FORM NO. H11-544 REV. 1
• Industry Standard R-410A Refrigerant Applications
• Models featuring Electric Heat without Indoor Cooling Coil
• Quiet and efficient X-13 (ECM) motor technology
• Only 35" tall and 4-way convertible for all those tight spaces
• Available from factory in upflow and horizontal configurations
• Nominal airflow up to 0.5" external static pressure with
reduced airflow up to 1.0" external static pressure
• Factory installed MultiFlex
®coils
• Sturdy steel construction with 1 inch [25.4 mm] of foil faced
insulation for excellent sound and insulating characteristics
• Permanent, easily accessible and washable filter furnished
standard
• Circuit breaker (standard on units with more than 11 kW)
meets U.L. and cUL requirements for service disconnect
• Factory installed auxiliary electric heat provides exact heat for
indoor comfort over a variety of applications
•Watt restrictors, standard on RBHP-17 models above 6 kW
and on RBHP-21, RBHP-24 & RBHP-25 models above 11 kW,
stage supplemental heat so that only the necessary amount is
engaged to maintain comfort in the conditioned space
• Fan settings for selectable, customized cooling airflow over a
wide variety of applications
Air Air Handlers
RBHP Series
RBHP- Series
X-13 (ECM) Motor
Efficiencies up to 16 SEER
Air Table of Contents
RBHP Series
2
TABLE OF CONTENTS
Engineering Features ......................................................................................3
Model Number Identification ............................................................................4
Dimensional Data ............................................................................................5
Airflow Directional Data ..................................................................................6
Airflow Performance Data ............................................................................7-9
Electrical Data ..............................................................................................10
Electrical Wiring ............................................................................................11
Accessories ............................................................................................................11
Limited Warranty ..........................................................................................12
Air Engineering Features
RBHP Series
3
Engineering Features
RBHP- Series
• Quiet, efficient X-13 (ECM) motor technology providing nomi-
nal airflow to 0.5 inch [12 kPa] of external static pressure.
• Field selectable airflow to meet the requirements of particular
applications.
• Low continuous fan speed.
• The most compact unit design available.
• Attractive pre-painted cabinet exterior.
• Rugged steel cabinet construction, designed for added
strength and versatility.
• 1" foil faced insulation mechanically retained in blower
compartment.
• Four leg rubber insulated wire motor mount.
• Circuit breakers standard on models above 11 kW and
optional on models with 11 kW or less.
• Models supplied with circuit breakers meet UL and cUL
requirements as a service disconnect switch.
• Provisions for field electrical connections from either side of
air handler cabinet.
• Tab lock blower housing with integrated electric heaters,
controls, motor and blower. Slide out design for service and
maintenance convenience.
•Exclusive dependable Incoloy sheath type electric heating
elements located in the blower housing provide mixed warm air.
• Field convertible for vertical upflow, vertical downflow, hori-
zontal left hand or right hand air supply.
• Common combustible floor base accessory fits all model
sizes when required for downflow installations on combus -
tible floors.
• Durable framed cleanable air filter provided as standard in
unit filter rack.
• MultiFlex
®indoor coil design provides low air side pressure
drop, high performance and extremely compact size. All coils
come with PVC condensate elbow standard.
• All indoor coils have tinned copper tubing and aluminum fins.
• Molded polymer corrosion resistant condensate drain pan is
provided on all indoor coils.
• Both supply and return duct flanges provided as standard on
air handler cabinet.
• Connection points for both high voltage and low voltage
control wiring inside air handler cabinet.
• Concentric knockouts are provided for power connection to
cabinet. Installer may pull desired hole size up to 2 inches
[51 mm] for 11/2 inch [38 mm] conduit.
• Patented watt restrictor on heat pump models to control
electric heat during heating operation.
• Internal checked TX valves are used on the RCHL indoor coil
for more quiet refrigerant metering.
• Front refrigerant and drain connections.
[ ] Designates Metric Conversions
Watt-restrictor
BLOWER
SECTION
X-13 (ECM)
MOTOR
Supplemental heat, provided by electric heating elements may be necessary in some areas
when heating requirements for indoor comfort exceed the capacity of the heat pump system.
When supplemental heat is required, units with the Watt Restrictor will restrict the amount
of supplemental electric heat that can be energized dependent on the heat output of the
heat pump (temperature of the air leaving the indoor heat pump coil).
