Loading...
HomeMy WebLinkAboutInstallation Manual (2) FS.o#05Connect ® Crossovers Conforms to HUD MHCSS 1115109 Figure 65.DWV connection to sewer/septic WjFloorm6ff Examples of I Connection Pipe and Fittings(Not Supplied by the I ow Manufacturer) o Support Strap at Maximum of 4 Feet on Center Cap and Chain Approved Coupler - Site Sewer Hook Up 5. Install supports. Install permanent drain line supports at a distance of four feet o.c.or less(see Figure 63,-Figure 65,and Figure 66). (2)0.131"Diax3 a"Nails Figure 66.DWV pipe sup- Min.2x3 Lumber port options 0.131"Diax3}"Nail Galy.or Alum.Strip (Drain 2)0.13 W tuber 2)0.131"Diax3 Nails Into Floor Joist Protect pipes from freez- 2)6 x 2"x16GA ing. If the home is to be left Staplesor(2) unheated in cold weather,0.131"Diax3,Nalls Each Endpour antifreeze solution into all drain traps, including (2)Staples or sinks,tubs,and toilets.Be Screws Each'Sidesure that the antifreeze is Galy.orAIum Strip safe for the fixtures and P-Min.2x3 Wmber traps.Pipe Installing quick disconnect fittings.Do not use tools, 6. Insulate. Replace all insulation and make sure all potentially exposed portions lubricants,or sealants with of the DWV system are well insulated to protect against freezing. quick disconnect fittings. X Gas test precautions.Do r STEP 6. CONNECT GAS LINES -not connect to gas service z The gas crossover connection may use quick disconnect fittings or threaded connec- until tests described in rn tors. Find the connection location below the floor at the marriage line and gather the Connect Utilities have been- n connectors(they may be shipped loose if not present under the home). successfully completed. For quick disconnect fittings(Figure 67),remove any dust caps and then with one 0 hand, pull back on the quick disconnect device,snap it over the quick disconnect adap- tor and release it to complete the connection. For threaded connectors(Figure 68),remove the black cap and nipple(or any other z plugs,such as a black iron plug)from both the supply and receiving sides and screw Z the connector onto the supply and return pipes as necessary. Check for leaks before connecting to gas service(see Connect Utilities,STEP 3. CONNECT GAS SERVICE, p.83). r D O z D z c D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 61 PFS certifies this document is current as of 12-16-09. • - PFS#°5 • • Conforms to 4Z�HUD MHCSS 1/15/09 Quids-Disconnect Figure 67.Gas crossover Male Fitting Flex with quick disconnect fittings Factory Installed Shut-Off Valve I nstalled on Quids-Disconnect Inlet side Figure 68. Gas crossover Female Fitting with threaded connectors Installed on Inlet Side Flex Connector Factory Installed Male Cap Femali Female Cap Or Installing wiring.When in- Male Cap stalling telephone and ca- Direction of Gas Flow Direction of Gas Flow ble television wires,do not damage electrical wires, STEP 7. CONNECT TELEPHONE AND CABLE TV WIRING plumbing lines,or ducts. Serious personal injury or Install telephone and cable television wiring in accordance with the requirements of the death could result from LAHJ,the NEC,and NFPA No.70-2005.When making crossover connections or in- damage to electrical wires. stalling telephone or cable television wires,do not run them in the same raceway as,or in close proximity to, high voltage electrical conductors or cables. Wires should only be installed by trained professionals. 00, .• to • " J a z a z O i-- a J J a F cc z z O F- a O n. O U W z J Y rn Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 62 PFS certifies this document is current as of 12-16-09. AVACS50#05 ' Interior Conforms to HUD MHCSS Complete the Interior 1/15/09 This chapter covers the completion of the home's interior finishes including finishing walls,ceilings,flooring,trim, and mis- cellaneous items. Follow the Steps • - • STEP 1.ALIGN MARRIAGE WALLS(p. 63) STEP 2.FINISH GYPSUM BOARD(p.63) STEP 3.COMPLETE WALL AND CEILING FINISHES(p.64) STEP 4.COMPLETE CARPET(p. 64) STEP 5.COMPLETE TRIM(p.64) STEP 6.INSTALL SHIP LOOSE ITEMS(p. 64) STEP 1. ALIGN MARRIAGE WALLS Align and secure walls at marriage line openings as follows: 1. Align walls.Align walls and clamp in place. 2. Fasten walls.Secure clamped walls together with metal straps or long screws so they do not move when the clamps are removed. Insert wood wedges in gaps between walls, and glue and screw to create a tight connec- tion. 3. Fill gaps.Fill any remaining gaps with wood or sheathing material. Does the home require patching and finishing gypsum board walls or ceil- 00, YES, go to STEP 2. FINISH GYPSUM BOARD, (p. 63) 110- • .• to STEP 3. COMPLETE •' r STEP 2. FINISH GYPSUM BOARD m Finish all unfinished gypsum board walls and ceilings as follows: n 1. Install panels.Install ship-loose gypsum panels using a 1/4 inch diameter / // X Ira bead of adhesive on all framing members and minimum 1-1/2 inch long dry- Fastening gypsum.When p wall screws,nails,or staples at six inches o.c.along panel edges and 12 attaching gypsum board, inches o.c. in the field into framing members. depress, but do not break 2. Mud seams.Mud and tape all seams and corners,filling all fastener depres- the,paper face with the fas- p sions. Follow mud manufacturer's directions. tener. Breaking the paper z 3. Paint.When the final coat of mud is dry, prime and paint all unfinished gyp- will weaken the connection. H sum board to match existing paint color and finish texture. Using alternative materials. CO) Obtain the home manufac- r _ the home have pre-finished _ , wall panels -•_ turer's approval before us- rD ing interior finish materials •• to STEP 3. COMPLETE • other than those provided p • with the home. z 00- NO, go to STEP 4. COMPLETE CARPET, (p. 64). K C r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 63 PFS certifies this document is current as of 12-16-09. Complete the Interior PFS#°5 STEP 3. COMPLETE WALL AND CEILING FINISHES Conrormsto Install interior ship loose wall and/or ceiling panels using a 1/4 inch diameter bead of Hun mHCss polyvinyl acetate(PVA)adhesive on all framing members and fasten with minimum 1- 1/15/09 1/2 inch long staples or nails at six inches o.c.along panel edges and 12 inches o.c.in the field into framing members. STEP 4. COMPLETE CARPET Install and seam ship loose or rolled carpet as follows: 1. Prepare floor.Clean the floor of all dirt and debris and smooth the floor deck / / A at the marriage line seams as necessary to ensure a level and smooth sur- Installing carpet.Only ex- face. perienced carpet installers 2. Lay pad.Lay down the carpet pad, if provided. should install carpet. Fail- 3. Stretch carpet.Ensuring all carpet"grain"runs in the same direction,fit and ure to follow the carpet secure the carpet using a power carpet stretcher. Stretch the carpet up to the manufacturer's directions seam and tack it down temporarily until the carpet is seamed. may void the carpet war- 4. Butter carpet."Butter"with carpet adhesive the edges of the carpet along the ranty. seam. 5. Seam carpet.Place heat bond tape under the seam with the glue side next to the carpet and apply heat from a seaming iron to the top of the seam, press- ing the carpet into the glue. Stagger seams. 6. Keep scraps. Retain reasonable size carpet scraps to protect carpet and Stagger all seams. For ex- flooring during move-in. ample,locate the carpet pad seam three inches to STEP 5. COMPLETE TRIM left of marriage line and the Using fine gauge wire staples or pin nails, install ship loose molding and wainscot pan- carpet seam three inches to eling to finish trimming out ceilings,marriage line walls,front and rear end walls,and right of marriage line. passageway doors where necessary. STEP 6. INSTALL SHIP LOOSE ITEMS Remove all strapping,blocking, and packaging from appliances,windows,and doors. Install any drapes, mini-blinds, mirrors,door stops, closet shelves,and hardware per the product manufacturer's installation instructions. 00, Pier and ground anchor, go to Install Stabilizing Systems, (p. 65) 00- Load bearing perimeter wall, go to Connect Utilities (p. 77). Proceed based on the foundation type: Z Q Z O a J J Q F- tn Z_ Z O Q O a W O U W Z J } Y Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 64 PFS certifies this document is current as of 12-16-09. Fs#os Conforms to HUD MHCSS Install Stabilizing Systems 1/15/09 Install Stabilizing Systems This chapter covers the design and installation of the stabilizing system which secures the home against lateral and upward forces caused by wind.The system covered here uses earth(or ground)anchors and steel straps connected to the home's longitudinal steel beams and/or exterior walls.Stabilizer plates may also be used to prevent the anchor head from moving. laterally in the ground.An anchor,strap, and stabilizer plate(if used)together are referred to as a tie-down. Anchors can also be mounted in concrete footings when there is enough concrete mass(weight)to resist the lateral and upward forces.This type of system is not covered in this manual. Follow the Steps • - • 1 jV STEP 1.DETERMINE ANCHOR LOCATIONS(p. 65) STEP 2.DETERMINE TIE-DOWN CONFIGURATION(p.71) iV STEP 3.SELECT ANCHORS(p.71) i STEP 4.INSTALL ANCHORS(p.72) t STEP 5.INSTALL STRAPS(p.73) i STEP 6.TIGHTEN AND ADJUST STRAPS(p.76) STEP 1. DETERMINE ANCHOR LOCATIONS Create a sketch of the home plan showing the exterior walls, marriage line(s)(if any)and frame 1-beams(this will be similar to the base sketch created in Prepare Footings,page 18). Need for a stabilizing sys- See Table 19 for a list of anchor locations,types,and where they are required. Pages tem.The manufactured where the requirements are provided are noted in the last column. home must be secured As each anchor location is determined, mark it on the sketch, noting important dimen- against the wind by the use sions such as spacing between anchors.When complete,this will be the home's tie- of an anchor assembly or down plan(Figure 69 and Figure 70). an alternative foundation system.Where site or TABLE 19.ANCHOR LOCATION TYPES other conditions prohibit Cn Wind Zones 11 the use of the manufac- and III instructions,a regis- r tered engineer or regis- Z Frame Yes Yes 66 M tered architect must design _ Vertical No' Yes 70 the stabilizing system. p End wall Frame Sometimes Yes 70 Flood and seismic forces. X Vertical Sometimes Yes 70 The stabilizing system re- 0 quirements in this chapter Frame Yes Yes 70 do not consider flood or -i Vertical No Yes 70 seismic loads and are not O Vertical No Yes 70 intended for use in flood or Z •• Yes Yes 70 seismic hazard areas. In those areas retain a regis- Connect any factory-installed sidewall tie-down straps to a ground anchor regardless of the wind tered engineer or regis- r zone in which the home is placed. tered architect to design r z.Install marriage line anchors prior to moving the home over the top of the anchor locations and the stabilizing system. > then return to Set the Home or Complete Multi-Section Set respectively. O Figure 69 and Figure 70 illustrate typical anchor locations for a double-section home in Z Wind Zone I and Wind Zones II and III respectively. D Z C D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 65 PFS certifies this document is current as of 12-16-09. ' ' ell PFS#°5 Conforms to HIM MHCSS 1/15/09 idewall Frame Tie-down Figure 69. Typical anchor locations for a double- section home in Wind Zone I Marriage wall vertical tie-down(some homes). .................® ............. ------ Marriage Line Key: Anchor Head �.—Strap ®,Vertical Tie-down idewall Frame Tie-down Figure 70. Typical anchor locations for a double- section home in Wind Zones ll or 111 Marriage wall vertical tie-down. ------- ----------------® ®-----------------Q ------ Extend strap to far I-Beam Marriage Line for Doublewide units with 7 5/12 Roof pitch. Endwall Tie-downs Sidewall vertical tie-down. SIDEWALL FRAME ANCHORS Use Tables 20,21,and 22 to determine the spacing between anchors for Wind Zones I, II,and III,respectively.Spacing requirements will vary depending on the type of home (single or multi-section),the slope of the roof,the width of the floor for each section,the Maximum spacing re- sidewall height, I-beam spacing,and the height from the ground to the strap attachment quirements.The LAHJ point.Determine the values for the home. Using the table for the appropriate wind zone, may have anchor spacing determine the column and row that corresponds to the characteristics of the home.The requirements that super- value on the tables is the maximum distance between anchors.Keep in mind that side- cede the values provided wall frame tie-downs must be located no more than two feet from each end wall. in this manual. Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 66 PFS certifies this document is current as of 12-16-09. FS#os Install Stabilizing Conforms to Systems HUD MHCSS 1/15/09 TABLE 20.WIND ZONE I SIDEWALL FRAME ANCHOR MAXIMUM SPACING Heigh Roof slope maximum 4.35/12 ..- roi rod to t degrees) t Sid -all I-beam spac- . . Floor width_, height ing tachment Up to" -------------------- 8 ° --- ----� ` T,It,���G,/',/ i 48"to 67' - 6'-0" ` GISTERF•,CJ, 25"to a8" - 8'-0° = PE19600312 s STATE OF Up to 25" - 7'-0' 9 4u --25"to 48— —-------71-0•------.J '��O•cF:/NDIANp:-�G���`�•� - More than48"l0 67" - - 7 0 i�7ONAL�N11���.� -- ' to Up to 25" - T-0• i ////l 1111111111 --_-- —--_-- Jeffrey-[t_egKwt--- 48"to 67" - _ - 7'0 i11:24:-12-05'00'--- Up to 25" 10'-9" 11'-3" 7'-6° 6'-6" 25"to 48"----7;-6------ 81 0" 5,-0-----4,6*---- -- 48"to -----7-6---------E-0--- ------5-0--- ---_.._—4.6" -- -- 1 Up to 25 8'-3• 8'-9• 5'-9' 5'-0' --- 25"to 48" ---- 7-6" -- -8 0' ------ 6-0"----------- 4 6"------- Up to 25" 9'-0" 10'-0" T-0" 6'-0" -- 25"to 48" --6,9"---- T-3° -----5.-0" --------4,3---- More than ---48"1067" ---59---------73"------ -- 5_0 4'-3" 8'-0" Up to 25""^- -- 7=6"--------- 7 9 ------ 5!3°-----------4-9"---- --- 25"to 48' 6'-9" T-3" 5'-0" 4'-3" - 48"to 67" 6 9" --.- �._3""------- 5"-0" ----.—.._-4 3"---- Up to 25" 11'-9" 13'_9" 8'-3" T_3" ---25"to 48" ------ 9,6-------- 101-0" --------6'-0"---------5,_3"----- 48°to 67•--- 7 9° ------ 8 3 -- 5'0"------- 5-3" ---- 1 6'-6" 25"to 48• T-9" 8'-3" 5'-0' 4'-3" Up to 25" 9'-3° 12'-3" T-9" 6'-9" Cl) More than 75.5"or 82.5" —25"to 48' -- 8'6�`---9---0 _ — -.5 9"___ -- 51 48"to 67" T-0" 7'-3• 4'-9" 4'-0' r 9141 Up to 25°_---10-0"-------1 1`0� . T-°---_--_-__.-6`0' Z�-. ITI 25"to 48" 7'-0" 7'-6" 4'-9: 4'-0' n Up to 25° 11'-9° 14'-0" 8'-3" 7'-0" -0 - 25"1048 ---- 11-"--- -- _ _12' " _-- -------6 9--- -- 5 9^--- r0 48"to 67" —9'-0" 10'-0" 51-6• 4'-9" D -------_13' - --'- ---- 4'------— -------- 'Up to 25" � — ----- 0 25"to 48" 10'-0" 11'-0" 6'-0" 5'-3" Z More than --48"l0 67•--8,°—-- 8,9°---------5--0.-------4,3—--- Z 15, Up to 25" 9'-3" 13'-0" T-9" 6'-9" (n 25"to 48• 9'-3• 10'-9° -5'-6• D More -- 48"to 67-----8 3 -----9-0------------5 3°------- a 6" ----- . 1 D Up to25"--------11-9"----------13-�--------- 7-6°--------- _6-6".-___ -I 25"to 48" 9'-0" 91_9" 5'-6" 5'-0' 0 48"to 67" - 7,-0——---- 7,9" -------4,_6°-----4'0'---- Z Z C r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 67 PFS certifies this document is current as of 12-16-09. Install Stabilizing #05 Systems Conforms to HUD MHCSS 1/15109 TABLE 21.WIND ZONE II SIDEWALL FRAME ANCHOR MAXIMUM SPACING slopeRoof degrees) (26.5 degrees) Single section Double section Single section Double section Up to 22" - 5'-4° _ ` �1111 d I1171p -22'to48°— - ---- ------ M.A. -�� � �kSj T.LFQ�G���'' I 48"to 67" - N.A '('j1STfiA••,• • Up to 25i - NA. - -- ------ -- ------ - PE19600312 -L- -- 25"to 48" - N.A.Lessthan - - --48"l0 67°� - N.A. --------- • S � •`i-- -- STATE OF 2' Up to 25" - 4�_0^ : 9 A•.:' 4i 25"to48" - N.A.More than --------------------------- —------ -------------- 48"to 67" - N.A. �•� • -- -Uplo25"-- ---- N.A. ' --------� pppp f( 1.09 11:23: _ 25"to 48° - N.A. 11:23:58-0.12100' --- 48"to 67" - -- NA. --------- ---- _------ Up to 25" 5'4" 5'4° - 64" • 25.to 48" N.A. N.A. ----------- ----- 64,-------- - 48°to67^-------"-N.A.--- -- N.A. ^--------- 64 Up to 25° 4'-0° 4'-0' 25"to 48" N.A. N.A. - 5'4' More than 48"to 67" --- N.A. ----_.-'--N.A.--------_-- 5,4,---- Up to 25" 4'-0" 4'-0" - 5'4' -- 25"to 48" N.A. - N.A. ------ 5'4' -..--- • than - 48"l0 67" N.A. N.A. - 5'4 ••�to ---Up to 25" ------N-A--------N-A.------ -:�_,_-___. 5'4'--- 25"to 48" N.A. N.A. - 5'4' ---48"to 67" - N.A--- N.A. ------+-- 5'4' --- - Up to 25" 64" 5'4" - 5'4' - -48"to67^------- N.A.----------- N.A. ---- ----_------------5-0------ Up to 25° 5'4" 514° - 5-4- 25"to 48" N.A. N.A. - 64 Up to 25" 64" 5'4" - 5'4 25"to 48" N.A. NA. ` - _-------54-- -- More than -- 48"to67" ------N.A. N.A----------..--_..-__ 5- _.-_-- •� • --Up to 25" -4-0°-------------4 "------ ---------------54'---25"to 48" N.A. N.A. - 64 - 48"to 67" N.A. - -- N.A. --------- ---_---------5-4 ----- - Up to 25" 5'4" 64" - 5'4' -- 25"to 48" -----4,_Oe----------4,-0e-----------_------ - 6 4 ----- Up to 25" 5'4" 5'4" - 5'4' 25"l0 48^--------4 O------------4.0------------_------------5 1,------ More than48"to 67" N.A. - N.A.-- ------_--------- 5,4, -._- Up to 25" 64" 5'-4" - 64 More than to----48°to 48" - N.A. - -- N.A. ---- --- ------5-4---- 96 0 to ----Up to25°°------- 5-4°--- 54" 54 25°to 48" 4'-0" - -- -- N.A. -------------_-------— 5-4- 48"to 67° ------N.A.