HomeMy WebLinkAboutCalc2.1Protected Premises:Date: 12/1/2020 Address: City:State: FL Zip: 34946 Prepared By:Phone: 772-232-2001 Address:Email: City:State: FL Zip: 34990 3.20 AMPS @ 120 VAC 0.04 Amps 4.45 Amps Secondary Load Requirements 5.91 Amp Hours Total (AH) 4.53 0.40 4.92 x 1.2 5.91 AH 7 Amp Hours TRUE Palm City Current required by source to power the fire alarm system. Current Draw Total Secondary Load from the calculation table below. Current load on the primary power supply during non-alarm conditions. Primary Standby Load Primary Alarm Load Current load on the primary power supply during alarm conditions. x0.189 A Secondary Standby Load System Power Requirements NFW-100X Fire Alarm Control Panel AC Branch Current Requirements Pursuit Boats 3891 St Lucie Blvd Fort Pierce Edward Pleffner 3150 SW 42nd Av Emilytaveras@adt.com Select batteries from the list below. 0.084 hours Required Alarm Time (hours) Required Standby Time Battery Selection 24 hours 7 AH BAT-1270 Battery (12 volt) Time (hours) Secondary Alarm Load Derating factor Total Secondary Load Secondary Load Requirements 4.716 A x Two Four (two 12VDC sets in parallel) Page 1 of 2 Battery Distribution Chart Comments 1.09 5.43 0.48 Secondary Alarm Load (AH) * Derating Factor 3. The selected batteries (7AH) are within the charger range of this power supply (7-18AH). Secondary Alarm Load Spare Battery Capacity Secondary Standby Load Battery Selection (AH) - Secondary Load Requirements (AH) Secondary Standby Load (AH) * Derating Factor 2. Selected battery size meets secondary load requirements. 1. Batteries will fit in the FACP cabinet. Shows amp-hour distribution of your selections. Spare Battery Capacity 15% Secondary Standby Load 78% Secondary Alarm Load 7%Spare Battery Capacity Secondary Standby Load Secondary Alarm Load Page 2 of 2