The Watt-restrictor utilizes sensing devices in the unit to sense the air temperature leaving
the indoor coil and disengage unnecessary heating elements when that temperature is at
least 85°F [29°C]. (In this mode your system is controlled by the first stage of the wall ther-
mostat.) This occurs only when the second stage of the wall thermostat calls for heat.
Since the heat output of the heat pump is dependent upon the outdoor air temperature, this
control performs the same function as a field installed outdoor thermostat.
An additional benefit of the Watt Restrictor is that it can sense a degradation in heat pump
performance due to causes other than outdoor temperature and react accordingly to bring
on more supplemental electric heat.
Coil
Code
Refrigerant
Type
2
Cabinet Width
R-410A
17
1 R-410A RCHL-24A2TH17
RCHL-36A1TH21
21 24 25
4 R-410A RCHL-48A1TH24
7 R-410A RCHL-60A1TH24
Air Model Number Identification
RBHP Series
4
Model Number Identification
J 00 N H D Coil Code
A = No Coil
Airflow Horizontal Multi-Position
Control N = No Circuit Protection (Single Circuit) S = Circuit Breaker (Single Circuit)
Electric Heat 00 = No Heat 14 = 14.0 kW 06 = 4.9 kW 18 = 17.5 kW 07 = 7.0 kW 21 = 21.0 kW 11 = 10.0 kW
Voltage A = 115V-1-60 J = 208/240V-1-60
R B H P 17
Rheem
Classification
B = Blower Unit
Application
H = Air Handler
Design Series
P = X-13 (ECM) Motor
Cabinet Size
17 = 17.5" [445 mm]
21 = 21.0" [534 mm]
24 = 24.5" [623 mm]
25 = 24.5" [623 mm]
[ ] Designates Metric Conversions
Available Models
(Without Coil)
RBHP-17J11SHA
RBHP-21J14SHA
RBHP-24J18SHA
RBHP-25J21SHA
Available Models
featuring R-410A
Refrigerant
RBHP-17A00NH1
RBHP-17J06SH1
RBHP-17J07SH1
RBHP-17J11SH1
RBHP-21A00NH2
RBHP-21J06SH2
RBHP-21J07SH2
RBHP-21J11SH2
RBHP-24A00NH4
RBHP-24J06SH4
RBHP-24J07SH4
RBHP-24J11SH4
RBHP-24J18SH4
RBHP-25A00NH7
RBHP-25J11SH7
RBHP-25J18SH7
—
5
Air Dimensional Data
RBHP Series
[ ] Designates Metric Conversions
Model Number
Cabinet Size
Unit
Width
“W” In. [mm]
Supply
Duct
“A” In. [mm]
Unit Weight/Shipping Weight (Lbs.) [kg]
Unit With
Coil (Max. kW)
17 171/2 [445]79/16 [192]92/99 [42/45]
21 21 [533]97/16 [240]109/117 [49/53]
24 241/2 [623]113/4 [298]125/134 [57/61]
25 241/2 [623]113/4 [298]125/134 [57/61]88/97 [40/44]
Unit Without
Coil (Max. kW)
66/75 [30/31]
79/87 [36/39]
88/97 [40/44]
Unit Dimensions
Unit Dimensions & Weights
Air Airflow Directional Data
RBHP Series
6
Airflow Directional Data
UPFLOW DOWNFLOW
HORIZONTAL LEFT
HAND AIRFLOW
HORIZONTAL RIGHT
HAND AIRFLOW
NOTE:Coil and blower section are always in a draw through configuration.
Air Airflow Performance Data
RBHP Series
7
Airflow Performance
Airflow performance data is based on cooling performance
with a coil and filter in place.Select performance table for
appropriate unit size, voltage and number of electric heaters to
be used. Make sure external static applied to unit allows oper-
ation within the minimum and maximum limits shown in table
below for both cooling and electric heat operation. For opti-
mum blower performance, operate the unit in the .2" to .5" in.
W.C. external static range. In general, the indoor motor speed
tap should be as shown in table for the appropriate cooling
capacity shown. Always check to make sure proper motor
speed tap is connected as units are shipped from the factory
connected for high speed operation (Speed Tap 5).
Airflow Operating Limits
NOTE:See Airflow Performance Data for Recommended Blower Motor Speed.
