REVIEW COMMENTS
Page 1
Owner(s):
Cindy M Powers / Mark T Powers
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 215 Block:
APPLICATION INFORMATION
Permit Number: 1804-0329 Stories:
Permit Type: BUILDING RESIDENTIAL (SFR UP TO 2 FLOORS)
CONTRACTOR INFORMATION
Contractor Name:
Business Name:
Business Addr:
City / State / Zip:
REVIEWS AND COMMENTS
Review Type
DOCUMENTS MISSING
4/12/2018 Comment:
4/12/2018 Comment:
4/12/2018 Comment:
V'14'116/2018 Comment:
/ ENVIRONMENTAL REVIEW
Comment:
✓ FRONT COUNTER REVIEW
Comment:
✓ PERMIT ON HOLD
Comment:
PLANS EXAMINER REVIEW
Comment:
4/24/2018
✓ 4/24/2018 Comment:
✓ 4/24/2018 Comment:
Automatic Sprinkler System? No
Fax, Number:
Email:
Status Reviewed By Date Started Date Completed Date Released
PENDING Lashahna Ingram
NEEDS PLUMBING SUB AGREEMENT
NEEDS ELECTRICAL SUB AGREEMENT
NEEDS HVAC/MECH SUB AGREEMENT
A VEGETATION REMOVAL OR EXEMPTION PERMIT IS REQUIRED AT TIME OF PICK UP. PLEASE SUBMIT
THE APPLICATION AS SOON AS POSSIBLE.
COMPLETE Ben Balcer 4/18/2018 4/19/2018 4/19/2018
COMPLETE
Lashahna Ingram
4/12/2018
4/12/2018
4/12/2018
COMPLETE
Lydia Galbraith
4/16/2018
4/19/2018
4/19/2018
INCOMPLETE William Durden 4/24/2018
• LINE SEVEN ON THE ENERGYY d CORRECT, MULTIPLE TYPES AND SIZES OF GLAZED
OPEK,DN PUNS. PL ASE �, :R� T ENERGY CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA
BUILE ENNE GY CON EIR1lATION 6TH EDITION.
LBM►•l'`T� ENERGY PERFOMANCE SHEETS OR SUBMIT A THE NFRC FENSTRATION
MANRE CERTIFICATE FOR THE U-FACTOR AND THE SHGC FOR EACH GLAZED OPENING
SHOWING COMPLIANCE WITH CHAPTER 4 SECTION 402.1.1 OF THE 2017 ENERGY CODE SIXTH EDITION.
• PLEASE CLARIFY LINE 9 AND 10 ON THE ENERGY CALC'S. INSULATION ON PLANS NOT MATCH ENERGY
CALC'S. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
f
Planning & Development Services
Building S Code Regulation Division
2300_Virgin ta Avenue
Fort Pierce, FL. 34982
Phone,4772)462-2172 Fax:(772)462.6443
REVIEW COMMENTS
2
Comment: • PLEASE CLARIFY LINE.9 ON THE ENERGY CALC'S. WOOD WALL INSULATION ON PLANS NOT SHOWN ON
4/24/2018
THE ENERGY CALC'S. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
Comment: • PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION BLOCK CONTAINING
THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN PROFESSIONAL SPECIFYING THE
4/24/2018
CUBIC VOLUME OF THE CONDITIONED SPACE. SEE CHAPTER 1 SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE.
Comment: • PLEASE SHOW FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX FOR WALL AND CEILING
4/24/2018
FINISHES IN ACCORDANCE WITH SECTION 302.9 OF THE 2017 FLORIDA RESIDENTIAL CODE.
Comment: • PLEASE SHOW THE FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR THE INSULATION AS
4/24/2018
REQUIRED IN SECTION 302.10 OF THE 2017 FLORIDA RESIDENTIAL CODE.
