HomeMy WebLinkAboutBuilding PlansSTRUCTURE._CRITERIA DESIGN: *THIS OVERALL DESIGN COMPLIES WITH THE GUIDELINES DEFINED IN CHAPTERS 16 AND 20 OF THE 2017 FLORIDA BUILDING CODE 6TH EDITION, BUILDING AND ALL OTHER APPLICABLE STANDARDS WIND CRITERIA: *VELOCITY: 150 MPH (3 SECOND GUST), EXPOSURE 'C', RISK CATEGORY I. FOR VELOCITY >100 MILES PER HOUR, IMPORTANCE FACTOR SHALL = 0.77. SCREEN DESIGN: *18 X 14 SCREEN WALLS: WW PRESSURE @ 19.6 PSF, LW PRESSURE @ 15.6 PSF, ROOF @ 5.4 PSF DESIGN PRESSURE ON BUILDING ENVELOPE ELEMENTS: *PER THE ALLOWABLE STRESS DESIGN FOUND ON TABLE 2002.4 AND 2002.4A OF THE FLORIDA BUILDING CODE. *THE AVERAGE SPACING BETWEEN BEAMS IS SHOWN IN THE DRAWING. THE ACTUAL SPACING BETWEEN ANY TWO BEAMS MUST BE THE AVERAGE SPACING, +/_ 2", AND THE CENTER TO CENTER MUST NEVER BE GREATER THAN 8'-0". *EXTERIOR GLAZED OPENINGS SHALL BE PROTECTED BY PRODUCTS WHICH MEET THE REQUIREMENTS OF SSTD 12. SCREEN ENCLOSURE ROOF TYPE *MANSARD ROOF ENCLOSURE WITH 3'0" RISE MAX. STRUCTURE IS CONNECTED TO EXISTING SINGLE STORY C.B.S. HOME WITH WOOD FASCIA. (SEE CONNECTION DETAIL 4 ON PAGE 3). CONCRETE; *THIS ENCLOSURE WILL BE CONSTRUCTED ON AN EXISTING CONCRETE PATIO, THIS FOUNDATION IS;ACCEPTABLE FOR THIS ENCLOSURE. *ALL HOLD DOWN FASTENERS MUST BE NO MORE THAN 12" ON CENTER W/2-1/4" MIN. EMBEDMENT INTO CONCRETE. ALUMINUM NOTES: MATERIALS SHALL CONFORM TO THE F.B.C., CHANGES SHALL BE DESIGNATED BY THE ENGINEER OF RECORD: 1: ALL EXTRUSIONS: ALUMINUM ALLOY #6005-T5 OR 6061-T6, (NOTE: SPLICE PLATE MATERIAL MAY BE EXTRUDED FROM ALUMT111.AM ALLOY 6061-T6, IF THIS ALLOY IS MORE READILY AVAILABLE). 2: FASTENERS: ALUMINUM ALLOY. # 2024-T4 & #7075-T6 DOUBLE CAD -PLATED STEEL, HOT DIPPED;GALVANIZIED STEEL OR 300-SERIES STAINLESS STEEL 3: MATERIAL UPGRADES (STRONGER OR HIGHER GRADE MATERIALS) CAN BE SUBSTITUTED AT ANY TIME. 4: NO EXPANSION BOLT MAY BE INSTALLED WITHIN 2" OF EDGE OF CONCRETE SLAB. 5: NON STRUCTURAL ALUMINUM SHALL HAVE A MINIMUM THICKNESS NO LESS THAN 0. 032" (KICKPLATES ETC.) 6: ALUMINUM IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PROTECTED WITH ALKALI RESISTANT COATING. 