[ ] Designates Metric Conversions
Model Cabinet Size 17 21 24 25
Cooling BTUH
Cooling Tons Nominal
18,000
1.5
24,000
2
30,000
2.5
36,000
3
42,000
3.5
48,000
4
60,000
5
60,000
5
Heat Pump or Air Conditioning
Maximum Heat/Cool CFM [L/s]
(37.5 CFM [18 L/s]/1,000 BTUH)
(450 CFM [212 L/s]/Ton Nominal)
675
[319]
900
[425]
1125
[531]
1350
[637]
1575
[743]
1800
[850]
2025
[956]
2250
[1062]
Heat Pump or Air Conditioning
Nominal Heat/Cool CFM [L/s]
(33.3 CFM [16 L/s]/1,000 BTUH)
(400 CFM [189 L/s]/Ton Nominal)
600
[283]
800
[378]
1000
[472]
1200
[566]
1400
[661]
1600
[755]
1800
[850]
2000
[944]
Heat Pump or Air Conditioning
Minimum Heat/Cool CFM [L/s]
(30.0 CFM [14 L/s]/1,255 BTUH)
(360 CFM [170 L/s]/Ton Nominal)
540
[255]
720
[330]
900
[425]
1080
[510]
1260
[595]
1440
[680]
1620
[765]
1800
[850]
Maximum KW Electric Heating
& Minimum Electric Heat CFM [L/s]
11
560 [264]
11
560 [264]
14
900 [425]
14
900 [425]
18
1220 [576]
18
1220 [576]
21
1460 [689]
21
1460 [689]
Maximum Electric Heat Rise °F [°C]85 [29]85 [29]70 [21]70 [21]65 [18]65 [18]65 [18]65 [18]
Air Airflow Performance Data
RBHP Series
8
Airflow Performance Data
Model
Cabinet
Size
Tonnage
Blower Motor CFM [L/s] (Watts)/External Static Pressure—Inches W.C. [kPa] with filter and Indoor Coil
Nominal
Speed
Tap
Volts .10 [.02].20 [.05].30 [.07].40 [.10].50 [.12].60 [.15].70 [.17].80 [.20].90 [.23]1.0 [.25]
-17
1.5 Ton
Air Flow
2 208/240 659 [311]
(74)
625 [294]
(80)
581 [274]
(84)
539 [254]
(88)——————
3 208/240 790 [372]
(98)
759 [358]
(105)
722 [340]
(113)
687 [324]
(119)
650 [306]
(126)
615 [290]
(131)
573 [270]
(139)
552 [260]
(145)
507 [239]
(150)
460 [217]
(155)
2 208/240 649 [306]
(79)
615 [290]
(84)
571 [269]
(88)
529 [249]
(92)——————
3 208/240 773 [365]
(110)
736 [347]
(113)
699 [330]
(118)
677 [320]
(126)
640 [302]
(132)
605 [286]
(141)
563 [266]
(146)
542 [256]
(154)
497 [235]
(157)
450 [212]
(162)
2 115 651 [307]
(76)
627 [295]
(82)
583 [275]
(86)
541 [255]
(90)——————
3 115 776 [366]
(105)
743 [351]
(109)
724 [342]
(118)
687 [324]
(122)
658 [311]
(131)
617 [291]
(136)
595 [281]
(144)
555 [262]
(148)
517 [244]
(152)
460 [217]
(162)
4 115 846 [399]
(143)
821 [387]
(148)
801 [378]
(157)
766 [361]
(162)————
2.0 Ton
Air Flow
4 208/240 844 [398]
(141)
819 [386]
(146
799 [377]
(155)
764 [360]
(160)——————
4 208/240 834 [393]
(146)
809 [831]
(150)
789 [372]
(159)
754 [355]
(164)——————
5 208/240 946 [446]
(179)
922 [435]
(189)
902 [426]
(193)
876 [413]
(203)
843 [398]
(206)
804 [380]
(216)
773 [365]
(221)
748 [353]
(231)
696 [328]
(240)
660 [311]
(243)
——
5 115 964 [455]
(167)
945 [446]
(178)
914 [431]
(181)
888 [419]
(191)
861 [406]
(196)
821 [387]
(205)
787 [372]
(210)
761 [359]
(218)
726 [342]
(220)
690 [326]
(230)
2 208/240 1068 [504]
