HomeMy WebLinkAboutProducts Review; NPE Series Tankless Water Heaters7A1.rILL4E,$S
�Nav�eN
Premium Condensing
Tankless Gas Water Heater
• Certified design according to ANSI Z21.10.3 - CSA 4.3-2015
standards for both indoor or outdoor installations (with
optional Outdoor Vent Kit)
• Compatible with 1/2" gas pipe up to a length of 24 ft*
("see Installation Manual for additional information)
• Compatible with 2" PVC vent up to 60 ft** and 150 ft**
using 3" PVC vent (•-with no elbows)
• Gas Input Ranges
NPE-150-120,000 to 18,000 BTUh
NPE-180-150,000 to 15,000 BTUh
NPE-210-180,000 to 19,900 BTUh
NPE-240-199,900 to 19,900 BTUh
• Hot Water Flow Rate Capacity (*based on 35*F temperature rise)
NPE-150 - 6.8 GPM
NPE-180 - 8.4 GPM
NPE-210 -10.1 GPM
NPE-240 -11.2 GPM
• Dual Primary and Secondary Stainless Steel Heat
Exchangers for optimum efficiency and durability
• Built-in Control Panel - allows adjustment of temperature
settings and displays the operating status and error codes
'(SOD IQI hT9F1OW -Technology - "A" models come included with
• built-in 0.5 gallon Buffer Tank and Recirculation Pump to provide
maximum comfort
• INTELLIGENT Preheating - recognizes hot water usage patterns
to intelligently provide hot water when needed (optional for "S" models)
• Temperature Options - available temperature settings for
Residential applications range from 98"F up to 140"17 with high
temperature Commercial mode capable of up to 1827
• Ready -Link Cascade Compatible for up to 16 units for increased
hot water production
• Common Vent Compatible - allows for cascade systems to use a
single exhaust and/or intake pipe for up to 8 units with the
use of the Common Vent Backflow Damper Collar Kit (#30014367A)
a
• Compatible with NavlLnk. Wi-Fi Control (#PBCM-As-oo1)
• Freeze Protection - maintains normal operation during freezing
ambient temperatures down to -5•17 (standard on all models)
• Uniform Energy Factor Ratings for NG and LP units
NPE-180A/210A/240A - 0.96 UEF (0.97 EF for Canada)
NPE-150S - 0.96 UEF (0.97 EF for Canada)
NPE-180S/210S/240S - 0.97 UEF (0.99 EF for Canada)
• Compatible with Natural Gas (NG) and Propane (LPG)***
r** requires installation of Included Field Conversion Kit by a qualified gas servicer)
• Approved for Installations on Mobile/Manufactured Homes
• Certified by CSA, NSF 5, AHRI, AB1953 CA Low Lead, SCAQMD
(Rule 1146.2 Type 1- Complies with 14 ng/J or 20 ppm NOx @ 3% 02)
• IS -Year Heat Exchanger and 5-Year Parts Warranty (Residential)****
8-Year Heat Exchanger and 5-Year Parts Warranty (Commercial)****
(**** see Navien Limited Warranty)
• Optional accessories are available (see below)
NPE Series Tankless Water Heaters
Specification Sheet
Sleek Design -Compatible with
2"PVC Vent and 1/2" Gas Pipe
Diagnosdo Up
Information b -- Down
Reset PowerOWOFF
Built -In Control Panel
with Diagnostics
Indoor and Outdoor
'Intake Cap —dill Venting Options
'Coup!ing-
r Pipe -
Non -Direct Vent (indoor)
Outdoor
Vent Cap--
Non -Direct Vent (outdoor)
OEM
cfA® CE0.TIFIED
Job Name:
Location:
Engineer.
