PRODUCT APPROVAL EVALUATION
RULE CHAPTER #61G20-3 • METHOD 1 OPTION D
FL 29677
Date: 5/29/2019
Detailed Product Description:
Manufacturer: EGS INTERNATIONAL, LLC
Manufacturer Address: 3133 SW 25TH STREET. PEMBROKE PARK, FL 33009
Model Name: ATLANTIC SERIES SM 130 ALUMINUM SLIDING GLASS DOOR
Maximum Panel Width: 60”
Maximum Height: 120”
Maximum Load: +130 PSF, -160 PSF (Small Missile Impact)
Installation Drawings # 19-46F
The above maximum parameters do not occur simultaneously.
See installation drawings for combination of span vs loads.
Comparative analysis used _X Yes No
Mandatory Tests (Tested in accordance with AAMA 501/101/I.S.2/NAFS/TAS 202)
TEST DESCRIPTION TEST LOCATION TEST REPORT
DATE
TEST
REPORT #
TEST
SEALED BY
ASTM E283 Air
Infiltration
Fenestration Testing
Laboratory, Inc.
05/18/04
05/01/98
FTL-4183
FTL-1622
Edmundo Largoeaspada, PE
Late Gilbert Diamond, PE
ASTM E331
or ASTM 547 &
TAS 202
Water
Penetration
Fenestration Testing
Laboratory, Inc.
05/18/04
05/01/98
FTL-4183
FTL-1622
Edmundo Largoeaspada, PE
Late Gilbert Diamond, PE
ASTM E330 &
TAS 202
Uniform
Static Air
Pressure
Fenestration Testing
Laboratory, Inc.
10/10/08
05/18/04
05/01/98
FTL-5728
FTL-4183
FTL-1622
Carlos Rionda, PE
Edmundo Largoeaspada, PE
Late Gilbert Diamond, PE
ASTM F842
or AAMA 1303.5
Forced Entry Fenestration Testing
Laboratory, Inc.
05/18/04
05/01/98
FTL-4183
FTL-1622
Edmundo Largoeaspada, PE
Late Gilbert Diamond, PE
Supplemental Tests (Tested in accordance with TAS-201 and TAS-203)
TEST DESCRIPTION TEST LOCATION TEST REPORT
DATE
TEST
REPORT #
TEST
SEALED BY
FBC 1626.3
(TAS 201 & 203)
Small Missile
Impact & Cyclic
Fenestration Testing
Laboratory, Inc.
10/10/08
05/18/04
05/15/00
05/01/98
FTL-5728
FTL-4183
FTL-2652
FTL-1622
Carlos Rionda, PE
Edmundo Largoeaspada, PE
Aldo P. Gonzalez, PE
Late Gilbert Diamond, PE
Under the limitations of the attached installation drawings, to the best of my knowledge and ability, the above
product conforms to the requirements of the 2017 Florida Building Code.
Evaluation Report Engineer:
Javad Ahmad PE # 70592
Al-Farooq Corporation EB # 3538
This product complies with the High Velocity Hurricane Zone (HVHZ) testing requirements.
Sealed 6/12/19