(138)
1041 [491]
(147)
1001 [472]
(153)
972 [458]
(161)——————
3 115 1138 [537]
(175)
1113 [525]
(186)
1075 [507]
(191)
1053 [497]
(203)
1004 [474]
(210)
957 [451]
(216)
932 [440]
(226)
901 [425]
(231)
2 208/240 1035 [488]
(143)
1007 [475]
(152)
966 [455]
(158)
936 [441]
(169)——————
3 208/240 1157 [546]
(182)
1132 [534]
(192)
1095 [517]
(198)
1069 [505]
(209)
1028 [485]
(218)
983 [464]
(228)
952 [449]
(239)
921 [435]
(250)
869 [410]
(255)
825 [389]
(262)
2 115 1070 [504]
(138)
1043 [492]
(147)
1004 [473]
(153)
974 [459]
(161)——————
855 [404]
(242)
800 [378]
(252)
4 208/240 1269 [598]
(207)
1236 [583]
(219)
1174 [554]
(226)
1149 [542]
(236)——————
5 208/240 1397 [659]
(287)
1377 [649]
(307)
1346 [635]
(317)
1318 [622]
(320)
1291 [609]
(322)
1264 [596]
(319)
1234 [582]
(312)
1190 [561]
(326)
1155 [545]
(351)
1126 [531]
(368)
Electric
Heaters
none
3 (max.)
none
none
3 (max.)
none
none
none
3 (max.)
3 (max.)
none
none
none
4 (max.)
4 (max.)
none
none
none
4 208/240 1241 [585]
(222)
1208 [570]
(234)
1174 [554]
(241)
1149 [542]
(251)——————
4 115 1269 [598]
(207)
1236 [583]
(219)
1174 [554]
(226)
1149 [542]
(236)——————
5 115 1370 [646]
(292)
1343 [634]
(302)
1309 [618]
(309)
1285 [607]
(319)
1258 [594]
(330)
1221 [576]
(336)
1182 [558]
(348)
1147 [542]
(357)
1117 [527]
(366)
1080 [510]
(375)
4 (max.)
none
none
5 208/240 958 [452]
(162)
934 [440]
(172)
914 [431]
(176)
888 [419]
(186)
855 [403]
(189)
816 [380]
(210)
785 [370]
(204)
760 [358]
(214)
708 [334]
(223)
672 [317]
(226)none
5 208/240 1366 [645]
(302)
1346 [635]
(313)
1315 [621]
(323)
1287 [608]
(331)
1260 [595]
(341)
1233 [582]
(346)
1203 [568]
(358)
1159 [547]
(371)
1124 [530]
(381)
1095 [517]
(387)4 (max.)
3 208/240 1187 [560]
(180)
1162 [548]
(188)
1125 [530]
(192)
1099 [518]
(200)
1058 [499]
(208)
1013 [478]
(215)
982 [463]
(223)
951 [448]
(232)
899 [424]
(234)
855 [403]
(237)none
2.5 Ton
Air Flow
-21
3.0 Ton
Air Flow
NOTES:
X-13 (ECM) NOTES (X-13 (ECM) Motor Speed Changes)
X-13 (ECM) Motors require no voltage change between 208 and 240 volts.
If application exceeds 0.5" of static, adjust the motor speed to the high static speed as described below:
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed 2 (Low Static) and speed tab 3 (High Static) are lower tonnage. Speed tab 4 (Low Static) and Speed
tab 5 (High Static) are for higher tonnage.
The lower static speed 2 (lower tonnage) and speed tab 4 (Higher tonnage) are used for external static below 0.5".
For external static exceeding 0.5", move the blue wire from the X-13 (ECM) motor to appropriate high static speed tab 3 (Lower tonnage) or speed tab 5 (Higher tonnage)
[ ] Designates Metric Conversions
Air Airflow Performance Data
RBHP Series
9
Airflow Performance Data (con’t.)
