Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
Energy Calcs - Herd
Air Calcs, LLC Load Short Form House Air Calcs, LLC Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Herd Residence, Air Conditioning Unlimited, LLC 5194 Tree Top Trail, Port St Lucie, FL 34951 Htg Clg Outside db (°F) 41 90 Inside db (°F) 70 75 Design TD (°F) 29 15 Daily range - L Inside humidity (%) 30 50 Moisture difference (gr/Ib) 2 57 HEATING EQUIPMENT Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 11.1 kW 37834 Btuh 27 °F 1283 cfm 0.035 cfm/Btuh 0.70 in H2O Infiltration Method Shielding / stories Pressure /AVF Blower door 3 (partial) / 1 50 Pa / 0 cfm COOLING EQUIPMENT Make Lennox Trade LENNOX Cond ML14XC1-041-230A** Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 13.0 EER, 16 SEER Sensible cooling 26950 Btuh Latent cool i ng 11550 Btuh Total cooling 38500 Btuh Actual airflow 1283 cfm Airflowfactor 0.055 cfm/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 0.70 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) CIgAVF (cfm) Bath 2 39 174 97 6 5 Bath 4 79 1603 569 56 31 Bed 2 218 5203 2214 182 121 Bed 3 156 1699 1512 59 83 Bed 4 254 5395 3777 189 206 Dining Room 102 1777 805 62 44 Great Room 436 6285 5060 220 277 Kitchen 217 721 2903 25 159 Laundry 74 213 710 7 39 M Bath 126 1938 596 68 33 M Hall 54 0 0 0 0 Master Bedroom 230 4700 2462 164 135 Mud Room 62 1400 352 49 19 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrightsoft" 2021-Jan-04 11:03:44 A .e • - -aw=v —— Right-Sute@universal 2021 21.0.02 RSU27054 ACCP. Page 1 ...cumerrts\WrightsoftHVAC\5194TreeTopTrail.rup CaIc=MJ8 Front Door faces: S Hall 63 0 0 0 0 Sitting Room 138 1287 912 45 50 Storage 30 609 142 21 8 WC/Tub 39 655 238 23 13 WIC 60 390 173 14 9 WIC 3 36 66 51 2 3 WIC 4 48 866 312 30 17 Wtr Clst 27 633 221 22 12 House d 2524 36678 23481 1283 1283 Other equip loads 2000 1062 Equip. @ 0.95 RSM 23414 Latent cool i ng 10416 TOTALS ' 2524 ' 38678 ' 33830 ' 1283 ' 1283 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrightsoft" 2021-Jarr04 11:03:44 A A I.Ik- I 1-k,I,- -naw,v<om,a y Right-Sute®Uriversal2021 21.0.02 RSU27054 ACCP. Page 2 ...cumerrts\WrightsoftHVAC\5194TreeTopTrail.rup CaIc=MJ8 Front Door faces: S Air Calcs, LLC Building Analysis House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.00m For: Location: St Lucie Co Intl, FL, US Elevation: 26 ft Latitude: 28 °N Outdoor: Dry bulb (°F) Daily range (°F) Wet bulb (°F) Wind speed (mph) Herd Residence, Air Conditioning Unlimited, LLC 5194 Tree Top Trail, Port St Lucie, FL 34951 Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa Indoor: Heating Cooling Indoor temperature (°F) 70 75 Design TD (°F) 29 15 Relative humidity (%) 30 50 Heating Cooling Moisture difference (grAb) 2.4 56.9 41 90 Infiltration: - 15 (L ) Method Blower door 77 Shielding / stories 3 (partial) / 1 15.0 7.5 Pressure /AVF 50 Pa / 0 cfm Component Btuh/ft2 Btuh %of load Walls 3.1 8260 21.4 Glazing 8.6 3284 8.5 Doors 0 0 0 Ceilings 1.6 4004 10.4 Floors 3.5 8862 22.9 Infiltration 2.7 7237 18.7 Ducts 5030 13.0 Piping 0 0 Humidification 0 0 Ventilation 2000 5.2 Adjustments 0 Total 38678 1 100.0 Component Btuh/ft2 Btuh % of load Walls 1.9 4995 20.4 Glazing 9.6 3656 14.9 Doors 0 0 0 Ceilings 1.2 3085 12.6 Floors 0 0 0 Infiltration 0.8 2155 8.8 Ducts 3339 13.6 Ventilation 1062 4.3 Internal gains 6250 25.5 Blower 0 0 Adjustments 0 Total 24543 100.0 Latent Cooling Load =10416 Btuh Overall U-value = 0.214 Btuh/ft2-°F Data entries checked. Glazing Ventilation !rnal Gains _ -pp- wrightsoft- 2021-Jan-0411:03:44 MCA M, r • dr, -.. Right -Suite@ Universal 2021 21.0.02 RSU27054 Page 1 cuments\WrightsoftHVAC\5194TreeTopTrail.rup Calc=MJ8 Front Door faces: S Air Calcs, LLC Component Constructions House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Location: St Lucie Co Intl, FL, US Elevation: 26 ft Latitude: 28°N Outdoor: Dry bulb (°F) Daily range (°F) Wet bulb (°F) Wind speed (mph) Herd Residence, Air