HomeMy WebLinkAboutBuilding plans- 503010-Rev1 - Digital Sealed1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET —BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON —HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-140" SELF —DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH.
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
------------------------------------------------------------
L-- - - - - --
-0"
ON I US:
SUB —GRADE SOILS:
—TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION
CONCRETE:
—MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
—ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
—MINIMUM GRADE 40 STEEL
—REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
—THE REBAR IS BENT COLD
—THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6—BAR DIAMETERS: AND
—REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
—COVER:
—2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 11" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF }" FOR FINE
GROUT, AND 4" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 11" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATION:
—METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
"x5�" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES —
AND EVERY OTHER END —WALL POST
2" MIN —BASE RAIL
GRADE
TT�7 I -III -I I °
I I If 1 I I I
MINIMUM SOIL BEARING
CAPACITY 2,000 PSF(TYP.)
N
2,500 PSI 4"
CONCRETE SLAB
W.W.F. OR FIBER
(2) #5 REBAR @ 6" O.C.
CONTINUOUS WITH MINIMUM
12" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR DETAIL
2 5" PLAN VIEW DOOR FRAMING
J" RECESS
4" I
OOR WIDTri
ELEVATION VIEW
DOOR FRAMING
RECESS
•75' "T L6;DOOR WIDTH
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
L-MIN. 2,500 PSI 4" CONCRETE SLAB WITH W.W.F. (OR FIBER
MESH) AND 12"x12" REINFORCED FOOTER PERIMETER �12"x12" REINFORCED FOOTER
I
SWINGING 0
DOOR
I
0
ROLL —UP 0
DOOR
R
-------------------------------------i
w
0
0
1
ire ;144 0�� 9
.WL L ma7ak,19'k,
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
INO
HURRICANE SHELTER USAGE
INO
SQUARE FOOTAGE
11,500 SQ. FT.
REVISIONS
REV
DESCRIPTON
DATE
BY
1
12020 FBC, WINDSPEED
1/7/21
MTB
MTB
5/17/20
N. Header Canal Rd., Ft. Pierce
50'L X 30'W X 1O'H
. 9
ocENSF OLG�i
NO.64608 2
i �':• STATE OF ; •4
WFLORIDP •; ��1�`�`
to
IIIII
0
Digitally signed
by Matthew
z
Baldwin
Date: 2021.01.07
11:00:02-05'00'
z
Q
MattheW T. BaldWin P.E.
Florida License #64608
Sheet: CA-1 OF 4
0'
ROLL -UP
DOOR
MID END WALL
-11j" I 3'-11j" I 3'-11j" I 3'-1
12
3L--- -
D.C.
FRONT END WALL
SWINGING
DOOR
I . '-11 I 3'-11 " 3'-11f"-
-050,_0"
LEFT/RIGHT(MIRRORED) SIDE WALL
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SHA AUTHENTICATION CODE MUST BE VERIFIED
ON ANY ELECTRONIC COPIES
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II-B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/- 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,500 SQ. FT.
REVISIONS
REVI
DESCRIPTON
I DATE
I BY
1
12020 FBC, WINDSPEED
1 1/7/21
1 MTB
MTB
5/17/20
N. Header Canal Rd., Ft. Pierce
50'L X 30'W X 10'H
REAR END WALL
Un
_W
C�
z_
Q
L�
O.C. MAX.
Z
W
Li
Matthew T. BOIdWin P.E.
Florida License #64608
-11
1j"
3'-4"
3'-4"
3'-4"
10'-0"
0
Sheet: CA-2 OF 4
FRONT/REAR END WALL
FRONT END WALL
SWINGING
DOOR
LEFT/RIGHT(MIRRORED) SIDE WALL
�'s q1H �- F.;� mm,
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SHA AUTHENTICATION CODE MUST BE VERIFIED
ON ANY ELECTRONIC COPIES
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-150mph
REAR END WALL
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,500 SQ. FT.
REV I DESCRIPTON I DATE I BY 11
1 12020 FBC, WINDSPEED 1 1/7/21 1 MTB 11
MTB
5/17/20
N. Header Canal Rd., Ft. Pierce
50'L X 30'W X 1O'H
W
Z
W
Matthew T. BaldWin P.E.
W Florida License #64608
Sheet:
CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
S)#12 14xi" SELF —DRILLING
CREWS4
T /V \BASE RAIL NIPPLE
BASE f
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SC)REWS 14xi" SELF —DRILLING
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
POST TO BASE RAIL END POST TO BASE RAIL
CONNECTION CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
NON—STRUCTURAL HEADER OR
WINDOW RAIL TO POST DETAIL
INTERIOR
#12-14xi" SELF —DRILLING
SCREWS ® 10" O.C. MAX.,
3" MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS VERTICALL'
EXTERIOR
DOOR FRAME TO POST
CONNECTION
18"
IV
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
SINGLE OR DOUBLETS
HEADER
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR HEADER CONNECTION
WINDOW RAIL DETAIL DETAIL OPTION 1
2"x2"x2" 16 GA. ANGLE CLIP SECURED
WITH (4) #12-14xi" SELF —DRILLING
SCREWS
r-VARIES
MAX. SPACIN
r--3" MIN.
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xj" SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
kvA' M
STD. MAX. SPRUCING
VARIES
SIDE WALL ROLL —UP
DOOR/FRAME OUT
HEADER DETAIL
INSTALL PER MANUFACTURERS INSTRUCTIONS
,4"IPPLE TO
#14x1" SELF —DRILLING
SCREWS ® 6" O.C. MAX.
& 6" MAX. FROM CORNERS
ROLL —UP DOOR TO
POST CONNECTION
Design Pressures -
150 mph Basic Wind Speed
Zone
Roof
Wall
1
2n
2r
2e
3r
3e
4
5
15.0
16.7
15.0
15.0
21.1
21.1
21.1
23.9
-18.0
-41.3
-34.4
-18.0
-66.5
-57.1
1 -22.7
-28.3
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-140" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTIO
VERTICAL SHEATHING OPTION
1 "x2j" 16 GA.
U—CHANNEL BRACE, MIN.
24" UP TO 7' POST, MIIN
48" OVER 7' POST. MIN.
45' TO MAX. 60' FROM
HORIZ. (EXCLUDE
END —WALLS). SECURED
WITH (4)#12-14xi"
SELF —DRILLING SCREWS.
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
BOX EAVE RAFTER TO
POST CONNECTION DETAIL
NIPPLE
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SCREWS 14x" SELF —DRILLING WMIMANYMBE
SINGLE OR DOUBLETS
IPPLE
ASE I
HEADER CONNECTION DETAIL
OPTION 2
NI
TO T
TRUSSED RAFTER
CONNECTION DETAIL
MINIMUM 6" TS NIPPLE.
NIPPLE SECURED TO WALL
POST WITH (4)#12-14xj"
SELF —DRILLING SCREWS
POST TO TRUSS
CONNECTION
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 —R1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL12765.3—R5
SERIES 3100
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,500 SQ. FT.
REVISIONS
REVI
DESCRIPTON
I DATE
I BY
1
12020 FBC, WINDSPEED
1 1/7/21
1 MTB
u ".j - MTB
DATE: 5/ 17/20
LOCATI
0 N. Header Canal Rd., Ft. Pierce
SIZE: 50'L X 30'W X 10'H
J
Q Matthew T. Baldwin P.E.
Florida License #64608
ww
o Sheet: CA-4 OF 4
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES