Loading...
HomeMy WebLinkAboutEnergy CodeWhole Building Performance Method for Commercial Buildings Form 400A-97 ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Community Affairs FLA/COM-97 Version 2.2 PROJECT NAME -PGA LEARNING CENTER ADDRESS: PORT ST. LUCIE, FLORIDA. OWNER: _PGA AGENT: BUILDING TYPE: _Business (Office) CONSTRUCTION CONDITION: New construction DESIGN COMPLETION: _Shell Building CONDITIONED FLOOR AREA: _7844 MAX. TONNAGE OF EQUIPMENT PER SYSTEM: COMPLIANCE CALCULATION: PERMITTING OFFICE: _Port St. Lucie CLIMATE ZONE: 6 PERMIT NO: JURISDICTION NO: 661200 5 NUMBER OF ZONES: 4 METHOD A DESIGN CRITERIA RESULT ----------------- -------------- ------ A. WHOLE BUILDING 45.70 100.00 PASSES PRESCRIPTIVE REQUIREMENTS: LIGIf f' .ZG LIGHTING CONTROL REQUIREMENTS PASSES HVAC EQUIPMENT COOLING EQUIPMENT 1. SEER 12.00 10.00 PASSES 2. SEER 12.00 10.00 PASSES 3. SEER 12.00 10.00 PASSES 4. SEER 12.00 10.00 PASSES HEATING EQUIPMENT 1. Et 12.00 N/A 2. Et 12.00 N/A 3. Et 12.00 N/A 4, Et 12.00 N/A AIR DISTRIBUTION SYSTEM INSULATION REQUIREMENTS 1. Conditioned Space 6.00 0.00 N/A 2. Conditioned Space 6.00 0.00 N/A 3. Conditioned Space 6.00 0.00 N/A 4. Conditioned Space 6.00 0.00 N/A REHEAT SYSTEM TYPES USED NO REHEAT SYSTEM is USED WATER HEATING EQUIPMENT 1. EF 20.00 0.90 PASSES yPIeING INSULATION REQUIREMENTS 1. Circulating 2.00 1.00 PASSES ---------------------------------------------------------------------------- COMPL'iANCE CERTIFICATION: I hereby certify that the plans and Review of the plans and specifica- specifications covered by this calcu- tions covered by this calculation lation are in compliance with the indicates compliance with the Florida Energy Efficiency Code. PREPARED BY: DATE: T hereby certify that this. building is ,iin rompliance,,withh -th Florida Energy Eff+iciency Code (3WNER/AGENT: DATE: Florida Energy Efficiency Code. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908, Florida Statutes. BUILDING OFFICIAL: DATE: I hereby "certify() that the system design is in compliance with the Florida Energy Effici'enay. Code. SYSTEM DESIGNER REGISTRATION/STATE ARCHITECT MECHANICAL:_ PLUMBING _ ELECTRICAL:_ LIGHTING _ (*) Signature by registered be used where is required where Florida law requires design to be performed design professionals. Typed names and registration numbers may all relevant information is contained on signed/sealed plans. A BUILDING ENVELOPE SYSTEMS COMPLIANCE CHECK 401-.------GLAZING--ZONE 1------------------------------------------------ v- F,levation Type U ---- SC VLT_ ---- ---- Shading -------------- Area(Sgft) ---------- --------- North --------------- Commercial 1.31 .80 .10 None 100 South Commercial 1.31 .80 .10 None 120 East Commercial 1.31 .80 .10 None 100 West Commercial 1.31 .80 .10 None 100 Total Glass Area in Zone 1 = 420 401.------GLAZING--ZONE 2------------------------------------------------ v- Elevation Type U ---- SC VLT ---- ---- Shading -------------- Area(Sgft) ---------- --------- North --------------- Commercial 1.31 .80 .10 None 100 South Commercial 1.31 .80 .10 None 0 East Commercial 1.31 .80 .10 None 30 West Commercial 1.31 .80 .10 None 0 Total Glass Area in Zone 2 = 130 401------- GLAZING --ZONE 3------------------------------------------------ v- Elevation Type --------------- U ---- SC VLT ---- ---- Shading -------------- Area(Sgft) ---------- --------- North Commercial 1.31 .80 .10 None 0 South Commercial 1.31 .80 .10 None 0 East Commercial 1.31 .80 .10 None 0 West Commercial 1.31 .80 .10 None 0 Total Glass Area in Zone 3 = 0 401------- GLAZING --ZONE 4------------------------------------------------ v- Elevation --------- Type --------------- U ---- SC VLT ---- ---- Shading -------------- Area(Sgft) ---------- North Commercial 1.31 .80 .10 None 60 South Commercial 1.31 .80 .10 None 460 East Commercial 1.31 .80 .10 None 40 West Commercial 1.31 .80 .10 None 40 Total Glass Area in Zone 4 = 600 Total Glass Area = 1150 402------- WALLS --ZONE 1------------------------------------------------ --- Elevation Type U Insul R Gross(Sgft) --------- North -------------------------------- 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc ----- ------- 0.149 4 ----------- 720 South 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 500 East 5/8"Stco/8"CMU/3/4"ISO BTWN2411oc 0.149 4 220 West 5/8"Stco/8"CMU/3/4"ISO BTWN2411oc 0.149 4 660 Total Wall Area in Zone 1 = 2100 402.------WALLS--ZONE 2------------------------------------------------ --- Elevation Type U Insul R Gross(Sgft) --------- North -------------------------------- 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc ----- ------- 0.149 4 ----------- 0 South 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 770 East 5/8"Stco/8"CMU/3/4"ISO BTWN2411oc 0.149 4 200 West- 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 130 Total Wall Area in Zone 2 = 1100 402.------WALLS--ZONE 3------------------------------------------------ --- Elevation Type U Insul R Gross(Sgft) --------- North -------------------------------- 5/8"Stco/8"CMU/3/4"ISO BTWN2411oc ----- ------- 0.149 4 ----------- 550 South 5/8"Stco/8"CMU/3/4"ISO 13TWN24"oc 0.149 4 0 East 5/8"Stco/8"CMU/3/4"ISO BTWN2411oc 0.149 4 190 West 5/8"Stco/8"CMU/3/4"ISO BTWN2411oc 0.149 4 0 Total Wall Area in Zone 3 = 740 402.------WALLS--ZONE 4 ------------------------------------------------ Elevation Type U Insul R Gross(Sgft) 71-------- ----- ------ --------------- - - - - -- - - - --- - - - - -- ----- - - - - - - North 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 440 South 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 660 Fast 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 150 West 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0.149 4 150 Total Wall Area in Zone 4 = 1400 Total Gross Wall Area = 5340 403.------DOORS--ZONE 1 ------------------------------------------------- Elevation Type U Area(Sgft) ---------- --------- North ------------------------------------------ 1-3/8 Wood -Door -Solid core flush ----- 0.39 0 South 1-3/8 Wood Door -Solid core flush 0.39 0 East 1-3/8 Wood Door -Solid core flush 0.39 24 West 1-3/8 Wood Door -Solid core flush 0.39 48 Total Door Area in Zone 1 = 72 403.------DOORS--ZONE 2 ------------------------------------------------ Elevation Type U Area(Sgft) --------- North ------------------------------------------ 1-3/8 Wood Door -Solid core flush ----- 0.39 ---------- 0 South 1-3/8 Wood Door -Solid core flush 0.39 0 East 1-3/8 Wood Door -Solid core flush 0.39 48 West 1-3/8 Wood Door -Solid core flush 0.39 24 Total Door Area in Zone 2 = 72 403.------DOORS--ZONE 3 ------------------------------------------------ Elevation Type U Area(Sgft) --------- North ------------------------------------------ 1-3/8 Wood Door -Panel with 7/16" panels ----- 0.57 ---------- 0 South 1-3/8 Wood Door -Panel with 7/16" panels 0.57 0 East 1-3/8 Wood Door -Panel with 7/16" panels 0.57 21 West 1-3/8 Wood Door -Panel with 7/16" panels 0.57 0 Total Door Area in Zone 3 = 21 403.------DOORS--ZONE 4 ------------------------------------------------ Elevation Type U Area (Sgft) --------- North ------------------------------------------ 1-3/8 Wood Door -Panel with 7/16" panels ----- 0.57 ---------- 21 South 1-3/8 Wood Door -Panel with 7/16" panels 0.57 0 East 1-3/8 Wood Door -Panel with 7/16" panels 0.57 0 West 1-3/8 Wood Door -Panel with 7/16" panels 0.57 0 Total Door Area in Zone 4 = 21 Total Door Area = 186 404.------ROOFS--ZONE 1 ------------------------------------------------ Type Color U Insul R Area(Sgft) ------------------------------------ Sngl Ply/3"Iso/l/2"WD ------ ------------ Deck/WD T Medium 0.040 30 ---------- 7840 Total Roof Area in Zone 1 = 7840 404.------ROOFS--ZONE 2 ------------------------------------------------ Type* Color U Insul R Area(Sgft) ------------------------------------ Shngl/1/2"WD Deck/WD ------ ------------ Truss/9" B Medium 0.027 30 ---------- 0 Total Roof Area in Zone 2 = 0 404------- ROOFS --ZONE 3 ------------------------------------------------ Type Color U Insul R Area(Sgft) Conc Tile/1/2"WD Deck/WD Truss/ Medium 0.028 30 0 ti Total Roof Area in Zone 3 = 0 404.------ROOFS--ZONE 4 ------------------------------------------------ Type - - - - - - - - - - - - - - - Color - - - - - - - U Insul R - - - - - - - - - - - Area(Sgft) - - - - - - - - - - - - -r - - - - Conc Tile/l/2"WD - - - - - - - - - - - - - Deck/WD Truss/ Medium 0.028 30 0 Total Roof Area in Zone 4 = 0 Total Roof Area = 7840 4-05.------FLOORS-ZONE I ------------------------------------------------ Type Insul R Area(Sgft) Slab on Grade/Uninsulated .10 1280 Total Floor Area in Zone 1 = 1280 405.------FLOORS-ZONE 2 ------------------------------------------------ Type Insul R ------- Area(Sgft) ---------- ------------------------------------------------ Slab on Grade/Uninsulated .10 2500 Total Floor Area in Zone 2 = 2500 405.------FLOORS-ZONE 3------------------------------------------------, Type Insul R Area(Sgft) Slab on Grade/Uninsulated .10 1600 Total Floor Area in Zone 3 = .1600' 405.------FLOORS-ZONE 4 ------------------------------------------------ Type Insul R ------- Area (Sgft) ---------- ------------------------------------------------ Slab on Grade/Uninsulated .10 2044 Total Floor Area in Zone 4 = 2044 Total Floor Area = 7424 406.------INFILTRATION -------------------------------------------------- ICHECK Infiltration Criteria in 406.1.ABCD have been met. MECHANICAL SYSTEMS CHECK --------------------------------------------------------- HVAC load sizing has been performed. (407.1.ABCD) ---- 407.------COOLING SYSTEMS ----------------------------------------------- Type No Efficiency IPLV Tons 1. Split System 1 12 12 3.42 2. Split System 1 12 12 3.79 3. Split System 1 12 12 2.00 4. Split System 1 12 12 5.00 408.------HEATING SYSTEMS ----------------------------------------------- Type No Efficiency --------------------------- BTU/hr 1. -------------------------------- Electric Resistance 1 12 7500 2. Electric Resistance 1 12 7500 3. Electric Resistance 1 12 7500 4. Electric Resistance 1 12 7500 409,.- ----- VENTILATION --------------------------------------------------- CHECK Ventilation Criteria in 409.1.ABCD have been met. I 410 ------ AIR DISTRIBUTION SYSTEM---------------------------------------- CHECK------ --------------------------------------------------- Duct sizing and design have been performed. (410.1.ABCD) ---- AHU Type Duct Location R-value 1. Air Conditioners Conditioned Space 6 2. Air Conditioners Conditioned Space 6 3.