----------N.A.----------_-------------5,�,------- Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 68 PFS certifies this document is current as of 12-16-09. FS#os Conforms to Install Stabilizing HUD MHCSS Syste 1115/09 TABLE 22.WIND ZONE III SIDEWALL FRAME ANCHOR MAXIMUM SPACING cRoof slope maximum 5/12 I . (26.5 degrees) Up to 25" - 4-0" %%W1111111pp�/j'' - 25"to 48" - N.A. ----J \``\O�P�Y T.L,- i-_-- 48"to 67"-- ---------�N.A. ?Q O N_A----_-,-- PE19d00312 J --- 25"to 48" - N.A. Less han48"to 67' - N.A. i -o STATE OF C Up to20" - 4'-0" _ %9Ox %. DIAV ..-'���. "More than -----------N.A. ---1 �/SS�ONAfNG 20 to 48° I-- 48"to 67" - N.A. ce,�0 6 0 • - Up to 25" ---- -- N.A. ----- !n 7� 2009.01.09 --- 25"to 48" - N.A. / °11:23:46 05'00' 48"to 67" —- N.A. -- -----i- - -- Up to 25" 4'-0° 4'-0' - 4'-0" - 8 25 --- "to 4" N.A.---------'N.A. ------.—.�._---4,-0"----- ---25" o "-------N.A------ N.A. ---------- -------4-0"--..-.- Up to 25" N.A. N.A. - 4'-0° 25"to 48" N.A. N.A. - 4'-0" Mor-than 48°to 67' N.A. ------N.A. -----------------`-4,-0e----to Up to 25" 4'-0" 4'-0' - 4'-0" -- 25"to 48" N.A. N.A. ------- ---------- 4'-0°-- -- More ----48"to 67 --N.A.-- --- N.A. -------`-- ---------4-0"---- - 91-01, to Up to 25" -- N.A. ----N-A----------`- -----------4 "-25"to 48" N.A. N.A. - 4'-0" - 48"to 67---- N.A. ---N.A. ---------------------4,-0-0----- Up to 25" 4'.0° 4'-0' - 4'-0" 25"to48" --N.A. N.A.-------- ---------4,-0e------ --48"l0 67" N.A------ N.A. ------------_------------ 4 0 -- ---- • • Up to 25" 4'-0" 25"to 48" - N.A. ------ N.A.-----------_------------4 0---- • -than 48"to67" -----N.A. N.A. 4'-0' Up to 25" 4'-0' 4'-0" - 4'-0° f) ---25"to 48" ----N.A----- N.A. ----- — -- -----4' "---- '� More than -48"to 67" N.A. N.A. - 4'-0" r Up to 25" 4'-0° 4'-0" - 4'-0° Z � --- --_-------- ----------------'--------- fit 25"to48 _ N.A. N.A. -,_.-----_-- - 4 0° --. 0 48"to 67" N.A. N.A. - 4'-0° 0 Up to 25" 4'-0" 4'-0" - 4'-0" X .D 25"to 48" ---4-0"--- 4,0------ _----------4--0 ---- 0 48"to 67" N.A. N.A. - 4'-0" D • • Up to 25° 4'-0° 4'-0° - 4'-0" -{ - -- -------------- -- --- - ------- '- - 0 25"to 48" N.A. N.A. - 4'-0" Z More than 48"to67' N.A. -------`--N.A.---------_----- 4,-0—------ Z Up to 25" 4'-0" 4'-0' - 4 0 -_--- 25"to 48" - N.A. ------...N.A.------- -------4'-0"More than D . ------- ---- - -------- ------- --_�_ ----- — r 48"to 67" N.A. N.A. - 4'-0" �- • to -- Up to 25�------41 0--------4'0----------`-- -- ------`--4 ------ >_ 25"to48" -- N.A. --- N.A. ----------------- 4 0 --- 0 ----48"to 67" N.A. N.A. - 4'-0"- -- Z D Z c D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 69 PFS certifies this document is current as of 12-16-09. InstallStabilizing Systems FS #o5 SIDEWALL VERTICAL ANCHORS Homes designed for Wind Zones II and III also require vertical tie-downs along the side- conforms to walls.The vertical tie-down anchor straps(or brackets for connecting to the home)are HUD iviHcss factory installed and indicate the locations.Vertical and frame sidewall tie-downs may 1i15/09 connect to one double-headed anchor or each to its own dedicated anchor. Any factory-installed sidewall tie-down straps must be connected to a ground anchor re- gardless of the wind zone in which the home is placed. END WALL FRAME ANCHORS End wall frame tie-downs are especially important for homes that are wider and have higher roof pitches because those features increase the surface area exposed to wind loads at the ends of the home. Use Table 23 to determine the number of end wall frame anchors required at the each end of each home section. End wall frame tie-downs are not required at Wind Zone I. TABLE 23.END WALL FRAME ANCHORS REQUIRED PER HOME SECTION ON EACH END OF THE HOME Wind Zone I I Wind Zone III Maximum 12' 14' 16'&18' 12' F1 4�o 16'&18' secct tior sidewall Maximum section section section section n sectionheight roof pitch width width width width width width \�Q��'�� Twidth 4.35/12 2 4 4 4 4 4 _�\ ;•P� SST! 5/12 N.A. N.A: N.A N.A. N.A. N.A. = PE19600312 4.35/12 4 4 4 4 4 4 • • --- S 'G I. STATE OF r 1Z 5/12 N.A. N.A. N.A. N.A. N.A. N.A. 9 <u 4.35112 3 3 3 3 3' 4 '�� OT••• O�ANP•:• ��`` 5112 3 3 3 3 4 4 ssl�NA'�sN�\\\``` 4.35/12 512 3 3 4 3 4 4 2009.01.09 11:2328 05'00'it MARRIAGE LINE VERTICAL ANCHORS In Wind Zones II and III, marriage line anchors are required along the marriage wall. In , Wind Zone I marriage line anchors are sometimes required.(Figure 80) / • /, There may be manufacturer-installed brackets indicating required tie-down locations When to install marriage (may be identified by tags or paint).If necessary to avoid interference with tie-downs,the line anchors.Anchors marriage line pier location may be offset horizontally from the column by a maximum of 6 along the marriage line inches. must be installed prior to the second half of a multi- TAG UNIT FRAME ANCHORS section home being set. See Addendum to these installation instructions for tie-down requirements for tag units. Setting the strap angle. When straps are con- TAG UNIT VERTICAL ANCHORS nected only to the near I- See Addendum to these installation instructions for tie-down requirements for tag units. beam,(Figure 71)the an- gle the strap makes with the ground should be be- At Wind Zone 11 or III install tie-down strap to a ground anchor through the factory in- tween 30 degrees and 60 stalled bracket. Install ground anchor and tie-down strap at each factory installed degrees. Angles greater bracket. than 60 degrees may re- OFFSET UNIT ANCHORS quire closer anchor spac- See Addendum to these installation instructions for tie-down requirements for offset ing. units. Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 70 PFS certifies this document is current as of 12-16-09. FS#o5 Install Stabilizing Conforms to Systems NIP- HUD MHCSS 3/19/09 STEP 2. DETERMINE TIE-DOWN CONFIGURATION There are two primary tie-down configurations:the near beam and the far beam meth- ods. Skyline Corporation use the near beam method for all Wind Zone I applications. The near beam method is also used at Wind Zones II and III,except when a unit has a 5 in 12 roof pitch,and then the far beam method is used. The two methods are described below: • Near Beam Method.Connect an anchor strap from the anchor head to the beam closest to the anchor. (Figure 71). In addition for Wind Zones II and II, connect a vertical sidewall strap from the sidewall of the home to the anchor head using a double-headed anchor. • Far Beam Method. Connect an anchor strap from the anchor head to the out- side beam. (Figure 71). In addition for Wind Zones II and ll, connect a vertical sidewall strap from the sidewall of the home to the anchor head using a double- headed anchor. The far beam method is only required for double wide units at Wind Zone II or III with a 5/12 roof pitch. Figure 71.Lateral tie-down Sidewall Vertical Tie-down Floor configurations (Wind Zonell or III). NearI-Beam �Farl-Beam Gro nd Level V ar Beam sidewall frame downgle-30 to 60 degrees ar Beam sidewall frame tie-down(5/12 Roof pitch units at Wind Zone II or III). te Ground Anchor r STEP 3. SELECT ANCHORS m Use the torque probe results from Prepare the Site,STEP 5.DETERMINE SOIL- 0 BEARING CAPACITY AND FROST LINE(p. 15)and the anchor manufacturer instruc- 0 tions;select the type and length of anchor to use.The installed ground anchor size (length)must be listed(i.e. approved)for the soil class. 0 Make sure the anchor is of sufficient length such that the top of the helix is below the frost line.Select a shaft diameter sufficient to resist excessive torsion,"ring-off'(when p the helix or anchor head separates from shaft)or shaft splitting.Consult the anchor sup- Z plier for guidance. Z N Review all of STEP 3.INSTALL ANCHORS(p.71)and STEP 4.INSTALL STRAPS(p. D 72)before making final anchor selections to determine when single-headed vs.double- r headed anchors should be used. Follow the specifications in Table 30 when selecting r D stabilizing system components. —I O z D z c D r 3/18/20091:30:55 PM Skyline Corporation (4-48 PG. 1) 71 PFS certifies this document is current as of 12-16-09. Install • ' PF49�FHUD]WHCSS #a Systemsonform10 1115109 TABLE 24.ANCHOR SYSTEM MATERIALS SPECIFICATIONS Component Specification Anchors must be tested and listed to-resist a minimum'ultimate load of 4,725 lbs and a minimum allowable working load of 3,1501bs or ultimate and corresponding working load limited by soil conditions and anchor length The working load is the maximum load the designer can use.Ground anchors must be provided with protection against weather deterioration and corrosion.at least equivalent to that provided by a coating of zinc on steel of not less than 0.30.oz per sq ft of surface coated. Straps must be minimum 1-1/4"x 0.035"zinc-coated(0.30 oz per sq ft)steel strapping conforming to ASTM D3953-97,Type 1,Grade 1,Finish B with a minimum allowable working load capacity of 3,150 lbs and a minimum ultimate load of 4,725 lbs.Slit or cut edges of zinc-coated strapping do not need to be zinc coated. The size and type of stabilizer plate,if required by,the ground anchor manufacturer,will be specified in the anchor manufacturer's instructions.Stabilizer plates mutt be provided with protection against weather deterioration and corrosion at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz per sq ft of surface coated.Alternatively,ABS stabilizer plates may used when listed and certi- fled for such use. STEP 4. INSTALL ANCHORS Before beginning anchor installation,check for obstructions under the home such as piers and frame members that may interfere with the tie down strapping. Check with util- ity companies to determine the location of underground utilities,such as electrical and phone lines,and water,sewer,and gas pipes that may be buried in potential anchor lo- cations.Also check for homeowner-installed wires and pipes,such as those connecting Grading area around anchors.Anchor exterior lighting or sheds to the home.These must also be avoided. heads should not rest in FRAME ANCHORS sunken spots. Grade the Frame anchors can be installed in two ways, in-line and against a stabilizer plate.The ground so that water does two methods are discussed below: not collect around anchor heads, but runs away from In-Line Configuration the anchor and out from The in-line configuration(Figure 72)for homes can be used in Wind Zone I only.Typi- under the home.Do not cally,in-line anchors are used under high homes where the anchors can be installed bury anchor heads. from under the home after the home is set. In-line anchors can also be installed before the home is set, however, precisely aligning the anchor with the home both vertically and horizontally is difficult. Using swivel connectors for the strap to beam connection can provide some horizontal flexibility. To install in-line frame anchors,drive the anchor into the ground at an angle and location such that a straight line can be drawn from the tip of the anchor through the anchor head and to the connection point on the I-beam(Figure 73). Figure 72.In-line anchor configuration Figure 73.Stabilizer plate Main Main configuration Beam Beam Sidewall Frame Sidewall Frame Tie-Down Strap P1ef Tie-Down Strap Pier Ground Ground Anchorwith Anchor Stabilizer Plate 31 I I I I I I I I I E 3 I I Stabilizer Plate Configuration Stabilizer plate configurations(Figure 73)are suitable for homes in all wind zones.An- chors may be installed after the home is set.A stabilizer device,typically an ABS or metal plate, is used to prevent the top of the anchor from slicing through the soil when the load is applied.Stabilizer plates are available in a variety of widths. Choose the wid- est plate that can be driven into the soil to maximize resistance to movement.The LAHJ Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 72 PFS certifies this document is current as of 12-16-09. Install Stabilizing Systems P FW�p #ts may have stabilizer plate requirements. � forms to Install anchors with stabilizer plates as follows: BUD macs 1. Locate anchor.Select a location for the anchor under the home but within six 1115109 inches of the exterior wall(Figure 74).Aviod locations that will interfere with skirting. Figure 74.Determining an- chor and stabilizer plate/o- F'°or cation �I 6"max. I-Beam 15 degrees 12"or 16" Stabilizer plate 2. Install anchor.To assure that the anchor attachment point will end up at the stabilizer plate,start the anchor insertion approximately 12 inches back from from the desired location if using a 48 inch long anchor,or approximately 16 inches if using a 60 inch long anchor. Install the anchor at about 15 degrees off, vertical,with the head tilted away from the home. Install the anchor to a depth of Soil depression. approximately one half its length. Do not locate anchor 3. Drive stabilizer plate.Drive the stabilizer plate into the ground to its full depth heads in soil depressions where water may pool. at the point determined in Step 1. 4. Complete anchor installation.Screw the anchor the rest of the way into the ground.The finished anchor must be installed to its full depth. VERTICAL ANCHORS N To install vertical anchors,screw the anchor into the ground directly under the strap at- tachment point on the home until the bottom of the anchor head is flush with the ground Z or no more than one inch above grade. m n STEP 5. INSTALL STRAPS Follow the instructions below to connect straps from the home to sidewall frame,end wall p frame and vertical anchors. Always protect straps at sharp corners including around kbeams with radius clips or other methods(Figure 75). Radius clips may be fabricated from 26ga(min)by 1 '/-inch 0 wide galvanized steel strap formed to fit around corners. Z Z N Figure 75.Radius clips D Longitudal D Bracket —� Protect Top and 0 Bottom of Beam if 1-Beam Z N Strap is Wrapped Around Beam r D Z c D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 73 PFS certifies this document is current as of 12-16-09. InstallStabilizing Systems SPLICING STRAPS PFS#°5 Splicing may be required when a re-cut strap is of insufficient length.Splices in tie-down Conforms 1n p g y q p p g P HUD MHCSS straps are not permitted in a'Y'configuration.Overlap straps by 12 inches,applying one 1/15/09 splice clip from above and the other from below;use a crimping tool to tightly seal the splice clips(Figure 76). Do not run any portion of the splice through an anchor head bolt. Figure 76. Tie-down strap splice Apply S plice Clips In Direction of Arrows Ad— Strap j {fj I I 'Y'Splice �Approx. 12�12" Not NO Permitted SIDEWALL FRAME ANCHORS Install straps to sidewall frame anchors as follows: 1. Connect strap to home.Connect one end of the strap to the home connection point using approved buckles or clips(swivel or hook clip preferred). Figure 77.Strap to beam connection Strap to beam connection. x Regardless of the strap supplier's recommenda- 1O Wrapbeam strap around main O Connect hook btopoconnect tions,the strap must be beam main beam and connect other end of strap to connected to the top of the anchor head. main beam to prevent damage to the structure. 2. Connect strap to anchor.Connect the other end of the strap to the split bolt in the anchor. Leave enough strap length to be able to make at least three, but no more than five complete turns around the bolt before it becomes tight(approxi- mately 2 1/2 inches per turn or 7 1/2 to 13 inches total). Fewer than three turns and the strap may not hold onto the bolt when force is applied. Conversely, more than five turns may not fit within the U-channel of the anchor head. Follow the procedure outlined in Figure 78. Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 74 PFS certifies this document is current as of 12-16-09. Install Stabilizing Systems PFS#°5 Conforms to HUD MHCSS 1/15/09 OInsert the tension bolt into the qO Place the strap through the slotted 5O Using a 15116"socket or open end anchor head and loosely attach shank of the tension bolt and bend wrench,rotate clockwise,wrapping the hex nut. up to 90°. the strap around the tension bolt. OOnce tensioned tolhepontthat O Once fully tensioned,align the If approved by the manufacturer, counterclockwise resistance square neck of the boltwith the double head anchors may be used appears,use a 5/6"open end square recess in the anchorhead for both diagonal and vertical wrench to hold the square neck and tighten the hex nut. This will tie-down strap tensioning.Tension while repositioning the15/16' draw the two togetherand lock the the diagonal tie-down strap first tensioning wrench to continue system into final position. Follow Steps 3 through 7 to install tensioning. Repeatasrequired. straps to anchorhead. Figure 78.Procedure for connecting the strap to frame and anchor 3. Pretension anchor.For anchors with stabilizer plates, pretension the anchor by pulling it up to the stabilizer plate using the strap and take-up bolt to move the anchor head.Continue pulling the strap until the plate moves a small i // amount(about 1/2 inch).This is called packing the plate and it will yield the • Cn strongest resistance(the bottom of the anchor head should be maximum 1/4 Anchor head location.As inch above the top of the stabilizer plate). the anchor is pulled up to '< END WALL FRAME ANCHORS meet the stabilizer plate, Z the head of the anchor will rn Attach straps to the bracket welded by the manufacturer to the frame(Figure 79). If no rise. In its final position,the 0 brackets have been installed,use approved beam clamps designed specifically for this O bottom of the anchor head purpose,available from anchor suppliers.Connect straps to anchors following same pro- should be no more than cedure as for sidewall frame anchors. 