Conditioning Unlimited, LLC 5194 Tree Top Trail, Port St Lucie, FL 34951 Indoor: Indoor temperature (°F) Design TD (°F) Relative humidity (%) Heating Cooling Moisture difference (gr/lb) 41 90 Infiltration: - 15 (L ) Method 77 Shielding / stories 15.0 7.5 Pressure /AVF Construction descriptions or Area U value ft, Btuh/ft"F Walls Blk Wall, Stuc Ext, R-4.1 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh n 332 0.109 e 642 0.109 s 563 0.109 w 742 0.109 all 2280 0.109 Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2N4" Wd 367 0.101 Frm, 16" OC Stud Windows Impact, Clear, Low-e: Impact, Clear, Low-e; NFRC rated (SHGC=0.21); n 4 0.250 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.4 ft overhang (1.2 ft Wndow ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.21); n 6 0.250 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (1.2 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Low-e: Impact, Clear, Low-e; NFRC rated (SHGC=0.19); n 30 0.290 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (6 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.19); n 108 0.310 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (9 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Low-e; NFRC rated (SHGC=0.19); n 20 0.310 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.4 ft overhang (6.7 ft Wndow ht, 1.5 ft sep.); 8 ft head ht Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa Heating Cooling 70 75 29 15 30 50 2.4 56.9 Blower door 3 (partial) / 1 50 Pa / 0 cfm Insul R Htg HTM Loss Clg HTM Gain ftz°F/Btuh Btuh/ft' Btuh Btuh/ft' Btuh 5.1 3.15 1047 2.02 670 5.1 3.15 2023 2.02 1294 5.1 3.15 1774 2.02 1135 5.1 3.15 2338 2.02 1496 5.1 3.15 7183 2.02 4594 11.0 2.94 1077 1.09 401 0 7.25 26 6.47 23 0 7.25 44 6.47 39 0 8.41 252 6.74 202 0 8.99 971 7.02 758 0 8.99 181 7.02 141 �- wrightsoft, 2021-Jarr0411:03:44 .M.CAM„ek•,de, •,- „a,n=-av o, Na„ Right-SUte@Universal 2021 21.0.02 RSU27054 Page 1 cumerds\WrightoftHVAC\5194TreeTopTrail.rup Calc=MJ8 FrontDoorfaces: S Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.19); a 12 0.290 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.4 ft overhang (4 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.19); a 18 0.290 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 9 ft overhang (6 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.21); s 12 0.250 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (2 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.19); s 54 0.290 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green w 30 0.290 grass (0.23); 1.4 ft overhang (6 ft window ht, 1.5 ft sep.); 8 ft head ht w 18 0.290 all 102 0.290 Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.19); s 30 0.290 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 5.3 ft overhang (6 ft window ht, 1.5 ft sep.); 8 ft head ht Impact, Clear, Lowe: Impact, Clear, Lowe; NFRC rated (SHGC=0.19); s 40 0.310 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (6.7 ft window ht, 1.5 ft sep.); 8 ft head ht Doors (none) Ceilings Attic, Shngl Roof, R-20 Roof Deck Ins, 112" Gyp Bd 2524 0.405 Floors DftFlor: On Grade Depth, Carpet 108 0.989 DftFlor: On Grade Depth, Tile Flr Fnsh 201 0.989 wrightsoft® Rig1t-Sute®Urrversa1202121.0.02RSU27054 ...amends\WrigfisoftHVAC\5194Tree Top Trail.rrp Calc=MJ8 FrordDoorfaces: S 0 8.41 101 20.3 244 0 8.41 151 8.80 158 0 7.25 87 8.47 102 0 8.41 454 8.74 472 0 8.41 252 20.3 610 0 8.41 151 20.3 366 0 8.41 858 14.2 1449 0 8.41 252 8.74 262 0 8.99 361 6.91 278 21.0 1.59 4004 1.22 3085 0 28.7 3098 0 0 0 28.7 5765 0 0 2021-Jarr04 11:03:44 Page 2 Pro ect Summa Job: Air Calcs, LLC 1 rY Dec Date: Dec 30, 2020 House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Herd Residence, Air Conditioning Unlimited, LLC 5194 Tree Top Trail, Port St Lucie, FL 34951 Notes: Weather: St Lucie Co Intl, FL, US Winter Design Conditions Outside db Inside db Design TD Summer Design Conditions 41 °F Outside db 70 °F Inside db 29 °F Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 31648 Btuh Ducts 5030 Btuh Central vent (63 cfm) 2000 Btuh Outside air Humidification Piping Equipment load Infiltration Method Shielding / stories Pressure /AVF 0 Btuh 0 Btuh 38678 Btuh Blower door 3 (ppartial) / 1 50 (partial) 0 cfm Heating Cooling Area (ft2) 2524 2524 Volume (ft3) 25690 25690 Airchanges/hour 0.53 0.30 Equiv.AVF (cfm) 227 127 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 11.1 kW 37834 Btuh 27 °F 1283 cfrn 0.035 cfi71/Btuh 0.70 in H2O 90 °F 75 °F 15 °F L 50 % 57 gr/lb Sensible Cooling Equipment Load Sizing Structure 20142 Btuh Ducts 3339 Btuh Central vent (63 cfm) 1062 Btuh Outside air Blower 0 Btuh Use manufacturer's data n Rate/swin multipplier Equipmen1sensibleload 0.95 23414 Btuh Latent Cooling Equipment Load Sizing Structure 5921 Btuh Ducts 2071 Btuh Central vent (63 cfm) 2424 Btuh Outside air Equipment latent load 10416 Btuh Equipment Total Load (Sen+Lat) 33830 Btuh Req. total capacity at 0.70 SHR 2.8 ton Cooling Equipment Summary Make Lennox Trade LENNOX Cond ML14XC1-041-230A** Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 13.0 EER, 16 SEER Sensible cooling 26950 Btuh Latent cool i ng 11550 Btuh Total cooling 38500 Btuh Actual airflow 1283 cfm Airflowfactor 0.055 cfm/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 0.70 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. w rig htsoft`a 2021-Jan-04 11:03:44 Right-Suite(D Universal 2021 21.0.02 RSU27054 Page 1 .4CCA g ...cumer><s\WrigtisoftHVAC\5194TreeTopTrail.rup CaIc=MJ8 From Door faces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name House Bath 2 2 Exposed wall 309.0 ft 0 ft 3 Room height 10.2 ft d 9.4 ft heat/000l 4 Room dimensions 6.5 x 6.0 ft 5 Room area 2524.0 ft2 39.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Bluh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Low-e Impact, Clear, Low-e 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 500 4 6 332 0 0 1047 26 44 670 23 39 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Low-e Impact, Clear, Low-e 0.290 0.310 n n 8.41 8.99 6.74 7.02 30 108 0 0 252 971 202 758 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.310 n 8.99 7.02 20 0 181 141 0 0 0 0 W G Blk Wall, StucExt, Impact, Clear, Low-e 0.109 0.290 e a 3.15 8.41 2.02 20.34 672 12 642 0 2023 101 1294 244 0 0 0 0 0 0 0 0 Impact, Clear, Low-e Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 18 699 18 563 151 1774 158 1135 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.250 s 7.25 8.47 12 12 87 102 0 0 0 0 Impact, Clear, Low-e 0.290 s 8.41 8.74 54 54 454 472 0 0 0 0 G Impact, Clear, Low-e 0.290 s 8.41 8.74 30 30 252 262 0 0 0 0 Impact, Clear, Low-e Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 40 790 40 742 361 2338 278 1496 0 0 0 0 0 0 0 0 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 30 18 0 0 252 151 610 366 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 367 367 1077 401 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 2524 2524 4004 3085 39 39 62 48 F DftRor 0.989 28.68 0.00 851 108 3098 0 0 0 0 0 F DftRor 0.989 28.68 0.00 1673 201 5765 0 39 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 24411 11736 62 47 12 a) Infiltration 7237 2155 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Ocwpants@ 230 5 1150 0 0 Appliancestother 5100 0 Subtotal (lines 6 to 13) 31648 20142 62 47 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 88 36 14 Subtotal 31648 20142 150 83 15 Dudloads 16% 17% 5030 3339 16% 17% 24 14 Total room load 36678 23481 174 97 Air required (dm) 1283 12831 6 5 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right-Suite®Universal2021 21.0.02 RSU27054 ,4CC,K Page 1 moments\WrightsoftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name Bath 4 Bed 2 2 Exposed wall 15.0 ft 47.5 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/000l 4 Room dimensions 1.0 x 78.8 ft 1.0 x 217.5 ft 5 Room area 78.8 ft2 217.5 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 