HomeMy WebLinkAboutBuilding PlansDESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS 1. THE 2017 FLORIDA BUILDING CODE, SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CH. 23 WOOD. 2. AA ASM 35 & SPECIFICATIONS FOR ALUMINUM STRUCTURES, PART 1-A OF THE ALUMINUM DESIGN MANUEL PREPARED BY THE ALUMINUM ASSOCIATION, INC. WASHINGTON D.C. 2005 ED. 3. ASCE 7-10 & SE17 4. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 5. AC1318 CONCRETE REFRENCE MANUAL. WIND LOADS 1. BUILDING OCCUPANCY CATEGORY; PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: D 3. WIND LOADS PER FBC TABLE 2002.4 (MWFRS) VULT = 150 MPH & EXPOSURE = D FOR 20 X 20 X 0.013" MESH SCREEN HORIZONTAL PRESSURES ON WINDWARD SURFACES = .51 PSF HORIZONTAL PRESSURES ON LEEWARD SURFACES = 40 PSF VERTICAL PRESSURES ON SCREEN SURFACES = 14 PSF VERTICAL PRESSURES ON SOLID SURFACES = 42 PSF FOR 18 X 14 X 0.013" MESH SCREEN; APPLIED FACTOR = .88 FOR ALLOWABLE STRESS DESIGN, APPLIED FACTOR = .6 FOUNDATION DESIGN FOOTING SIZE EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. SPECIFICATIONS THE FOLLOWING SPECIFICATIONS ARE APPLICABLE TO THIS PROJECT: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: a. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS_: i. PORTLAND CEMENT TYPE 1 - ASTM C 150 ii AGGREGATES - LARGE AGGREGATE 3/4 MAX. - ASTM C 33 iii. AIR ENTRAINING +/- 1 %- ASTM C 260 iv. WATER REDUCING AGENT - ASTM C 494 v. CLEAN PORTABLE WATER vi. OTHER ADMIXTURES NOT PERMITTED b. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 ii. WELDED WIRE FABRIC - ASTM A185 c. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. d. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. e. MOIST CURE OR POLYETHYLENE CURING PERMITTED. f. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. g. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. WHEN PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT 3. WHEN APPLICABLE FOR NEW SLAB ADDITION TO ADJACENT DRILL & EPDXY #5 X 8" REBAR INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) 48" O.C. TYP. ALL LOCATIONS 4. WHEN APPLICABLE FOR NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 6" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHERWISE NOTED. ALUMINUM SPECIFICATIONS 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE NOTED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH # 12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. 5. 1 "X2" & 1 "X3" NON STRUCTURAL MEMBERS MAY BE USED INTERCHANGEABLY. FASTENER SPECIFICATIONS 1. FASTENERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG. SPECIFICATIONS) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, FASTENERS AND SCREENS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1 /4" X 3-1 /2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1 /4" X 2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14 X 2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE # 10 X 1-1 /2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE 1 "X2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5-0" IN HEIGHT. MISCELLANEOUS 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE 2 x 4 SMB: 2"x4"x0.044"x0.100" UNLESS OTHERWISE INDICATED. RESPONSIBILITIES 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND ENSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE N141TH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2" x 2" x 0.050" 2 x 3: 2" x 3" x 0.050" 2 x 4: 2" x 4" x 0.050" 2x5:2"x5"x0.050" OPEN BACK SECTIONS 1 x2: 1"x2"x0.044" 1 x3: 1"x3"x0.045" SNAP SECTIONS 2x2SNAP: 2"x2"x0.045' 2 x 3 SNAP: 2" x 3" x 0.059 2 x 4 SNAP: 2" x 4" x 0.045" SELF MATING (SMB) 2 x 4 SMB: 2" x 4" x 0.046" x 0. 100" 2x5SMB: 2"x5"x0.050"x0.116" 2 x 6 SM B: 2" x 6" x 0.050" x 0. 120" 2 x 7 SMB: 2" x 7" x 0.055" x 0.120" 2 x 8 SMB: 2" x 8" x 0.072" x 0.224" 2x9SMB: 2"x9"x0.072"x0.224" 2 x 9(H) SMB: 2" x 9" x 0.082" x 0.306" 2 x 10 SMB: 2" x 10" x 0.092" x 0.374" DETAIL A a G( 6-0 i REV. M E® FOR CODE COMPLIANCE ST. LUCIE COUNTY �C1cC % I 2� FILE C®PY 0\I1111111111�����///// =Z •co o O O. J :W 0 = co O =y0z . ......... 2XZX125ANGLE CLIP ANGLE W/ #I4 Ie T-IRUANGLELEG INTO BEAM E, SIDE IYP. SEETABLEFOR QUANTITY FASTENER NOTES: / MAMA N 1/2'SEPAPATION BETWEEN FASTENERS. PER PLAN MAINTAIN 3/8' MIN FASTENER SEPARATION FROM EDGE FASTENERS MAY BESTACG6ABJ TO ENSURE PROPER QUANRTY PERMITTED (PATTERN MAY APPEAR DIFFERENT 1AN GLECLry W/ FROM ILUUSTRAPON) / 10' XT GA LAMA Taa TNRUANGLE U. INTO HMTWALL BEAM TO WALL w/1/S"RECEIVER TABLE BEAM SIZE QUANTITY/SIZE LEG TO BEAM E/S QUANTITY TAPCON TO HOST (INTERNAL) 3 TOP VIEW 2X4 4 #12 - 2 #16 l) l) 2 1 4" LAGS I) / BEAM PER PLAN 2x5 (5)#12-(3)— 1211/4"LAGS (2X7SMB ILLUSTRATED) 2X6 (5) #12 - (3) #16 (3)1/4"LAGS V 2%2X125' ANGLE CLIP W/ 2X7 (6) #14 - (4) #16 (3) 1/4"LAGS M plw/4" THRUANGLEUE P1T0 BEAM EA.SIDETYP. 2%8 (7) #14 - (4) #16 (4) 1/4' LAGS H / j o Sff TABLE fdR QVANRIY 2X9 (8) #14 - (5) 916 (4) 1/4"LAGS Q ZXZXI2S ANGtECIPw/ 2X30 1 (9) #14 - (6) #16 (5)1/4"LAGS 2 THWAN UELE UGS�Swc. 1HRUANGLE LEG HTO HOST WALL SIDE VIEW BEAM TO WOOD HOST WALL CONNECTION SCALE: N.T.S. i— 8'-01f i (2) ROWS OF 3/4" SMS QUANTITY/ SIZE = SEE TABLE I O G CARRIER Q PER PLAN ZXI-1/2'Al/E'REC. CHANNEL CUT TO FIT H) ROWSOF"f'SMS QUANTITY/ SIZE SEETABLE BEAM TO COLUMN w/ RECEIVER TABLE BEAM SIZE QUANTITY/ SIZE LEG TO BEAM E/S QUANTITY/SIZE TO COL. INTERNAL 2X4 (4) #12-(2) #16 (8) #12-(3) #16 2X5 (5) #12-(3) #16 (10) #12-(3) #16 2X6 (5) #12-(3) #16 (10) #12-(4) #16 2X7 (6) #14-(4) #16 (12) #14-(4) #16 2X8 (7) #14-(4) #16 (12) #14-(6) #16 2X9 1 (8) #14-(5) #16 (14)#14-(6)#16 2X10 (9)#14-16)#16 (14)#14-(7)#16 BEAM TO COLUMN CONNECTION DETAIL SCALE: N.T.S. HOST 36" O/H r-------------------------------- I' 3" X .032" X 11-13 0, COMPOSITE PANELS 3105-H 154 1/4"-1' SLOPE (MIN.) (FL.