1/4 inch above the top of O the stabilizer plate. Bracket Figure 79.End wall frame p anchor attachment method Z Main Beam Z I D r Pier End Wall Tie- D 30-45 Down Strap —I degrees\ Z D Z c Anchor with -- D Stabilizer Plate r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 75 PFS certifies this document is current as of 12-16-09. PFS#°5 MARRIAGE LINE VERTICAL ANCHORS orms to Co If vertical straps have been attached to the home by the manufacturer,connect the other HUDf MHCSS end of the straps to the anchor heads. Factory installed marriage line uplift straps must 1115109 be attached to anchoring equipment. The types of straps used are shown below. (Figure 80)Type 1 is a strap used at Wind Zone I only. Some Wind Zone I units do not require marriage line vertical uplift tie-downs. These units will not have any of the straps shown below factory installed and will have double marriage line walls. Type 2 and 3 are used at Wind Zone II or III only. All Wind Zone II or III multi wide units require marriage line vertical tie-downs. Figure 80.Marriage line ver- tical tie-downs Uplift connector capacity is 3114 lbs.each to be T le 3 resisted by anchoring equipment. Factory installed standard Uplift connector capacity is T T e2 hurricane strap.capacity 1242lbs.each to be resisted by Type Is 3150Ihs. anchoring equipment. \ 1; 1/4"cable thimble inserted in connector hole. 7132'or 114" / galvanized steel Slot in strap is for `Standard hurricane is cable.Tension attachment of standard Li to be connected per manufacturer hurricance strap. directly to an instructions. anchor. ground anchor. STEP 6. TIGHTEN AND ADJUST STRAPS After all anchors have been installed and pre-tensioned, recheck all anchor straps to as- sure that they are tight and that the anchor shafts have remained in contact with the sta- bilizer plates.Do not over-tension straps. 10, .• to • Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 76 PFS certifies this document is current as of 12-16-09. PFS#®5 Connect Conforms to Connect Utilities HUDM HCSS 12/16/0909 This chapter contains procedures and requirements for the connection and testing of utility hook-ups. Responsibility for making utility connections varies by location.Consult the LAHJ and the utility before connecting the home to any utilities. Follow the Steps • - • STEP 1.CONNECT ELECTRICAL SERVICE(p.77) 1 STEP 2.CONNECT WATER SERVICE(p.80) STEP 3.CONNECT GAS SERVICE(p.83) I � STEP 4.CONNECT OIL SERVICE(p.84) t STEP 1. CONNECT ELECTRICAL SERVICE The home is designed for connection to an electrical wiring system rated at 120/240 volt AC. All electrical field work must be done by a licensed electrician or other person ap- proved by the LAHJ. - Special precautions when 50 AMP POWER SUPPLY CORD installing electrical ser- The power supply to a Skylne Corporation manufactured home may be by a listed 50 vice.Installation of the AMP power supply cord. The power cord shall be permanently attaced to the distribution electric power to the home panel board or to a junction box. The listed 50 AMP power supply cord shall bear the fol- can cause exposure to live lowing marking: FOR USE WITH MOBILE HOMES—50 AMPERES. electrical circuits. Exposure to live electrical circuits or FEEDER WIRE AND EQUIPMENT SIZES improper grounding of the The current rating(in amperes)of the home can be found on the tag located on the out- conductor in the panel side next to the feeder or service entrance,and on the electrical distribution panel. Using board may result in severe this information,determine the required feeder wire size from Table 25.These sizes are shock or possible electro- based on an ambient temperature of 86 degrees Fahrenheit and do not take voltage drop cution.A qualified installer into consideration. must make the connec- Acceptable conductor types are: RHH, RHW, RHW-2,THHN,THHW,THW,THW2, tions for the electric power. THWN,THWN-2,XHHW,XHHW-2,SE, USE,and USE-2. TABLE 25.ELECTRICAL FEEDER WIRE AND EQUIPMENT SIZES FOR COPPER ca CONDUCTORS X Minimum Conductors(Cu) r Size z Junction Raceway Red& White Green MiSare m box size Conduit Black n DiameterO 50 6x6x6 1 #6 AWG I #6 AWG '.#10,AWG' F #8, 0 100 8x8x4 1-1/4 #3 AWG #3 AWG #8 AWG #8 125 10x10x4 1-112 #2 AWG #2 AWG #6 AWG #6 55 150 10x10x4 1-1/2 1/0 AWG #2 AWG #6 AWG #6 Z 200 12x12x4 2, 3/0 AWG 1/0 AWG #6 AWG Lam"" Cn Z 225 15x12x4 2-1/2 3/0 AWG 110 AWG #4 AWG #4 r r D O Z D Z c D r 12/8/20092:42:53 PM Skyline Corporation (4-48 PG. 1) 77 PFS certifies this document is current as of 12-16-09. PFSo #05 onforms to HUD MHCSS 1/15/09 FEEDER CONNECTIONS Feeder connections are made from above or from below the home as follows: i // From above—mast weatherhead feeder The routing,connection,and support of the service drop must meet local codes. Homes Power supply.A large equipped this way contain all necessary conduits to the electrical distribution panel. enough power supply must However,the feeder conductors(not provided with the home)are installed on site. If the be available at the site.An masthead is located above the roof overhang,allow a minimum clearance of eight feet inadequate power supply above all roof points that the conductors pass over.There are two exceptions to this rule: may result in improper op- (1)The vertical clearance may be reduced to three feet if the roof has a minimum slope eration of and possible of 4 in 12;and(2)The vertical clearance may be reduced to 18 inches if no more than damage to motors and ap- four feet of service-drop conductors pass above the roof overhang,and if they terminate pliances. It may also in- at a through-the-roof raceway or approved support.A minimum clearance must also be crease electricity costs. provided from the final grade to the service-drop conductors.This measurement may vary from 10 feet to 18 feet,depending on the types of traffic anticipated below the ser- vice drop(refer to the NEC). Unless impractical,locate service heads above the point of attachment of the service-drop conductors and make them rain-tight. If individual conduc- tors do not extend downward,form drip loops. From below—underside junction box feeder A section of conduit is factory installed through the floor cavity.Connect to that conduit with approved fittings and conduit(not provided with the home)to the point where the service entrance cable enters the crawl space. Install properly-sized service entrance conductors from the main power supply to the panel board. Depending on the location of the main panelboard inside the home,or the point at which the service entrance conduc- tors enter the crawl space,a separate service disconnect may be required. Refer to Table 25 for the conductor and junction box requirements.The installer must provide the supply connection including the feeder conductors,junction box,and conduit connectors. Protect conductors emerging from the ground from a minimum of 18 inches below grade to eight feet above grade,or to the point of entrance to the home.The distance meas- ured from the top surface of a buried cable,conduit,or raceway to the finished grade must meet the minimum burial requirements outlined in the NEC. Use a moisture-proof bushing at the end of the conduit from which the buried cable emerges. GROUNDING The home must be properly grounded to protect the occupants.The only safe and ap- proved method of grounding the home is through an electrically-isolated grounding bar in the manufactured home distribution panel board.This grounds all non-current-carrying Grounding the electrical metal parts to the electrical system in the home at a single point. system.Do not provide Q Each neutral conductor must be connected to the system grounding conductor on the the electrical power until the Z supply side of the main disconnect in accordance with Articles 250.24,250.26, and grounding electrode is in- Q 250.28 of the National Electrical Code,NFPA No.70-2005. stalled and connected. M When the meter base is Z Where the meter base has a disconnect(typically when the meter is more than 6 feet not on the house never use O from the service electric panel, although this may vary by LAHJ)the ground and neutral the neutral conductor of Qshould be bonded at that disconnect and then grounded to the driven earth ground. Four the feeder cable as a wires will leave the service electric panel to the disconnect.Three wires will enter the ground wire. Q disconnect from the meter base(refer to Figure 81). Where there is no disconnect on the meter base or between the meter base and service co electric panel(typically when the meter is within 6 feet from the service electric panel,al- Z though this may vary by LAHJ),the main circuit breaker in the service electric panel be- 0 comes the first disconnect. In this case,the neutral and ground are bonded in the service Q electric panel and connected to the driven earth ground from the service electric panel.Three wires lead between the meter base and the service electric panel(refer to O Figure 82). a rr O L) w Z J Y Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 78 PFS certifies this document is current as of 12-16-09. FS#os � Connect Utilities Conforms to HUD MHCSS 1115109 Service Entry Figure 81.Electrical feeder Main Panel (May Be Above Or Below Ground) connection when meter has Enclosure a disconnect installed(typi- 2"ServiConce Head call more than 6 feet from IB2 utral Service Head y Equipments Bar service electric panel). Ground Bus Bar Meter By Udlity, Meterbase Company Ground From Meter Enclosure Disconnect nding.Strap 2"Conduit t Installed Disconnect Grounding Lug Conduit (Fused) To Chassis To GroundingRod To MainfPanelMetallic Conduit OBe Effectively GrouEquipment Groundck-"HOT"ToA OrB Red-"H OT"To A Or B White To.Neutral Bus Bar Ground To Equipment Ground Figure 82.Meter base wir- �Main Pam] service En,/ ing when there is no sepa- Endoswe (Aboee Or Below Ground) rate disconnect installed —2'COMuit To B Naemal seMes tread (typically within 6 feet of ser- Eund! panel). l Bea Be, Groround vice electric l). Bus Bar Meter By u- Company Meter Endosurs Bonding Strap yCantlud Installed By L nufacnmr Grounding Lug Canduil To Chassis To Grounding Rod To Main —Panel Metaac Contluit Or Rtmgs To Be Effecrrrely Grounded To Equipment Bladc-'FIOT'To AOre Ground Red-'FtOr To AOrB White To Neutral Bus Bar In all cases,a grounding electrode conductor and a ground wire must be installed ac- cording to the following specifications: 1. Grounding wire to be per Table 25 provided by the manufacturer. If manufac- Cl) turer provides a minimum 1/2 inch EMT or conduit raceway,the#6 minimum < bare copper wire is provided by the retailer for installation. r— z 2. The clamp connecting the grounding wire to the electrode shall be suitable for m direct burial and located flush or below ground level. n O 3. Use a listed 5/8 inch diameter by eight foot long iron.electrode or nonferrous rod -'o of at least 1/2 inch diameter by eight feet long for grounding(larger sizes may 0 be required by the LAHJ due to soil impedence). D 4. Drive the electrode to a depth of not less than eight feet so that at least eight p feet of the electrode is in contact with the soil. z 5. When rock is encountered,the electrode may be driven at an angle not to ex- Cn ceed 45 degrees from vertical or buried in a trench that is at least 2-1/2 feet D deep. r r D FIELD INSTALLED METER BASE O When a meter base is,installed in the field, Figure 83 and the following requirements z must be adhered to: D • Install the meter base according to the manufacturer's instructions. z C • Use straps to support any conduit. Do not use the meter base equipment for D support. r • Use exterior equipment and enclosures listed as weatherproof and entrance 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 79 PFS certifies this document is current as of 12-16-09. Connect Utilities PFS#°5 Conforms to HUD MHCSS 1115109 conductors listed for wet locations. • The grounding bar may be installed separate from the neutral bar for purposes of testing the electrical system. • The grounding bar may be isolated during the electrical check and re-attached, after the tests are completed. • Check with the local electrical utility to verify meter base requirements and loca- tions and distances for the main panel and meter box. • The field installed meter base enclosure must be installed in accordance with its listing. Fasten securely to exterior wall studs and provide fora weather-tight seal. • Check the local code for any requirements regarding the location of the meter base. f Exterior Wag Meter Meter Enclosure Figure 83.Meter base clearances. 114°Air Space Between Meter Enclosure And Exterior Wag STEP 2. CONNECT WATER SERVICE CONNECTION To connect the home's water system to the water source, identify the water inlet located • under the home(usually below the water heater compartment or utility room)and follow Selecting heat tape.Use the procedure described below(refer to Figure 84): only pipe-heating cable 1. Flush pipe.Flush field-installed water piping free of all debris prior to connec- (tape)listed for manufac- tion to the home's water inlet. tured homes,and install it z 2. Clean threads.Ensure that pipe threads are clean. in accordance with the ca- M 3. Install pressure-reducing valve.If the local water supply exceeds 80 psi in- ta l(tape)manufacturer in- s z stall a pressure-reducing valve. talation instructions. O 4. Connect valve. Install a main shut-off valve between the water supply and the Maximum water pressure. Qinlet on the home. Locate the riser for the shutoff valve underneath or adjacent The water system for the J to the home. Select a full flow gate or ball shutoff valve,or equivalent valve.To home was designed for a maximum inlet pressure of Hprevent the possibility of fresh water contamination install an anti-siphon valve 80 psi. co on all field installed exterior faucets. z z O O a W O W z M Y Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 80 PFS certifies this document is current as of 12-16-09. N#os Connect Conforms to HUD MHCSS 1/15/09 Figure 84. Water system connection Factory-Installed Turning on Water Service. Water Pipe Do NOT turn on the water service to the home until the Optional Hose Bb (Not Supplied) drain lines have been com- ConnectToTn- _-_--_______:; pleted and connected to the Here For Water �'--' u--Service sewer system. System Test Service Connection (Not Supplied) Locate-Water Riser Undemeath or I j Mandatory Shut-off Adjacent to Home Valve(Not Supplied) I I. 5. Install water heater discharge drain.Inspect the drain opening on the water heater to ensure that it is clear of any obstruction. If the home is to be installed on a basement or enclosed crawlspace, install drain pipe connecting the dis- charge from the water heater temperature and pressure relief valve to the out- @Using check side or to a sump. valves. Install a check 6. Install water heater drip pan drain.Assure that the drain for the water heater valve on the water inlet to drip pan does not terminate under the home. Using the materials provided and prevent water system the accompanying instructions run a drain line from the water heater drip pan drainage in the event of a through the floor to the exterior of the crawl space.Terminate the line between loss of water pressure from six and 24 inches above grade. (Figure 85). Make the termination point rodent the source.Such pressure proof. loss could cause the water heater to drain,exposing the heating elements of electric water heaters causing them to fail. Water Heater(factory installed) Figure 85. Water heater drip pan and drain N Exterior wall Note 1.Water heater drip r pan drain pipe has been fac- Water heater installed) tory installed through the m (factory instal bottom board. A 90 degree O elbow has been factory in- 0 stalled to accept the pipe ex- M Floor decking tension. Floor)oist Note 2. Insert the CPVC or PVC drain pipe extension 0 (factory provided—field in- E stalled)into the factory in- z stalled 90 degree elbow. Be I J� sure to provide'/<"per foot r / CPVC or PVC water heater of slope to provide positive r / Bottom board drainage. D drip pan aver-flow drainage g —I pipe(factory installed). See Q Install screen over end of CPVC or PVC pipe extension note 1. Z pipe extension(not (field installed). See note 2. 