HomeMy WebLinkAboutEnergy Calculation Form & Manual J's FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 7008 Plumosa Ln 1650 B RHG-S Builder Name: WADE JURNEY HOMES
Street: 7008 Plumosa Ln Permit Office: St.Lucie
City,State,Zip: ,FL, Permit Number:
Owner: WADE JURNEY HOMES Jurisdiction: 661000
Design Location: FL,MELBOURNE_REGIONAL_AP County: St.Lucie(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(1456.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Block, Exterior R=4.1 1164.00 ft2
b.Frame-Wood,Adjacent R=13.0 292.00 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 4 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (1650.0 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 1650.00 ft2
6. Conditioned floor area above grade(ft2) 1650 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11.Ducts R ft2
7. Windows(126.0 sqft.) Description Area a.Sup:Attic,Ret:Main,AH:Main 6 330
a. U-Factor: Dbl,U=0.35 126.00 ft2
SHGC: SHGC=0.29
b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 22.2 SEER:14.50
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a.Electric Heat Pump 22.2 HSPF:8.20
SHGC:
Area Weighted Average Overhang Depth: 1.000 ft.
Area Weighted Average SHGC: 0.290 14.Hot water systems
8. Floor Types (1650.0 sqft.) Insulation Area a.Electric Cap:50 gallons
a.Slab-On-Grade Edge Insulation R=0.0 1650.00 ft2 b. Conservation features EF:0.920
b.N/A R= ft2 None
c.N/A R= ft2 15.Credits Pstat
Glass/Floor Area: 0.076 Total Proposed Modified Loads: 48.18 PASS
Total Baseline Loads: 48.32
1 hereby certify that the plans and specifications covered by Review of the plans and OItVu S7_44
this calculation are in compliance with the Florida Energy specifications covered by this
Code. calculation indicates compliance
with the Florida Energy Code.
PREPARED BY: _' ' - _____---___ Before construction is completed
DATE: -_____ __ this building will be inspected for Q, y
i
compliance with Section 553.908
I hereby certify that this buildi a designed, is i pliance Florida Statutes.
with the Florida Energy Cod . COp WIE
OWNER/AGENT: BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2).
7/24/2020 8:26 AM EnergyGauge@ USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 4
FOW R405-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: 7008 Plumosa Ln 1650 B RH Bedrooms: 4 Address Type: Street Address
Building Type: User Conditioned Area: 1650 Lot#
Owner Name: WADE JURNEY HOMES Total Stories: 1 Block/Subdivision: LWP
#of Units: 1 Worst Case: No PlatBook:
Builder Name: WADE JURNEY HOMES Rotate Angle: 0 Street: 7008 Plumosa Ln
Permit Office: St.Lucie Cross Ventilation: No County: St.Lucie
Jurisdiction: 661000 Whole House Fan: No City,State,Zip: ,
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
/ Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,MELBOURNE_REGI FL_MELBOURNE_REGI 45 90 70 75 369 69 Medium
BLOCKS
Number Name Area Volume
1 Blockl 1650 13200
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 Main 1650 13200 Yes 5 4 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Main 145.5 ft 1650 ft2 ---- 0.29 0 0.71
ROOF
Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Gable or Shed Composition shingles 1739 ft2 274 ft2 Dark N 0.6 N 0.6 No 0 18.4
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 300 1650 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) Main 30 Blown 1650 ft2 0.1 Wood
7/24/2020 8:26 AM EnergyGauge@ USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
1 S Exterior Block Main 4.1 18 0 8 0 144.0 ft2 0 0.25 0.4 0
2 E Exterior Block Main 4.1 36 6 8 0 292.0 ft2 0 0.25 0.4 0
3 N Exterior Block Main 4.1 38 6 8 0 308.0 ft2 0 0.25 0.4 0
4 W Exterior Block Main 4.1 52 6 8 0 420.0 ft2 0 0.25 0.4 0
5 - Garage Frame-Wood Main 13 36 6 8 0 292.0 ft2 0 0.25 0.4 0
DOORS
# Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 S Insulated Main None .4 3 6 8 20 112
2 N Wood Main None .4 2 8 6 8 17.8 ft2
3 Wood Main None .46 2 8 6 8 17.8 ft2
WINDOWS
Orientation shown is the entered, Proposed orientation.
/ Wall Overhang
V/ # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 S 1 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds None
2 E 2 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 It 0 in 1 It 4 in Drapes/blinds None
3 N 3 Vinyl Low-E Double Yes 0.35 0.29 N 6.0 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds None
4 N 3 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds None
5 W 4 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 It 0 in 1 ft 4 in Drapes/blinds None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 403 ft2 403 ft2 46 ft 8 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 1540 84.54 159 .1339 .7
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump/ Split HSPF:8.2 22.2 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split SEER:14.522.2 kBtu/hr 666 cfm 0.75 1 sys#1
7/24/2020 8:26 AM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 3 of 4
FOgM R405-2017 INPUT SUMMARY CHECKLIST REPORT
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.92 50 gal 70 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ftz
DUCTS
----Supply---- ----Return---- Air CFM 25 CFM25 HVAC#
# Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 330 ftz Main 82.5 ft2 Default Leakage Main (Default) (Default) 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
CoolingJan Feb Mar Apr May Jun Jul Au Se Oct Nov Dec
He Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Venting Jan H Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default 8 Ibs/s .ft. 0 ftz Oft 0.3 Main
7/24/2020 8:26 AM EnergyGaugeO USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 4 of 4
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 7008 Plumosa Ln Permit Number:
FL,
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
❑ R401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law
(Section 553.9085,Florida Statutes)requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building.A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal enveloW building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1,as applicable to the method of construction.Where required
by the code official,an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2,and three air changes per hour in Climate Zones 3 through 8.Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 pascals).Testing shall be conducted by either
individuals as defined in Section 553.993(5)or(7), Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i)or
an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions,alterations,renovations,or repairs,of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or
other infiltration control measures.
2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended
infiltration control measures.
3.Interior doors,if installed at the time of the test,shall be open.
4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5.Heating and cooling systems,if installed at the time of the test,shall be turned off.
