Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
YOUNG- MANUAL J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Project Summary Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information YOUNG RESIDNECEFor: 10251 S OCEAN DRIVE, JENSEN BEACH, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh25285 Struc ture Btuh20080 Ducts Btuh7250 Ducts Btuh10533 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh32536 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh29082 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh5609 Ducts Btuh2878 Central vent (0 cfm)Btuh0 CoolingHeating (none) 23422342Area (ft²)Equipment latent load Btuh8487 2342023420Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh37569 Equiv. AVF (cfm)62125 Req. total capacity at 0.70 SHR ton3.5 Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIER Model Cond CA16NA04200G0B0 AHRI ref Coil FX4DNF049L AHRI ref 202024777 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW8.3 Sensible cooling Btuh29400 Heating output Btuh28199 Latent cooling Btuh12600 Temperature rise °F18 Total cooling Btuh42000 Actual air flow cfm1400 Actual air flow cfm1400 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.046 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House POWDER RM 2 Exposed wall 176.0 ft 6.0 ft 3 Room height 10.0 ft 10.0 heat/coolft 4 Room dimensions ft6.0x7.0 5 Room area 2342.0 ft²42.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 660 493 1974 1079 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 135 0 2457 3628 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 8 0 146 215 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 24 0 437 645 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 490 412 1650 901 60 60 240 131 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 16 20 291 313 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 30 30 546 632 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 32 20 582 746 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 240 225 901 492 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 15 15 273 316 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 370 349 1397 764 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 12 0 218 323 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 9 0 164 242 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2342 2342 3713 3204 42 42 67 57 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2342 176 6692 0 42 6 228 0 6 c) AED excursion 0 -9 Envelope loss/gain 21442 13500 535 179 12 a) Infiltration 3844 1030 131 35 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 5550 200 Subtotal (lines 6 to 13)25285 20080 666 415 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 25285 20080 666 415 15 Duct loads 29%52%7250 10533 29%52%191 217 Total room load 32536 30613 857 632 Air required (cfm)Air required (cfm)1400 1400 37 29 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LAUNDRY KITCHEN/DINING 2 Exposed wall 0 ft 12.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft6.0x10.0 ft512.0x1.0 5 Room area 60.0 ft²512.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 120 72 288 158 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 16 10 291 313 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 32 10 582 746 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 60 60 95 82 512 512 812 701 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 60 0 0 0 512 12 456 0 6 c) AED excursion -15 212 Envelope loss/gain 95 67 2430 2129 12 a) Infiltration 0 0 262 70 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 600 1900 Subtotal (lines 6 to 13)95 667 2692 4099 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 6 5 14 Subtotal 95 667 2698 4105 15 Duct loads 29%52%27 350 29%52%774 2153 Total room load 122 1017 3472 6258 Air required (cfm)Air required (cfm)5 47 149 286 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 3 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 BEDROOM 3 2 Exposed wall 5.0 ft 25.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft56.0x1.0 ft12.0x13.0 5 Room area 56.0 ft²156.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 120 105 420 230 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 15 7 273 316 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 50 50 200 109 130 115 460 252 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 15 7 273 316 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 56 56 89 77 156 156 247 213 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 56 5 190 0 156 25 951 0 6 c) AED excursion -10 6 Envelope loss/gain 479 176 2625 1333 12 a) Infiltration 109 29 546 146 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 250 600 Subtotal (lines 6 to 13)588 455 3171 2079 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 17 14 14 12 14 Subtotal 605 469 3185 2091 15 Duct loads 29%52%174 246 29%52%913 1097 Total room load 779 715 4098 3188 Air required (cfm)Air required (cfm)34 33 176 146 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 4 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LINEN WIC 3 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft2.0x4.0 ft6.0x5.0 5 Room area 8.0 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 8 8 13 11 30 30 48 41 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 8 0 0 0 30 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 13 11 48 40 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)13 11 48 40 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -13 -11 21 18 14 Subtotal 0 0 68 58 15 Duct loads 29%52%0 0 29%52%20 30 Total room load 0 0 88 88 Air required (cfm)Air required (cfm)0 0 4 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 5 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC 2 BEDROOM 2 2 Exposed wall 12.0 ft 26.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft6.0x7.0 ft13.0x13.0 5 Room area 42.0 ft²169.