9 provided). D Support pipe extension every 4'-0" Z C D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 81 PFS certifies this document is current as of 12-16-09. Connect UtilitiesPFS#°5 Conforms to ' HUD MHCSS 7. Insulate. In areas subject to freezing temperatures, protect with insulation or 1/15/09 heat tape pipes,valves and pressure reducers that are exposed to the out- doors;and pipes in water heater compartments with non-insulated doors.Con- nect heat tape to the electrical outlet under the home near the water supply inlet. Selecting heat tape.Use only pipe-heating cable (tape)listed for manufac- TESTING tured homes,and install it After testing the electrical system and connecting the water lines check the water system in accordance with the ca- for leaks using one of the procedures described below. Before testing,close all water ble(tape)manufacturer in- faucets,spigots,and toilet-tank.float valves. stallation instructions. Hydrostatic(preferred): Testing water lines.Only use pneumatic(air)testing 1. Bypass water heater.Bypass the hot water heater by disconnecting the hot when hydrostatic testing is outlet and cold inlet water lines from the water heater and joining them together. not practical.Air under This will protect the hot water tank from damage and protect those involved in pressure is explosive. Ex- the test from possible injury. ercise extreme caution and 2. Fill water heater.Confirm that the water heater tank is full of water. notify all site personnel of 3. Pressurize system.Connect a hydrostatic pump,valve,and gauge to the loca- the test.Wear protective tion shown in Figure 84. Pressurize the system with water at 100 psi,and then eyewear and take precau-, isolate it from the pressure source. Bleed all air from the highest and farthest tions to prevent impact points in the system. damage to the system while the test is in pro- 4. Hold pressure.Monitor the pressure for at least 15 minutes. gress. Do not pneumati- 5. Fix leaks.If the pressure drops below 100 psi,locate and correct any leaks by cally test CPVC systems. cutting out and discarding bad pipe sections or joints and installing new pipe or Pneumatically test Flow joints with couplings. Guard Gold systems only 6. Repeat. Repeat the test until all leaks have been eliminated. at low pressure levels(20 psi or less). Pneumatic: Pressurizing water lines. 1. Bypass water heater.Bypass the hot water heater by disconnecting the hot When pressurizing the wa- outlet and cold inlet water lines from the water heater and joining them together. ter system,connect the This will protect the hot water tank from damage and protect those involved in pump to a location above a the test from possible injury. closed shut-off valve so as 2. Pressurize system.Connect an air pump and pressure gauge to the water not to introduce pressure inlet, pressurize the system to 100 psi and isolate the pressure source from the into the municipal water system. supply. 3. Hold pressure.Monitor the pressure for least 15 minutes. If the pressure drops below 100 psi,locate any leaks by applying soapy water to the connections and Q looking for bubbles. Z4. Fix leaks.Correct any leaks by cutting out and discarding bad pipe sections or joints and installing new pipe or joints with couplings. Z 5. Retest. Repeat the procedure until all leaks have been eliminated. O 6. Restore connections.Reconnect the water heater and the water supply. H J FREEZE PROTECTION FOR UNOCCUPIED HOMES _J If the home is to be left unheated in cold weather,protect water lines from freezing as fol- lows: Z 1. Disconnect supply.Turn off the water supply and disconnect the water supply Z inlet. 0 2. Drain water heater.Turn off the water heater;if necessary,attach a hose to the valve to direct water away from under the home,open the drain valve and drain the tank completely. C- 3. Drain faucets.Open all faucets throughout the home(including the.laundry parea if plumbed,and any exterior faucets)and let them drain completely. U 4. Drain toilets.Flush toilets and drain water tanks completely. LU Z 5. Close faucets.Close all water faucets with the exception of one. } 6. Connect compressor.Connect a maximum of 30 psi air supply to the water co inlet connection using a low pressure compressor. 7. Open faucets.With the air supply on the system,open one faucet at a time Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 82 PFS certifies this document is current as of 12-16-09. Connect #®5 throughout the home. 4go:5 8. Disconnect compressor.After the entire system has been drained of all water, onforms to disconnect the air supply and close the water inlet valve. - MID nlxcss 9. Pour anti-freeze.Pour an antifreeze solution into all drain traps, including 1n5i09 sinks,tubs,and toilets.Be sure that the antifreeze is safe for the fixtures and P- traps. STEP 3. CONNECT GAS SERVICE CONNECTION If the home uses natural or liquid petroleum gas(LPG,also known as propane)for water • or space heating,cooking or other appliances,follow the procedure described below: Installing gas lines.Only 1. Inspect vents.Assure that all exhaust vents on gas-fired equipment are se- qualified professionals may curely connected and that roof jacks and stacks have not come loose during connect and test gas ser- transit and they are properly installed. vice. 2. Review appliance instructions.Review each appliance manufacturer's in- structions before the home is connected to the gas supply. Most gas appliances are typically configured to operate on natural gas. If the gas supply will be LPG, consult the appliance manufacturer's instructions to determine what changes need to be made. For homes located above 3,000 feet,appliances may require a different orifice. 3. Remove cap.Remove the protective cap from home inlet pipe and install a full flow shut-off valve at the supply inlet(Figure 86). 4. Install regulator.The gas piping system is designed for a pressure that is at least seven inches of water column(4 oz.per sq in or 0.25 psi)but not more than 14 inches of water column(8 oz.per sq in or 0.5 psi). If gas from any sup- ply source exceeds,or could exceed this pressure,install a regulator if required by the LAHJ. 5. Connect supply.Using matching threaded fittings,connect the gas supply to the inlet side of the shut-off valve. 6. Close valves.Close all valves at appliances prior to opening the main supply valve. Figure 86. Gas service con- nection Full Flow Shutoff Valve Required Floor . (Supplied By Others) r- Z m n O Dust Cover M O Union(Supplied By Others) 0 Source of Gas Z Z TESTING Test the gas piping system in the following two ways: 1)piping only and 2)entire system. D Consult with the LAHJ for any additional testing or start-up requirements. D Before testing is begun,the temperature of the ambient air and the piping should be ap- Fill gas water heaters. Be- proximately the same.Conduct the tests when and where air temperatures will remain fore lighting the pilot on a Z constant. gas powered water heater, 9 Piping only test(all appliances isolated) fill the tank with water. Fail- Z 1. Isolate appliances. Isolate all appliances from the system by closing all appli- ure to do so could damage C ance shut-off valves. the water heater. r- 2. Attach gauge.Attach to the home's gas inlet a mercury manometer or slope 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 83 PFS certifies this document is current as of 12-16-09. Connect Utilities RE#05 Conforms to WOO HUD MHCSS gauge calibrated in increments of not more than 1/10 lb. 1/15/09 3. Pressurize system.Using an air compressor, pressurize the system with com- pressed air to three psi and isolate the pressure source from the system. 4. Monitor pressure. Monitor the pressure for at least 10 minutes. 5. Check for leaks. If pressure drops below three psi,check for leaks by applying a non-corrosive,ammonia-free gas leak detection fluid to the joints at all valves, appliance connections,and crossover connections(do not use dish washing de- tergents,soap, or other household chemicals). If bubbles form,tighten the con- nection and recheck. 6. Repair leaks. If leaks persist, replace defective pipes or fittings with sound ma- terial and retest. 7. Release pressure. Release pressure and open all appliance shut-off valves. 8. Rinse connections.Thoroughly rinse all tested connections with water to re- move leak detection fluid. Entire system test(with appliances) 1. Close appliances.Close all gas equipment controls and pilot light valves ac- cording to the individual gas equipment manufacturer's instructions. 2. Open valves.Assure that gas shut-off valves for all gas equipment are in the open position. 3. Attach gauge.Attach to the home's gas inlet a pressure gauge calibrated in ounces. 4. Pressurize system.Pressurize the system with compressed air to six to eight ounces(3/8 to 1/2 psi,or 10 to 14 inches of water column). 5. Check for leaks.Check for leaks as described above in step 4 of the Piping only test. Replace defective pipes or fittings with sound material and re-test. 6. Rinse connections.Thoroughly rinse all tested connections with water to re- move leak detection fluid. GAS APPLIANCE START-UP Open the shut-off valve for each appliance and adjust the burners according to the appli- ance manufacturer's instructions.Verify that the furnace and water heater thermostats are operating properly and set them to the desired temperatures. STEP 4. CONNECT OIL SERVICE Homes that are equipped with oil burning furnaces must have oil supply piping installed _J and tested on site by a qualified professional in accordance with NFPA 31,Standard for Q the Installation of Oil Burning Equipment,2001 or the requirements of the LAHJ,which- Testing oil tanks.All oil Z ever is more stringent.The home manufacturer does not supply oil piping or tanks. storage tank and piping in- OIL CONNECTION stallations and tests must Z Consult the furnace manufacturer's instructions for proper pipe-sizing and installation meet all applicable local 0 procedures.Where piping is run through the bottom of the home,ensure all holes in the regulations and should be Qbottom board are sealed tight with foam, mastic,and/or tape specially made for that pur- made only by experienced; J pose and made rodent proof. qualified personnel. J HWhen equipping the home with an oil storage tank,comply with the following: Z0 Install the pipe with a gradual slope toward the fill end or drain plug(if so Z equipped)to facilitate pumping or draining of water and sludge. 00 Provide a readily accessible approved manual shut-off valve at the outlet,in- stalled to close against the supply. Equip the tank with an approved oil filter or strainer located downstream from IL the tank shut-off valve. Use a filter or strainer containing a sump with a drain to 0 trap water. U • Equip under ground tanks with a filler neck extending one foot above grade and W a minimum 1-1/4 inch diameter vent pipe extending at least two feet above Z grade. YLocate the tank to be accessible for service and inspection, and safe from fire and other hazards. Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 84 PFS certifies this document is current as of 12-16-09. Connect • If the tank is located inside a compartment of the home, provide ventilation at PFS#°5 the bottom of the compartment to permit diffusion of vapors. If the tank is fixed to the home,provide for.filling and draining from the outside. HunrMlMcss • Insulate interior tanks from the structural members of the home.Provide tanks 11 1 5109 so installed with an outside fill and vent pipe and an approved liquid level gauge. • Install tanks that feed vaporizing type oil furnaces so that oil flows by gravity.To achieve efficient gravity flow, make sure that the bottom of the tank is at least 18 inches above the furnace oil control level. • Tanks for gun type oil furnaces(these furnaces include a fuel pump)may be in- stalled above or below ground. OIL SYSTEM TESTING Before operating the system,fill the tank to capacity with the fuel to be burned and visu- ally check all joints in the system for leakage. Replace(do not repair)parts that leak. go to Prepare Appliances and Equipment (p. 86) Cn - r z m n O „ O O Z z Cn D r r D O Z D Z C - D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 85 PFS certifies this document is current as of 12-16-09. Prepare /PF�HUDMHCSS # 5 • 1/15/09 Prepare Appliances and Equipment This chapter provides instructions for installing and/or preparing appliances and other equipment.While the items below can be completed in any order,the last item,CONDUCT ELECTRICAL TEST, must be done last. Follow - • . - • 7V711NSTALL AIR CONDITIONER OR HEAT PUMP(p.86) ` PREPARE HEATING SYSTEM(p.87) INSTALL REMOTE HEATING AND COOLING EQUIPMENT(p. 87) PREPARE VENTILATION SYSTEM(p.88) PREPARE FUEL-BURNING WATER HEATER(p.88) fV PREPARE CLOTHES DRYER(p. 89) i • i PREPARE SMOKE ALARMS (p.90) jV PREPARE FIREPLACES(p.90) i t { i V PREPARE KITCHEN AND BATH APPLIANCES/FIXTURES(p.92) { INSTALL EXTERIOR LIGHTING(p.93) INSTALL CEILING FANS AND LIGHTING(p.93) j V TEST ELECTRICAL SYSTEM (p. 95) INSTALL AIR CONDITIONER OR HEAT PUMP (if applicable) CENTRAL UNITS i // Z Install split system or unitary central air conditioners and/or heat pumps as follows: 0 g 1. Check suitability.Check the home's Comfort Cooling Certificate(may be in- Use listed appliances.All Z cluded with the data plate)to confirm that the home is suitable for installation applicable appliances must 0 of central air. If so, note the air distribution system's rated duct capacity be listed or certified by a Q (BTU/hr), any equipment sizing guidance provided by the manufacturer and nationally recognized test- J information provided to calculate the home's heat gain. ing agency for the applica- ~ tion for which the unit is in- not exceeding the maximum indicated on the home's data plate and a rated Z cooling capacity sized in accordance with Chapter 28 of the 1997 ASHRAE cordance with the terms of Z Handbook of Fundamentals or ACCA Manual J, Residential Cooling Load, 8th its listing or certification. 0 edition. Information needed to calculate the home's heat gain can be found on Properly sizing equipment. the home's comfort cooling certificate. Choose equipment with a min.circuit Oversized cooling equip- 0� amperage(found on the equip. rating plate)no greater than the branch circuit ment can lower energy effi- 00. rating of the exterior air conditioning receptacle(indicated on the adjacent ciency, reduce comfort, W tag), if present. shorten equipment life,and 0 3. Install A-coil.When installing a cooling A-coil in a down-flow furnace that in- may cause moisture prob- 0 corporates a fresh air intake duct, position the duct in the furnace cavity ac- lems in the home(including w potentially damaging the z cording to the furnace manufacturer's instructions(Figure 87). For electric p y g g _J down-flow furnaces,trim the ventilation duct as needed to allow installation of home's structure).Sizing Ythe A-coil and secure the duct to the wall of the compartment or to the top of guidance is provided by the Manufactured Housing Re- Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 86 PFS certifies this document is current as of 12-16-09. PFS#o5 Prepare Appliances Conforms to - • • • ment HUD MHCSS 1/15/09 the A-coil. Do not restrict the flex duct opening;allow the duct insulation to search Alliance Cooling contact the A-coil,or allow the duct to become kinked, restricted,or config- Equipment Sizing Guide- ured to form a trap. lines available at www.mhrahome.org. Figure 87. Whole house ventilation flex duct in an electric down-flow furnace. From left to right.as pre- pared in the factory,•proper TAP installation with A-coil,im- proper installation with A-coil "Whole 'Whole House" House" Ventilation Ventilation Flex Duct Flex Duct A-Co0 Selecting A-coils. Use only A-coil units compatible and listed for use with the fur- Fumace Furnace nace in the home and in- Furnace Cabinet Furnace Cabinet Furnace stalled in accordance with the furnace manufacturer's instructions. PREPARE HEATING SYSTEM Installing flue stacks with a If the home does not contain a factory installed heating appliance, install a remote hinged roof.If flue stack heating appliance according to INSTALL REMOTE HEATING AND COOLING components are installed EQUIPMENT, p.87. Prepare fuel-burning heating systems included with the home as above the finish roof line follows: (as is often the case with 1. Inspect for damage. Inspect the furnace and report any damage to the home hinged roofs),an terna- le tive Construction letter is manufacturer. normally required along 2. High altitude.If the home is located more than 2,000 feet above sea level or with a follow-up inspection. as indicated in the furnace manufacturer's instructions,derate gas furnaces Contact the factory for 4%for each 1,000 feet above sea level.This work must be done by a qualified guidance. (and in some jurisdictions, licensed)technician. Venting appliances to the 3. Convert for LPG gas. If LPG gas(propane)will be used,convert the appli- outside.Vent to the exte- ance from natural gas to LPG gas use.Conversion must be made by a quali- rior of the home all com- Cn fied and(if required by the LAHJ)licensed technician. bustion appliances except X 4. Install intake air pipe.Consult the appliance manufacturer's instructions for ranges and ovens. maximum allowable pipe run length,requirements for air dampers,locations Selecting ducts.Exterior m relative to expected snow levels(check with the LAHJ for expected snow lev- ductwork for remote units n els),acceptable materials,pipe supports,and pipe termination requirements. must be provided by the in- 0 5. Install flue.For combustion appliances, install the flue roof cap and stack as- staller or HVAC contractor. X sembly as described in PREPARE FIREPLACES,Chimneys(p.90). Ducts must be approved for O exterior installation and X INSTALL REMOTE HEATING AND COOLING EQUIPMENT should be wrapped with in- I sulation of at least R-4 un- O Install remote units in compliance with all heating and cooling equipment requirements der a vapor barrier with a Z in this chapter above and the following: perm rating of not greater m 1. Locate connections to the home. Find the manufacturer-installed connec- than one. (For ENERGY tors, labels,or tags under the home indicating the required connection points STAR homes,the R-value r for supply and return air. If connectors are not provided nor location indicated, must be at least that speci- r select a supply duct location such that there are approximately equal numbers fied on the manufacturer's > of supply registers forward and rear of the connection point.Locate the return ENERGY STAR Site Instal- duct in the center of the home. lation Checklist—generally Z 2. Install ducts.Install the appropriate supply and return ducts(not provided) a minimum of R-6 or R-8.) D between the remote unit and the home(Figure 89), making connections ac- Z cording to the instructions for crossover ducts in Crossover Connections(p. D 52). r 3. Install dampers.If installing a remote cooling unit in a home with a factory in- 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 87 PFS certifies this document is current as of 12-16-09. Prepare Appliances #05 4Z� • • Equipment Confors o SMHCSHUD 1/15/09 stalled furnace;install dampers between the furnace and the home's air duct system,and between the remote unit'and the home's air duct system to pre- vent warm air in heating mode from escaping to the remote cooling unit and vice versa. Figure 88.Remote unit to damper locations Frrrrace io 0 III Exterior Dud Dampers Remote tfiit Hone 4. Connect wiring.Install a thermostat containing a fan switch.Connect utilities in accordance with all manufacturer's instructions and local codes. 