Wholesaler:
Contractor:
Model No.:
Submitted to:
1
Remote Controller
NR-20DU
! (30009757A)
1 condensate
PltunbEasyValveSet(3/41
(30009323A-Lead Free)
(30012581 A - for Pipe Cover)
Neutralizer
(GXXX001322-SingleUniO
(GXXX001324-Upto6Units)
(GXXX001325-Up to16Units)
Ready-Ligk
Communication Cable
(GXXX000546)
OutdoorYetrtlOt
(30010604A)
i EldemalPumpWke
(GXXX001319)
3"VeMTermination
Caps andWagflanges
1 (GXXX3B73B)
NavieN
Premium Condensing
Tankless Gas Water Heater
Dimensions
NPE Series Tankless Water Heaters
Specification Sheet
Specifications
Item
NPE-1505
NPEA80A NPE-1805
NPE-210A I NPE-210S
NPE-240A I NPE-2405
Heat
Natural Gas
181000-
15,000-150,000 BTU/H
19,900-180,000 BTU/H
19,900-199,900 BTU/H
Capacity
120,000
Propane Gas
15,000-150,000 BTU/H
19,900-180,000 BTU/H
19,900-199,900 BTU/H
(Input)
BTU/H
Efficiency
UEF (for NG & LP)
0.96
0.96 10.97
0.96 10.97
0.96
0.97
Ratings
EF (Canada) (for NG a LP)
0.97
0.97 10.99
0.97 10.99
0.97
0.99
35"F(19°C)Temp Rise
6.8 GPM
(26 Um)
8A GPM (32 Um)
10.1 GPM (38 Um)
11.2 GPM (42 Um)
Flow Rate
45°F(25°C) Temp Rise
53 GPM
6.5 GPM (25 Um)
7.8 GPM (30 Um)
8.7 GPM (33 Um)
(DHW)
(20 Um)
67"F(36°C) Temp Rise
3.2 GPM
43 GPM
1 4.2 GPM
5.0 GPM
5.2 GPM
5.6 GPM
5.7 GPM
(12 Um)
(16 Um)
(16 Um)
(19 Um)
(20 Um)
(21 Um)
(22 Um)
Dimensions
17.3"(W) x 27.4"(H) x 13.2"(D)
55lbs
75lbs
67lbs
82lbs
75lbs
82lbs
75lbs
Weight
(25kg)
I (34kg)
(30kg)
(37 kg)
(34kg)
(37 kg)
(34kg)
Installation Type
Indoor or Outdoor Wall -Hung
Venting Type
Forced Draft Direct Vent
Ignition
Electronic Ignition
Water Pressure
15-150 PSI
Natural Gas Supply Pressure
3.5 in WC-10-5in WC
(from source)
Propane Gas Supply Pressure
8 in WC-13in WC
(from source)
Natural Gas Manifold Pressure
-0.04 in WC-
-0.04 in WC --0.84 in WC
-0.05 in WC--0.361n WC
-0.05 in WC--0.581n WC
(min -max)
-0.38 in WC
Propane Gas Manifold Pressure
-0.04 in WC-
-0.05 in WC --0.50 in WC
-0.10 in WC --0.66 in WC
-0.101n WC--0.78 in WC
(min -max)
-0.42 in WC
Minimum Flow Rate
OS GPM (1.9 Um), < 0.01 GPM (0.04 Um) option for'A"models*
Cold Water Inlet
3/4 In NPT
Connection
Sizes
Hot Water Outlet
3/4 in NPT
Gas Inlet
3/4 in NPT
Main Supply
120V AC, 60Hz
Power
Supply
Maximum Power
200W (max 2A), 350W (max 4A) with external pump connected
Consumption
Casing
Cold Rolled Carbon Steel
Materials
Primary Heat Exchanger: Stainless Steel
Heat Exchangers
Secondary Heat Exchanger: Stainless Steel
Exhaust
2" or 3" PVC, CPVC, Polypropylene
2" or 3" Specal Gas VentType BH (Class 11, A/B/C)
Venting
Intake
2" or 3" PVC, CPVC, Polypropylene
2" or 3" Special Gas VentType BH (Class II, AB/C)
Vent Clearances
0" to combustibles
Safety
Flame Rod, APS, Ignition Operation Detector, WaterTemperature High Limit Switch, Exhaust Temperature High Limit Sensor,
Devices
Power Surge Fuse
*Available for A"models configured/n an optional ComfortF/ow recirculation mode. Additional energyuse will occur when using recirculation.