Model
Cabinet
Size
Tonnage
Blower Motor CFM [L/s] (Watts)/External Static Pressure—Inches W.C. [kPa] with filter and Indoor Coil
Nominal
Speed
Tap
Volts .10 [.02].20 [.05].30 [.07].40 [.10].50 [.12].60 [.15].70 [.17].80 [.20].90 [.23]1.0 [.25]
-24
3.5 Ton
Air Flow
2 208/240 1438 [678]
(205)
1409 [664]
(217)
1375 [648]
(229)
1341 [632]
(252)——————
3 208/240 1568 [740]
(279)
1538 [725]
(290)
1507 [711]
(303)
1471 [694]
(313)
1435 [677]
(333)
1403 [662]
(338)
1362 [642]
(358)
1318 [622]
(365)
1287 [607]
(374)
1250 [589]
(405)
2 208/240 1414 [667]
(230)
1384 [653]
(242)
1350 [637]
(254)
1315 [620]
(277)——————
3 208/240 1548 [730]
(304)
1518 [716]
(316)
1487 [701]
(328)
1451 [684]
(338)
1415 [667]
(358)
1383 [653]
(368)
1342 [633]
(388)
1298 [612]
(395)
1267 [597]
(409)
1230 [580]
(455)
2 115 1448 [683]
(205)
1419 [669]
(217)
1385 [653]
(229)
1351 [637]
(252)——————
3 115 1559 [735]
(294)
1527 [720]
(308)
1497 [706]
(322)
1466 [691]
(335)
1431 [675]
(349)
1378 [650]
(367)
1349 [636]
(379)
1306 [606]
(393)
1271 [599]
(406)
1250 [589]
(417)
4 115 1642 [774]
(311)
1606 [757]
(326)
1589 [749]
(335)
1561 [736]
(376)————
4 208/240 1640 [773]
(311)
1604 [757]
(326)
1587 [748]
(335)
1559 [735]
(376)——————
4 208/240 1613 [761]
(331)
1574 [742]
(346)
1557 [734]
(355)
1529 [721]
(396)——————
5 208/240 1759 [830]
(433)
1732 [817]
(447)
1701 [802]
(453)
1669 [787]
(469)
1637 [772]
(482)
1605 [757]
(502)
1572 [741]
(518)
1516 [715]
(536)
1485 [700]
(549)
1435 [677]
(562)
——
5 115 1811 [854]
(423)
1791 [845]
(436)
1760 [830]
(451)
1730 [816]
(464)
1700 [802]
(479)
1669 [787]
(492)
1606 [757]
(516)
1573 [742]
(529)
1538 [725]
(542)
1462 [689]
(555)
2 208/240 1872 [883]
(373)
1837 [866]
(393)
1798 [848]
(407)
1763 [832]
(419)——————
3 115 2075 [979]
(497)
2036 [960]
(511)
2017 [951]
(533)
1984 [936]
(553)
1944 [917]
(563)
1910 [901]
(582)
1889 [891]
(599)
1846 [871]
(617)
2 208/240 1831 [854]
(393)
1795 [847]
(413)
1756 [828]
(427)
1720 [811]
(439)——————
3 208/240 2043 [964]
(517)
2004 [945]
(531)
1985 [936]
(553)
1951 [920]
(573)
1912 [901]
(583)
1878[886]
(602)
1857 [876]
(619)
1814 [856]
(637)
1773 836]
(646)
1751[826]
(658)
2 115 1872 [883]
(373)
1837 [866]
(393)
1798 [848]
(407)
1763 [832]
(419)——————
1805 [851]
(626)
1783 [841]
(638)
4 or 5 208/240 2102 [992]
(550)
2072
[977](568)
2042 [963]
(584)
2011 [949]
(593)
1974 [931]
(610)
1949 [919]
(631)
1916 [904]
(644)
1884 [889]
(662)
1851 [873]
(669)
1810 [854]
(692)
4 or 5 208/240 2070 [976]
(560)
2040
[962](578)
2010 [948]
(594)
1979 [933]
(613)
1942 [916]
(620)
1917 [904]
(641)
1884 [889]
(654)
1852 [874]
(672)
1819 [858]
(679)
1778 [839]
(702)
Electric
Heaters
none
5 (max.)
none
none
5 (max.)
none
none
none
5 (max.)
5 (max.)
none
none
none
5 (max.)
5 (max.)
none
none
5 (max.)
