HomeMy WebLinkAboutfire departmentq
SAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC FMO Permit # B-20-411
Project Name WAWAs BLDG Permit # 2005-0373
Address 121 South King Highway ( City Ft Pierce ^�
Contractor
Address 1803 South 13th Street City F:tP,:, rce
State FL Zip 34947 Telephone (772)468-3689
1
Architect/Engineer Cuhaci & Peterson I Telephone (407) 661-9100
Occupancy Type Mercantile Construction Type �Vr B Square Feet 7208
Occupant Loaad163 per plans Numbbe�r of Stories Access Box Access Key Switch
AFS Permit ! I FA Permit
L � FFP Permit
IGeneral Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper LIL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code compliance.
10. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVIA
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector.
2. Emergency shut off is required for inside the store and outside.
Page 1❑ of 1❑ Reviewed by Tony verger _—___ I Date 12-28-2020