6.Supply and return registers,if installed at the time of the test,shall be fully open.
R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors,and outdoor combustion air.Where
using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127,the doors shall be tested and listed for the
fireplace.Where using tight-fitting doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows,skylights and doors.
7/24/2020 8:27 AM EnergyGauge@ USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8,where open combustion air ducts provide combustion air to
open combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room,isolated from inside the thermal envelope.Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential.
❑R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)pressure differential.All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5)or
(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing(Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1, Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the system,including the
manufacturer's air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the
entire system,including the manufacturer's air handler enclosure.Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑R403.4 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 1050F(41°C)
or below 55°F(131C)shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that
caused by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause
degradation of the material.Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory). Heated water circulation systems shall be in
accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump.The system return
❑ pipe shall be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy.The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515.Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
7/24/2020 8:27 AM EnergyGaugeOO USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.5.5 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 1/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies(Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature
setting range shall be from 100°F to 140OF(38°C to 60oC).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of
combustion types of service water-heating systems to be turned off.
R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water-heating category.Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors,
and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar
water-heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal;and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential,or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation
including:Natural,Infiltration or Mechanical means.Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole-house mechanical ventilation system fan efficacy. When installed to function as a whole-house mechanical
ventilation system,fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2,Ventilation for Acceptable
Indoor Air Quality,shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces,attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s),then the walls of the space(s)from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19,space permitting,or R-10
otherwise.
R403.7 Heating and cooling equipment(Mandatory).
❑ R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and
indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1.This Code does not allow designer safety factors,provisions for future expansion or other factors that
affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems.New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY a AIRFLOW RATE MAXIMU
(CFM) (CFM/WATT) (CFM)
Range hoods Any 2.8 cfm/watt Any
In-line fan Any 2.8 cfm/watt Any
Bathroom,utility room 10 1.4 cfm/watt <90
Bathroom,utility room 90 2.8 cfm/watt Any
For SI:1 cfm=28.3 Umin. a. When tested in accordance with HVI Standard 916
7/24/2020 8:27 AM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
ElR403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacturer's
expanded performance data shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation(or entering water temperature for water-source equipment),the blower CFM provided by the expanded
performance data,the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space.
Exceptions:
1. Attached single-and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida-registered engineer,in attached single-and multiple-family units,the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1,and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls(Mandatory) Snow-and ice-melting systems,supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F(10°C),and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F(4.81C).
❑ R403.10 Pools and permanent spa energy consumption(Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an
integral part of the heater mounted on the exterior of the heater,or external to and within 3 feet(914 mm)of the heater.Operation
of such switch shall not change the setting of the heater thermostat.Such switches shall be in addition to a circuit breaker for the
power to the heater.Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors.Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar-and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating,computed over an operation season,is from site-recovered
energy,such as from a heat pump or solar energy source,covers or other vapor-retardant means shall not be required.
R403.10.4 Gas-and oil-fired pool and spa heaters. All gas-and oil-fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16,2013,when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
7/24/2020 8:27 AM EnergyGauge@ USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 4 of 5
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is
required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard.
❑ R403.11 Portable spas(Mandatory)he-energy consumption of electric-powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment(Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
Exception:Low-voltage lighting.
R404.1.1 Lighting equipment(Mandatory).Fuel gas lighting systems shall not have continuously burning pilot lights.
7/24/2020 8:27 AM EnergyGaugeO USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 5 of 5
1
' 2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 100
The lower the Energy Performance Index, the more efficient the home.
1.New home or,addition 1. New(From Plans) 12. Ducts, location&insulation level
a)Supply ducts R 6.0
2.Single-family or multiple-family 2. Single-family b) Return ducts R 6.0
c)AHU location Main
3.No.of units(if multiple-family) 3. 1
4.Number of bedrooms 4. 4 13.Cooling system: Capacity 22.2
a)Split system SEER 14.5
5. Is this a worst case?(yes/no) 5. No b)Single package SEER
c)Ground/water source SEER/COP
6.Conditioned floor area(sq.ft.) 6. 1650 d) Room unit/PTAC EER
e)Other
7.Windows,type and area
a) U-factor:(weighted average) 7a. 0.350
b)Solar Heat Gain Coefficient(SHGC) 7b. 0.290 14.Heating system: Capacity 22.2
c)Area 7c. 126.0 a)Split system heat pump HSPF 8.2
b)Single package heat pump HSPF
8.Skylights c) Electric resistance COP
a) U-factor:(weighted average) 8a. NA d)Gas furnace,natural gas AFUE
b)Solar Heat Gain Coefficient(SHGC) 8b. NA e)Gas furnace,LPG AFUE
f)Other
9.Floor type,insulation level:
a)Slab-on-grade(R-value) 9a. 0.0
b)Wood, raised(R-value) 9b. 15.Water heating system
c)Concrete,raised(R-value) 9c. a) Electric resistance EF 0.92
b)Gas fired,natural gas EF
10.Wall type and insulation: c)Gas fired, LPG EF
A. Exterior: d)Solar system with tank EF
1.Wood frame(Insulation R-value) 10A1. e) Dedicated heat pump with tank EF
2.Masonry(Insulation R-value) 10A2. 4.1 f) Heat recovery unit HeatRec%
B.Adjacent: g)Other
1.Wood frame(Insulation R-value) 10131. 13.0
2.Masonry(Insulation R-value) 1062.
16. HVAC credits claimed(Performance Method)
11.Ceiling type and insulation level a)Ceiling fans
a)Under attic 11 a. 30.0 b)Cross ventilation No
b)Single assembly 11b. c)Whole house fan No
c) Knee walls/skylight walls 11 c. d)Multizone cooling credit
d) Radiant barrier installed 11 d. No e)Multizone heating credit
f) Programmable thermostat Yes
'Label required by Section R303.1.3 of the Florida Building Code,Energy Conservation,if not DEFAULT.
I certify that this home has complied with the Florida Building Code,Energy Conservation,through the above energy
saving features which will be ins d(or exceeded)in this home before final inspection.Otherwise,a new EPL
display card will be complet a d on installed code compliant features.