5. Seal penetrations.Repair or replace all floor insulation disturbed during the duct installation and seal holes in the bottom board using foam, mastic,or tape specially made for that purpose. Air Conditioning or Figure 89.Ducts connecting Heating Equipment exterior heating and/or cool- supply Marriage Supply Retum ing equipment to the home -J Duct Line Duct Duct Q Z Q Z Support Straps at upport Block 48"in.O.C.Minimum Q Minimum Clearance Between Ducts and Ground to be4in. J PREPARE VENTILATION SYSTEM ZPrepare the whole-house ventilation system according to the ventilation system manu- Z facturer's instructions.Confirm that any fresh air intake ducts extend to the exterior and / // p do not draw air from the crawlspace under the home.Do not allow any fresh air ventila- - H Choosing pipe lengths. tion intake ducts to become kinked or restricted,forming a trap(Figure 89). Q The appliance manufac- turer may designate the a PREPARE FUEL-BURNING WATER HEATER length of the pipe run W The water heater discharge and drip pan drains should have been installed in Connect based on the pipe diameter 0 Utilities(p.77). and the number of turns in U ul In homes with direct-vent water heaters(that utilize gas,oil,or other combustion fuel), the pipe run. Z and where the water heater is not independently vented to the exterior through a grilled Y opening, provide combustion air from under the floor using pipe and cement acceptable to the appliance manufacturer or through the roof via a double-walled flue pipe. If pro- vided through the floor,run the air piping to the exterior of the home,with supports Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 88 PFS certifies this document is current as of 12-16-09. Conforms to • • • • HUD MHCSS 1/15/09 spaced every 3-1/2 feet o.c.or less.Terminate the pipe facing downward a minimum of 12 inches above the ground surface and provide a screen on the pipe vent cap. Venting exhaust systems. PREPARE CLOTHES DRYER Exhaust vents must extend DRYER VENTS to the home's exterior . If the home includes a clothes dryer,the components for ventilating the dryer are in- through skirting.Termina- cluded with the home(but not necessarily installed)and a vent opening has been tion of the dryer exhaust roughed in either in the wall or floor. (If a dryer is not installed,seal all dryer vent open- underneath the home can ings). cause condensation and moisture damage to the Run the dryer vent to the outside through the exterior wall or through the floor to a point home.Lint and dust accu- beyond the perimeter of the home, using materials approved by the clothes dryer mulation can ignite, causing manufacturer(see Figure 90). a fire.The exhaust system must not contain reverse slope. Vent Below Floor Vent Through Extedorwall Figure 90. Clothes dryer Elbowwith Clampm ventilation ductwork through Rigid Duct Vent Cap igid or Flex Duct floor left or exterior wall (right) Clamp to Dryer Exterior Connection I)J Wall Dryer Vent + Cap t Clampm El Seal Botbm Vent Cap ' ll�llpn.._"I-..� Milli Boats ClamptoDryer Elbow with Connection Dryer Vent Rigid Duct Cap Support Strap Rigid or Flex Duct Wood Frame Secured to Bottom of Rim Plateor Install Through Skirting Install the vent as follows: 1. Remove temporary caps.Remove any temporary seals and duct caps from the vent rough openings. • fn 2. Install ductwork. Install ductwork using clamps(do not use screws or other Avoid damaging structural fasteners that penetrate into the duct)and support the duct with metal straps elements. Do not cut or connected to the floor joists or chassis at two feet o.c.or less. Ensure duct otherwise damage struc- Z connections are internally overlapped to prevent inhibiting the flow of air and tural elements such as floor rn thereby causing lint accumulation. joists or wall studs for the p 3. Install cap and damper.Install an approved dryer vent cap with damper on installation of the dryer ex- the exterior termination of the duct. If the vent terminates at skirting,secure haust system. p the cap to framing or skirting with sheet metal screws and seal edges with Gas.Ventilation components D caulk or sealant. If the vent terminates through a wall,apply a bead of sealant that may be included with to the back of the cap around the opening and secure with sheet metal screws the home for an electric O to metal, hardboard or fiber cement siding or with wood screws to a mount dryer may not be accept- Z block for vinyl siding. able for gas dryers. Consult N 4. Seal opening.Seal openings inside and outside of the home including at the the gas dryer manufacturer i floor, interior walls,siding and skirting(with caulk),and at the bottom board instructions. r using foam, mastic and/or tape specially made for that purpose. r- =j GAS DRYERS p If the home was not fitted for a gas dryer, installing one requires substantial alteration Z to the home.Gas supply piping and adequate venting must be provided as specified by Installing ducts. D the dryer manufacturer and installed by a trained professional. Do not cut major struc- Keep ductwork straight and Z tural elements to accommodate a gas dryer. smooth as possible without C excess slack.Slope it r slightly downward towards the exterior to facilitate 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 89 PFS certifies this document is current as of 12-16-09. Prepare Appliances • Equipment Conforms to VP_ HUD MHCSS 1/15/09 moisture drainage. PREPARE SMOKE ALARMS The home has several factory installed smoke alarms that are wired to a 120-volt cir- cuit. If the home was designed for placement on a basement,an additional alarm is provided for installation at a pre-wired location under the home.Connect the basement smoke alarm and test all alarms as follows: 1. Check circuit. Ensure that electrical power to the home is activated and that the smoke alarm circuit is on. 2. Remove batteries. Make sure backup batteries(if any)are removed from all smoke alarms. 3. Test alarms.Press the test button on each alarm sequentially.All alarms should sound simultaneously when the test button on any one smoke alarm is pressed.Replace(with the same brand as those installed elsewhere in the home)any alarms that do not sound and retest. 4. Replace batteries.After successful test,replace the backup batteries,dis- carding the protective tabs. PREPARE FIREPLACES Install chimneys,chimney flashing and roofing,fireplace combustion air inlets,and hearths according to the manufacturer's instructions and the procedures described be- low. CHIMNEYS Fireplace and wood stoves may require on-site installation of additional sections of ap- proved chimney pipe,a spark arrestor,and a rain cap assembly. Follow the manufac- turer's instructions and the procedures described below: 1. Remove coverings.Remove protective materials covering the roof flashing and any foreign material from the installed part of the chimney. 2. Install chimney pipe.Assemble and seal the chimney per the fireplace or wood stove manufacturer's installation instructions and if there is a conflict be- tween the instructions and the figure,follow the instructions.To assure suffi- cient draft for proper operation,extend the chimney at least three feet above the highest point where it penetrates the roof and at least two feet higher than any surface within 10 feet of the chimney(Figure 92). Use additional sec- tion(s)of chimney pipe(not provided)if required by local code or if the site Dhas obstructions within 10 feet of the chimney. z Q Z O H Q Q t— Z Z O F- O a IY O U W Z J Y C Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 90 PFS certifies this document is current as of 12-16-09. Prepare Appliances ® Equipment Conforms to HUD MHCSS oof Top Assay* 1n5i09 Figure 91. Chimney and TE Rain Cap combustion air intake duct Spark Arrestor installation Chimney Cap Adler 3'Min Triple Wall PPe Sierra Cola Roof Her)1 Flashig Selecting the appropriate Flrestop Thirtle flue.Wood fireplaces use larger diameter flues than gas fireplaces. Make sure flue matches the appliance type. Gas fireplaces cannot burn wood because the flue is too small and smoke will back up into the home. If wood fireplaces are con- verted to gas the flue will be too large resulting in ex- cessive heat loss through the chimney. 9� i 4 4 i Above nov Level Air Intake From Odskle Less-an 10' Figure 92. Chimney clear- ance 12'Min. 3'Min. 11 2'Min. 10' 3'61in. Cl) r z m n 3. Install shingles. Install shingles up to the edge of the flue cut-out in the roof p deck.Secure shingles installed under the roof flashing with asphalt cement. X M 4. Install flashing.Place flashing over pipe section and shingles and set in as- 0 phalt cement.Secure flashing to roof deck at top two corners with roofing D nails. --I 5. Complete shingles.Cut shingles in successive courses to fit around the pipe z and embed them in asphalt cement where they overlap the flashing.Secure shingles with roofing nails through flashing and apply asphalt cement over nail heads.The completed installation should appear as shown in Figure 93,with D the lower part of the flange overlapping the lower shingles and the side and r upper shingles overlapping the flange. r D O z D z C D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 91 PFS certifies this document is current as of 12-16-09. Prepare Appliances, ��#®5 • • Equipment Conforms to HUD MHCSS 1115109 �-� Figure 93.Roof flashing and Push Doom Upper and Side shingle installation around Roof Shingles Shingles Overlap Caulking Flange and Are Set In chimney Flange Flange Asphalt Cement Storm Collar Flashing r-- -- I I I I Flue Pipe Lower Part of Flange z Trim With Sheet Metal 9 Sheers If Mcult To Make Overlaps Lower Shingle Flashing Lay Flat On Roof COMBUSTION AIR INLETS Combustion air inlets provide combustion air through the floor or an exterior wall to a combustion appliance. If through an exterior wall,site installation is not required. If • through the floor,extend the duct from its point just below the floor to the outside(addi- Installing combustion air tional duct material required for this may or may not be provided with the home).Lo- inlets.Do not install the cate the inlet damper above expected snow levels(contact the LAHJ for snow levels). combustion air inlet such Follow the fireplace manufacturer's instructions(typically in the fireplace/stove or with that material from the the chimney parts). hearth can drop beneath the home. HEARTHS If shipped loose, install the fireplace hearth according to the fireplace manufacturer's instructions. PREPARE KITCHEN AND BATH APPLIANCES / FIXTURES Install kitchen and bath appliances according to the manufacturer's instructions and the procedures described for each appliance below. / • / A COOKING APPLIANCES Installing exhaust ducts. If the home is provided with a range,cook top and/or grill containing its own exhaust Route exhaust ducts so system that penetrates the floor,complete the exhaust system as follows: they do not terminate be- 1. Remove covers. Remove the cover on the factory-installed exhaust pipe pro- neath the home. truding from beneath the floor near the appliance. 2. Install termination fitting.Secure the provided termination fitting at the outside edge of the floor. J 3. Install duct. Use the provided flexible metallic duct to connect the elbow pro- Q trading from the floor and the termination fitting. Refer to the manufacturer's z z installation instructions for guidance on supporting the duct and making the Q connections. z SITE-INSTALLED GAS APPLIANCES 0 Install only appliances with a Btu capacity equivalent to or less than the capacity of the ~ facto installed piping and at the location of a facto Installed as riser. Q ry P P 9 rY- 9 J J REFRIGERATOR Q Prepare the refrigerator as follows: z 0 Remove straps, blocks,or other securement devices used for shipping and z patch any resulting marks on floors or walls. H If the refrigerator has an icemaker,check water lines for leaks upon installa- < tion and a few days later to make sure no leaks have developed. IX 0 SITE-INSTALLED APPLIANCES AND FIXTURES a ce If sinks,tubs,showers or other fixtures or appliances are to be site-installed,follow the 0 manufacturer's installation instructions. Use only products listed for use in manufac- V W tured homes and follow all applicable local codes. z J • Y Skyline Corporation (4-48 PG. 1') 1/9/2009 9:22 AM 92 PFS certifies this document is current as of 12-16-09. #0, Prepare Appliances F J ® Equipment Conforms to HUD MHCSS 1/15/09 INSTALL EXTERIOR LIGHTING Install exterior lighting according to Figure 94 and the following: 1. Remove cover. Remove the screws and cover from electrical junction box. / • /, 2. Install flash ring.Place the non-combustible flash ring over.the junction box. Lighting installation.A 3. Connect wires.Connect fixture wires to house wires in the box, black to qualified electrician should black,white to white, and equipment ground to equipment ground,using listed install lighting. Before con- wire connectors. Push wires into the box. necting lighting,disconnect 4. Connect fixtures.Connect the fixture to the junction box or strap using power to the lighting circuit. screws provided with the light fixture. Ground all exterior light fix- tures. 5. Weatherproof.Weatherproof/caulk around the base of the fixture,leaving a Using a non=combustible small gap in the caulking on the bottom to permit drainage of water that may ring.Install a non- accumulate. combustible ring completely 6. Complete installation.Install bulb and globe on the fixture and verify proper covering any combustible operation. surfaces the fixture may be mounted on(e.g. hard- board,clad wood and vinyl siding),or when ceiling ma- terial is exposed between the light fixture canopy and the junction box. Wire From SM& Figure 94.Exterior lighting Non-CombustibleR'rg Wire From Wire Nut connection (If Required) Wire Nit (Type (Type9 Fixture Caxty I �/ '1rou hi t c) la Whiff / • �/ la round Installing ceiling fans.A �I qualified electrician should Globe install lighting and fans. Be- Pigtail for Ground Cofiu'y fore connecting.the ceiling Jun d`"�" fan or light,disconnect Wire to Cther Baum power to the fan wires.Any unit installed outside of the INSTALL CEILING FANS/LIGHTS home(such as in a porch ceiling)shall be listed for Install ceiling fans with the trailing edges of the blades at least six feet-four inches wet locations. above the finished floor.Comply with all unit manufacturers'instructions and the re- z quirements below. Electrical boxes for use with ceiling fans have a maximum allowed m weight(usually 35—50 Ibs). This is stamped inside the box. Check the maximum n weight of the fan versus the allowable weight for the electrical box before installing the fan. CEILING FAN/LIGHT MOUNTED TO FACTORY-INSTALLED ELECTRICAL BOX y IN CEILING =j Before installing the unit,make sure that adequate structural bracing is present in the O ceiling. If uncertain,check with the manufacturer.Follow the fan or light manufacturer's z instructions to connect the unit and complete the wiring. If the instructions are not z available,connect the wiring as shown in Figure 95. D r r D O z D z c D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 93 PFS certifies this document is current as of 12-16-09. • 9 , 911 . 