Gas -fired, tankless, condensing, wall -mounted water heaters) shall be direct vent NPE Series models as manufactured by Navien, Inc and are certified by CSA Group to the
latest edition ofANSI standard Z21.10.31CSA 4.3. Water heater(s) shall have a 15 year limited Heat Exchanger warranty and 5-year limited Parts warranty (8 year Heat
Exchanger and 5-year Parts for Commercial use) per Navien Limited Warranty. Unit(s) shall be designed to burn natural gas and can be for use with propane when a Field
Conversion Kit is installed. Water heater(s) shall have a nominal flow rate capacity of GPM/GPH at °F rise with rated input of BTU/hr. Water
heaters) shall be vented with 2"PVC/CPVC vent pipe at a distance not to exceed 60' (or equivalent) with each elbow equal to 8' of pipe length or 3"PVC/CPVC vent pipe at a
distance of I50' (or equivalent) with each elbow equal to 5' of pipe length. Water heater(s) is rated for 150 PSI working water pressure and 300 PSI test pressure. Gas supply
pressure shall be 3.5" to 10.5" WCfor natural gas and 8.0" to 13.0"WC for propane. Unit(s) shall have a steel case, dual stainless steel heat exchangers, eco premixed burner,
negative pressure gas valve, dual ventvri, 3/4" inletgas connection, 3/4" brass inlet/outlet water connections, water holding capacity of 0.6 gallons for the NPE-1505,1.0
gallon for the NPE-180A model (0. 7gallonsfor NPE-1805 model),1.2 gallons for the NPE-210A/NPE-240A models (0.7 and 0.9 gallons for NPE-2105 and NPE-2405 models
respectively), and a condensate collector. The NPE-1505 model weighs 55lbs, the NPE-180A model weighs 75lbs (NPE-1805 weighs 671bs), and the NPE-210A/NPE-240A
models weigh 82 lbs (NPE-2105 and NPE-2405 weigh 75lbs). Unit(s) shall include features such as an adjustmentfor installations at high elevation, temperature lockout and
temperature options from 98-1207in 1 °Fintervals and 125-140°Fin 5°F intervals. The unit(s) shall include additional temperature options of 150-180°Fin 10°F intervals,
and 182°F for high temperature commercial applications. All NPE 'A"models shall include an internal circulation pump and 0.5gallon buffer tank. The water heater(s) shall
be controlled by an internal circuit board that monitors the inlet and outlet temperatures with installed thermistors, sensing and controlling flow rate to set point temperature
with air fuel ratio controls in order to maintain thermal combustion efficiency. Unit(s) shall include safetyfeaturessuch as flame sensor system, high limit sensors, overheat
prevention device, freeze protection mode, and fan motor rotation detector. Multi -system (cascade) applications that require 2 to 16 units shall be installed by connecting the
units using cable -only connections (Ready -Link). Cascade systems can be common vented with up to 8 units when a Common Vent Backflow Damper Collar Kit is
installed. The water heater(s) exceeds the energy efficiency requirements ofASHRAE 90.1-2013 and is listed by SCAQMD rule 1146.2 (Type I)for Low NOx that complies with
14 ng/j or 20 ppm NOx requirements @ 3% 02.
*Navien reserves the right to change specifications at any time withoutprlor notice
Navien, Inc. 20 Goodyear, Irvine, CA 92618 Ph: (949)420-0420 Fax: (949)420-0430 www.Navien.com Rev.11/16