Builder Signature: Date:
Address of New Home: 7008 Plumosa Ln City/FL Zip: , FL
7/24/2020 8:27:05 AM EnergyGauge®USA 6.0.03(Rev.1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
2017- AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 7008 Plumosa Ln 1650 B RHG-S Builder Name: WADE JURNEY HOMES
Street: 7008 Plumosa Ln Permit Office: St.Lucie
City,State,Zip: FL, Permit Number: Y
U
Owner: WADE JURNEY HOMES Jurisdiction: 661000 W
Design Location: FL,MELBOURNE_REGIONAL_AP
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
Ceiling/attic the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity
sealed. with a material having a thermal resistance of R-3
Knee walls shall be sealed. per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/door jambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spac 3s.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the drywall. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind p'pung and wiring,
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a.In addition,inspection of log walls shall be in accordance with the provisions of]CC-400.
7/24/2020 8:27 AM EnergyGaugeOO USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 1
Project Summary Job: 7008 Plumosa Ln 1650 B...
wrightsoft9 Date: 07/24/2020
House By: LVL
One Stop Cooling and Heating Plan: 1650 B LHG
7225 Sardscove Coot,Winter Park FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:wwwOreStopCooling.com License:CAC1817652
Proiect Information
For: WADE JURNEY
Notes:
Design Information
Weather: Melbourne Regional AP,FL,US
Winter Design Conditions Summer Design Conditions
Outside db 43 OF Outside db 91 OF
Inside db 68 OF Inside db 74 OF
Design TD 25 OF Design TD 17 OF
Daily range L
Relative humidity 50 %
Moisture difference 65 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13431 Btuh Structure 12819 Btuh
Ducts 1382 Btuh Ducts 2875 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 14813 Btuh Use manufacturers data n
Rate/swin multiplier 0.96
Infiltration Equipmen sensible load 15035 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 3581 Btuh
Ducts 771 Btuh
Central vent(0 cfm) 0 Btuh
Heating Cooling (none)
Area(ft2) 1641 1641 Equipment latent load 4352 Btuh
Volume(ft3) 13130 13130
Air changes/hour 0.38 0.20 Equipment Total Load(Sen+Lat) 19387 Btuh
Equiv.AVF(cfm) 83 44 Req.total capacity at 0.75 SHR 1.7 ton
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carrier
Trade CARRIER Trade CARRIER
Model CH14NBO2400GOA0 Cond CH14NBO2400GOA0
AHRI ref 9162301 Coil FB4CNP025L
AHRI ref 9162301
Efficiency 8.2 HSPF Efficiency 11.5 EER,14.5 SEER
Heating Input Sensible cooling 16650 Btuh
Heating output 22200 Btuh @ 470F Latent cooling 5550 Btuh
Temperature rise 0 IF Total cooling 22200 Btuh
Actual airflow 0 cfm Actual airflow 740 cfm
Air flow factor 0 cim/Btuh Airflowfactor 0.047 cfm/Btuh
Static pressure 0 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.78
Capacity balance point=34 OF
Backup:
Input=13 kW, Output=43093 Btuh,100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrightsc ft- 2020-,U-240821:01
- -•� � Rigft-Sute®Uriversal 201919.0.19 RSU27934 Page 1
...\Des1Rop\TEMP\7008 Plunosa Ln 1650 B RHG-S.rd Calc=W8 Frord Door faces:S
+wrightsoft° Right-JO Worksheet Job: 7008 Plumosa Ln 1650 B RHG...
House Date: 07/24/2020
LVL
One Stop Cooling and Heating Pan: 1650 B LHG
7225 Sandscove Coat,Winter Park FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:wewvOrLStopCooling.com License:CAC1817652
1 Room name House Krr
2 Exposed wall 145.5 ft 12.0 It
3 Room height 8.0 It d 8.0 ft heaHcool
4 Room dimensions 12.0 x 12.5 It
5 Room area 1641.3 ftz 150.0 ftr
Ty Construction U-value Or HTM Area (ft) Load Area UP) Load
number (Btuh/ftZ°F) (Btu 2) or perimeter (ft) (BWh) or perimeter (ft) (Btuh)
Heat Cool Gross NIPS Heat Cool Gross N1P/S Heat Cool
6 13A-4as - - 0.143 ne 3.52 2.80 308.- 253 889 708 96 90 317 252-G 4A5-2ov 0.320 ne 7.87 17.44 6 0 47 105 6 0 47 105
-G 4A5-2ov 0.320 ne 7.87 17.44 30 0 236 523 0 0 0 0
p 11 D0. ---.- -- _-- 0.390 ne _9,59. 12.01 19 19. _ __185 _ 231--- -- - 0 -. _. __0 ._.._ _ -0 .. _ _. 0
11 13A-4ocs 0.143 se 3.52 2.80 292 262 922 734 0 0 0 0
4A5-2ov 0.320 se 7.87 1723 30 2 236 517 0 0 0 0
13A-4ocs - _...0.143 -sw 3.52 2.80 144 94 -- -329 - 262 6 ---0 0 - 0
4A5-2ov 0.320 sw 7.87 1723 30 2 236 517 0 0 0 0
11DO".._-_--___ _- ------0.390. sw 9.59__-. 7.84.. _.__.20 __._20 _.._196 .160:._._ _ 0 _ 0 ._---_ 0 _ 0
V)/ 13A-4ocs 0.143 nw 3.52 2BO 420 390 1372 1093 0 0 0 0
4A5-2ov -0.320._n ---7.87 17.44___ 30 0 _-__236 - _523- O-- 0-.._ _ O
12C-Osw 0.091 - 224 1.45 292 274 614 397 0- 0 0 0
-D
.� _11D0 -- 0.390_ .n.. 9.59._ .." 7.84 ..._.18 18_ _. ,-169- --.-138 - - 0. _ _0 ...__.. 0.