4 or 5 115 2102 [992]
(550)
2072
[977](568)
2042 [963]
(584)
2011 [949]
(593)
1974 [931]
(610)
1949 [919]
(631)
1916 [904]
(644)
1884 [889]
(662)
1851 [873]
(669)
1810 [854]
(692)none
5 208/240 1789 [844]
(413)
1762 [831]
(427)
1731 [816]
(433)
1699 [801]
(449)
1667 [786]
(462)
1635 [771]
(482)
1602 [756]
(498)
1546 [729]
(516)
1515 [715]
(529)
1465 [691]
(542)none
3 208/240 2075 [979]
(497)
2036 [960]
(511)
2017 [951]
(533)
1984 [936]
(553)
1944 [917]
(563)
1910 [901]
(582)
1889 [891]
(599)
1846 [871]
(617)
1805 [851]
(626)
1783 [841]
(638)none
4.0 Ton
Air Flow
5.0 Ton
Air Flow-25
NOTES:
X-13 (ECM) NOTES (X-13 (ECM) Motor Speed Changes)
X-13 (ECM) Motors require no voltage change between 208 and 240 volts.
If application exceeds 0.5" of static, adjust the motor speed to the high static speed as described below:
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed 2 (Low Static) and speed tab 3 (High Static) are lower tonnage. Speed tab 4 (Low Static) and Speed
tab 5 (High Static) are for higher tonnage.
The lower static speed 2 (lower tonnage) and speed tab 4 (Higher tonnage) are used for external static below 0.5".
For external static exceeding 0.5", move the blue wire from the X-13 (ECM) motor to appropriate high static speed tab 3 (Lower tonnage) or speed tab 5 (Higher tonnage)
[ ] Designates Metric Conversions
Air Electrical Data
RBHP Series
10
Blower Motor Electrical Data: A Voltage (115V)
Electric Heat Electrical Data
Blower Motor Electrical Data: J Voltage (208/240V)
Model
Size/Elec.
Designation
Voltage Phase Hertz HP [W]RPM Speeds Circuit
Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
RBHP-17A00NH*115 1 60 1/3 [249]300-1100 5 3.3 5.0 15
RBHP-21A00NH*115 1 60 1/2 [373]300-1100 5 5.0 7.0 15
RBHP-24A00NH*115 1 60 3/4 [559]300-1100 5 5.8 8.0 15
RBHP-25A00NH*115 1 60 3/4 [559]300-1100 5 7.7 10.0 15
Model
Elec./KW
Designation
PH/HZ
Type Supply Circuit
Single Circuit
Multiple Circuit
Minimum
Circuit
Ampacity
RBHP-17J06SH*1/60 Single Circuit 25/29
Heater
KW
Volts
208/240
3.7/4.9
Heater
No./KW & 240V
2/2.5
Circuit
Amps.
19.8/22.4
Maximum
Circuit
Protector
25/30
RBHP-17J07SH*1/60 Single Circuit 35/395.3/7.0 2/3.5 27.5/31.2 40/40
RBHP-17J11SH*1/60 Single Circuit 48/557.5/10.0 3/3.3 38.1/43.7 50/60
RBHP-21J06SH*1/60 Single Circuit 27/303.7/4.9 2/2.5 20.9/23.5 30/30
RBHP-21J07SH*1/60 Single Circuit 36/415.3/7.0 2/3.5 28.6/32.3 40/45
RBHP-21J11SH*1/60 Single Circuit 49/567.5/10.0 3/3.3 39.2/44.8 50/60
RBHP-21J14SH*1/60
Single Circuit 68/7710.5/14.0 4/3.5 54.1/61.4 70/80
Multiple Ckt. 1 36/415.3/7.0 2/3.5 28.6/32.3 40/45
Multiple Ckt. 2 32/375.3/7.0 2/3.5 25.5/29.2 35/40
RBHP-24J06SH*1/60 Single Circuit 28/313.7/4.9 2/2.5 22.0/24.6 30/35
RBHP-24J07SH*1/60 Single Circuit 38/425.3/7.0 2/3.5 29.7/33.4 40/45
RBHP-24J11SH*1/60 Single Circuit 51/587.5/10.0 3/3.3 40.3/45.9 60/60
RBHP-24J18SH*1/60
Single Circuit 85/9713.2/17.5 5/3.5 67.7/77.1 90/100
Multiple Ckt. 1 38/425.3/7.0 2/3.5 29.7/33.4 40/45
Multiple Ckt. 2 48/557.9/10.5 3/3.5 38.0/43.8 50/60
RBHP-25J11SH*1/60 Single Circuit 53/607.5/10.0 3/3.3 41.8/47.4 60/60
RBHP-25J18SH*1/60
Single Circuit 87/9913.2/17.5 5/3.5 69.2/78.6 90/100
Multiple Ckt. 1 39/445.3/7.0 2/3.5 31.2/34.9 40/45
Multiple Ckt. 2 48/557.9/10.5 3/3.5 38.0/43.8 50/60
RBHP-25J21SH*1/60
Single Circuit 98/11215.0/20.0 6/3.3 77.8/89.0 100/125
Multiple Ckt. 1 53/607.5/10.0 3/3.3 41.8/47.4 60/70
Multiple Ckt. 2 46/537.5/10.0 3/3.3 36.1/41.7 50/60
Supply circuit protective devices may be fuses or “HACR” type circuit breakers. Largest motor load is included in single circuit and circuit 1 multiple circuit. If non-standard fuse size is specified,
use next size larger standard fuse size.
[ ] Designates Metric Conversions
Model
Size/Elec.
Designation
Voltage Phase Hertz HP [W]RPM Speeds Circuit
Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
RBHP-17A00NH*115 1 60 1/3 [249]300-1100 5 3.3 5.0 15
RBHP-21A00NH*115 1 60 1/2 [373]300-1100 5 5.0 7.0 15
RBHP-24A00NH*115 1 60 3/4 [559]300-1100 5 5.8 8.0 15
RBHP-25A00NH*115 1 60 3/4 [559]300-1100 5 7.7 10.0 15
Air Electrical Wiring
RBHP Series
11
Electrical Wiring
Combustible Floor Base for Downflow Installations
Model Cabinet Size Combustible Floor
Base Model Number
Opening Front of Unit
“W” Width-Inches [mm]
Opening Side of Unit
“D” Depth-Inches [mm]
All Models RXBB-AA 143/8" [365]205/8" [524]
ACCESSORIES—KITS—PARTS
•Combustible Floor Base RXBB-AA for downflow
applications.
•Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert
single phase multiple three circuit units to a single supply
circuit. Kit includes cover and screw for line side terminals.
•Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert
single phase multiple two circuit units to a single supply circuit.
Kit includes cover and screw for line side terminals.
•Note:No jumper bar kit is available to convert three phase
multiple two circuit units to a single supply circuit.
•Finger Safe Circuit Breaker Cover—Part Number
45-23203-01. One is required for each circuit breaker pole,
if jumper bar is removed to provide multiple supply circuits.
•Evaporator Horizontal Drain Pan Model RXBD-CB:all
unit sizes.
•External Auxiliary Horizontal Drain Pan. RXBM-AA06—Fits
all models.
•Replacement Filters
Model Cabinet Size Filter Size In. [mm] Part Number
17 16.25 x 21 [413 x 533] 54-23217-02
21 19.75 x 21 [502 x 533] 54-23217-03
24 23.25 x 21 [591 x 533] 54-23217-04
25 23.25 x 21 [591 x 533] 54-23217-04
[ ] Designates Metric Conversions
Power Wiring
• Field wiring must comply with the National Electrical Code
(C.E.C. in Canada) and any applicable local ordinance.
•Supply wiring must be 75°C minimum copper conductors only.
•See electrical data for product Ampacity rating and Circuit
Protector requirement.
Grounding
• This product must be sufficiently grounded in accordance with
National Electrical Code (C.E.C. in Canada) and any applicable
local ordinance.
•A grounding lug is provided.
Air Limited Warranty
RBHP Series
12
GENERAL TERMS OF LIMITED WARRANTY*
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
periods stated, in accordance with the terms of the limited
warranty.
Conditional Parts (Registration Required)..........Ten (10) Years
*For complete details of the Limited and Conditional Warranties, including
applicable terms and conditions, contact your local contractor or the
Manufacturer for a copy of the product warranty certificate.
Air Notes
RBHP Series
13
Air Notes
RBHP Series
14
Air Notes
RBHP Series
15
The new degree of comfort.™
Rheem Heating, Cooling & Water Heating • P.O. Box 17010
Fort Smith, Arkansas 72917 • www.rheem.com
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
PRINTED IN U.S.A 1/18 QG FORM NO. H11-544 REV. 1