7: ALUMINUM IN CONTACT WITH WOOD SHALL BE PAINTED WITH TWO COATS OF HEAVY BODIED BITUMINOUS PAINT. 8: SELF MATING BEAMS (SMB) UP TO 8" TO BE FASTENED WITH BEAM STITCH SCREWS @ 16" 0/C. BOTH SIDES. (#12 SMS), FOR 9" & 10"' SELF MATING BEAMS (SMB) TO BE FASTENED WITH BEAM STITCH SCREWS @ 12" 0/C. =0 WPM � HOH..7� aC.1�aa�04 w d � ¢c �O�OF O aGaz 0� Cj Qmo �'c'n cn 00 w Ga cq a a H w '402V 17-4 (404-0 , o.7ep FREVIEW p�IAN CC� E- Cot) C®UN 13®CC SHEET NUMBER 1 OF 5 B=BEAM P=POST/PURLIN CR=CHAIR RAIL DJ=DOOR JAMB K/B=KAY-BRACE W/B=WIND BRACE 0 c � a PLAN VIEW ELEVATION A. 02 SIDE WALL 7'-10" ELEVATION B. 3 FRONT WALL DOUBLE 2" X 8" CARRIER BEAM, SEE CONNECTION DETAIL 5 ON PAGE 4 25'-2" 41'-0" MEMBER SCHEDULE MARK SIZE MAT. THICKNESS DESIGN W. F. B1 2% 8" ALUM. 0.072 0.224 PER ENG. P1 4"X 4' ALUM. 0.125 0. 125 PER ENG. P2 2"X 3" ALUM. 0.050 0.050 PER ENG. P3 2'X 6' ALUM. 0.050 0.116 PER ENG. P4 1"X 2' ALUM. 0.046 0.046 PER ENG. CR 2"X 3" ALUM. 0.050 0.050 PER ENG. DJ 2"X 2' ALUM. 0.046 1 0.046 PER. ENG. W/B 2"X 2" ALUM. 0.090 0.090 PER. ENG. K/B 3% 2" ALUM. 0.070 0,070 PER, ENG. 00 ) N W �rn c/) W U U�cm U W o V goy G] ­4 G. 00 Q cy Wrn 4#M � U W N 7 O.N N ® a a 00 m o , a U C.0 zM QMLo m U� o ti 00 H C-1 r� T `o 0 P4 a w 8'-0" w oo xlkoe SHEET NUMER 2OF5 SLPICE PLATE ALLOY: MIhil SPLICES SHOWN FOR MANSARD SPLICES, IDENTICAL 6061T6 OR 5052H32 S?1%-IFICATIONS FOR GABLE AND/OR STRAIGHT RBAM SPLICES •' o' 0 0 c •'� 00 0 o 0'; `0 0 0 0 1-0�,INT$RNAL SPLICE PLATE o 0 0 p , r SCREW POSITIONS NEAR MITER 1I2e�,'ce QER ���� 4oy � y0I0 OF TSCREW ACCWODATE FURLIN,MITE SPACEJOINT BETWEENYPAST� BE ERSTED ALONG MITER JOINT MAY 1 1/2- TO 2", MANfAIN MAXIMUM AND MINIMUM DISTANCES BETWEEMF Sam. EDGE DISTANCE FOR SCREWS: 3/4' MINIMUM SCREW SPACING: 5/8' SPLICE SPECIFICATIONS PER TABLE 109 BELOW TYPICAL ELEVATION FOR BEAM MITER SPLICE 1 (DETAIL MAY BE ROTATED FOR GABLE RIDGE SPLICE, AND MAY ALSO SERVE AS SPECIFICATIONS FOR A STRAIGHT SPLICE, MANTAIN PLATE AND CONNECTOR SPECIFICATIONS IN TABLE 109 FOR ALL) l BEAM SLPICE DETAILS SPLICE PLAT'; DI.- NTIO TABLI? 