Comment: • PLEASE ADD TO THE PLANS THE CLIMATIC AND GEOGRAPHIC DESIGN CRIERIA WEATHERING AND
4/24/2018
TERMITE:AREA IN ACCORDANCE WITH TABLE 301.2.(1)
Comment: • PLEASE FURNISH DESIGN CRITERIA INCLUDING BUT NOT LIMITED TO WIND LOAD,DESIGN PRESSURES,
4/24/2018
EXPOSURE CATEGORY, RISK CATEGORY AND DESIGN CODES IN ACCORDANCE WITH SECTION 301 OF
THE FLORIDA RESIDENTIAL CODE
4/24/2018
Comment: • PLEASE PUT ON THE PLANS THE SOIL DENSITY OR SUBMIT GEOTECHNICAL REPORT IN COMPLIANCE
WITH R401 OF THE 2017 RESIDENTIAL BUILDING CODE.
Comment: • PLEASE FURNISH A INTERIOR STAIR DETAIL SHOWING STAIR WIDTH, HEADROOM, RISER HEIGHT,
4/24/2018
TREAD DEPTH, HAND RAIL HEIGHT AND GRIP SIZE IN ACCORDANCE WITH SECTION R311.7 AND R312 OF
THE 2017 FLORIDA RESIDENTIAL CODE
Comment: • PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLICATE REVIEWED AND
APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH 61 G15-30.005 OF THE FLORIDA
,/4'/24/2018
ADMINISTRATIVE CODE
Comment: • PLEASE FURNISH TRUSS ENGINEERING IN DUPLICATE PER 107.2.1 OF THE 2017 FLORIDA BUILDING
4/24/2018
CODE
Comment:
• STRUCTURE IS LOCATED IN FLOOD ZONE AE. PLEASE SHOW ON PLANS THE FINISH FLOOR
4/24/2018
ELEVATIONS SO THE LOWEST ENCLOSED AREA FINISHED FLOOR CAN BE DETERMINED ALONG WITH ANY
REQUIREMENTS OF SECTION R322 OF THE 2014 RESIDENTIAL CODE AND SECTION 107 OF THE 2017
FLORIDA BUILDING CODE.
Comment:
PLEASE ADD SECTION R322.3.6 CONSTRUCTION DOCUMENTS TO THE PLANS. THE CONSTRUCTION
4/24/2018
DOCUMENTS SHALL INCLUDE DOCUMENTATION THAT IS PREPARED AND SEALED BY A REGISTERED
DESIGN PROFESSIONAL THAT THE DESIGN AND METHODS OF CONSTRUCTION TO BE USED MEET THE
APPLICABLE CRITERIA OF THIS SECTION.
4/24/2018 Comment:
PLEASE SHOW ON THE PLANS THAT THE PROTECTION OF MECHANICAL, PLUMBING, AND ELECTRICAL
MET THE RFOI 1IREMENT'S OF 322.1.6.
4/24/2018 Comment:
PLEASE SHOW ON THE SURVEY THE LOCATION OF THE FLOOD ZONE'S AND FLOOD WAYS. SEE SECTI
107 OF THE 2017 FLORIDA BUILDING CODE, AND SECTION 7.04.01 (D) OF THE LAND DEVELOPMENT COD
Response:
Flood zone has been labeled and Floodway Boundary line has been.added.
Comment:
STRUCTURE IS LOCATED IN A FLOODWAY PLEASE SUBMIT A HYDROLOGIC AND HYDRAULIC ANALYSES
4/24/2018
TO SHOW NO INCREASE IN FLOOD LEVELS WITHIN THE COMMUNITY DURING THE OCCURRENCE OF THE
BASE FLOOD DISCHARGE. IN ACCORDANCE WITH 44 CFR 60.3 - FLOOD PLAIN MANAGEMENT CRITERIA
-
FOR FLOOD -PRONE AREAS AND SECTION 322.1 OF THE 2017 FLORIDA BUILDING CODE.
Response:
Hydrologic and Hydraulic analysis has been included in this submittal.
