—TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION
—BOTTOM OF CONCRETE FOOTING SHALL BE MINIMUM OF 12" BELOW UNDISTURBED OR
ENGINEERED GRADE
CONCRETE:
—MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
—ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
—MINIMUM GRADE 40 STEEL
—REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
—THE REBAR IS BENT COLD
—THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6—BAR DIAMETERS: AND
—REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
—COVER:
—3" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF J" FOR FINE
GROUT, AND J" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATION:
—METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
J"x5j" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES —
AND EVERY OTHER END —WALL POST
2" MIN ABASE RAIL
GRADE —
_ I III II
2,500 PSI 4" CONCRETE
B WITH 10GA. W.W.F.
/MINIMUM
OR FIBER MESH
SOIL BEARING
CO)N INUOUS WITH MINIMUM
CAPACITY 500 PSF(TYP.)
25" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR
DETAIL
Ir 00
MIN. 2,500 PSI 4" CONCRETE SLAB WITH 10GA. W.W.F. (OR
FIBER MESH) AND 12"x12" REINFORCED FOOTER PERIMETER 12"02" REINFORCED FOOTER
------------- FRAME -------------------- ------------------------------------------------------------------------------------------------------------ --------------------------------------------------------------------------- -----
OUT WINDOW
I I " I 8'-1�„
44'-0" 6
1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET —BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON —HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS WITH SEAL WASHERS @ 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH.
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
792 SQ. FT.
REVISIONS
REVI
DESCRIPTON
I DATE
I BY
1
DOOR TO FRAME OUT
12/22/20
MTB
2
SHEET 1 FRAME OUT
12/30/20
MTB
""""'" o'. MTB
DATE: 12/17/20
LocAnoN: 7601 Miramar Ave., Ft. Pierce
SIZE: 44'L X 18'W X 9'H
L\CENSF Oly��i
NO.64608 :2
`n STATE OF 441
i6.o'..., FLORIDN
•llol I I I �-
�/
Digitally signed
by Matthew
Q
Baldwin
Date:2020.12.30
08:57:29-05'00'
z MottheW T. BOIdWin P.E.
Florida License #64608
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w Q
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES a_ Sheet: CA-1 OF 6
2 5" PLAN VIEW DOOR FRAMING
J" RECESS
4' DOOR WIDTH I
ELEVATION VIEW
DOOR FRAMING
RECESS
--
T
•75"J 4" DOOR WIDTH
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
e
12
3L-----
1 10L 1 w
�IO
I
O
I
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
792 SQ. FT.
REVISIONS
11»
3'-616
11»
3' -616
11»
3'-616
18'_0„
FRONT END
3-616
WALL
11» 3-616
11»
REV
DESCRIPTON
DATE
BY
1
DOOR TO FRAME OUT
12/22/20
MTB
2
SHEET 1 FRAME OUT
12/30/20
MTB
-4' -78,>
4, _ 13„
8
O
I
DRAWN BY: MTB
DATE: 12/ 17/20
�ocAnoN:
7601 Miramar Ave., Ft. Pierce
SIZE: 44'L X 18'W X 9'H
W
2'-6"
WINDOW
N
00
FRAME
I OUT
3'-0"
11»
-616
11»
3 -616
MID
11» 11»
3 -61 6 3 -616
18'-0"
END WALL
11»
3 -616
-
PRINTED
THE SHA
COPIES OF THIS
AUTHENTICATION
18'-0"
REAR END WALL
DOCUMENT ARE NOT CONSIDERED SIGNED AND
CODE MUST BE VERIFIED ON ANY ELECTRONIC
-
SEALED AND
COPIES
C�
Z
Q
r--)
w Z
� W
MattheW T. BOIdWin P.E.
Florida License #64608
Sheet:
CA-2 OF 6
4'-0" 4'-0"
I
4' O.C. MAX. WINDOW
FRAME `A
OUT
6" Z.
1'-32" 1'-6"���
8'-0"
3'-114" 3'-114
LEFT SIDE WALL
3'-114" 3'-114" 3'-114" 3'-114"
10'-0"
ROLL -UP
o DOOR
I
i�
' O.C. MAX.
-114" 3'-113,,
-0"
4'-0"
5'-0"
I
FRAME
OUT
Aga
CAMMANYMEM
CODE INFORMATION
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
EXPOSURE
B
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 300Ib P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
792 SQ. FT.
REVISIONS
REV
DESCRIPTON
IDATE
BY
1
DOOR TO FRAME OUT
12/22/20
MTB
2
ISHEET 1 FRAME OUT
12/30/20
MTB
MTB
12/17/20
7601 Miramar Ave., Ft. Pierce
44'L X 18'W X 9'H
LLJ
1» 7» 3» 3» 3» 3» 3» 1„ >
3'-92 1'-108 3'-114 3'-114 3'-114 3'-114 3'-11� 1'-6" 1'-32
36'-0" -0" C�
44' -0" Z
RIGHT SIDE WALL
Q
ry
LL
Matthew T. Baldwin P.E.
W Florida License #64608
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w o
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES U) Sheet: CA-3 OF 6
I
1 ■, ej
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
INONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-165mph
ENCLOSURE ENCLOSED/0
I
INTERNAL PRESSURE COEFF. +/— 0.18/0
p� IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD 10PSF
ROOF LIVE LOAD 20PSF OR 31
FLOOR DEAD LOAD 10PSF
FLOOR LIVE LOAD 50PSF
"R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 792 SQ. FT.