C 166-30ad 0.032 0.79 1.74 _1 641 1641 1292 2852 150 150 118 26.1
F.,__. 22A-tpm;._. ..-.__- __.._...1JW 2903._- -0.60 1641 -..._- 146__.._ 4224 - - - -
0 150 12 348 0
6 c)AED exausion 0 -110
Envelopeloss/gain 11183 8761 830 508
12 a) Infiltration 2248 808 185 67
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants@ 230 5 1150 0 0
Applianoes(other 2100 1200
Subtotal(lines 6 to 13) 13431 12819 1016 1774
Less e)temalload 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 13431 12819 1016 1774
15 Ductloads 1100/0 229% 1382 2875 10-/,.l 220X 105 398
Total roam load 14813 15694 1120 2172
Air required(cfm) 0 740 0 102
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-rlF wrGghtsoR� 2020-Ju-240821:01
" ' """' Right-Sute®Uriversal 201919.0.19 RSU27934 Page 1
1DesIdop\TEMPV008 Planosa Ln 1650 B RHG-S.ru Calc=W8 Front Door faces:S
1-wrightsoft Right-J®Worksheet Job: 7008 Plumosa Ln 1650 B RHG...
House Date: 07/24/2020
B}r. LVL
One Stop Cooling and Heating Pfan: 1650 B LHG
7225 Sandsmve Coot,Wirder Park,FL 32792 Phora:(407)629-6920 Fax:(407)629-9307 Web:wwwOreStopGoolirg.com License:CAC1817652
1 Room name LAUN FOY
2 E)posed wall 0 ft 3.5 ft
3 Room height 8.0 ft heat/cool 8.0 ft heaU000l
4 Room dimensions 7.0 x 4.0 ft 1.0 x 211.0 ft
5 Room area 28.0 f12 211.0 ft2
Ty Construction U-value Or HTM Area (ft) Load Area (ft2) Load
number (BtuhAF-OF) (Btu I or perimeter (ft) (Bluh) or perimeter (it) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V 13A-4ocs -'0.143 ne 3.52 2.80 - 0 0 . .-. 0 - 0 - - 0 6- 0 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0,
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
11D0_ _...__.___._. .._...._ _,_0.390 ne 9.59 .12.01 _ 0 _0. _ ._O -0., - __ 0 -----.-0
11 W 13A-4ocs 0.143 se 3.52 2BO 0 0 0 0 0 0 0 0
I� 4A5-2oy-- --0.320 se. _ _7.07. _ 1723 ._-0 -0 .. --0 ---0 - -M 0 0 _ __ _ 0 _ 0
_- 13A-4ocs 0.143 sw 3.52 2.80 0 0 0 0 8 - 27 21
4A5-2ov 0.320 sw 7.87 1723 0 0 _ 0 0 0 0 0 0
_ 11DO----_-- _- _ - 0.390 sw_ -.9.59, -- 7.84- _ _ _ 0 .._. _-_O- .._._. 0 0. _ _ 20 20 -196-_--- . 16Q
13A-4ocs 0.143 nw 3.52 2,80 0 0 0 0 0 0 0 0
_--_ , 4A5-2ov_. 0.320 nw 7.87 17.44 0._---- 0 --- ---0- - 0--._ __ 0 0 0 0
R 12C Osw 0091 224 1.45 0 0 0 0 132 114 256 166
�A 11 D0..---. -0.390- n _9,59 _ 7.84 ---0--- 0 ._-__0 _ %.. -_._18 __ _ .18 169. .- -- .138_
C 166-30ad _ 0.032 0.79 1.74 28 28 22 49 211 211 166 367
_F.. 22A tpm, _ _.1.180 = 29.W -0.00 . ..28 0 _ 0 0 211 _._..-4 102 __0
6 c)AED excursion -35 -63
Envelope losstgain 22 13 915 788
12 a) Infiltration 0 0 54 19
b) Room ventilation 0 0 0 O
13 Internal gains: Ooaipants@ 230 0 0 0 0
Applianoes(other 500 100
Subtotal(lines 6 to 13) 22 513 969 908
Less e)temalload 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution -22 513 969 -908
14 Subtotal 0 0 0 0
151 Dud loads 10% 22% 0 0 100/1 220X 0 0
Total room load 0 0 0 0
Air required(cfm) 0 0 0 0
Calculations approved bVACCA to meet all requirements of Manual J 8th Ed.
- wrigFrrtsoft- 2020-Jul-2408:21:01
"�A Right-Sute®Uriversal201919.0.19RSU27934 Paget
NDesktop\TEMP17008 Plunosa Ln 1650 B RHG-S.rut Calc=MJ8 Frort Door faces:S
-wrightsoft Rig ht-J®Worksheet Job: 7008 Plumosa Ln 1650 B RHG...
House Date: 07/24/2020
B y. LVL
One Stop Cooling and Heating Plan: 1650 B LHG
7225 Sardscove Coot,W ir4er Park,FL 32792 Ptnne:(407)629-6920 Fax:(407)629-9307 Web:www.OreStOPCODlirig.com License:CAM 817652
1 Room name FLEX
2 5posed wall 0 It 10.5 ft
3 Room height 8.0 ft heatt000l 8.0 ft heat/cool
4 Room dimensions 3.5 x 3.0 ft 14.0 x 10.5 ft
5 Room area 10.5 ftz 147.0 ft2
Ty Construction U-value Or HTM Area Load Area (W) Load
number (BWhR -F) (Btuh/ftz) or perimeter (ft) (B[uh) or perimeter (ft) (Bluh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Coal
6 13A flocs -- 0.143 ne ..- 3.52 - 2.80. 0 0 .. /0 6 0. _0.__.... ....0 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
_=-71D 11D0_ _-____--- - ----_0390 ne _.- _9.59,- 12.01 - 0 0. -- 0 _ _ ..0...__--- 0- - --0 - -.- 0-- - -----0-
11 VV 13AAors 0.143 se 3.52 2.80 0 0 0 6 0 0 0 0
I� im- ._ __ ._ ... 0.390 ..sw 987 1723 _ __ .6 -_ 0 _-.--5- -- _ 0. _ _ _0 0 _ _0 6 4A5.2ov 0.320 � 7`87 723 0 0 0 0 0 0, 0 0
4A5-2ov 0.320 sw 7.87 1723 0 0 0 0 0 0 0 0
1N 13A-flocs --- - - 0.143 sw 3.59 ..7.84 __. .'_0 _ ___ 0 -- 0 _ 0..__.. 0_._. .0 __ __0 .__..0
13A-4ocs 0.143 nw 3.52 2.80 0 0 0 0 84 69 243 193
--_-T-G 4A5.2ov_---- - __0320, nw_ _ -_7B7 _- -,17.44 _._ 0. 0 _0 _ 0 15 0 118 262
R 12C-0sN 0.091 224- 1.45 28 28 63 41 0 _-.0._.._ -0 _ .0.
----D 11D0 �- - 0.390 .n- ----9.59 7.84 0:_ .0 - 0. 0---- -.0 - -0
C 16B-30ad 0.032_ 01.9 1.74 11 11 8 18 147 147 116 _ 255
F _ _ 22A-tpm-.__ - -: 1,180 29.03 0.00 11 _. 0 0 _0 ._. _147. 11._ _.. 305 0
6 c)AED excursion -4 55
Envelope lossdgain 71 551 781 766
12 a) Infiltration 0 0 162 58
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants@ 230 0 0 0 0
Applianoes/other 0 300
Subtotal(lines 6to 13) 171 55 944 1124
Less extemalload 0 0 0 0
Less transfer 0 0 0 0
Redistribution -71 -55 143 134
14 Subtotal 0 0 1087 1258
15 Dudloads 100/0 220/6 0 0 10°/ 22% 112 282
Total room load 0 0 1199 1540
Air required(dm) 0 0 0 73
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
OFF wrigi�tsoR�� """'"' '"'"""""'�'^ Right-Bu 2020-JJ-240821:01
te®Universal 2019 19.0.19 RSU27934 Page 3
.\Desktop\TEMP\7008 Plunosa Ln 1650 8 RHG-S.rut Calc=MJ8 Front Door faces:S
"wrightsoft Right-M Worksheet Job: 7008 Plumosa Ln 1650 B RHG...
House Date: 07/24/2020
LVIL
One Stop Cooling and Heating Pan: 1650 B LHG
7225 Sardscove Court,Winter Park FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:wwwOrLStopGoolirig.com License:GAM 817652
1 Room name BED 3 BA 2
2 Exposed wall 10.0 ft 5.5 ft
3 Room height 8.0 it head ool 8.0 ft heaVcool
4 Room dimensions 14.0 x 10.0 ft 10.0 x 5.5 ft
5 Room area 140.0 ft2 55.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (fie) Load
number (BtuhAt--n (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V 13A-46cs- -- - 0.143 ne 3.52 2.80 _.....0._ 0 0 0'
0 .0._.. 0 .0
�--L-(G 4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
11D0_` __ .. _ - -_ 0.390_,ne _ 9.59 - _12.01 , 0. _ - 0 _ 0_--- 0. _ 0_. . -0 0 _ _- ._0
11 13AAocs 0.143 se 3.52 2.80 0 0 0 0 0 0 0 0
4A5-2ov - .0.320 se 7.87 ,1723 -0 0 --0 - - 0 0 0-- 0 ._0.
13A-4 0.143 sw 3.52 2.80 0 0 0 0 0 0 0 0
as
4A5-2ov 0.320 sw 7.87 1723 0 0 0 0 0 .0 0 0
.11D0_ --- - ___0.390._sw 9.59._. ..7.84. _0 _. . .,..0 0-. 0 ._...:._ _0.
�j 13A-4ors 0.143 nw 3.52 2.80 80 65 229 182 44 44 155 123
�-G 4A5-2w _ _0_320_rrvv ._....787----17.44 -----15 -- -0 118 _. _ 262 .-- -0 -0 ---- 0 - O
R 12C-bw 0.091 224 1.45 0 0 0 0 0 0 0 0
11 D0_. p,390 n _ 9.59: ._7.84 -0 -- 0 - - --0- 0 0
16B30ad ... -y0.032_ - -079. -1..74_.._._.__.140 140 _--110, - - 243 ..... . .. - - --
F- _ ,22A-tpm_-- _ - - __ 1.180_._ 29.03-- --0.00._. _.: 1.40 . _ 10 290 0 ___- 55 . 6 -_--_ 160 -
6 c)AED excursion 62 -16
Envelope losstgain 747 748 358 203
12 a) Infiltration 155 56 85 31
b) Room ventilation 0 0 0 0
13 Internal gains: Occupantspa 230 1 230 0 0
Appliancestother 0 0
Subtotal(lines 6 to 13) 902 1034 443 233
Less extemal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 191 179 75 70
14 Subtotal 1093 1213 518 304
15 Dudloads 1 100/0 229/. 112 272 10% 22°/ 53 68
Total room load 1205 1485 571 372
Air required(dm) 01 70 0 18
Calculations approved byACCAto meet all requirements of Manual J 8th.Ed.
-r §- wrightsoR- 2020-Jul-240821:01
ACCP. RiglI-Sute®Uriversal 2019 19.0.19 RSU27934 Page 4
\DesMop\TEMP\7008 Plurnosa Ln 1650 B RHG-S.nd Calc=W8 Frond Door faces:S
-wrightsoft° Right-M Worksheet Job: 7008 Plurnosa Ln 1650 B RHG...
House Date: 07/24/2020
LVL
One Stop Cooling and Heating Pan: 1650 B LHG
7225 Sandscove Court,W inter Parr FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:wwkOneftpGooling.corn License:CAC1817652
1 Room name BED 2 BED 1
2 Fxlcosed wall 28.5 ft 10.5 it
3 Room height 8.0 ft heat/tool 8.0 ft heaUCool
4 Roomdmensons 1.0 x 162.3 ft 11.0 x 10.5 ft
5 Room area 162.3 ft2 115.5 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Bluh/ft2--R (BtuhAt2) or perimeter (ft) (Btuh) or perimeter (ft) (BWh)
Heat Cool Gross N/PA3 Heat Cool Gross N/P/S Heat Cool
6 W 13A-4ocs _. 0.143 ne 3.52 2.80 0 0 0 0 -0 0 6 0
�L--GG 4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
11D0_ _-_-_ _. _ _ -_-.._.0.390_ne_,_____.9.59 --_ 12.01 _0_ - -- ..-0_._r_ _ .-0..-_-_._-_0.---..._ _0- 0.