4/24/2018
Comment:
DESIGN CRITERIA ON PAGE CVR DOES NOT MATCH THE DESIGN CRITERIA ON PAGE A001. PLEASE
CORRECT AND SUBMIT SIGNED AND SEALED DRAWINGS IN, DUPLICATE. SEE SECTION 107 OF THE 2017
FLORIDA BUILDING CODE.
Comment:
WINDOW AND DOOR SCHEDULE IS INCOMPLETE ON THE PLANS. NO INSTALL ATION METHOD SPECIFIED.
4/24/2018
• SUBMIT THE PRODUCT APPROVALS, IN DUPLICATE OR PRODUCT REVIEW AFFIDAVIT COMPLETE WITH
FLORIDA PRODUCT APPROVAL OR N.O.A. NUMBER WITH INSTULATION INSTRUCTIONS AND SIGNED
SEALED AND DATED BY THE DESIGN PERSON OF RECORD FOR ALL COMPONETS AND CLADING IN
ACCORDANCE WITH 553.842 OF THE FLORIDA STATUTES. PRODUCT APPROVAL'S MUST BE HIGHLIGHTED
OR MARKED IDENTIFYING THE OPENING OR CLADDING COMPONENTS, WITH FASTENERS AND DESIGN
4/24/2018
PRESSURES.
Comment:
• PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
SUBMITTED DOCUMENTS. ADDITIONAL REVIEW.MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS.
ZONING REVIEW
COMPLETE Lydia Galbraith 4/16/2018 4/19/2018 4/19/2018
Comment:
`t�,�taGGPi �Orysr
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462-2172 Fax:j772)462-6443
REVIEW COMMENTS
4/24/2018 Comment:
• PLEASE CLARIFY LINE 9 ON THE ENERGY CALC'S. WOOD WALL INSULATION ON PLANS NOT SHOWN ON
THE ENERGY CALC'S. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
Comment:
• PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION BLOCK CONTAINING
4/24/2018
THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN PROFESSIONAL SPECIFYING THE
CUBIC VOLUME OF THE CONDITIONED SPACE. SEE CHAPTER 1 SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE.
4/24/2018 Comment:
- PLEASE SHOW FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX FOR WALL AND CEILING
FINISHES IN ACCORDANCE WITH SECTION 302.9 OF THE 2017 FLORIDA RESIDENTIAL CODE.
4/2412018 Comment:
• PLEASE SHOW THE FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR THE INSULATION AS
REQUIRED IN SECTION 302.10 OF THE 2017 FLORIDA RESIDENTIAL CODE.
4/24/2018 Comment:
• PLEASE ADD TO THE PLANS THE CLIMATIC AND GEOGRAPHIC DESIGN CRIERIA WEATHERING AND
TERMITE AREA IN ACCORDANCE WITH TABLE 301.2.(1)
Comment:
• PLEASE FURNISH DESIGN CRITERIA INCLUDING BUT NOT LIMITED TO WIND LOAD,DESIGN PRESSURES,
4/24/2018
EXPOSURE CATEGORY, RISK CATEGORY AND DESIGN CODES IN ACCORDANCE WITH SECTION 301 OF
THE FLORIDA RESIDENTIAL CODE
4/24/2018 Comment:
• PLEASE PUT ON THE PLANS THE SOIL DENSITY OR SUBMIT GEOTECHNICAL REPORTIN COMPLIANCE
WITH R401 OF THE 2017 RESIDENTIAL BUILDING CODE.
Comment:
• PLEASE FURNISH A INTERIOR STAIR DETAIL SHOWING STAIR WIDTH, HEADROOM, RISER HEIGHT,
4/24/2018
TREAD DEPTH, HAND RAIL HEIGHT AND GRIP SIZE IN ACCORDANCE WITH SECTION R311.7 AND R312 OF
-
THE 2017 FLORIDA RESIDENTIAL CODE
Comment:
•PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLIDREVIEVVEDA-4124/2018
APPROVED BY THEDESIGN PERSON OF RECORD IN ACCORDANCE WITH 61G15-30.ADMINISTRATIVE
CODE
4/24/2018Comment:
• PLEASE FURNISH TRUSS ENGINEERING IN DUPLICATE PER 107.2.1 OF THE 2017 F
CODE
Comment:
• STRUCTURE IS LOCATED IN FLOOD ZONE AE. PLEASE SHOW ON PLANS THE FINISH FLOOR
4/24/2018
ELEVATIONS SO THE LOWEST ENCLOSED AREA FINISHED FLOOR CAN BE DETERMINED ALONG WITH ANY
REQUIREMENTS OF SECTION R322 OF THE 2014 RESIDENTIAL CODE AND SECTION 107 OF THE 2017
FLORIDA BUILDING CODE.