# 21443-R1) r.. _ r 0-36" 0/1-1 (MAX.) 32'-011 BRICK PAVER DECK OPTION OS SODDED GRADE /\ 12•\ MIN. 12" (2) 05 BAR CONTINUOUS FOOTING NOTES I. PROVIDE 1-1/2' COVERAGE TOP, SIDES, BOTTOM AND I- BETWEEN ADJACENT REBAR LAPS. 2. PROVIDE MIN. 3" COVERAGE OF REBAR FOR ALL CONCRETE IN CONTACT WITH THE EARTH. 3. FOOTING CONCRETE SHALL BE MIN. 3000 PSI AT 28 DAYS 4. FOOTING REINFORCEMENT SHALL BE MIN. GRADE 60 5. PROVIDE POSITIVE DRAINAGE AWAY FROM STRUCTURE TO CITY / CO. REQUIREMENTS 6. PROVIDE 2500 PST BEARING (TYPICAL) UNDER FOUNDATION 7. SEE GENERAL NOTES FOR TYING INTO EXISTING FOUNDATIONS 8. SEE GENERAL NOTES FOR ADDITIONAL CONCRETE INFORMATION & SPECS. 12"xl2" RIBBON FOOTING SCALE: NTS HOST 12" O/H I-71-0 1 1 �J -------------- SLOPE ,I 0 w I z = CO m L U r-I I M LL x a � u, m''�� o j Fw-• = O �' I CD Ln N Ln 0 N,1 0 O x X � ,i Cy')-j'i x � m O 2X5SMB C.B.', Ln i0 - 0 IN O -0 I� N ' i0 co co a a 2X4 PB co a m Cl- m a CID a N N N N N x N N on 1X2 TYP. 6'-4 3 —�t� I —6'-4 3—t-6'-4 I 3---6'-4 31I 1X2 1 ir1 2X4 PB N N _ x x ;t 2X4 PB LT'1 2X4 PB N LV N x N O N � 2X3 PB 0 iIo 1X2 I--- 8' —011 12"X12" FOOTER \�\\\\11llllllllr//r,/, a .�� 4�Z- �2 _ LLI C ch v> ' z i 0 W r/111111111\\ U � 0 fl I REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC ALE C®Py RECEIVED DEC 0 7 2020 Permitting Department St. Lucie County 024 FLASHING SEALED TO *EXTRUDED P.) #14x1/7'S.M.S. W/ INTEGRAL 3/4" 0 WASHER AND NEOPRENE GASKET @ 12' O.C., TOP & BOTTOM. IF CLEARANCE PROHIBITS INSTALLATION OF TOP FASTENERS USE # 14x4"S.M.S. W/ 1-1/4"0 FENDER WASHER AND NEOPRENE GASKET @ 12'O.C. (3) PER PAN FOR PANS OR BRAKE -FORMED ROOF HEADER R RECEIVING CHANNEL (0.044" MIN. THICKNESS) ITH MIN. 1-1 /2' BEARING LEG. HOST STRUCTURE 1 /4" 0 x 2-1 /2" LONG WOOD LAG SCREW OR MASONRY OR WOOD 1/4" 0 x 2-1/4" LONG MASONRY ANCHORS @ 24" O.C. MAX. ROOF PANEL ATTACHMENT - MASONRY SCALE: N.T.S. c�co 2Uj EXISTING RAFTER OR TRUSS # 14x4" S.M.S. w/ 1-1/4" 0 FENDER WASHER = O O w p O < #14x1 /7' S.M.S. W/ INTEGRAL 3/4"0 O WASHER AND NEOPRENE GASKET AND NEO-PRENE GASKET @ 17' O.C. O C� ; V O O 0 @ 17' O.C., TOP & BOTTOM # 12 X 9/16" W/ 5/8" NEO-WASHER = - O _ O (3) PER PAN FOR PANS (3) PER PAN FOR PANS EXTRUDED OR BRAKE -FORMED ROOF HEADER OR RECEIVING CHANNEL (0.044" MIN. THICKNESS) ROOF PER PLAN COVER END OF PANEL �� '� EACH EACH RAFTSECUREER TAIL W/ WITH MIN. 1-1/2' BEARING LEG. / Lij (1)A /40 0 x 4" LONG / PAN HEAD LAG SCREWS BEFORE ATTACHING REC. CHANNEL (1) 1 /4" 0 x 2" LAG SCREW @ 24" O.C. ENTIRE LENGTH OF RECEIVING CHANNEL , I I I I I I I1111��\\ U ROOF PANEL ATTACHMENT -WOOD FRAME 3"X7'X.050"MIN. (SEE PLAN) r , N cc SCALE: N.T.S. O Lo J ROOF PANEL TO CARRIER BEAM CONNECTION SCALE: N.T.S. _., I— M ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL w/(4) # 1 Ox.75" INTO GIRT OR PURLIN & (2) #14x.75" 4 #lOxl-1/7' SMS INTO INTO BEAM OR UPRIGHT 0.062 ANGLE () CLIPS MAYBE USED SCREW BOSSES PURLIN MEMBER UPRIGHT, BEAM -SNAP, SELF MATING, OR HOLLOW DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE: NTS 1/8'k7'x2"x ANGLE SELF MATING OR 5032 H-32 ANGLE � SNAP SECTION TYP. (2) - # 12 SMS INTO COLUMN 1/4" MASONRY ANCHOR EACH 1' 12' O.B. BASE PLATE-TYP. ANGLE - EACH SIDE COL. o 0 0 0 1-1 /4" MIN. CONC. ANCHOR EMBEDMENT a 2-1/4" MIN. CONC. ANCHOR EMBEDMENT SECONDARY ANGLE ° d ° 3000 PSI CONC. SLAB/ FTG. 6x6-1Ox10 WWM OR FIBERMESH 1/4" MASONRY ANCHOR AT EACH ANGLE 2-1/4" MIN. CONC. ANCHOR EMBEDMENT SECONDARY ANGLE a e 7' MIN. INCREASE DISTANCE WHEN GREATER THAN 2X4 ° UPRIGHT IS USED SIDE VIEW �(2) - # 12 SMS 1 /4" TAPCON XL (RED HEAD MFG. OR EQUAL) //i//i////// 2 @ lx2 BASE 2 @ SLAB (BEYOND) A'. 3000 PSI CONC. SLAB/FTG. 6x6-1Ox10 WWM FRONT VIEW OR FIBERMESH DETAIL "B" - 2"x4" OR LARGER SELF MATING UPRIGHT TO DECK DETAILS SCALE: NTS 1'52" BASE PLATE ANCHORED TO CONC w/ 1/4" MASONRY ANCHOR 6' MAX EACH SIDE OF POST AND 24" O.C. MAX 1-IX CONC. EMBEDMENT TYP NOTE WHERE PAVERS ARE PRESENT USE 5/16' TAPCON XL (RED HEAD MFG.) MASONRY ANCHORS TO PENETRATE UNDERLYING CONCRETE FOOTING 2-1/4" (MIN.) ANCHORING UPRIGHT TO FOUNDATION NOTES: l .- IF PAVERS ARE PRESENT, CONCRETE ANCHORS SHALL PENETRATE INTO FOOTING 2-1/4- MIN. (TYP.) 2.- WHEN FASTENING TO WOOD USE 1 /4" GALV. LAG SCREW IN LIEU OF CONC. ANCHORS AND ENSURE 2-1/4" MIN. PENETRATION INTO STRUCTURAL FRAMING BENEATH (TYP.) 3.- NO SECONDARY ANGLE REQUIRED FOR 2X3 UPRIGHTS OR DOOR JAMBS. REVIEWED FUR FASTEN TOP OF HEADER TO INTERSECTING COPL5AICE ��eLUCIE ®� MEMBER (4) # 10 SMS (INTERNAL) 2" MIN. INTO SCREW BOSS OF INTERSECTING MEMBER Bocc 3X2 EDGE BEAM 252k3'kl/8" ANGLE W/ it II (2) # 10 x 3/4" SMS INTO EDGE BEAM (2) # 10 x 3/4" SMS INTO POST (NO ANGLE REQUIRED UNLESS EDGE CENTRAL COLUMN li li BEAM SPLICED OR CORNER ATTACHMENT) SIZE PER PLAN II II III CORNER COLUMN SIZE PER PLAN -\ C 2"X2"Xl/8" ANGLE CUT TO FIT W/ (3) 412x.75" EACH LEG EACH SIDE OF UPRIGHT TYP. SEE UPRIGHT TO DECK CONNECTION DETAIL 2X3/ 2X4 COL. TO 2X3/ 2X4 EDGE BEAM CONNECTIO�TILE®Pv SCALE: N.T.S. #14x4" S.M.S. w/ 1-1/4" 0 FENDER WASHER AND NEO-PRENE GASKET @ 12" O.C. 1 • S.M.S. w/ ¢ FENDER WASHER 2"X2"Xl/8" ANGLE CUTTO FIT AND#14N GASKET O.C. AND NEO-PRENE GASKET @ w/#12x.75" @ 1" SPACING MAX. LL FOR NON -LOAD BEARMG WALLS:- (4) PER LEG (MIN.) EACH SIDE TYP. (4) ALTERNATELY CLIPS MAYBE USED 1/4" DIA. TAPCON 6" FROM ENDS PRIMARY UPRIGHT PER PLAN SIDE WALL UPRIGHT 24" O.C. MAX 1-1/4" EMBEDMENT 10 PER PLAN INTO UNDERLYING CONC. ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNELw/(4) #10x.75" INTO GIRT OR PURLIN & (2) #14x.75" INTO BEAM OR UPRIGHT 0.062 /- (4) #1Gx2" SMS INTO SCREW BOSSES CLIPS MAYBE USED MAYBEANGLEUSED CHAIR RAIL PER PLAN 'ANGLE REQUIRED ONE SIDE ONLY AT CORNER AND DOOR OPENINGS WHERE KICK PLATE IS INDICATED FASTEN W/ #10 X 9/16" SMS 6" FROM CORNERS 18" IN FIELD (2) #lOx2" SMS INTO 1/4" DIA. TAPCON 6" FROM ENDS OR FASTEN W/ #8 X 9/16" SMS SCREW BOSSES OR 24" O.C. MAX 1-1/4" EMBEDMENT 2" FROM CORNERS8" IN FIELD CLIPS MAY BE USED INTO UNDERLYING CONC. FOUNDATION PER PLAN SCREEN ROOM END WALL DETAIL SCALE: N.T.S.