11 V)/ 13A-4ocs 0.143 se 3.52 2.80 20 20 70 56 84 69 243 193
G 4A5-2ov .0320 -se- _ 7.87 1723_ 0 0 0 0_.- 15 1 118 258
13A-4ocs 0143 sw 3.52 2.80 116 86 303 241 0 0 0 6
4A5-2ov 0.320 sw 7.87 1723 30 2 236 517 0 0 0 0
11D0_.--_- _ 0.390_ sw _ 9.59._ _.7.84 _....:0 _ 0 ._-0 .._-- _.0. ._. 0 0 0 _0
W 13A-4ocs 0143 nw 3.52 2.80 92 92 324 258 0 0 0 0
I--G 4A5-2ov __ 0.320._nw 7.87 17.44_ 0 0-. 0- 0 . .--- 0- 0-- - 0-- -----0
R 12C-Osw -0.091 - 224 1.45 -- 0 0 0 0 BB -88 197 127
I-D .11D0 - - 0390 n - 9.59. 7.84 - 0 - _0-_, _ --0-.-- 0,----, -_0 __0 ._ 0 0
C _16B-30ad._.._ ._._. 0.032 0.79 _ --1,74 .. ._ 162__-- 162- 128..._ 282- _118 . .. 116_-.._._ 91. __.._201.
_.
.22A-tpm„-_- - __._ .1.180 _. __29.03. 0.00......__162 _-- . .29 ._ -_827 __-- _.,._0_ 116.. 1,1 __-- 305- _---__.0
6 c)AED excursion 127 54
Envelopelos/gain 1888 1480 954 834
12 a) Infiltration 440 158 162 58
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants@ 230 1 230 1 230
Appliances(other 0 0
Subtotal(lines 6to 13) 2328 1869 1116 1123
Less extemal load 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 184 173 48 45
14 Subtotal 2512 2041 1164 1167
15 Ductloads 10% 22% 259 458 10°/ 220/6 120 262
Total room load 2771 2499 1283 1429
Air required(cfm) 0 118 0 67
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrGgtitsoft- 2020-JU-24 0821:01
RigN-Scite6Uriversa1201919.0.19 RSU27934 Page s
\Deskep\TEMPV008 Plunosa Ln 1650 B RHG-S.rut Calc=W8 Front Door faces:S
-wrightsoft° Right-M Worksheet Job: 7008 Plurnosa Ln 1650 B RHG...
House Date: 07/24/2020
VL
One Stop Cooling and Heating Pan: 1650 B LHG
7225 Sandscove Court,W irder Park,FL 32792 Phore:(407)629-6920 Fax:(407)629-9307 Web:wwwOneStopCooling.com License:CAM 817652
1 Room name NEED MWIC
2 Exposed wall 11.0 It 18.5 ft
3 Room height 8.0 ft heal/cool 8.0 It heaVcool
4 Room dimensions 14.5 x 11.0 ft 6.0 x 12.5 ft
5 Room area 159.5 ft2 75.0 ft2
Ty Construction U-value Or HTM Area (ftz) Load Area (ft2) Load
number (BtijhAtz--q (BtuhM) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/PS Heat Cool Gross N/PS Heat Cool
6 VI 13A-4ocs 0.143 ne 3.52 2.80 0 _ . 6 ..0 0 . __49 48 169 135
L-G 4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0;
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
--_ 11 DO-_ _ _. 0.390 -ne-- ._ 9.59 _ .12.01 ..__ -.0- 0._ _. 1-0 0_
11 vp 13A-4ocs 0.143 se 3.52 2.80 88 73 257 205 100 100 352 280
4A5-2ov _ -_ _0.320 _se _-- 7.87_ 1723 _ _ 15 _ _. 1 118 _ 258 _
W, 13A-46 s 0.143 svv 3.52 2.80 0 0 0 0 0 0 0 0
l�-pG 4A5-2ov .0.320 sw 7.87 1723 0 0 0 0 . 0 0 0 0
11D0 ._ -- _.._0,390- sw -_ 9.591._-7.84. _ _-_ 0 __ 0 ._A -- _ -0 -- - _.0 _ . O__ _0. --_0.
W 13A-4ocs 0.143 nw 3.52 2.80 0 0 0 0 0 0 0 0
t-G 4A5-2ov.._ . - 032.._.n.w --7.87 . .17.44 ._._....0 --- - 0- ------0 - O...v -- -0 - - 0- 0 �.
R 12C-0sw 0.091 - 224 1.45 0 0 6 0 0 -0 0 0
-D 11D0-_,-- _ __ 0.390 n 9.59 .7.84 _ -:0_. 0 .--- 0 p.._-_ -0. _ -- A --- _ -0-
_ ,.Q
C 16B-30ad 0.032 _ 0.79 1.74 _ _160 1.60 126 277 ___ 75 75 59 130
F.___ •22A-ipm__. 1.180 _ 29.03 .. •0.00 _ :_160 v_ 11 - . 319 ,._ - 0 75 19. _ 537 _0
6 c)AED excursion 42 -42
Envelope loss/gain 820 782 1117 503
12 a) Infiltration 170 61 286 103
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants@ 230 2 460 0 0
Applianoes(other 0 0
Subtotal(lines 6 to 13) 1990 1303 1403 606
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 48 45 0 0
14 Subtotal 1037 1348 1403 606
1151 Duct loads 10% 220/a 107 302 100/6 22% 144 136
Total room load 1144 1650 1547 742
Air required(dim) 0 78 0 35
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
F wrightsoft� 2020-J11-2 4 0 8 21:01
Rigfd-Sllte®Uriversal 201919.0.19 RSU27934 Page 6
ACCN ..\Desktop\TEMP\7008 Plurnosa Ln 1650 B RHG-S.nd Calc=MJ8 Frort Door faces:S
-wrightsoft° Right-M Worksheet Job: 7008 Plumosa Ln 1650 B RHG...