Comment:
PLEASE ADD'SECTION R32Z.3.6CONSTRUCTiON DOCUMENTS TO THE PLANS. THE CONSTRUCTION
4/24/2018
DOCUMENTS SHALL INCLUDE DOCUMENTATION THAT IS PREPARED AND SEALED BY A REGISTERED
DESIGN PROFESSIONAL THAT THE DESIGN AND METHODS OF CONSTRUCTION TO BE USED MEET THE
APPLICABLE CRITERIA OF THIS SECTION.
4/24/2018 Comment:
PLEASE SHOW ON THE PLANS THAT THE PROTECTION OF MECHANICAL, PLUMBING, AND ELECTRICAL
E IREMENTS OF 322.1.6.
4/24/2018 Comment:
PLEASE SHOW ON THE SURVEY THE LOCATION OF THE FLOOD ZONE'S AND FLOOD WAYS. SEE SECTI
107 OF THE 2017 FLORIDA BUILDING -CODE, AND SECTION 7.04.01 (D)" OF THE LAND DEVELOPMENTCOD
Response:
Flood zone has been labeled and Floodway Boundary line has been added.
Comment:
STRUCTURE IS LOCATED IN A FLOODWAY PLEASE SUBMIT A HYDROLOGIC AND HYDRAULIC ANALYSES
/2018
TO SHOW NO INCREASE IN FLOOD LEVELS WITHIN THE COMMUNITY DURING THE OCCURRENCE OF THE
L
BASE FLOOD DISCHARGE. IN ACCORDANCE WITH 44 CFR 60.3 - FLOOD PLAIN MANAGEMENT CRITERIA
FORFLOOD-PRONE AREAS AND SECTION 322.1 OF THE 2017 FLORIDA BUILDING CODE.
Response:
Hydrologic and Hydraulic analysis has been included in this submittal.
4/24/2018
Comment:
DESIGN CRITERIA ON PAGE CVR DOES NOT MATCH THE DESIGN CRITERIA ON PAGE A001. PLEASE
CORRECT AND SUBMIT SIGNED AND SEALED DRAWINGS IN DUPLICATE. SEE SECTION 107'OF THE 2017
FLORIDA BUILDING CODE.
Comment:
WINDOW AND DOOR SCHEDULE IS INCOMPLETE ON THE PLANS. NO INSTALL ATION METHOD SPECIFIED.
4/24/2018
• SUBMIT THE PRODUCT APPROVALS, IN DUPLICATE OR PRODUCT REVIEW AFFIDAVIT COMPLETE WITH
FLORIDA PRODUCT APPROVAL OR N.O.A. NUMBER WITH INSTULATION INSTRUCTIONS AND SIGNED
SEALED AND DATED BY THE DESIGN PERSON OF RECORD FOR ALL COMPONETS AND CLADING IN
ACCORDANCE WITH 553.842 O��rTH I UTES. PRODUCT APPROVAL'S MUST BE HIGHLIGHTED
OR MARKED_IDENTIFYING THE+OP INd' DING COMPONENTS, WITH FASTENERS AND DESIGN
4/24/2018
PRESSURES, I,II
Comment:
• PLEASE�NOTE�THAT TFiE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED•
DOCUMENTS.
ZONING REVIEW
COMPLETE Lydia Galbraith 4/16/2018 4/19/2018 4/19/2018
Comment: