HomeMy WebLinkAboutEngineeringForensic Engineering Consultants, Inc. METAL PANEL ATTACHMENT CALCULATIONS Project Name Reserve Association Gatehouse Report No.: SRI-MP-21.001 Project Address 9701 Reserve Boulevard Port St. Lucie, FL - 34986 Deck Substrate Wood Non -Insulated Mean Roof Height 12.0 Feet Configuration Steep Slope Roof Area (Approx.) 576 Sq.Ft. Category II Roof Width 24.0 Feet Exposure Condition C Perimeter Width 7.2 Feet Building Type Enclosed Parapet Height 0.0 Feet Base Wind Speed Sloped Roof Type 7.2' x 7.2' Each Slope V 6.0 Slope H 12.0 Slope Angle° 26.57 Uplift Pressures qZ = 0.00256 KZ Kt Kd Ka V2 P = qZ (GCp - GCp;) qZ KZ KZt Kd Ke V GCp GCp; 53.453 0.850 1.000 0.85 1.00 170 -1.50 0.18 Field & Eave Perimeter -2.50 0.18 Ridge & End Perimeters -3.60 0.18 Ridge & Eave Corners Field & Eave Perimeter P1, ult. -89.80 psf Pl, asd -53.88 psf Ridge & End Perimeters P2 ult. -143.26 psf P2 asd -85.95 psf Ridge & Eave Corners P3 pit.-202.05 psf P3 asd -121.23 psf Proposed System Dynamic Metals 1700 Series 26 Ga. 1-1/2" Galvalume Standing Seam Panel Product Approval No. FL30751-R3 Panel Width 19 inches (Per NOA) 19 inches (Actual) System Design Pressure -128.5 psf (Field) -128.5 psf (Perimeter/Corner) Fasteners Approved 3-1/2" Clips, with two #1 0x1 "Pancake Head Fasteners Fasteners must be long to penetrate through sheathing a minimum of 3/16" Max. Clip Spacing per NOA 12 inch (Field) 12 inches (Perimeter) # Rows 1 Clip Withdrawal Resistance-203.46 Ibf (Field) -203.46 Ibf (Perimeter/Corner) Clip Spacing {(MCRF/P;) x 144}/(Panel Width/No. of Rows of Fasteners) Field & Eave Perimeter Fastener Spacing (Zones 1 & 2e) 28.62 inches Ridge & End Perimeter Fastener Spacing (Zones 2r & 2n) 17.94 inches Ridge & Eave Corner Fastener Spacing (Zones 3r & 3e) 12.72 inches RECOMMENDED CLIP SPACING Field & Eave Perimeter 12" o.c. Ridge & End Perimeters 12" o.c. Ridge & Eave Corners 12" o.c. These calculations have been done in accordance with ASCE 7-16, based on the information provided by the contractor. The roof system must be installed in accordance with the FBC & manufacturer's recommendations. Ensure that roof system meets insulation & fire rating requirements of the Florida Building Code, before installation. ` ``��11111111////I `SP,\LAPp' Digitally signed Sincerely ��CENS'C 'o Rava n a sa by Forensic Ertiping'erinConsultants, YYl UCi Ca lil N Ravanasamudra No. — �' _ m N Sailappan R. N. Saila�ipa E. STATd � = Sailappan Date:2021.01.14 Principal Eng�n4'... ��C� 10 p . ' �<v�� , , Florida Regis c Nib: 14:03:13 _ 05 00 Forensic EngineerinnZ0,SYW1nc,iC #8265), P.O. Box 970034, Boca Raton, FL - 33497 Ph (561) 901 8490 Fax (561) 218 3830 I M 11111%