1 Conforms to HUD MHCSS 1/15/09 Ground Wre Figure 95. Wiring for a ceil- ing fan or chain-hung light fixture. Color Coded Wires Ground Strap Wire Nut ailing Ceiling Box Mounting Limited cr Screw Noncombustible Ring(If Required) hain CEILING FAN/LIGHT MOUNTED ON SITE-INSTALLED DECORATIVE BEAM 'Where the electrical box will be mounted in a site-installed decorative center beam at- tached to the ridge beam,connect the fixture as follows(see Figure 96): 1. Cut hole. If the decorative beam(shipped loose)does not contain a precut Choosing ceiling fan junc- hole for the electrical box,cut a hole with a diameter approximately 1/4 inch tion boxes.Connect ceil- larger than the box's using a hole saw.Align the hole with the supply wire lo- ing fans only to junction cation and center on the beam. boxes listed and marked for 2. Install box. Install the box in the hole and secure the flange(plastic boxes ceiling fan application in only)to the decorative beam with four#6 x 1"screws. accordance with Article 3. Insert wire.Insert the ceiling wire through a knock-out hole in the side of the 314.27(b)of 2005 NEC. electrical box. It may be necessary to cut a notch in.the top of the decorative Always ground metal junc- beam(on the supply wire side of the center beam hole)allowing the supply tion boxes. wire to be inserted into the electrical box without binding against the beam Selecting fan weight.Do during installation.Leave approximately four inches of wire free in the box. not use any ceiling fans or 4. Attach beam.Secure the decorative beam in place over the center line joint, light fixtures that exceed checking that the supply wire is not pinched or penetrated by beam fasteners. the weight rating of the box Secure the electrical box to the ridge beam with#8 x 2 1/2"wood screws (35 Ibs unless otherwise through the two holes in the top of the box. noted). 5. Strip wires.Strip about 3/4 inch of insulation from the white and black con- Grounding electrical de- ductor ends of the supply wire. vices.Ground fans/lights using a fixture-grounding 6. Position ring.Position the non-combustible flash ring(provided)over the device or a fixture- electrical box so that the finished surface(adjacent to electrical box)which is grounding wire-as specified to be covered by the fan canopy is not exposed. in the manufacturer's in- 7. Install and wire unit. Follow the unit manufacturer's installation instructions structions. for mounting the fan/light assembly to the box and for electrical wiring. Use J provided electrical connectors for splicing wire. Figure 96. Ceiling fan/light z mounted to flush ridge beam Q z' ORidge Beam Q J J Q H z I I 1 l Q Ceiling 2x6 Center Beam-Shipped Loose . l for Field Installation I I I I Supply Wire Coiled And Hole for Box Cut Through 2x6 O Secured for Shipment (May Be Cut in Plant orin Field) 1zNotch Beam at Hole if Necessary forwireChase " Secure Box to Ridge Beam V (field installed) LU Secure Box to 2x6 Center z Beam(field-installed) Electrical Box J YSupply Wire InsertedinField N Through Side Knockout of Box Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 94 PFS certifies this document is current as of 12-16-09. Prepare Appliances • • Equipment PFS4j� #05 TEST ELECTRICAL SYSTEM or to After completion of all electrical wiring and connections,including crossovers, appli- Hun MHcss ances,lights,and ceiling fans, inspect and test the electrical system as follows: 1/15109 1. Fill water heater. Fill water heater before turning on power to the home or switching on the circuit breaker. 2. Test continuity.Before turning on the electrical power to the home,conduct an electrical continuity test to ensure that exposed metallic parts of the home and the chassis are effectively bonded. 3. Test operation.After turning on the electrical power to the home,conduct operational tests of all devices(except water heaters,electric ranges,electric furnaces,dishwashers,clothes washers/dryers,and portable appliances)to demonstrate that they are connected and in working order. 4. Test polarity.After turning on the electrical power to the home,conduct elec- trical polarity checks to determine that connections of electrical equipment in- stalled or completed during installation have been made properly.Visual veri- fication is an acceptable electrical polarity check. 00- •• to • •. Cn r z m n O X M O X D O z z rn D r r D O z D z C D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 95 PFS certifies this document is current as of 12-16-09. Complete Exterior PFS#°5 Work Conforms to HUD MHCSS 1/15/09 Complete Exterior Work This chapter covers sealing the bottom board, installing the ground cover and skirting, preparing wind protection shutters, and completing site-built structures. Follow the Steps • - • STEP 1.REPAIR AND SEAL BOTTOM BOARD(p.96) ! STEP 2.INSTALL GROUND MOISTURE RETARDER(p.96) STEP 3 INSTALL SKIRTING(p.97) STEP 4 ASSEMBLE OPTIONAL WIND PROTECTION SHUTTERS(p.97) ! i iV STEP 5.COMPLETE SITE-BUILT STRUCTURES(p.97) STEP 1. REPAIR AND SEAL BOTTOM BOARD Tears and openings in the bottom board can result from transportation or installation activities. Inspect for holes and gaps the entire bottom board,especially areas around service penetrations,crossover connections,pipe and duct hangers,foundation ele- Sealing bottom boards.A ments,and the perimeter of the floor. Using approved materials appropriate for the type continuous and sealed bot- of repair,repair the bottom board wherever torn or loosened as follows: tom board is critical for 1. Insulate.Replace any missing insulation prior to closure and repair of the bot- home performance,energy tom board, paying particular attention to insulation gaps that may have been efficiency, protection created at P-traps. against moisture problems, 2. Repair large openings.Repair large openings with a durable patch made of prevention of pipe freezing, bottom board fabric or other compatible material and fastened with vinyl bot- and protection against in- tom board tape held in place by fasteners installed with a divergent stapler. sects and rodents. Seal the edges around patches with foam or mastic. For large openings, in- Bottom board sealing stall a rigid backer board behind the bottom board to provide a fastening sub- methods.Tapes shall strate for the patch. never be used alone to re- 3. Repair small openings. Repair small gaps and tears with a combination of pair a bottom board.Diver- vinyl bottom board tape,patches,mastic,or foam sealant. gent staples or mastic must be used in tandem with Q STEP 2. INSTALL GROUND MOISTURE RETARDER tape to prevent future tear D If the space under the home is to be enclosed with skirting or other materials,a ground Z moisture retarder of a minimum six mil thick polyethylene sheeting or equivalent must Fastening vinyl siding. Do be installed covering the ground under the home.Moisture retarders are not required in not install fasteners directly Z and regions(less than 15 inches of rainfall annually)with dry soil conditions. If on- into vinyl siding.Allow for O grade(surface)footings are used,install the ground moisture retarder prior to placing siding thermal expansion the footings,or install it around the footings after all other work under the home is com- by pre-drilling minimum 1/2 J plete. inch diameter fastener holes or fastening skirting Install the ground moisture retarder as follows: to a ledger under the home Z 1. Apply sheeting.Unroll the ground moisture overlapping joints in the sheeting a (see Best Practice tip). Z minimum of 12 inches and covering the entire area under the home except for O areas under recessed entries,decks,and porches. < 2. Seal joints.Seal joints in the retarder with mastic. O 3. Weigh down.To keep the retarder in place,weigh it down with stones,concrete Avoiding radon. Wblocks,or other heavy,durable materials. For enclosed perimeter wall U4. Repair tears.Repair any voids or tears in the retarder by patching with like ma- ar foundations in u1 terial,maintaining a minimum 12-inch overlap and sealing joints with mastic. areeasas w ce where radon is com- Z monly found in the soil, :i continue the moisture re- Ytarder up the perimeter wall Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 96 PFS certifies this document is current as of 12-16-09. PFS#0 and Equipment °5 Prepare A • • Conforms to HUD MHCSS 1/15/09 at least 12 inches,sealing STEP 3. INSTALL SKIRTING the edges and between the Skirting is any structural or non-structural perimeter crawlspace enclosure.Complete seams with mastic. site-built structures(see STEP 5.COMPLETE SITE-BUILT STRUCTURES,p.98)that Attaching vinyl siding.To abut the home(such as porches,attached garages,and steps)prior to installing skirt- install skirting on vinyl- ing. sided homes,screw a treated 2 x 4 on edge to the TABLE 26.ANCHOR SYSTEM MATERIALS SPECIFICATIONS underside of the floor joists Specification two inches back from the edge of the home.Screw Skirting must be of weather-resistant materials or provided with protection skirting tight to the 2 x 4. against weather deterioration at least equivalent to that provided by a coat- ing of zinc on steel of not less than 0.30 oz per sq ft of surface coated. Skirting made from wood or wood products and used within six inches of the ground needs to be made of materials naturally resistant to decay and termite infestation or pressure treated. Avoid backfilling against Ventilation openings must be covered for their full height and width with a skirting.Do not backfill perforated(1/4 inch maximum opening in any dimension)corrosion and against non-structural skirt- weather-resistant covering that is designed to prevent the entry of rodents. In areas subject to freezing,the coverings for the ventilation openings must ing. have an operable damper,permitting them to be in the open or closed posi- tion depending on the weather. To design and install skirting,comply with the skirting manufacturer's instructions(if provided)and the following: 1. Configure skirting.Run the skirting along the perimeter of the home's heated,conditioned space. Do not enclose with skirting areas under recessed entries,porches,or decks(whether constructed as part of the home or added on site)unless skirting is of the fully vented type and installed so as to allow water to freely flow out from under the home. 2. Fasten skirting. Recess the skirting under the siding or trim and attach it to the home in a manner that prevents water from being trapped between the siding or trim and the skirting. For wood,aluminum,or fiberglass skirting,in- stall a skirt rail(lumber strip)under the floor inset at least 1-1/2 inches from the edge of the siding for attachment of the skirting.Allow for frost heave when installing skirting in areas subject to frost. 3. Provide ventilation. Unless the skirting has integral ventilation openings that meet the following ventilation requirements,install equally sized ventilation openings on at least two opposite sides of the foundation.Size ventilation area to equal at least one square foot or each 150 square feet of under-floor X area(or for each 1,500 square feet if a ground moisture retarder is installed r according to STEP 2.INSTALL GROUND MOISTURE RETARDER, p.96). Z Place vents as high above the ground as practical. m 4. Install access.Provide an access opening not less than 18 inches wide and p 24 inches high and located so that any utility connections located under the home are accessible. 5. Extend vents,drains,and inlets.Run appliance exhaust vents,combustion air inlets,and air conditioner condensation drains through the skirting to the outside and terminate each as instructed in the sections of this manual corre- sponding to each appliance. Z Z STEP 4. ASSEMBLE OPTIONAL WIND PROTECTION SHUT- n TERS r r If desired, prepare temporary protective window covers for use during severe wind > storms and hurricanes according to Figure 97,Table 27,and the procedure below. O 1. Assemble extension framing using with two 16d common nails at each con- Z nection. 2. Assemble shutter panels as shown in Figure 97. Z 3. Store the shutters such that they are protected from the weather,are not in di- y rect contact with the ground,and are easily accessible by the homeowner. r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 97 PFS certifies this document is current as of 12-16-09. Complete Exterior PFS"5 WorkConforms to HUD MHCSS t/15/09 To attach shutters to the home: 1. Fasten extension framing to wall framing materials with 16d double-headed nails or#8 x 3"screws,toe nailed/screwed, per Table 27. 2. Fasten assembled panel(s)to extension framing with 12d nails, per Table 27. After use, remove shutters from the home, patch nail holes with caulk and store them as above. Cut If Died Figure 97. Wind protection shutter construction pp—1' Approx.30 Degrees Extension Fr.riM#3 or Stud Grade SPF 2x3 or2x4 Secure OSS or Plywood to Studding WM 12d Nails.1 6"O.C. 2A#2 SPF Studding.Regimed When Plywoodur 0SI3 used Is Y'or / Less In THUcness TABLE 27.SHUTTER CONSTRUCTION SPECIFICATIONS Fastening to wall framing Panel Fastening to extensio-S Fastening to wall framing Window Extension thickness width (in) �� screws 2 x 3* 7/16,1/2 6 in.o.c. 8 in.o.c. 22 in.o.c. 6 in.o.c. 16 in.o.c. 2 x 3 23/32,3/4 6 in.o.c. 8 in.o.c. 22 in.o.c. 4-1/2 in.o.c. 12 in.o.c. • 2 x 3* 7/16,1/2 4 in.o.c. 5 in.o.c. 14 in.o.c. 3 in.o.c. 8 in.o.c. *2 x 3 perimeter extension with 2 x 4 studding at 16 inches o.c. STEP 5. COMPLETE SITE-BUILT STRUCTURES MInstall site-built structures such as steps,landings,garages,awnings,carports, Z breezeways, porches,decks, railings,sheds,and utility rooms according to manufac- < turer's instructions(if any),in compliance with all local regulations including fire separa- tion and electrical requirements,and according to the following: Designing site-built struc- Z tures.All site-built struc- O 0 Construct site-built structures to be structurally independent unless provided tures must support their Qfor in the design of the home(instructions will be provided by the manufac- own dead, live,and wind J turer). loads and must not Do not damage the integrity of the home's structural or weatherproofing sys- transmit any loads to the tem.Seal any weatherproofing connections between the site-built structure home's structure.All car- ? and the home and flash any roof connections. ports should be freestand- z 0 Utilize only GFCI outlets for site-built structures. ing. O Q Install and test smoke alarms in any site-built structures according to local code. O It 110- go to Prepare Home for Occupancy(p. 99). U W Z J `1 N Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 98 PFS certifies this document is current as of 12-16-09. Prepare Home • Occu • . Prepare Home for Occupancy #°5 Conforms to Follow these steps for final inspection and completion of the home. HUD MUM 1/15/09 Follow the Steps • ' • I STEP 1.VERIFY ALTERNATIVE CONSTRUCTION(A/C)INSPECTION(p.99) i STEP 2.COMPLETE INSPECTION CHECKLIST(p.99) STEP 3.COMPLETE ENERGY STAR CHECKLIST(p. 99) iV STEP 4.CLEAN THE HOME(p.99) STEP 1. VERIFY ALTERNATIVE CONSTRUCTION (A/C) IN- SPECTION This is normally the responsibility of the retailer and the manufacturer,however,the in- stallation is not complete until the alternative construction inspection has been passed and documented. STEP 2. COMPLETE INSPECTION CHECKLIST After all previous steps have been accomplished,inspect the home to verify that it has been completely and properly installed using the checklist starting on p. 100. Correct any deficiencies found,if possible,or if not possible, inform the retailer or manufacturer immediately. STEP 3. COMPLETE ENERGY STAR CHECKLIST For ENERGY STAR qualified homes(check with the retailer or manufacturer),this step is to be completed by the manufacturer's designated representative.Ask the retailer or the manufacturer who this is. The manufacturer's representative must complete the Energy Star Site Installation x Checklist,obtain signatures on the ENERGY STAR label,and return the completed r ENERGY STAR Site Installation Checklist to the manufacturing plant. z m STEP 4. CLEAN THE HOME o Remove and properly dispose of all installation-generated dust,debris,and packaging X materials from the home and the surrounding property. Ensure that the home is in p "move-in"condition. D -i Installation is Completez z z Cn D r r D O z D z C D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 99 PFS certifies this document is current as of 12-16-09. #o0 5PFSonforms to_4W HUDMHCSS 1115109 Complete Installation Checklist Use this checklist to confirm that the listed aspects of the installation are complete and correct. FOUNDATION Footings properly sized and constructed for the soil conditions i ' /, Pier spacing per data plate and applicable table and roof load zone Limits of the checklist.This Piers properly constructed and vertical checklist is not all-inclusive. Perimeter blocking installed (if required) Some homes have impor- Piers at each side of large sidewall openings tant features not listed here.Completing this Center line piers installed at columns checklist does not guaran- Shims in place and tight tee that all installation re- quirements have been met. ANCHORS Approved anchors are used Anchors are installed at correct angles Anchor spacing and installation correct Longitudinal ties installed(if required) Anchor straps are tensioned UNDER THE HOME Moisture retarder installed The ground is properly graded to prevent water accumulation HVAC ducts are supported off the