M.A. CORSON & ASSOCIATES, Inc.
ARCHITECTURE * STRUCTURAL DESIGN
412 Colorado Ave., Stuart, Fl. 34994
(772) 223-8227 * Lic. #AR91665
To: St. Lucie County - Building & Code Regulation Division
Date: December 11, 2020
Re: Maureen Pizzano
7380 S. Ocean Drive, Unit 918 (Middle unit)
Jensen Beach, Fl. , 34957
It is acceptable to replace existing double hung window, picture window, sliding glass door
openings and mullion bars for the address listed above with the units as follows:
1) D.H.- The PGT Window Systems "SH 5560" Impact PVC double hung window L.M.I. has a
Miami Dade NOA #20-0401.06 The nominal wind speed is 132 mph and the ultimate wind speed
is 170 mph. It has a +70 /-110 design pressure and has a small & large missile "D" approval and
HVHZ.
2) P.W.- The PGT Window Systems "PW 5520A" Impact PVC picture window has a Miami
Dade NOA #20-0401.16. The nominal wind speed is 132 mph and the ultimate wind speed is 170
mph. It has a +80 /-100.0 design pressure and has a large missile "D" approval and HVHZ. This
unit is located in a Zone 4.
3) S.G.D. - The PGT "5570/2770" series PVC S.G.D. has a Miami Dade NOA #20-0429.05.
The nominal wind speed is 132 mph and the ultimate wind speed is 170 mph.
It has a +100 / -100 design pressure. It has a small and large missile "D"
approval HVHZ. This unit is located in a Zone 4.
3) MULLION BARS - The Series "PGT" Clipped Extruded Aluminum Tube Mullion - has a
Miami Dade NOA # 20-0406.03. The nominal wind speed is 132 mph and the ultimate wind
speed is 170 mph. It has a +170.0 /-170.0 design pressure and has a large & small missile "D"
approval and HVHZ . This unit is located in a Zone 4.
SCOPE OF WORK: New double hung & picture window, sliding glass door and mullion
bar replacement.
DESIGN PARAMETERS AND ASSUMPTIONS USED:
1. DESIGN CODE: Florida Building Code Sixth Edition (2017) with 2020 Supplements using
ASCE 7‐10
2. Structure Designed: Enclosed
3. Risk Category: II Exposure Category: D
4. Design Wind Velocity 170 mph End Zone Width: 4 ft
5. Mean Roof Height 153 ft Roof Pitch: 0:12 Parapet: N/A ft
6. Components & Cladding Design Pressures Used: Zone 4: +58.7 / -63.7 P.S.F. &
Zone 5: +58.7 / -78.5 P.S.F. Worst case scenario has been calculated.
7. Design Loads: Floor: N/A Roof/Dead: N/A Roof/Live: N/A Balcony: N/A Dock: N/A
Deck: N/A Stairs: N/A Fence: N/A Railings: N/A
8. Were Shear Walls Considered For Structure? N/A Not Applicable Explain Why Not:
9. Is A Continuous Load Path Provided? N/A
10. Design Soil Bearing Pressure: N/A Soil Test Reports Submitted? N/A
Thank you for your time and consideration. If you have any questions please call.
Respectfully,
Mark A Corson
Mark A. Corson A.I.A., NCARB President