HomeMy WebLinkAboutResidential Plans Examiner Review FormACCK e
Aroraaryosemsaranem
County, Town, Municipality, Jurisdiction
Header Information
Contractor Florida Breeze
Mechanical License # CAC1814113
Building Plan # EASTHAM
Home Address (Street or Lot#, Block, Subdivision) CREEKSIDE LOT 71
REQUIRED ATTACHMENTS'
Form
RPER 1.01
8 Mar 10
ATTACHED
Manual A Form (and supporting worksheets):
Yes 0
No ❑
or MJ1AE Form' (and supporting worksheets):
Yes ❑
No ❑X
OEM performance data (heating, cooling, blower):
Yes ❑X
No ❑
Manual D Friction Rate Worksheet:
Yes ❑
No ❑X
Dud distribution system sketch:
Yes ❑
No ❑X
` esign Loonanions
Building Construction Information
Winter Design Conditions
Building
" Outdoor temperature
42
OF
Orientation (Front door faces)
North
Indoor temperature
70
OF
North, East, West, South, Northeast, Northwest, Southeast, Southwest
,.t Total heat loss
25729
Btu/h
Number of bedrooms
3
Summer Design Conditions
Conditioned floor area
1747 Sq Ft
Outdoor temperature
90
of
Number of occupants
4
Indoor temperature
75
OF
Windows
Grains difference 61
0 Gr @ 50 % Rh
Eave overhang depth
Ft Roof
Sensible heat gain
19699
Btu/h
Internal shade
<—
Eave
Latent heat gain
5494
Btu/h
Blinds, drapes, eft
Depth
Window
Total heat gain
25192
Btu/h
Number of skylights
— 0
40
Heating Equipment Data
Cooling Equipment
Data
Blower Data
Equipment type
Heat pump
Equipment type
Heat pump 1385 CFM
Heating CFM
Furnace, Had pump, Boiler, etc.
Air conditioner, Heat pump,etc
Model 25HBC530A*030* Model
25HBC530A*030*
Cooling CFM 1 A CFM
Heating output capacity
28200 Btu/h
Sensible cooling capacity
21300 Btu/h
Heat pumps - capacity at whiter design outdoor conditions
Latent cooling capacity
71 0 0 Btu/h
Auxiliary heat output capacity
Btum
Total cooling capacity
28400 Btu/h
HVAC DUCT DISTRIBUTION
Design airflow
1480 CFM
Longest supply duct:
Ft Duct Materials Used (circle)
Trunk Duct: Duct board le Sheet metal,
External Static Pressure (ESP)
0.46 IWC
Longest return duct:
17 Ft Lined sheet metal, Other (specify)
Component Pressure Losses (CPL) 0 25 IWC
Available Static Pressure (ASP) 0.213 IWC
ASP = ESP - CPL
Contractor's Printed Name
Contractor's Signature
Total Effective Length (TEL) 63 Ft
Friction Rate: 0.34 IWC
Friction Rate = (ASP ■ 100) + TEL
Branch Dud: Duct board, lax Sheet metal,
Lined sheet metal, Other (specify)
Date 3/12/2020
= The AHJ shag have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of Instructions.
If abridged version or Manual J is used for load calculation, then verify residence meets requirements, we Abridged Edition Checklist on page 13 of Instructions.
Form generated by ACCAapproved Manual J Eighth Edition Version 2 Elite Software Rhvac program.