14 0 0 14 0 0 44 0 0 28 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 a a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 141 0 141 0 444 0 284 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 14 0 14 0 44 0 28 0 164 0 146 0 462 0 295 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 18 18 151 157 G Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 113 0 113 0 355 0 227 0 141 0 141 0 444 0 284 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 79 79 125 96 218 218 345 266 F DflHlor 0.989 28.68 0.00 0 0 0 0 218 48 1362 0 F DflHlor 0.989 28.68 0.00 79 15 430 0 0 0 0 0 6 c) AED excursion -7 -26 Envelope loss/gain 999 374 3209 1261 12 a) Infiltration 383 114 1214 362 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 250 Subtotal (lines 6 to 13) 1383 488 4423 1872 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 66 27 14 Subtotal 1383 488 4489 1899 15 Dudloads 16% 17% 220 81 16% 17% 713 315 Total room load 1603 569 5203 2214 Air required (cfm) 56 31 182 121 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- rightsoft 2021 -Jan-04 11:03:44 w°-""""" 1-l'-, Right -Suite@ Universal2021 21.0.02 RSU27054 gCC,K Page 2 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By. Vicki Lynne Nisa 1 Room name Bed 3 Bed 4 2 Exposed wall 12.0 ft 46.5 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/000l 4 Room dimensions 13.0 x 12.0 ft 17.5 x 14.5 ft 5 Room area 156.0 ft2 253.8 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 164 4 0 141 0 0 444 26 0 284 23 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 20 0 181 141 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 a a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 136 12 124 0 392 101 251 244 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 113 0 95 0 299 0 191 0 136 0 106 0 335 0 214 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 18 0 0 0 151 0 366 30 0 0 0 252 0 610 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 156 156 247 191 254 254 403 310 F DftRor 0.989 28.68 0.00 156 12 344 0 0 0 0 0 F Mor 0.989 28.68 0.00 0 0 0 0 254 47 1334 0 6 c) AED excursion 160 58 Envelope loss/gain 1042 908 3466 2136 12 a) Infiltration 307 91 1189 354 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 250 750 Subtotal (lines 6 to 13) 1348 1249 4655 3240 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 117 48 0 0 14 Subtotal 1466 1297 4655 3240 15 Dudloads 16% 17% 233 215 16% 17% 740 537 Total room load 1699 1512 5395 3777 Air required (cfm) 59 83 189 206 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right-Suite®Universal2021 21.0.02 RSU27054 ,4CC,K Page 3 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name Dining Room Great Room 2 Exposed wall 12.0 ft 35.5 ft 3 Room height 12.0 ft heat/cool 12.0 ft heat/cool 4 Room dimensions 12.0 x 8.5 ft 1.0 x 436.3 ft 5 Room area 102.0 ft2 436.3 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 144 0 6 108 0 0 340 0 44 218 0 39 168 0 0 60 0 0 189 0 0 121 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 30 0 0 0 252 0 202 0 0 108 0 0 0 971 0 758 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 a a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 0 0 0 0 0 0 0 0 234 0 152 0 478 0 306 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 12 12 87 102 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 30 30 252 262 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 40 24 40 24 361 76 278 48 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 102 102 162 125 436 436 692 533 F DftRor 0.989 28.68 0.00 0 0 0 0 0 0 0 0 F DftRor 0.989 28.68 0.00 102 12 344 0 436 36 1018 0 6 c) AED excursion -10 -60 Envelope loss/gain 1142 574 4125 2349 12 a) Infiltration 392 117 1158 345 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 3 690 Appliancestother 0 900 Subtotal (lines 6 to 13) 1534 690 5283 4284 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 140 57 14 Subtotal 1534 690 5423 4340 15 Dudloads 16% 17% 244 114 16% 17% 862 720 Total room load 1777 805 6285 5060 Air required (dm) 62 44 220 277 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right-Suite®Universal2021 21.0.02 RSU27054 ,4CC,K Page 4 cuments\WrightsoftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name Kitchen Laundry 2 Exposed wall O ft O ft 3 Room height 12.0 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 1.0 x 217.3 ft 1.0 x 74.0 ft 5 Room area 217.3 ft2 74.