House Date: 07/24/2020
By.� LVL
One Stop Cooling and Heating Pfan: 1650 B LHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:www0neStopCooling.com License:CAM 817652
1 Room name MBA WIC 1
2 Exposed wall O ft O ft
3 Room height 8.0 It headcool 8.0 ft heat/cool
4 Room dimensions 5.5 x 11.0 ft 1.0 x 24.5 ft
5 Room area 60.5 112 24.5 f12
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Bhuh/ft-°Fj (BluW) or perimeter (ft) (Bhjh) or perimeter (ft) (Btuh)
Heat Cool Gross NjPS Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 ne 3.52 2.80 0 0 .. 0 0 - 0- 6 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 .0 0 0
4A5-2ov 0.320 ne 7.87 17.44 0 0 0 0 0 0 0 0
--- _ 11D0--- - _. .._0.390 ne_ 9.59----. 12.01 ---0 - -- 0 __0.----- 0 _. .-- 0- - -0 _.Q.--_- --0-
11 13A-4ocs 0.143 se 3.52 2.80 0 0 0 0 0 0 0 0
4A5-2ov 0.320 se 7.87 1723 0 0 0 0 0 0 0 0
- -_ -
T;;G
13A-4as _-0.143. sw ---3.52 2.80 -0- O -__-•-O---- 0 0 0 -0 --0
D 4A5-20v 0.320 sw 7.87 1723 0 -0 0 0 0 0 0 0
pppp 11D0 - _ ---- -0.390 _sw. ' .- .9.59 _ _ 7.84 .0 _- - -0 -- ---_0 - . . 0 --- .- 0._ O_._ .0 . .._ 0
W 13A-4o s 0.143 nw 3.52 2.80 0 0 0 0 0 0 0 0
4A5-2ov_.-. .- .. _ __ 0,320 nw_- 7B7,. _-17.44 0. __.___0_- __-_0--- 0 0 0 0-
R - 12C-Osw 0.091 224 1.45 70 0 0 0 44 496 64
11DO_ _. __ _0.390 n 9.59. __ 7.84 0 _- _ 0 _ 0 _. 0 0
C.._._.. 166-30ad___...... 0.032_ _0.79_ __1,74_. _...._61 0 61 r_.... 48, ___ 105 ,._ - -25 25. 19 _. _ 43
F 22A-4�m 1.180 - 29.03. 0.00 61 1-0 0 .- 25 - 0 - 0 0
6 c)AED excursion. -7 -7
Envelopeloss(gain 48 98 118 99
12 a) Infiltration 0 0 0 0
b) Roomventlation 0 0 0 0
13 Internal gains: Occupants@ 230 0 0 0 0
Applianoestother 0 0
Subtotal(lines 6 to 13) 48 98 118 99
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redisbibution 191 179 120 594
14 Subtotal 239 277 238 693
15 Duct loads 10% 229/. 25 62 10% 220% 25 155
Total room load 263 MO 263 849
Air required(cfm) 0 16 0 40
Calculations approved bVACCA to meet all requirements of Manual J 8th Ed.
_HF wrightsoft- 2020-Jt1-2408:21:01
'" Righ-SuiteOUriversal201919.0.19 RSU27934ACCk Page 7
Desktop%TEMPV008 Plumosa Ln 1650 8 RHG-S.rud Calc=MJ8 Frort Door faces:S
I-wrightsoft° Right-JO Worksheet Job: 7008 Plurnosa Ln 1650 B RHG...
House Date: 07/24/2020
VIL
One Stop Cooling and Heating Phan: 1650 B LHG
7225 Sardscove Coat,W irter Park,FL 32792 Phore:(407)629-6920 Fax:(407)629-9307 Web:owwvOreStc)pCooling.com License:CAM 817652
1 Room name LIV
2 EVosed wall 35.5 ft
3 Room height 8.0 ft heat/000l
4 Room dimensions 1.0 x 302.5 ft
5 Room area 302.5 ftz
i
Ty Construction U-value Or HTM Area (112) Load Area Load
number (Bluh/Rz°F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter
Heat Cool Gross N/PS Heat Cool Gross N/P/5 Heat Cool
6 VI 13A-4ocs.. - 0.143 ne 3.52 2.80 164 -115 464 - -322
{L�--(CG 4A5-2ov, 0.320 ne 7.87 17.44 0 0 0 0
4A5.2ov 0.320 ne 7.87 17.44 30 0 236 523
11D0- - 0.390_ne _ 959 9.59 12.01. 19 .. .__ 19 -j85 --231-
11 W 13A-4o s 0.143 se 3.52 2.80 0 0 0 0
I-G 4A5-2ov- -- ---0.320 se 7.87 1723 -- 0 - --- 0 -„ 0--- ---g
1::�G
13A-flocs 0.143 sw 3.522.80 0 0 0 0
4A5-2ov 0.320 sw 7.87 1723 0 0 0 0
11 D0._____. 0.390. sw, 9.59 .. ._7.84._. _ -.0 .. - 0 _ __-0 __0
13A-4ocs - 0.143 nw 3.52 2.80 120 120 422 336
t-- 4A5-2ov- 0.320 rnv_ 7.87 17.44, ----0 - 0 0 -- 0 - --
R 12C-Osw 0.091 a24 1.45 0. 0 0 0
D 11 DO__..... . - .- 0.390. 0 9.59 ._7.84 0 -. ..__0 _0_ 0•.
C 16B-30ad 0.032 0.79 1.74 303 303 238 526
F- 22A-tpm._.. . . 1.180 _- 29.03 . ..0.00. .303 36 1030--_ 0 .
6 c)AED excursion -56
Envelope loss(gain 2515 1882
12 a) Infiltration 549 197
b) Room ventilation 0 0
13 Internal gains: Occupants Ca 230 0 0
Applianceslother 0
Subtotal(lines 6 to 13) 3064 2079
Less external load 0 0
Less transfer 0 0
Redistribution 61 58
14 Subtotal 3125 2137
15 Duct loads I 10% 22°/ 322 479
Total room load 3447 2616
Air required(dm) I 1 0 123
Calculations approved bVACCAto meet all requirements of Manual J 8th Ed.