WINDOW
18'-0"
MID END WALL
FRAME
OUT
18'-O" - I REV DESCRIPTON DATE
1 DOOR TO FRAME OUT 12/22/20
FRONT E N D WALL 2 SHEET 1 FRAME OUT 12/30/20
DRAWN By.. MTB
DATE: 12/17/20
LOCATION:
7601 Miramar Ave., Ft. Pierce
SIZE: 44'L X 18'W X 9'H
CD
18'-0" _
REAR END WALL C/,
w
0
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND J z
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
Matthew T. Baldwin P.E.
Florida License #64608
Sheet: CA-4 OF 6
I
FRAME
OUT
M
LEFT SIDE WALL
FRAME
OUT
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-165mph
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
792 SQ. FT.
REVISIONS
REV DESCRIPTON I DATE I BY
1 IDOOR TO FRAME OUT 12/22/20 1 MTB
2 ISHEET 1 FRAME OUT 12/30/20 1 MTB
44'-0" - C/71
RIGHT SIDE WALL w
W
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND J
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
MTB
12/17/20
7601 Miramar Ave., Ft. Pierce
44'L X 18'W X 9'H
Matthew T. Baldwin P.E.
Florida License #64608
Sheet: CA-5 OF 6
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SC) 12 14x4" SELF —DRILLING
A�411/ NIPPLE TO
'T\ BASE RAIL NIPPLE T
BASE RAI
POST TO BASE RAIL
CONNECTION
2"x2"x2" 16 GA.
ANGLE CLIP
SECURED WITH (4)
# 12-14xi"
SELF —DRILLING
SCREWS
NON—STRUCTURAL
HEADER OR WINDU
IINTERI(
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xj"
SELF —DRILLING SCREWS
END POST TO BASE RAIL
CONNECTION
Ir
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR
WINDOW RAIL DETAIL
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
SINGLE OR DOUBLETS
HEADER
HEADER CONNECTIO
DETAIL OPTION 1
2"x2"x2" 16 GA. ANGLE CLIP SECURED
WITH (4) #12-14xi" SELF —DRILLING
SCREWS 26 GAUGE ROOF SHEATHING
SECURED WITH (1)#12-14xi"
VARIES NIPPL f;c" SELF —DRILLING SCREWS
TO TRUSS '2-1-2-1' (6" O.C. (9" O.C. MAX.))
STD. MAX. SPACING _
MINIMUM 6" TS
3" MIN. L NIPPLE. NIPPLE___ ----
SECURED TO WALL
POST WITH _-- _-
(4)#12-14xi„-
SELF—DRILLING _
STD. MAX. ACING SCREWS 1" 16 GAUGE FURRING CHANNEL
OVARIES (2) O.C. MAX. SECURED WITH
(2)#12-14x1" SELF —DRILLING
Fy— SCREWS TO EACH RAFTER.
SIDE WALL ROLL —UP
1 DOOR/FRAME OUT POST TO TRUSS ROOF PANEL CONNECTION
1 HEADER DETAIL CONNECTION VERTICAL SHEATHING OPTION
INSTALL PER MANUFACTURERS INSTRUCTIONS
# 12-14)4"
SELF —DRILLING SCREWS
CAD 10" O.C. MAX., 3"
MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS
VERTICALLY
19
EXTERIOR
DOOR FRAME TO POST
CONNECTION
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xi" SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
#14x1"
SELF —DRILLING
SCREWS ® 6" O.C.
MAX. & 6" MAX. 3' _o' M1 .
FROM CORNERS — -Z' MA
ROLL —UP DOOR TO
POST CONNECTION
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-140" SELF —DRILLING
SCREWS TO EACH RAFTER.
OAx:
—0"
SAVE & RIDGE REINFORCED ROOF PANEL CONNECTION
(RIDGE 3r AND EAVE 3e)
Design Pressures - 165 mph Basic Wind Speed
Zone
Roof
Wall
1
2n
2r
2e
3r
3e
4
5
17.6
22.9
17.6
17.6
25.1
25.1
25.1
28.4
-21.4
1 -60.0
1 -41.0
1 -21.4
1 -79.3
1 -68.1
-27.0
-33.6
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
C..AMIRT15- ERE
IPPLE T SINGLE OR DOUBLETS
ASE RAIL b r�HEADER
HEADER CONNECTION DETAIL
nPTInNI 7
LE TO
1 "x2j" 16 GA.
U—CHANNEL BRACE, MIN.
�_ 24" UP TO 7' POST, M11'
6" 48" OVER 7' POST. MIN.
45' TO MAX. 60' FROM
HORIZ. (EXCLUDE
END —WALLS). SECURED
WITH (4)#12-14xj"
SELF —DRILLING SCREWS.
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
BOX SAVE RAFTER TO
POST CONNECTION DETAIL
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 —R1
Hampton Rib Roof Panel
WALL SHEATHING(LAP)
Carports Anywhere
FL27403.2
Resi—Lap Wall Panel
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL21450.3
SERIES 3100
WINDOW
MI WINDOWS AND DOORS
FL17499.1 —R5
MODEL 185 SH
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-165mph
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/— 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
792 SQ. FT.
DOOR TO FRAME OUT 12/22/20
SHEET 1 FRAME OUT 12/30/20
DRAWN BY: MTB
DATE: 12/17/20
LOCATION:
7601 Miramar Ave., Ft. Pierce
441 X 18'W X 9'H II
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
J
Q Matthew T. Baldwin P.E.
Florida License #64608
LJ
Sheet:
CA-6 OF 6