hollow-Ext 0.15 4.1/0.0 305.5 2.4 729 Btuh 3 Concrete Blk,Hollow-Ext 0.15 4.1/0.0 214.0 2.4 511 Btuh 4 Concrete Blk,Hollow-Ext 0.15 4.1/0.0 283.0 2.4 676 Btuh 5 Frame-Wood-Adj 0.09 11.0/0.0 142.2 1.5 216 Btuh Wall Total 1276 (sqft) 2922 Btuh Doors Type Area (sqft) HTM Load I Insulated-Exterior 20.0 14.3 285 Btuh 2 Wood-Garage 17.8 14.3 254 Btuh Door Total 38 (sqft) 539 Btuh Ceilings Type/Color/Surface U-Value R-Value Area(sqft)' HTM Load 1 Vented Attic/Light/Shingle 0.032 30.0/0.0 1763.0 1.43 2527 Btuh Ceiling Total 1763 (sqft) 2527 Btuh Floors Type R-Value Size HTM Load 11 Slab On Grade 0.0 1763(ft-perimeter) 0.0 0 Btuh Floor Total 1763.0 (sqft) 0 Btuh Zone Envelope Subtotal: 13510 Btuh Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM= Load Natural 0.56 17630 1.00 163.6 2876 Btuh Internal Occupants Btuh/occupant Appliance Load gain 8 X 230 + 1200 3040 Btuh Sensible Envelope Load: 19426 Btuh Duct load Extremely sealed,Supply(R6.0-Attic), Return(R6.0-Attic) (DGM of 0.172) 3345 Btuh Sensible Zone Load 22772 Btuh EnergyGauge@'/USRCZB v5.1 Page 1 Manual J Summer Calculations Residen 'al Load - Component Details (continued) ��3v RENAR Project Title: Climate:FL VERO_BEACH_MUNICIPAL A SCHWARTZBERG FT. PIERCE, FL 4126i2017 ,a The followin window Excursion will tie assi ne i to the system loads{ 9. . 9 Windows July excursion for System 1 896 Btuh Excursion Subtotal: 896 Btuh Duct load 154 Btuh Sensible Excursion Load 1050 Btuh �.T EnergyGauge@ i USRCZB v5.1 Page 2 Manual J Summer Calculations Residential Load - Component Details (continued) 93o Project Title: Climate:FL_VERO_BEACH_MUNICIPAL_A RENAR SCHWARTZBERG FT. PIERCE, FL 1 4/26/2017 y 4 WHOLE HOUSE-TOTALS Sensible Envelope Load All Zones 20322 Btuh Sensible Duct Load 3500 Btuh Total Sensible Zone Loads 23822 Btuh Sensible ventilation 0 Btuh Blower 0 Btuh Whole House Total sensible gain 23822 Btuh Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 6890 Btuh Latent ventilation gain 0 Btuh Latent duct gain 578 Btuh Latent occupant gain (8.0 people @ 200 Btuh per person) 1600 Btuh Latent other gain 0 Btuh Latent total gain 9068 8tuh k7 TOTAL GAIN 32889 Btuh EQUIPMENT 1. Central Unit # 35600 Btuh "Key: Window types(Panes-Number and type of panes.of glass) (SHGC-Shading coefficient of glass as SHGC numerical value) (U-Window U-Factor) (InSh-Interior shading device:none(No),Blinds(B),Draperies(D)or Roller Shades(R)) - For Blinds:Assume medium color, half closed For Draperies:Assume medium weave,half closed For Roller shades:Assume translucent,half closed f (IS-Insect screen:hone(N), Full(F)or Half(%2)) .+ ". (Ornt-compass orientation) Version 8 M EnergyGauge®/USRCZB v5.1 Page 3