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 e a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 217 217 345 266 74 74 117 90 F DftRor 0.989 28.68 0.00 0 0 0 0 74 0 0 0 F DftRor 0.989 28.68 0.00 217 0 0 0 0 0 0 0 6 c) AED excursion -33 -8 Envelope loss/gain 345 232 117 82 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliancestother 1700 500 Subtotal (lines 6 to 13) 345 2392 117 582 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 277 98 66 27 14 Subtotal 622 2490 183 609 15 Dudloads 16% 17% 99 413 16% 17% 29 101 Total room load 721 2903 213 710 Air required (cfm) 251 159 7 39 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right -Suite® Universal2021 21.0.02 RSU27054 ,4Ccr. Page 5 cuments\WrightsoftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name M Bath M Hall 2 Exposed wall 22.0 ft 10.0 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 1.0 x 125.8 ft 6.0 x 9.0 ft 5 Room area 125.8 ft2 54.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 e a 3.15 8.41 2.02 20.34 80 0 80 0 252 0 161 0 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 0 0 0 0 0 0 0 0 56 0 56 0 178 0 114 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 0 38 0 38 0 118 0 76 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 127 127 373 139 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 126 126 200 154 54 54 86 66 F DftRor 0.989 28.68 0.00 0 0 0 0 0 0 0 0 F DftRor 0.989 28.68 0.00 126 22 631 0 54 10 287 0 6 c) AED excursion -7 -5 Envelope loss/gain 1455 446 669 251 12 a) Infiltration 217 65 256 76 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 1672 511 924 327 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -924 -327 14 Subtotal 1672 511 0 0 15 Dudloads 16% 17% 266 85 16% 17% 0 0 Total room load 1938 596 0 0 Air required (cfm) 68 33 0 0 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right -Suite@ Universal2021 21.0.02 RSU27054 ,4CC,K Page 6 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name Master Bedroom Mud Room 2 Exposed wall 39.0 ft 18.5 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/000l 4 Room dimensions 17.0 x 13.5 ft 1.0 x 61.8 ft 5 Room area 229.5 ft2 61.8 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 9 0 0 9 0 0 30 0 0 19 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 e a 3.15 8.41 2.02 20.34 127 0 127 0 400 0 256 0 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 160 0 124 0 390 0 250 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 36 36 303 315 0 0 0 0 G Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 80 0 80 0 252 0 161 0 14 0 14 0 44 0 28 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 150 150 442 165 C Attic, Shnql Roof, 0.405 1.59 1.22 230 230 364 280 62 62 98 75 F DftRor 0.989 28.68 0.00 230 39 1119 0 0 0 0 0 F DftRor 0.989 28.68 0.00 0 0 0 0 62 19 531 0 6 c) AED excursion -28 -4 Envelope loss/gain 2827 1233 1144 283 12 a) Infiltration 997 297 64 19 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13) 3824 2030 1208 302 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 231 82 0 0 14 Subtotal 4055 2112 1208 302 15 Dudloads 16% 17% 644 350 16% 17% 192 50 Total room load 4700 2462 1400 352 Air required (cfm) 164 135 49 19 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right -Suite® Universal2021 21.0.02 RSU27054 ,4CC,K Page 7 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name Pantry Hall 2 Exposed wall 7.5 ft 4.5 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/000l 4 Room dimensions 7.5 x 5.0 ft 4.5 x 14.0 ft 5 Room area 37.5 ft' 63.