-1k- wrGght .vt:- 2020-.h1-240821:01
"'" Rigtt-SuteOUriversall 201919.0.19 RSU27934 Page 8
\Desktop\TEMP\7008 Plurnosa Ln 1650 B RHG-S.rut Calc=W8 Frort Door faces:S
Duct System Summary Job: 7008 Plumosa Ln 1650 B...
wrightsofty Y rY Date: 07/24/2020
House By-. LVL
One Stop Cooling and Heating Plan: 1650 B LHG
7225 Sandscove Coot,Wirter Park,FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:wwwOneStopCooling.com License:CAC1817652
Project • •
For: WADEJURNEY
Heating Cooling
External static pressure 0 in H2O 0.50 in H2O
Pressure losses 0.16 in H2O 0.16 in H2O
Available static pressure -0.2 in H2O 0.34 in H2O
Supply/return available pressure -0.080/-0.080 in H2O 0.170/0.170 in H2O
Lowest friction rate -0.12 in/100ft 0.264 in/100ft
Actual air flow 0 cf-n 740 cf n
Total effective length(TEL) 129 ft
SupplyDeta il Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FIR (in) (in) Mat Ln(ft) Ln(ft) Trunk
BA 2 c 372 0 18 0.311 4.0 Ox 0 VI Fx 14.2 95.0 sti
BED 1 c 1429 0 67 0.282 6.0 Ox 0 VIFx 20.5 100.0 sti
BED2 c 2499 0 118 0.300 6.0 Ox0 VIFx 18.3 95.0 sti
BEDS c 1485 0 70 0.295 6.0 Ox0 VIFx 15.4 100.0 sti
FLEX c 1540 0 73 0.299 5.0 Ox 0 VIFx 23.6 90.0 st2
Krr c 2172 0 102 0.264 6.0 Ox 0 VIFx 28.6 100.0 st2
Llv c 2616 0 123 0.293 6.0 Ox 0 VIFx 26.1 90.0 st2
MBA c 340 0 16 0.293 4.0 Ox 0 VIFx 21.2 95.0 st2
MBED c 1650 0 78 0.305 6.0 Ox 0 VIFx 21.5 90.0 st2
MWIC c 742 0 35 0.266 4.0 Ox 0 VIFx 33.0 95.0 st2
WIC 1 c 849 0 40 0.313 4.0 Ox 0 VI Fx 13.7 95.0 sti
SupplyDetail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk
st2 PeakAVF 0 427 0.264 544 12.0 0 x 0 VinIFIX
sti PeakAVF 0 313 0.282 708 9.0 0 x 0 VInIFIX
-Fk Wrightsoft- 2020-JU-240821:02
•.,.,.• ••�, _•, Right-SuteOUriversal 201919.0.19 RSU27934 Page 1
XCK
..\Desktop\TEMPV008 Plunosa Ln 1650 B RHG-S.nd Calc=W8 Front Door faces:S
TableReturn Branch Detail
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening(in) Mat Trunk
rb1 Ox 0 0 740 0 0 0 0 Ox 0 VIFx
t Wrlgilt9oft" 2020-JJ-240821:02
RigM-Su 9
te®Uriversal 201919.0.19 RSU27934 Page 2
...\DeslQop\TEMP17008 Plunasa Ln 1650 B RHG-S.nd Calc=MJ8 Frort Door faces:S
Static Pressure and Friction Rate Job: 7008 Plumosa Ln 1650 B...
+�- wrightsoft® Date: 07/24/2020
House By: LVL
One Stop Cooling and Heating Plan: 1650 B LHG
7225 Sardscove Coot,W inter Parr FL 32792 Ptnre:(407)629-6920 Fax:(407)629-9307 Web:wwwOreStopCooling.com Licerse:CAC1817652
Project • •
For: WADEJURNEY
AvailablePressure
Heating Cooling
(in H2O) (in H2O)
External static pressure 0 0.50
Pressure losses
Coil 0 0
Heat exchanger 0 0
Supply diffusers 0.03 0.03
Return grilles 0.03 0.03
Filter 0.10 0.10
Humidifier 0 0
Balancing damper 0 0
Other device 0 0
Available static pressure -0.2 0.34
Total •
Supply Return
(ft) (ft)
Measured length of run-out 13 0
Measured length of trunk 16 0
Equivalent length of fittings 100 0
Total length 129 0
Total effective length 129
Friction
Heating Cooling
(in/100ft) (in/100ft)
Supply Ducts -0.124 <0.06 0.264 >0.18
Return Ducts -0.124 <0.06 0.264 >0.18
Fitting Equivalent LengthDetails
Supply 4X--35,11 A=20,11 G=5,11 G=5,1 A=35:Total EL=100
Return TotalEL=0
wrightsoft- 2020,U-24 0621:02
•• • R gFd-Srite®Uriversa1201919.0.19 RSU27934 Page 1
\Deskop\TEMP\7008 Plunosa Ln 1650 B RHG-S.rrt Calc=W8 Frort Door faces:S
Main
LN pp KIT MWIC
1�2xcfm
10x8 6" Bx
123 cfm 35'fm
4"
6 �StRFLEX1D 678c�m�c 72cfm1. 4 x4 MBED
12„ Bx4
24x4 �p5
BED 3 6Scfm
4"Dryer Dud to Roof
Cap wlDryerVent Box p 5 m
7'0 cfm T LAUN 40x f_
RA 24x14 WIC 1
740 cfm 6 BED 1
24 x 4 A/C-1:2.0 rCN
14.0 SEER H.P.
13A2 8x4 ACSLAB BYBUILDER
18 cfm 2'FRCM WALL
4"Bath Ductto Roof
WIFan
Broan 1688F 6" SRB 2 2.0 ton W15KW @240V 1PH
x 14X14 Plen
ON Platform
fiw cfm
FOY
GAR
BED 2
Job#:7008 Plumosa Ln 1650 B RHG-S One Stop Cooling and Heating Scale:1 :74
Performed by LVL for: Page 1
WADE JURNEY 7225 SandSCOve Court Right Suite®Universal 2019
1s.o.lsRsu2793a
Winter Park,FL32792
Phone:(407)629-6920 Fax:(407)629-9307
www.OneStopCooling.com