109 BEAM S #14 SMS PER SIDE PER END TOTAL #14 SMS PER SPLICE FASTENER SI?AGI's5 HICKNESS LENGTH HEIGTH NUMBER 0 SPACES HORIZONTAL VERTICAL 2X6X0.00X0. 120 SMB 3/16" sl6" 5 1/4" 14 56 3 3 2X7X0.05$X0.120 SMB 3/16" 6 1/4" 14 56 3 3 2X8X0.07:2X0.224 SMB 3/16" ,7.$" 7 1/4" 16 1. 64 4 3 2X9X0.082.X0.306 SMB ' 3/16" >IB' 8 1/4' 18 72 2X10X0.092X0.389 SMB 1/4" 2,0", 9" 22 88 4 6 IF DESIRED THE 3/8" BOLT SMBC>VVN IN THE WIND BRACING COI%WECTION . THAT SECURES THE 2 X 2 X O.S)OMEMBER TO THE U BRACKET AND THE 0- BRACKET TO THE ROOF BEAM CAN BE REPLACED WITH FOUR (4) $14 SMS. THE #14 SMS. MUST BE 112" FROM THE END OF THE U-BRACKET AND AT LAST 3/4' p (STAGGERED) FROM EACH OTl•MER. I 1/4" THROUGH ]30LT �-- U-8�4CKET � (CHANNEL) # 14 SMS TWO ON EACH SIDE OF BRACE ROOF BEAM 1/8" OD # 14 SMS TWO ON EACH SIDE OF BRACE 0 J�IINSIDE -BRACKET CHANNEL VIEW WITH 4 # 14 SriB`. Tb BEAM OR PERLIN) ALTERNATE CONNECTION OF CHANNEL (4) CtI 414 SMS KRU CHANNEL BEAM OR PERL N B TIBIU BEAR WEBINTO BA(1;10s PLATE (U-BRACES K�ET�C�FIANNBLl I� 1/4" THROUGH BOLT--�---`�� PURLIN OR EAVE RAIL 03. S!CRMN DIAGONAL BIND` ORAC � �114 ]CIS (TYPICAL) PosT/c6u1M1Rv [AG(WAL K-BRACE PARTIAL ELEVATION UPPER K—BRACE AT EAVE RAIL SCREEN SIDE K-BRACE SCREEN SIDE GUSSET PLATL' SPECIFICATIONS: 1) ALLOY 6063T6 OR 606116 OR 505202 2 MINT.MUN TFIICIWESS .090" ON TIIE OUT SIDE FLAT BAR AND, 0625 ON THE ANSIDE 112",gNNCLE PLATF, 3)SIZE'SUFFICIEN°f TO ACCOMODATE kld SMS AT A MINIMUM SPACING AND EDGE DISTANCE 1%2" 4)EpUAL NUMBER OF SCREWS INTO VERTICAL AND HORIZONTAL MEMBERS (INSIDE AND'OLfTSIDE) POST/COLUMN Cc ARTIAL ELEVA ION OWER �C—BRACE AT SOLE PLATE SCREEN SIDE CONNECTION (INSIDE) I' x 3' x.09375 ANGLE INTERIOR ANGLE( LENGTH EQUAL TO GElifl OF SCREEN SIDE PLATE). 2 i SSCTIOPI / K-BRACE NSIDE "Z" GUTTER INSERT,IN SUPER GUTiCER TO DOUSE CONNEC°iIMON, 10' LONG (0.125 THICK) EXTRUDED 'Z' 1u1F. GUTTER INSIiRT, TYP. CENTERED ON EACH ROOF BEAM, WITH (4) POUR # 14 TEKS THRll TOP LIP OF GUTTER 5' STRUCTURAL GUTTER COUNT.) a ; GUTTER INSERT b" SUPER GUTTER GUTTER ELEVATION TYP. 2X? SCREEN ROOF BEAU (MAY -BE FLAT OR SLOPED:c 4- 1/4" X 2 1/4' LAGS IN EACH 10' INCH INSERT AND AT 