Loading...
HomeMy WebLinkAboutds84487 Calculator-44207-3320717593 (2)84485 | 44207-3320717593 | Page 1/4 Date: January 11th, 2021 ASCE 7 Components & Cladding Wall Pressure Calculator Prepared For: 6710 Benjamin Rd. #200 Tampa FL Project: Snyder Project Address: 9650 S ocean drive 2009 Jensen Florida Box for Engineer Seal Only-Original Rqd for Permit & Use Frank Bennardo, PE FL46549 or Richard Neet, PE FL86488 The following has been considered in determining allowable stress design (ASD) wall opening pressures for the above- referenced location. ASCE: ASCE 7-10 (6TH EDN FLORIDA BUILDING CODE, 2017 FBC, 2015 IBC) Wind Velocity: 170 MPH Exposure Category: D Kd: 0.85 Kzt: 1 Elevation Above Sea Level: 0 FT Minimum Building Dimension: 170FT Mean Roof Height: 189FT Unit Elevation: 170FT ROOF SLOPE: FLAT (<10°) Number Of Openings: 5 Shutter: YES Mark: 1 Height Of Opening: 62 IN Width Of Opening: 52 IN Zone: 4 Mark: 2 Height Of Opening: 62 IN Width Of Opening: 72 IN Zone: 4 Mark: 3 Height Of Opening: 96 IN Width Of Opening: 142 IN Zone: 4 Mark: 4 Height Of Opening: 96 IN Width Of Opening: 70 IN Zone: 4 Mark: 5 Height Of Opening: 96 IN Width Of Opening: 142 IN Zone: 4 Based on the above, the following ASD design pressures apply for the Corp. Office: 160 SW 12th Avenue Suite 106, Deerfield Beach, Florida 33442 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com 84485 | 44207-3320717593 | Page 2/4 opening marks which shall correspond with contractor-supplied building layout: a: 17 FT Mark: 1 Wall Positve Pressure: 63.7PSF Wall Negative Pressure: -65PSF Mark: 2 Wall Positve Pressure: 61.9PSF Wall Negative Pressure: -63.8PSF Mark: 3 Wall Positve Pressure: 55.7PSF Wall Negative Pressure: -59.7PSF Mark: 4 Wall Positve Pressure: 59.6PSF Wall Negative Pressure: -62.3PSF Mark: 5 Wall Positve Pressure: 55.7PSF Wall Negative Pressure: -59.7PSF Design pressure results are in accordance with the Building & ASCE 7 codes listed above for an ENCLOSED structure only (Gcpi=+-0.18). Results are based on contractor-supplied data and are not field verified by this office. Input shall be verified by others prior to permit & use. Selection of all components & their respective approvals shall be by others and are to be within the ASD design pressure limitations stated herein. Results only valid with original or verifiable digital seal by a licensed PE of this firm. For more information on any of the terms listed herein, or to use a design tool to evaluate your openings, visit EngineeringExpress.com/Wind. Corp. Office: 160 SW 12th Avenue Suite 106, Deerfield Beach, Florida 33442 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com 84487 | 44207-3320717593 | Page 3/4 Date: January 11th, 2021 ASCE 7 Components & Cladding Wall Pressure Calculator Prepared For: 6710 Benjamin Rd. #200 Tampa FL Project: Snyder Project Address: 9650 S ocean drive 2009 Jensen Florida Box for Engineer Seal Only-Original Rqd for Permit & Use Frank Bennardo, PE FL46549 or Richard Neet, PE FL86488 The following has been considered in determining allowable stress design (ASD) wall opening pressures for the above- referenced location. ASCE: ASCE 7-10 (6TH EDN FLORIDA BUILDING CODE, 2017 FBC, 2015 IBC) Wind Velocity: 170 MPH Exposure Category: D Kd: 0.85 Kzt: 1 Elevation Above Sea Level: 0 FT Minimum Building Dimension: 170FT Mean Roof Height: 189FT Unit Elevation: 170FT ROOF SLOPE: FLAT (<10°) Number Of Openings: 5 Shutter: YES Mark: 1 Height Of Opening: 62 IN Width Of Opening: 52 IN Zone: 4 Mark: 2 Height Of Opening: 62 IN Width Of Opening: 72 IN Zone: 4 Mark: 3 Height Of Opening: 96 IN Width Of Opening: 142 IN Zone: 4 Mark: 4 Height Of Opening: 96 IN Width Of Opening: 70 IN Zone: 4 Mark: 5 Height Of Opening: 96 IN Width Of Opening: 142 IN Zone: 4 Based on the above, the following ASD design pressures apply for the Corp. Office: 160 SW 12th Avenue Suite 106, Deerfield Beach, Florida 33442 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com 84487 | 44207-3320717593 | Page 4/4 opening marks which shall correspond with contractor-supplied building layout: a: 17 FT Mark: 1 Wall Positve Pressure: 63.7PSF Wall Negative Pressure: -65PSF Mark: 2 Wall Positve Pressure: 61.9PSF Wall Negative Pressure: -63.8PSF Mark: 3 Wall Positve Pressure: 55.7PSF Wall Negative Pressure: -59.7PSF Mark: 4 Wall Positve Pressure: 59.6PSF Wall Negative Pressure: -62.3PSF Mark: 5 Wall Positve Pressure: 55.7PSF Wall Negative Pressure: -59.7PSF Design pressure results are in accordance with the Building & ASCE 7 codes listed above for an ENCLOSED structure only (Gcpi=+-0.18). Results are based on contractor-supplied data and are not field verified by this office. Input shall be verified by others prior to permit & use. Selection of all components & their respective approvals shall be by others and are to be within the ASD design pressure limitations stated herein. Results only valid with original or verifiable digital seal by a licensed PE of this firm. For more information on any of the terms listed herein, or to use a design tool to evaluate your openings, visit EngineeringExpress.com/Wind. Powered by TCPDF (www.tcpdf.org) Corp. Office: 160 SW 12th Avenue Suite 106, Deerfield Beach, Florida 33442 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com