In-Place Density Test Report
Client: Kjartan H.Valdimarsson UES Technician: Mark Rogers
2390 S. Brocksmith Road Date Tested: 01/06/2021
Fort Pierce, FL 34945
Project: Valdimarsson Residence Deck Addition
2390 South Brocksmith Road, Fort Pierce, County, FL 34945
lype of Test:
Area Tested: Foundation footings for 2nd floor balcony Field: ASTM D-6938 Nuclear Gauge Method
Material: Backfill Laboratory: ASTM D1557 Modified Proctor
Reference Datum: 0=Top of Footing
The tests below meet the 95%minimum compaction requirement.
Maximum Optimum Field Dry Field Soil Pass
Test Density Moisture Density Moisture Compaction or
No. Location of Test Range (pcf) (%) (pcf) (%) (%) Fail
1 Northern footings 0-1 ft 109.0 12.0 105.7 12.5 97 Pass
2 Southern footings 0-1 ft 109.0 12.0 106.3 12.7 98 Pass
3 Eastside footings 0-1 ft 109.0 12.0 105.0 12.6 96 Pass
Reviewed By
GFA International,Inc
Certificate of Authorization No.4930
s Digitally signed
John ct by John Kent
A,
;` °Date:
Ken ft rl-'-202:1 .08
67 15:19:54-05'00'
John Kent
Senior Project Engineer
STATE OF FLORIDA
Professional Engineer No.63218