24' O.C. (MA):. SPACING) IN THE REST OF THE GUTTER (PILO]' DF:ILL FASCIA W/5/32' BIT TO AVOID SPLITTING) 1X2 SCRIck;N FRAME (TYP. ) 2'X3" X 0,125' �'(,T 2' LONG) WITH 3-INCH LEG AGAINST 1X2 CLT}', TALL NAYS FOUR (4) # 14 INTO SIDE OF RObF # ANDTW,9 (2) #14 X 2' LONG TEKS (PER e1t�.k' CLIP) TR3U GUTTER AND INTO CUTTER INS`E:HI:- .ONE ANGLE CLIP ON EACH SIDE OF EACH i`•3A11 2"X3"X 3/16" BY 2" LONG ANGLE EACH SIDE 3 EACH #14 S.M.S. EACH SIDE (3/4" 0. C. MIN. 3/8" DIA CONCRETE ANCHOR W/2" EMBEDMENT (MIN. ) 2" X 7" SMB COLUMN (SHOWN) (COLUMN SIZED PER TABLE) -- 2"X3" X 3/16" BY 3" LONG (MIN.) EACH SIDE 4 EACH #14 S.M.S EACH SIDE 1/4" TOP CON W/2 1/2" EMBEDMENT INTO CONCRETE M F0UMDATION FOR LOAD CONDITION 3 LOAD CONDITION 3 - CONNECTION UPLIFT CAPACITY = 2,400# CONNECTION SHEAR CAPACITY = 2,400# 2" X 2"/ 2" X 3" OR 4POST1INTO SCREWFROM SPLINESINSIDE OFFACE HOLLOW HORIZONTAL HOLLOW (GIRT). GIRT ( 1" EMBEDMENT MINIMUM.) - 2" x 3" PURLIN MAY BE SLOPING OR HORIZONTAL COLUMN (PER TABLE) SELF MATING POST OR HOLLOW POST. OVERLAP BEAM WITH 2- #12 S.M.S ON EACH SIDE 2 EACH #10 S. M. S X 4" LONG THRU EAVE RAIL 2X2 INTO SLOPING PURLIN SCREW SPLINES END WALL PERLIN CONNECTION DETAIL 2- 3/8" TOPCONS W/2 1/2" MIN. EMBEDMENT INTO CONCRETE .25"INTERNAL SLEEVE 4" X4" ALUM. POST 2- 3/8" THROUGH BOLTS W/1/2" WASHERS G)--Rc!�ale-:3 4"X 4" POST-SECTI = 1 - ROC1Q QCAee PERLIN FRONT VIEW #12 X 3/4" SMS @24, 0/C. TOP & BOTTOM - DBL., ALUM. BEAM P14 x3/4' SAIS @24" O/C. TOP AND BOTTOM STAGGERED. 4" X 16' X 1/8" ALUM.STRAP EACH SIDE. ALUM. POST -�--2- 3/8" THROUGH BOLTS .---a %1/2" WASHERS. DBL., BEAM FASTENIN'- 2"X 3" PERLIN WITH 1 #14 INTO BEAM @ 16" 3" ANGLE EACH SIDE BEAM WITH 3414 S.M.S.. INTO EACH BEAM. 0-BEAN- LTTACHMENT T(j FRONT WALL 2" X 3" PURLIN (MAXIMUM PURLIN SPACING T'-0" ) SCREEN ROOF BEAMS - SIZE PER TABLE / MAXIMUM SPACING 8' - 0" 0. C. ROOM BEAM 2" X 3" ANGI; ON EAQF avl OF BEAM 0)oik 3-#14 $.M -t INTO EACH BEAM. 'SIDE VIEW BEAM STITCH SCREW M 24" O.C.. TOP AND BOTTOM (#12 SMS TYPICAL) 4 EACH #10 X 2" LONG S.. M. S. (TYPICAL) INTO SCREW.BOSSES. 7 !,00F/SECTT0N� OF CONCEALED FASTENER COMNECTION