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 e a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 42 0 42 0 133 0 85 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 70 0 70 0 222 0 142 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 38 38 59 46 63 63 100 77 F DftRor 0.989 28.68 0.00 0 0 0 0 0 0 0 0 F DftRor 0.989 28.68 0.00 38 8 215 0 63 5 129 0 6 c) AED excursion -3 -3 Envelope loss/gain 497 185 362 160 12 a) Infiltration 192 57 115 34 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 688 242 477 194 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 231 82 -477 -194 14 Subtotal 920 323 0 0 15 Dudloads 16% 17% 146 54 16% 17% 0 0 Total room load 1066 377 0 0 Air required (cfm) 37 21 0 0 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right -Suite@ Universal2021 21.0.02 RSU27054 ,4CC,K Page 8 moments\WrightsoftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name Sitting Room Storage 2 Exposed wall 9.5 ft 8.5 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 11.5 x 12.0 ft 3.5 x 8.5 ft 5 Room area 138.0 ft2 29.8 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Lowe Impact, Clear, Lowe 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Lowe Impact, Clear, Lowe 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Lowe 0.109 0.290 e a 3.15 8.41 2.02 20.34 89 0 71 0 225 0 144 0 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 18 0 18 0 151 0 158 0 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 G Impact, Clear, Lowe 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Lowe Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 80 80 235 87 C Attic, Shnql Roof, 0.405 1.59 1.22 138 138 219 169 30 30 47 36 F DftRor 0.989 28.68 0.00 138 10 272 0 0 0 0 0 F DftRor 0.989 28.68 0.00 0 0 0 0 30 9 244 0 6 c) AED excursion -11 -2 Envelope loss/gain 867 460 526 122 12 a) Infiltration 243 72 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 250 0 Subtotal (lines 6 to 13) 1110 782 526 122 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1110 782 526 122 15 Dudloads 16% 17% 176 130 16% 17% 84 20 Total room load 1287 912 609 142 Air required (cfm) 45 501 21 8 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right-Suite®Universal2021 21.0.02 RSU27054 ,4CC,K Page 9 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name WC/Tub WIC 2 Exposed wall 6.0 ft 1.0 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 6.5 x 6.0 ft 1.0 x 60.3 ft 5 Room area 39.0 ft2 60.3 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Low-e Impact, Clear, Low-e 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Low-e Impact, Clear, Low-e 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Low-e 0.109 0.290 e a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 G Impact, Clear, Low-e Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 G Impact, Clear, Low-e 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Low-e Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 56 0 56 0 178 0 114 0 0 0 0 0 0 0 0 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 9 9 28 10 C Attic, Shnql Roof, 0.405 1.59 1.22 39 39 62 48 60 60 96 74 F DflHlor 0.989 28.68 0.00 0 0 0 0 0 0 0 0 F DflHlor 0.989 28.68 0.00 39 6 172 0 60 1 29 0 6 c) AED excursion -3 -1 Envelope loss/gain 412 158 152 83 12 a) Infiltration 153 46 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 565 204 152 83 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 185 65 14 Subtotal 565 204 337 148 15 Dudloads 16% 17% 90 34 16% 17% 54 25 Total room load 655 238 390 173 Air required (cfm) 23 131 14 9 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- 2021 -Jan-04 11:03:44 rightsoft w°-""""" 1-l'-, Right -Suite® Universal2021 21.0.02 RSU27054 ,4CC,K Page 10 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name WIC 3 WIC 4 2 Exposed wall 0 ft 8.0 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/000l 4 Room dimensions 4.5 x 8.0 ft 6.0 x 8.0 ft 5 Room area 36.0 ft2 48.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number (Btuh/f -°F) (Btuh/IE) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Blk Wall, StucExt, Impact, Clear, Low-e Impact, Clear, Low-e 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Low-e Impact, Clear, Low-e 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.310 n 8.99 7.02 0 0 0 0 0 0 0 0 W LG Blk Wall, StucExt, Impact, Clear, Low-e 0.109 0.290 a a 3.15 8.41 2.02 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 G Impact, Clear, Low-e Blk Wall, StucExt, 0.290 0.109 a s 8.41 3.15 8.80 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.250 s 7.25 8.47 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Low-e 0.290 s 8.41 8.74 0 0 0 0 0 0 0 0 Impact, Clear, Low-e Blk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 0 75 0 75 0 237 0 152 Impad, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I� �G P Frm Wall, 1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 0 0 0 0 C Attic, Shnql Roof, 0.405 1.59 1.22 36 36 57 44 48 48 76 59 F DftRor 0.989 28.68 0.00 36 0 0 0 0 0 0 0 F DftRor 0.989 28.68 0.00 0 0 0 0 48 8 229 0 6 c) AED excursion -1 -4 Envelope loss/gain 57 43 543 207 12 a) Infiltration 0 0 204 61 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 57 43 747 267 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 57 43 747 267 15 Dudloads 16% 17% 9 7 16% 17% 119 44 Total room load 66 51 866 312 Air required (cfm) 2 31 30 17 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- rightsoft 2021-Jan-0411:03:44 w°-""""" 1-l'-, Right-Suite®Universal2021 21.0.02 RSU27054 ,4CC,K Page 11 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynm@aircalcs.com Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa 1 Room name WtrClst 2 Exposed wall 6.0 ft 3 Room height 9.4 ft heat/cool 4 Room dimensions 4.5 x 6.0 ft 5 Room area 27.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh/ft---°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G G Bilk Wall, StucExt, Impact, Clear, Low-e Impact, Clear, Low-e 0.109 0.250 0.250 n n n 3.15 7.25 7.25 2.02 6.47 6.47 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear, Low-e Impact, Clear, Low-e 0.290 0.310 n n 8.41 8.99 6.74 7.02 0 0 0 0 0 0 0 0 G Impact, Clear, Low-e 0.310 n 8.99 7.02 0 0 0 0 W LG BlkWall, StucEA, Impact, Clear, Low-e 0.109 0.290 e e 3.15 8.41 2.02 20.34 56 0 56 0 178 0 114 0 G Inn pad, Clear, Low-e Bilk Wall, StucExt, Impad, Clear, Low-e 0.290 0.109 0.250 e s s 8.41 3.15 7.25 8.80 2.02 8.47 0 0 0 0 0 0 0 0 0 0 0 0 W Impact, Clear, Low-e 0.290 s 8.41 8.74 0 0 0 0 G Impact, Clear, Low-e 0.290 s 8.41 8.74 0 0 0 0 Impact, Clear, Low-e Bilk Wall, StucExt, 0.310 0.109 s w 8.99 3.15 6.91 2.02 0 0 0 0 0 0 0 0 W Impact, Clear, Lowe Impad, Clear, Lowe 0.290 0.290 w w 8.41 8.41 20.34 20.34 0 0 0 0 0 0 0 0 C. P Frm Wall,1/2" Gyp B 0.101 2.94 1.09 0 0 0 0 C Attic, Shnal Roof, 0.405 1.59 1.22 27 27 43 33 F DftFlor 0.989 28.68 0.00 0 0 0 0 F DftFlor 0.989 28.68 0.00 27 6 172 0 6 c) AED excursion -3 Envelope loss/gain 393 144 12 a) Infiltration 153 46 b) Room ventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Appliancestother 0 Subtotal (lines 6 to 13) 546 190 Less external load 0 0 Lesstransfer 0 0 Redistribution 0 0 14 Subtotal 546 190 15 Ductloads 16% 17% 87 31 Total room load 633 221 Air required (cfm) 22 12 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed -ri- rightsoft 2021-Jarr0411:03:44 w.