ground and connected tightly to collars at all ends Fireplace combustion air intake free and unrestricted No holes or tears in bottom board Skirting has been installed per manufacturer's instructions with proper vent- ing and provision for frost heave Dryer vent, range/cook top exhaust,water heater temperature and pressure overflow pipe and AC condensate drain installed to perimeter of crawl space EXTERIOR Shingled roofs are free of visible damage and serious defects and there are D no missing or loose shingles Z 4 Shingle close-up and ridge cap have been completed per applicable details Z All hold down straps on shingled roofs have been removed and staple holes O have been properly sealed QPenetrations at roof stacks,vents and chimneys have been properly sealed J J Siding and trim is free of gaps,voids, missing fasteners,damage,and seri- ous defects.All seams are sealed and hardboard edges are sealed co Drip edge and fascia is properly installed and free of damage and serious de- Z fects O Gutters and downspouts are installed properly such that water is diverted p~ away from the home Trees and bushes have been trimmed to prevent brushing against the home tL in windy conditions or under snow loads 0 The HUD label is exposed, intact and legible LU The exterior of the home and immediate surroundings is clean,clear of con- Z struction materials,dust,and debris J Y rn Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 100 PFS certifies this document is current as of 12-16-09. Complete Checklist INTERIOR PFCeilings,walls,and floor coverings are free from damage and serious defects Conforms to 4j� HUD MHCSS Carpeting is properly stretched and seamed 1/15/09 All trim and molding is installed properly and free of damage and defects All cabinets,countertops, plumbing fixtures,appliances,furnishings,and window coverings are free of damage or serious defects All cabinet doors and drawers work properly All interior and exterior doors and windows open,close,and latch properly One window in each bedroom meets emergency egress requirements, has operating instruction labels on it,and operates properly All temporary shipping hardware has been removed Floors are level The data plate is intact and legible Smoke alarms have been tested The interior of the home is clean,clear of materials,dust,and debris WATER AND DRAIN SYSTEMS Crossover and service connection and splices have been properly made with correct materials Water and drain lines are insulated or otherwise protected from freezing Pipe supports are installed and properly spaced Proper slope has been maintained on all drain lines All necessary inspections and tests have been performed All sinks, basins,tubs,and toilets operate properly All hot and cold water lines are properly connected to fixtures,dispense wa- ter as labeled,and operate properly ELECTRICAL SYSTEMS The panel amperage matches the connection to the home r_ The home has been properly grounded Z m The main power supply has been properly connected and tested by a li- O censed electrician 0 All electrical crossovers have been connected O All receptacles,switches, and light fixtures operate properly D Ground fault circuit interrupters operate properly =1 O All exterior lights have been properly installed Z GAS/FUEL OIL SYSTEMS ccn The gas system pressure test has been conducted D Connections between units are properly made with access as required D The main fuel line has been properly connected and tested by a qualified technician O Z APPLIANCE OPERATING AND VENTING ?. All appliances are working properly Z Appliance venting is in accordance with the manufacturer's instructions y r Fresh air intakes are properly installed Whole house, kitchen,and bath exhaust fan operation are correct Fireplace chimney stack extension and roof cap have been installed in ac- cordance with the manufacturer's instructions 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 101 PFS certifies this document is current as of 12-16-09. Complete Installat Checklist 4j� #05 Air conditioner/heat pump is sized properly Conforms to MISCELLANEOUS HUD Macs Installation/anchoring certificates or seals have been issued and installed(if 1/15/09 required) Owner's and operation manuals are available for all appliances This installation manual is left with home J Q Z Q Z O i= Q J J Q H CO) Z_ Z O O a O U UJ Z J Y Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM 102 PFS certifies this document is current as of 12-16-09. Indexof e • PFS#05 Index of Steps Co to s HUD MHCSS 1/15/09 INTRODUCTION.......................................................................................................3 IMPORTANTNOTICES.............................................................................................................................3 SAFETY...................................................................................................:.................................................3 RESOURCES............................................................................................................................................4 FEDERAL PREEMPTION..........................................................................................................................4 DEFINITIONS...................................................................................................................:........................4 ENGINEER'S STAMP................................................................................................................................6 SYMBOLS USED IN THE MANUAL.........................................................................................................6 ABBREVIATIONS......................................................................................................................................6 ALTERNATIVE FOUNDATION SYSTEMS...............................................................................................6 DISPLAY AND STORAGE OF THE HOME..............................................................................................6 GETTING STARTED.................................................................................................8 STEP 1.LOCATE THE DATA PLATE......................................................................................................8 STEP 2.CONFIRM WIND ZONE...............................................................................................................8 STEP 3.CONFIRM THERMAL ZONE.......................................................................................................9 STEP 4.CONFIRM ROOF-LOAD ZONE...................................................................................................10 STEP 5.CHECK LOCAL CODES AND SECURE PERMITS....................................................................12 PREPARETHE SITE................................................................................................13 STEP1.PLAN SITE ACCESS..................................................................................................................13 STEP 2.DETERMINE HOME LOCATION AND LAYOUT........................................................................13 STEP 3.CLEAR AND GRADE THE SITE.................................................................................................14 STEP 4.DETERMINE SOIL CONDITION.................................................................................................14 STEP 5.DETERMINE SOIL-BEARING CAPACITY AND FROST LINE...................................................15 STEP 6.DETERMINE GROUND ANCHOR HOLDING CAPACITY..........................................................16 INSTALL FOOTINGS................................................................................................18 STEP 1.DESIGN POINT LOAD SUPPORTS...........................................................................................18 STEP 2.DESIGN FRAME SUPPORTS(Homes Without Perimeter Blocking)......................................21 Z STEP 3.DESIGN FRAME AND PERIMETER SUPPORTS Homes With Perimeter Blocking) 22 m ( 9)............ n STEP 4.SELECT FOOTING MATERIALS................................................................................................23 O STEP 5.SIZE FOOTINGS 'a STEP 6.INSTALL FOOTINGS........:......................................................................................................... O CONSTRUCT FOUNDATIONS.................................................................................28 STEP 1.OBTAIN A FOUNDATION DESIGN............................................................................................28 O Z STEP2.EXCAVATE.................................................................................................................................28 Z STEP 3.CONSTRUCT THE FOOTING OR SLAB....................................................................................28 to STEP 4.CONSTRUCT THE PERIMETER WALL.....................................................................................28 r STEP 5.INSTALL INTERIOR SUPPORTS...............................................................................................29 r- D STEP 6.WATERPROOF FOUNDATION WALL.......................................................................................29 STEP 7.BACKFILL AND GRADE O SETTHE HOME........................................................................................................30 v STEP 1.PREPARE FOR SET...................................................................................................................30 Z C STEP 2.POSITION HOME SECTION ...........................................................................30 STEP3.LIFT HOME..................................................................................................................................30 STEP 4.CONSTRUCT PIERS...................................................................................................................32 COMPLETE MULTI-SECTION SET..........................................................................36 STEP 1.INSTALL MARRIAGE LINE ANCHORS.....................................................................................36 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 103 PFS certifies this document is current as of 12-16-09. Index . . PG Conforms to HUD MHCSS STEP 2.REMOVE PROTECTIVE SHIPPING MATERIALS................................................................ ..36 1/15/09 STEP 3.COMPLETE HINGED ROOF.......................................................................................................36 STEP 4.REPAIR OR INSTALL MARRIAGE LINE GASKET....................................................................38 STEP 5.POSITION ADDITIONAL HOME SECTIONS..............................................................................39 STEP6.CONNECT FLOORS...................................................................................................................39 STEP7.CONNECT ROOF........................................................................................................................41 STEP8.CONNECT WALLS.....................................................................................................................43 STEP9.ATTACH TAG UNITS..................................................................................................................45 STEP 10.REMOVE TEMPORARY ITEMS................................................................................................46 STEP 11.FASTEN HOME TO FOUNDATION..........................................................................................46 STEP 12.BACKFILL AND GRADE..........................................................................................................46 STEP13.BUILD STAIRS..........................................................................................................................46 COMPLETE ROOF AND EXTERIOR WALLS..........................................................47 STEP 1.COMPLETE ROOF......................................................................................................................47 STEP 2.COMPLETE TAG UNIT ROOF....................................................................................................49 STEP 3.COMPLETE SIDE WALLS:.........................................................................................................51 CONNECT CROSSOVERS.......................................................................................52 STEP 1.CONNECT DUCTS.......................................................................................................................52 STEP 2.CONNECT ELECTRICAL CROSSOVERS.................................................................................56 STEP 3.INSTALL ELECTRICAL BONDING............................................................................................58 STEP 4.CONNECT WATER LINES..........................................................................................................59 STEP 5.CONNECT DRAIN,WASTE,AND VENT LINES........................................................................60 STEP 6.CONNECT GAS LINES...............................................................................................................61 STEP 7.CONNECT TELEPHONE AND CABLE TV WIRING..................................................................62 COMPLETE THE INTERIOR ....................................................................................63 STEP 1.ALIGN MARRIAGE WALLS..........................................................................:.............................63 STEP 2.FINISH GYPSUM BOARD...........................................................................................................63 STEP 3.COMPLETE WALL AND CEILING FINISHES............................................................................64 STEP 4.COMPLETE CARPET.................................................................................................................64 STEP 5.COMPLETE TRIM.......................................................................................................................64 J STEP 6.INSTALL SHIP LOOSE ITEMS...................................................................................................64 Q D INSTALL STABILIZING SYSTEM 65 Z ............................................................................ Q STEP 1.DETERMINE ANCHOR LOCATIONS.........................................................................................65 z STEP 2.DETERMINE TIE-DOWN CONFIGURATION................... O STEP 3.SELECT ANCHORS....................................................................................................................71 Q STEP 4.INSTALL ANCHORS......................... JSTEP 5.INSTALL STRAPS.:....................................................................................................................73 STEP 6.TIGHTEN AND ADJUST STRAPS..............................................................................................76 co Z CONNECT UTILITIES...............................................................................................77 Z STEP 1.CONNECT ELECTRICAL SERVICE...........................................................................................77 O F- STEP 2.CONNECT WATER SERVICE....................................................................................................80 Q STEP 3.CONNECT GAS SERVICE.............................. O STEP 4.CONNECT OIL SERVICE................................................................................. ............84 a w O PREPARE APPLIANCES AND EQUIPMENT..........................................................86 V INSTALL AIR CONDITIONER OR HEAT PUMP W 86 Z PREPARE HEATING SYSTEM.................................................................................................................87 J INSTALL REMOTE HEATING AND COOLING EQUIPMENT..................................................................87 Y cq PREPARE VENTILATION SYSTEM.........................................................................................................88 104 Skyline Corporation (4-48 PG. 1) 1/9/2009 9:22 AM PFS certifies this document is current as of 12-16-09. Fs#05 Conforms to HUD MHCSS 1115109 PREPARE FUEL-BURNING WATER HEATER........................................................................................88 PREPARE CLOTHES DRYER..................................................................................................................89 PREPARESMOKE ALARMS...................................................................................................................90 PREPARE FIREPLACES..........................................................................................................................90 PREPARE KITCHEN AND BATH APPLIANCES/FIXTURES.................................................................92 INSTALL EXTERIOR LIGHTING...............................................................................................................93 INSTALL CEILING FANS AND LIGHTING...............................................................................................93 TEST ELECTRICAL SYSTEM...................................................................................................................95 COMPLETE EXTERIOR WORK...............................................................................96 STEP 1.REPAIR AND SEAL BOTTOM BOARD.....................................................................................96 STEP 2.INSTALL GROUND MOISTURE RETARDER............................................................................96 STEP 3.INSTALL SKIRTING....................................................................................................................97 STEP 4.ASSEMBLE OPTIONAL WIND PROTECTION SHUTTERS......................................................97 STEP 5.COMPLETE SITE-BUILT STRUCTURES...................................................................................98 PREPARE HOME FOR OCCUPANCY.....................................................................99 STEP 1.VERIFY ALTERNATIVE CONSTRUCTION(A/C)INSPECTION................................................99 STEP 2.COMPLETE INSPECTION CHECKLIST.....................................................................................99 STEP 3.COMPLETE ENERGY STAR CHECKLIST.................................................................................99 STEP4.CLEAN THE HOME.....................................................................................................................99 COMPLETE INSTALLATION CHECKLIST..............................................................100 r z m n O .D O D O z z D r r D O z M D z c D r 1/9/2009 9:22 AM Skyline Corporation (4-48 PG. 1) 105 PFS certifies this document is current as of 12-16-09. ADDENDUM TO INSTALLATION INSTRUCTIONS IIIIE FOR TIE-DOWNS ON SINGLEWIDE UNITS Bringing America Home LOCATED IN WIND ZONE Il OR III, EXPOSURE D. FS#US 4.35/12 max.roof pitch .di \t11CS 12 S x DRHICS 4.35 IiUp 11 ' I1/13/08 Sidewall Straps and Anchors to be spaced 4'-0" o.c. max.Wind m Zone II or III, Exposure D. r Factory installed tie ```)ljillllrlrrli/��_ down strap See note 1. Site installed tie- �.