•Air Conditioners Conditioned Space 6 .4. Air Conditioners Conditioned Space 6 CHECK Testing and balancing will be performed. (410.1.ABCD) 411. ----- PUMPS AND PIPING -ZONE ----------------------------------------- Basic prescriptive requirements in 411.1.ABCD have been met. PLUMBING SYSTEMS 411------ PUMPS AND PIPING -ZONE 1 Type R-value/in ---------- Diameter -------- Thickness --------- 1. ------------------------ Circulating 4 .75 2 411.-----PUMPS AND PIPING -ZONE 2 --------------------------------------- Type R-value/in ---------- Diameter -------- Thickness --------- 1. ------------------------ Circulating 4 .75 2 411.-----PUMPS AND PIPING -ZONE 3 --------------------------------------- Type R-value/in ---------- Diameter -------- Thickness --------- 1. ------------------------ Circulating 4 .75 2 411.-----PUMPS AND PIPING -ZONE 4 --------------------------------------- Type R-value/in ---------- Diameter -------- Thickness --------- 1. ------------------------ Circulating 4 .75 2 412------ WATER HEATING SYSTEMS -ZONE 1 ---------------------------------- Type ------------------------ Efficiency ---------- StandbyLoss -------------------- InputRate Gallons ---------- 412------ WATER -HEATING SYSTEMS -ZONE 2 ---------------------------------- Type Efficiency ---------- StandbyLoss -------------------- InputRate Gallons ---------- 1. ------------------------ Electric(<=12 KW) 20 0 400 20 412------ WATER HEATING SYSTEMS -ZONE 3 ---------------------------------- Type ------------------------ Efficiency ---------- StandbyLoss -------------------- InputRate Gallons ---------- 412------ WATER HEATING SYSTEMS -ZONE 4 ---------------------------------- Type ------------------------ Efficiency ---------- StandbyLoss -------------------- InputRate Gallons ---------- ELECTRICAL SYSTEMS CHECK 413.-----ELECTRICAL POWER DISTRIBUTION---------------------------- ----- Metering criteria in 413.1.ABCD have been met. 414.-----MOTORS --------------------------------------------------- ----- Motor efficiencies in 414.1.ABCD have been met. 415.-----LIGHTING SYSTEMS -ZONE 1 --------------------------------------- Sp4ce Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) ---------- ----------------- ----------------- --- ------ ---------- General Ex 1 On/Off 2 None 0 500 1280 Total Watts for Zone 1 = 500 Total Area for Zone 1 = 1280 415.-----LIGHTING SYSTEMS -ZONE 2 --------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) ---------- ----------------- ----------------- --- ---------------- Type D(Gen 1 On/Off 2 None 0 500 1800 Total Watts for Zone 2 = 500 Total Area for Zone 2 = 1800 415 ------ LIGHTING SYSTEMS -ZONE 3--------------------------------------- --- Space Type No Control Type 1 No Control Type 2 No --- ------ Watts Area(Sgft) ---------- ---- ------ ----------------- --- Recreation 1 On/Off -------------- 2 None 0 500 700 Total Watts for Zone 3 = 500 • Total Area for Zone 3 = 700 415.-----LIGHTING SYSTEMS -ZONE 4--------------------------------------- --- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) ---------- ----------------- --- Fast Food/ 1 On/Off -------------- 2 None --- ------ 0 500 ---------- 2044 Total Watts for Zone 4 = 500 Total Area for Zone 4 = 2044 Total Watts = 2000 Total Area = 5824 CHECK Lighting criteria in 415.1.ABCD have been met. 16. Operation/maintenance manual ---------------------------------------------------------------------------- will be provided to owner.(102.1)