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 30 30 120 66 130 115 460 252 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 15 0 273 403 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 60 60 240 131 130 115 460 252 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 15 7 273 316 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 30 30 120 66 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 42 42 67 57 169 169 268 231 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 42 12 456 0 169 26 989 0 6 c) AED excursion -9 -42 Envelope loss/gain 1003 311 2723 1411 12 a) Infiltration 262 70 568 152 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1265 382 3291 2063 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 14 12 14 Subtotal 1265 382 3305 2075 15 Duct loads 29%52%363 200 29%52%948 1089 Total room load 1628 582 4253 3164 Air required (cfm)Air required (cfm)70 27 183 145 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 6 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALLWAY FOYER 2 Exposed wall 0 ft 7.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft6.0x11.0 ft13.0x7.0 5 Room area 66.0 ft²91.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 70 38 152 83 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 8 0 146 215 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 24 0 437 645 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 66 66 105 90 91 91 144 125 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 66 0 0 0 91 7 266 0 6 c) AED excursion -2 -24 Envelope loss/gain 105 88 1145 1043 12 a) Infiltration 0 0 153 41 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)105 88 1298 1084 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -105 -88 24 21 14 Subtotal 0 0 1322 1105 15 Duct loads 29%52%0 0 29%52%379 580 Total room load 0 0 1701 1684 Air required (cfm)Air required (cfm)0 0 73 77 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 7 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING RM M BATH 2 Exposed wall 22.0 ft 12.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft19.0x22.0 ft213.0x1.0 5 Room area 418.0 ft²213.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 220 160 641 350 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 60 0 1092 1613 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 120 111 444 243 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 9 0 164 242 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 418 418 663 572 213 213 338 291 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 418 22 837 0 213 12 456 0 6 c) AED excursion -92 70 Envelope loss/gain 3232 2443 1402 846 12 a) Infiltration 480 129 262 70 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1500 0 Subtotal (lines 6 to 13)3712 4072 1664 917 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 21 18 0 0 14 Subtotal 3733 4089 1664 917 15 Duct loads 29%52%1070 2145 29%52%477 481 Total room load 4804 6234 2142 1397 Air required (cfm)Air required (cfm)207 285 92 64 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 8 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET M WIC 2 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft3.0x5.0 ft6.0x6.0 5 Room area 15.0 ft²36.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 15 15 24 21 36 36 57 49 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 15 0 0 0 36 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 24 20 57 48 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)24 20 57 48 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 24 20 57 48 15 Duct loads 29%52%7 11 29%52%16 25 Total room load 31 31 73 73 Air required (cfm)Air required (cfm)1 1 3 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-30 16:01:27 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 9 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Right-J® Worksheet Sep 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 1 MASTER BEDROOM 2 Exposed wall 12.0 ft 37.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft6.0x12.0 ft356.0x1.0 5 Room area 72.0 ft²356.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 30 30 120 66 180 120 480 263 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 60 0 1092 1613 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 19.5719.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 23.3123.31 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 30 30 120 66 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 60 60 240 131 190 178 713 389 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 12 0 218 323 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 72 72 114 99 356 356 564 487 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 12 456 0 356 37 1407 0 6 c) AED excursion -9 -72 Envelope loss/gain 1051 352 4475 3002 12 a) Infiltration 262 70 808 216 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1313 422 5283 3218 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1313 422 5283 3218 15 Duct loads 29%52%376 221 29%52%1515 1688 Total room load 1689 643 6798 4906 Air required (cfm)Air required (cfm)73 29 293 224 2020-Sep-30 16:01:32 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Job:Duct System Summary Sep 30, 2020Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information YOUNG RESIDNECEFor: 10251 S OCEAN DRIVE, JENSEN BEACH, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1400cfm1400 Total effective length (TEL)ft185 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2115.032.3VlFx0x05.01.0003334779hBATH 2 st4135.043.8VlFx0x08.01.0001451834253hBEDROOM 2 st4135.044.5VlFx0x08.01.0001461764098hBEDROOM 3 st4135.049.6VlFx0x06.01.00077731684cFOYER st3115.09.0VlFx0x08.01.000143753129cKITCHEN/DINING st2115.024.8VlFx0x08.01.000143753129cKITCHEN/DINING-A st3115.010.0VlFx0x06.01.0004751017cLAUNDRY st2115.025.1VlFx0x08.01.0001431033117cLIVING RM st2115.027.5VlFx0x08.01.0001431033117cLIVING RM-A st1115.023.7VlFx0x06.01.00064922142hM BATH st1115.023.0VlFx0x04.01.0001131cM TOILET st1115.023.0VlFx0x05.01.00029731689hM WIC 1 st1115.023.0VlFx0x04.01.0003373cM WIC 2 st1115.026.7VlFx0x08.01.0002242936798hMASTER BEDROOM st3115.014.9VlFx0x05.01.0002937857hPOWDER RM st4135.046.4VlFx0x05.01.00027701628hWIC 2 st4135.042.8VlFx0x04.01.0004488cWIC 3 2020-Sep-30 16:01:32 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...s\Wrightsoft HVAC\YOUNG RESIDENCE- OCEAN DR.rup Calc = MJ8 Front Door faces: NE Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 462 322 1.000 847 10.0 0x0 VinlFlx st4 Peak AVF 506 398 1.000 928 10.0 0x0 VinlFlx st2 st2 Peak AVF 821 859 1.000 804 14.0 0x0 VinlFlx st3 Peak AVF 117 219 1.000 626 8.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 14000 1400 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������