�,-lV� E down strap. �:C�. F�.• >. to Main I-Beam iz PE19600312 = °' (typical). ;- fl ' STATE OF :'It- Floor 4t%::� H _ Jeffrey T.Legault 20f)8,11.13 Unit Table 1 Strap angle Width H max. Strap Angle max. Typical pier and footing (typical) 12' 48" 21.7 degrees 14' 48" 20.0 degrees Sidewall Tie-Down Straps Ground anchor(typical) 16' 48" 18.6 degrees Bracket Main Beam 4 Endwall Straps and Anchors at Pier End Wall Tie- each end of unit at Wind Zone II 30-45 Down Strap degrees or III, Exposure D. Anchor with Stabilizer Plate-_i Endwall Tie-Down Straps Notes: 1)For strap to 1-Beam attachment refer to the Skyline Corporation Manufactured Home Installation Manual. 2)For all other requirements refer to the Skyline Corporation Manufactured Home Installation Manual. 3)Straps and anchors to be rated for 3150 lbs.of working stress(min.). 4)Main 1-acrim spacing is 99.5"for 14'and 16'.wiiles,82.5"for 12'wides. Sec::, 4 5)Exposufe*, is intended for homes located within'1500 feet to the coast in Wind Zone 11 or 111. Ill.:,51 Page 93B 7-4004-000o.085=.0aa Addendum to lnstallati;on Instructions, for - :; Siil.: 51 Pg,jendwall ------ D:oublew�des with,Site %attached"Car ort Bringing America Home Tie-Down sand Ground Attach Carport directly -See Detail'A' P framing prior to installing siding an Anchors req'd at 5'-4"O.C. :20'-0''max. endwall. n max.at Wind Zone it and 4'-0" - o.c.max.at Wind Zone Ill. Carport �. '� _ Carport i Perimeter blockingrequired 4'- Perimeter blocking required 4'-0" Support,Design and q Support;gea d land ngA sctions' o.c.max.at Carport area. Min. PP 9 0"c.c.max.at Carport area. for Garportand itashmg&siding by, footing size to be 16'x16'k4"or ' Connections for Carport by Mm footing size to be others,and shall rrieet,requiertients' others,and shall meet �p x20 X9'-or equivalent. of locat.iuthoiity equivatent. requiements of local authority. _Field Installed Diagonal I Tie-Down Strap + Factory Installed Vertical—► Factor Installed Strap.Vertical----------► Tie-Down Strap. 71 -/4 Strap Angle- H-See table. See table. Typical pier Typical pier Typical Sidewall A �llcatlon Third party listed roof truss, y pp \YPAOI.ground anchor Typjcal Endwall Application Site installed carport. Design _ 90"max, sidewall'108"max.sidewall 108"max.sidewall and attachment by others. Wind Zone II or III Wind Zone It Wind Zone III - .•�`�� Qtir�l �FGy�''�:; Factory installed H Max. Max. H) Max. Max. H) Max' Max. ��`�;•tiG> T qF �� Q -d\' -- - rail may be Pier St Pier Strap Pier 1,-----� rap p + Strap _ PEi960... 3;1,2 ' _ covered with Unit Height Angle Height Angle Height Angle exterior painted — . • l metal. Width (inches) (Degrees) (inches) '(Degrees) (inches) :(Degrees) = STATE OF �, Attach Carport to 2x4 or 2x6 rail as 24' 48 23.2 __ 33 16.4 48 23,2 _ ,�90,�' �NpyArP ate` ,` required by Carport design and local 26'Or 28' 48 20.3 36.5 15.7 48 20.3 `�'�izSS�pNA4 �G�`��`` authority. Vlnyl Siding !� Detail'A' 32" 48 19.0 34.5 13.9 48 19.0 !/rrrullln>t��`� 12"min.pier height. For Triplewides use 26 or 28'wide information. JeffreyT. LegaulThird party listed #.�2' Q 2014.0t.PE Site installed carport. Design - _roof truss [ 2014.07.16 and attachment by others. �� ® 16,38:38-04'00' X Conforms to Factory installed HUD MHCBS __:.__•-_--. ___1 rail may be Notes: 8/18/14 covered with 1)Applicable to all double or triple wide units at Wind Zone 11 or M. 20 psf max.roof live load.9'max. exterior painted sidewall height. Carport roof to have;a 8 psf max.dead load and a 2 psf min.dead load. Attach Carport to 2x{Q;rail as required by 2 Piers and footings required under main I-Beams per normal requirements. Carport design grid local authority. g �l P eq 3);;1000 psf min.,soil bearing capacity.required. Vinyl Siding 4)Tie-down straps and ground anchors to rated for a minimum working load of 31501bs. Alt.Detail'A' 5)See Skyline Corporation Manufactured Home Installation Manual for additional setup requirements. 6),This addendum is not applicable to 5112 roof,pitch units. �.. III.SLINUINE Sec.: 4 Addendum'to 11h9bihti6h lfisftadi,o.hs for�Doublewides : '51 Pggendwall Bringing America Home with.5/;12- Roof P,itch::& Site:Attached' C_ arport. See Detall'A' 5112 roof pitch max. Attach Carport directlyTie-Down Straps and framing prior to installi Ground Anchors re 20',D"max. endwall. 20'4" ax. / 12 - Q'd at, E. ► Carport Carport Support,Design and Perimeter blocking required 4'- Perimeter blocking required 4'-0" Connections for Carport by 0'o.c.max.at Carport area. support,Oeslgn:and'Connections O.C.max at Carport area. Min. others,and shall meet Min.footing size to be for.Carport and,flashing`&:siding;by footing size to be 16'x16"x4"or 20'i OW"or equivalent others,and shall meet requiements j requiements of local authority- Field Installed Diagonal oflocel authority. Kypical Went Tle-Down Strap Factory Installed VerticalFactory Installed VerticalTie-Down Strap. = Tie-Down Strap. Strap Angle- H-See table. See table. Typical pier pier Typical Sidewall Application' { liti \Typicai ground anchor Typical Endwall Application Third,party,listed roof truss Site installed carport Design / . Wind Zone 11 Wind Zone III K and attachment by osiers.. (H) Max. Max. (H) Max. Max. ----> Factory installed rail Pier Strap Pier Strap -== may be covered with Unit- Height Angle Height Angle i exteriorvinyl. Width (inches) (Degrees) (inches) (Degrees) Attach Carport to 2x10 rail as required by 24' 48- 23.2 37 18.3 Carport design and local authority. 26'Or 28' 48 20.3 39 16.7 ``\���\111ltllllll7l//��� Vt�,Siding 32' 48 Y T. ,� 19.0 35 14.1 .�' E E . Q.. • 9�;':, Detail'A' 12"min.pier height : G'ST PE19600312 _ . _ STATE7-01 4. .._. Notes: !f•FS: CGS � QNAk-' w��� #02 1 '°` p Applicable to all doublewide units at Wind Zone II or M. 20 sf max.roof live load. 9 max.sidewall 1f11 rt pFS ® height. Carport roof to have a 8 psf max.dead load and a 2 psf min.dead load. Jeffrey T.Legault PE 2)Piers and footings required under main I-Beams per normal requirements.Q 2014.07.1616:41c41 Conrormsto. l 3)1000 psf min.soil bearing capacity required. ' -04�00• HUD MHCSS 8/18114 4)•Tie-down straps and ground anchors to rated for a minimum working load of 3150 lbs. 7-400-S-006Q.60e,7-420-s-078CA 5)See Skyline:Corporation Manufactured Home Installation Manual for additional setup requirements: A-ddendum to`Instaltatiii d Insfructions:.for,.Shed Bringing America Home Roof`-Singl.ewiq$;..With Site-:Attact ed ;Carport Attach Carport directly to endwall framing prior to installing siding on 20'-0"max. See Detail'A' 20'-0"irfax. endwall. < 1 Tie-Down Straps and Carport Ground Anchors req'd at I i 4'-0"max.at Wind Zone II ^ _ and 2'-8"max.at Wind Carport Zone III. Support,Design and Perimeter blocking required 4'-0' Perimeter blocking required 4'-0" Connections for Carport by p ort,Design and Cori6ections o-c.max.at Carport or area. Min. others,and shall meet o.c,max at Carport or area. Su for.-arpoft and.,flashtng�&'siding by footing size to be 16"x16'k4°or Min.footing size to be others;and shall'.meetre- wements requiements of local authority. � P 4• eplilyalenL: -2CS"x20 x4!or equivalent. -Field Installed Diagonal 5f local authority. Tie-Down Strap Factory Installed Vertical-► -H-See rote 7 Factory Installed Vertical -► ------ -Tie-Down SVaP Tie-DownSVaP_._.---.-. _._-=--•-•---•- - - =V- - - -- -•. .�, •-'- .: _ .. .^`1tttii{II,II'fU1(jr-. Strap Angle- Typical pier Typical ground anchor-". See note 8. �` f�Q'• �,9. �� Typical pier T -pical Sidewall A kation ��s7 R G� T. Ical Endwall A Ilcation Y PP � r Q`� Fo :�' YP• PP• Remove vinyl siding to expose PE19bQ63d 2 - ridge for attachment. Replace - -_ after site work completed. U.L.listed roof truss = . TO • •{ STATE OF 'XU� Site installed carport. Design �����` '9VOIA.. 4�\���� and attachment by others. ---,---' Ridge plywood-glued and layers fastened together. �►' '--__t Jeffrey T.Legault. Z 201407.16 Attach Carport to ridge beam;a-s - - �' 16:29:05-04'00' required by Carport design and Iocal,authority. ft�Shed roof Notes: sidewall O.Applicible to 12;74'-and;161:Shed roof sin'glgwide unifs:at Wind Zone II or III. 20 psfmax-roof live load.Carport roof to ha,e a 8 psf max dead load_;aiid'a 2 psf min.,;dead load. Detail'A' 2).Plers and footings:requiredunder;ctiatn 1 Beams per normal requirements, - Sj I OOOlpsf mrn soil beanng:capacity required;, $�02•_ 4)Tie do-%"straps.and grouti0 anchors,to rate d&for a minimum working load of 3150 lbs. AM As'r 5)See Skyline.Coiporation Manwafactuied Home Installation Manual for additional setup requirements. 6)This'addend"um is•not appl'icableto•�l12 roof pitch units; HUD MHCSS 7)Hmax.,=d3'!: Sec. . 4 8118114 8)The max strap angle is 23.2 degrees for IT wides,20.0 degrees for 14'wides and 18.9 degrees III.: 51 Fig 91 D for 16'wides. L4L INS Adclendllim to Installation Instructions for Bringing America Home Singlewides with Site Attached Carport Attach Carport directly to endwall See Detail'A'. framing prior to installing siding on 20'4'max. Tie-Down Straps and 20'-0"inax.: endwall. 19-8"max for 16'wides Ground Anchors req'd at 4'-0"max,at Wind Zone It Carport and Wind Zone Ill. Carport 4:: Support,Design and Connections Perimeter blocking required 4'- Perimeter blocking required 4%0" for Carport b others,and shall 0'o.c.max at CarpoRarea. Siipppoorl,Design and,Connections' o.c.'max:at Car Min.footing rpo Y for Carport,arid flashing&'si Ilng'by size to>be.18 x16"z4'or meet requiements of local Min.footing size to be 'others,and:shali•rrieetraquiem.ents equivalent: authority. 20"z2VA,or equivalent. - local auth'orj15 Field,lnstalled Diagonal Tie-Down Strap Factory Installed Vertical--► H-See note 7. Factory Installed Vertical---i _ Tie-Down Strap. Tie-Down Strap. \"Stra1`tttutunrrrrrr�� �. Typical ground anchor'~ See not Angle8. Typical pier `♦`♦♦�� �Y,T.(F-qG ij�i p ♦ Q� G Typical pier Typcal,,SidewallAppJication `',_ Typical Endwall Application PEI 600312 STATE OF Site Installed carport Design U.L.Listed roof truss Nil; /ONA 11St���♦♦` 902 and attachment by others. pFs Q Jeffrey T.Legault.PE m Factory installed C' 2014;07.161'6;3428 Cunformsto rail maybe Z , 04'QD' HUD NIHCSS ' - covered with 8/18114 exterior painted Attach Carport to 2x10 rail as required by metal. Notes: Carport design and local authority. 1)Applicable to IT, 14'and 16'singlewide units at Wind Zone 11 or III. 20 psf max.roof live load. vinyl Siding, Carport roof to have a 8 psf max.dead load and a 2 psf min.dead load. Detail�A� 2)Piers and footings required under main I-Beams per normal requirements. - 3)1000 psf min.soil bearing capacity required. 4)Tie-down straps and ground anchors to rated for a minimum working load of 31501bs. 5)See Skyline Corporation Manufactured Home Installation Manual for additional setup requirements. 6)This addendum is not applicable to 5/12 roof pitch units. 7)Hmax.=48". Hmin.=12". Sec.: 4 8)The max.strap angle is 23.2 degrees for 12'wides,20.0 degrees for 14'wides and 18.6 degrees I III.::51 P2.'91.A for 16'wides. Addendum to Installation Instructions for Applicable To: Multi-Section Units with End Porches All Double or Triple Wides Brining America Home All Wind Zones,All Roof Loads Note A: Install a 5"bead of exterior grade caulk at the following locations: 1)At porch endwall mating line,from the porch deck up. 2)At porch floor mating line,from endwall out. 3)Along porch floor/wall intersection,each side of mating line. Porch Endwall Mating Line i _- See note A,number See note A,number 1 Porch decking See note A,number 3 See note A,number 2 Mating Line oF�02 Instructions: coaro�sao: HUD MHCss 1)Brings units together as described in the Skyline Corporation Manufactured Home Installation Manual. 9/22/14 2)Install exterior grade caulk as at the porch floor/wall mating line as described in note A and detail above. 3)All other aspects of the setup shall be per the Skyline Corporation Manufactured Home Installation Manual. Sec.: 4 Ref:ILEaad 141 r -6n3n4" 1 �1\TLTF1-�CTURED H- 'O.mE I.NS.. ... TALLI�TI01\T FOR., SI-IIl\TGLE R0 .0' WITH RID GE VEN'T (SUPPLEMENT TO MANUFACTURED HOME INSTALLATION MANUAL) BRINGING AMERIGI HOME.BRIN61N6 Ah1ERIfA[UN. The technical content of this Installation Manual has been reviewed APPROVED by PFS Corporation and found to be in accordance with the Federal PFS Corporation Manufactured Home Construction and Safety Standard. Madison Wi 01/31/05 HUD Manufactured Horne Construction& Safety Standard I-NSTA.LLATION OF SHINGLE. ROOF `WITH RIDGE VENT 1. Fold back the underlayment. 8. Complete the installation of the shingles. See figures 2 and 3. 2. Remove the roof sheathing at the ridge beam on one or both halves, which was 9. In the area the ridge vent is to be installed, temporarily secured to the roof at the use a utility knife to cut away the shingles factory. (Note that there is a notch in the and underlayment along the edge of the sheathing for the installation of the ridge sheathing. vent). 10. Install the ridge vent per the included 3. Bolt the ridge beam halves together as manufacturer installation instructions. See out-lined in the Skyline Corporation figures 4, 5 and 6. Manufactured Home Installation Manual. ' 11. Install ridge shingles to the area of ridge not 4. See figure 1. Replace sheathing using covered by ridge vent. Start at the vent and 12Ga.x7/16"x1-1/2" staples or 8d twist work towards roof edges. See figure 7. nails 4 inches on center at butt joints and at each truss between joints. Maintain the 12. Nail ridge vent cap shingles in place using 2 gaps between the sheathing and the ridge inch roofing nails. Start at one end of the vent beam where the ridge vent is to be and work towards other end. Nail shingles in installed. place utilizing 5-inch shingle exposure. See figure 8. Seal ends of ridge-vent per the vent' 5. Tack roofing underlayment back in place. manufacturer installation instructions. 6. Center and staple the additional strip of 13. Install closure cap at eave joint. underlayment on the ridge. Note: See the Skyline Corporation Manufactured 7. Fasten the drip edge to the sheathing at Home Installation Manual for any additional infor- the roofs edge (above underlayment). mation. RIDGE VENT SITE INSTALLED �( SHINGLES(4 OR 5 COURSES) SEE STEP 9 UNDERLAYMENT PAPER ' 'r ROOFING UNDERLAYMENT FOLDED BACK FOR BEAM BOLTING - Ai SHEATHING Av for DRIP CAP r t =r RIDGE BEAM FIG. 1 FIELD INSTALLED SHEATHING 16" UNDERLAYMENT PAPER lea k� 18"SHINGLE FIELD INSTALL... 24"SHINGLE 24"SHINGLE FIELD INSTALL _ 30"SHINGLE- FIELD INSTALL _ 36"SHINGLE- FIELD INSTALL SEE FIG.3 FOR FASTENING REQUIREMENT IF THE ROOFING IN THE AREA OF THE FRONT RAKE HAS BEEN COVERED TO PROTECT FROM WIND DAMAGE DURING TRANSIT,THE PROTECTIVE COVERING AND FASTENERSARE TO BE CAREFULLY FIG. 2 REMOVED. SEAL THE FASTENER HOLES WITH ASPHALT ROOFING CEMENT. FASTENERS: USE 1"CROWN x 1"LEG 16 GA. GALVANIZED STAPLES OR 1 1/4" 12 GA.GALVANIZED ROOFING NAILS WITH 3/8"DIAMETER HEADS 36"_SHINGLE . 40 NAIL 1" FROM EACH END 5 5/8"ABOVE EXPOSED BUTT& 5/8"ABOVE EACH CUT OUT FIG.3 3: . moo 44 --- _ �,; Via'" _ •, ' FIG. 4 _ FIG. 5 FIG. 6 NAIL OR STAPLE RIDGE SHINGLES AS INDICATED. SEE FIG. 3 FOR FASTENER SIZES k O co 5" EXPOSURE RIDGE LINE FIG. 7 wr •.♦ , .N M ♦ L'♦ to t • ;I 1 •I .�`• - -r .� aa i V7 i w Po ovq E ON 9 . 5GR GP�p F