-""1.1.1 "`" __ Right-Suite®Universal2021 21.0.02 RSU27054 ,4CC,K Page 12 cuments\Wrig%oftHVAC\5194Tree Top Trail.rp Calc=MJ8 FrontDoorfaces: S Air Calcs, LLC Duct System Summary House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Herd Residence, Air Conditioning Unlimited, LLC 5194 Tree Top Trail, Port St Lucie, FL 34951 External static pressure Pressure losses Available static pressure Supply/return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.535 / 0.165 in H2O 0.092 i n/100ft 1283 cfm 757 ft Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.535 / 0.165 in H2O 0.092 in/100ft 1283 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath h 174 7 6 0.095 4.0 Ox0 VIFx 64.4 500.0 St6 Bath h 1603 67 37 0.095 5.0 Ox0 VIFx 62.9 500.0 st5 Bed 2 h 5203 218 145 0.093 10.0 Ox 0 VI Fx 75.8 500.0 St6 Bed 3 c 1512 71 99 0.095 6.0 Ox 0 VI Fx 62.9 500.0 St6 Bed 4 c 3777 227 248 0.092 10.0 Ox 0 VI Fx 78.7 500.0 st5 Dining Room h 1777 75 53 0.236 5.0 Ox 0 VIFx 26.4 200.0 SO Great Room c 2530 132 166 0.159 8.0 Ox0 VIFx 37.2 300.0 st3 Great Room -A c 2530 132 166 0.159 8.0 Ox0 VIFx 36.7 300.0 st3 Kitchen c 1452 15 95 0.246 6.0 Ox0 VIFx 17.5 200.0 st1 Kitche A c 1452 15 95 0.247 6.0 Ox0 VIFx 16.2 200.0 st1 Laundry c 710 9 47 0.119 4.0 Ox0 VIFx 48.2 400.0 st4 M Bath h 1938 81 39 0.242 6.0 Ox 0 VI Fx 16.2 205.0 st2 Master Bedroom h 2350 99 81 0.233 6.0 Ox 0 VI Fx 24.5 205.0 St2 Master Bedroom -A h 2350 99 81 0.235 6.0 Ox 0 VI Fx 22.9 205.0 st2 Mud Room h 1400 59 23 0.238 5.0 Ox 0 VI Fx 24.6 200.0 st1 Pantry h 1066 45 25 0.241 4.0 Ox0 VIFx 21.5 200.0 st1 Sitting Room c 912 54 60 0.095 5.0 Ox 0 VIFx 65.4 500.0 St5 Storage h 609 26 9 0.239 4.0 Ox0 VIFx 24.1 200.0 st1 W C/Tub h 655 27 16 0.095 4.0 Ox 0 VI Fx 65.7 500.0 St6 W Ic h 390 16 11 0.244 4.0 Ox 0 VI Fx 14.3 205.0 St2 WIC 3 c 51 3 3 0.119 4.0 Ox 0 VI Fx 48.8 400.0 St4 WIC 4 h 866 36 20 0.094 4.0 Ox 0 VI Fx 67.8 500.0 st5 WtrClst h 633 27 15 0.237 4.0 Ox0 VIFx 20.5 205.0 st2 wrightsoft® M=e •I a b =.- -,I—— Right-Sute@Universal 2021 21.0.02 RSU27054 �CA...cuments\WrigWoftHVAC\5194Tree Top Trail.rup Calc=MJ8 FrontDoorfaces: S 2021-Jarr04 11:03:46 Page 1 Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st5 PeakAVF 384 365 0.092 489 12.0 0 x 0 VinlFlx st4 st6 PeakAVF 325 266 0.093 413 12.0 0 x 0 VinlFlx st4 st4 PeakAVF 720 681 0.092 516 16.0 0 x 0 VinlFlx st3 st3 PeakAVF 984 1013 0.092 573 18.0 0 x 0 VinlFlx st1 st1 PeakAVF 1218 1314 0.092 743 18.0 0 x 0 VinlFlx st2 PeakAVF 322 226 0.233 728 9.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb2 Ox0 717 792 178.7 0.092 567 16.0 Ox 0 VIFx rt1 rb1 Ox0 214 173 175.4 0.094 484 9.0 Ox 0 VIFx rt1 rb6 Ox 0 263 268 0 0 0 0 Ox 0 VI Fx rb5 Ox 0 54 60 0 0 0 0 Ox 0 VI Fx rb4 Ox 0 74 102 0 0 0 0 Ox 0 VI Fx rb3 Ox 0 218 145 0 0 0 0 Ox 0 VI Fx Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 931 964 0.092 546 18.0 0 x 0 VinlFlx wrightsoft® A.. • I a b =-1—,1—— Right-Sute®Urrversal2021 21.0.02 RSU27054 �CA...cuments\WrigWoftHVAC\5194Tree Top Trail.rup Calc=MJ8 FrordDoorfaces: S 2021-Jarr04 11:03:46 Page 2 Air Calcs, LLC Manual S Compliance Report House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Herd Residence, Air Conditioning Unlimited, LLC 5194 Tree Top Trail, Port St Lucie, FL 34951 Design Conditions Job: 1403 Date: Dec 30, 2020 By: Vicki Lynne Nisa Outdoor design DB: 90.4°F Sensible gain: 24543 Btuh Entering coil DB: 75.9°F Outdoor design WB: 77.4°F Latent gain: 10416 Btuh Entering coil WB: 63.8°F Indoor design DB: 75.0°F Total gain: 34959 Btuh Indoor RH: 50% Estimated airflow: 1283 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1-041-230A**+CBA27UHE-048-230*++TDR Actual airflow: 1283 cfm Sensible capacity: 26950 Btuh 110% of load Latent capacity: 11550 Btuh 111 % of load Total capacity: 38500 Btuh 110% of load SHR: 70% Design Conditions Outdoor design DB: 41.0°F Heat loss: 38678 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1283 cfm Output capacity: 11.1 kW 98% of load Meets all requirements ofACCA Manual S. Entering coil DB: 68.4°F Temp. rise: 50 °F wrightsoft© 2021-Jarr0411:03:46 AM,.ek•Iae,.n„��„naw,1—p , Right-Sute®Universal2021 21.0.02 RSU27054 �CA Page 1 ...cumerrts\WrightsoftHVAC\5194Tree Top Trail.rup CaIc=MJ8 Front Door faces: S Job M 1403 Performed by Vicki Lynne Nisa for: Herd Residence 5194 Tree Top Trail Port St Lucie, FL 34951 Level 1 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 243 Page 1 Right-Suite(g) Universal 2021 21.0.02 RSU27054 2021-Jan-04 11:04:07 ...oft HVAC\5194 Tree Top Trail.rup