HomeMy WebLinkAboutEnergy CodeAPPENDIX 13-D
Effective March 1, 2009
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
FORM 1100B-08 Residential Component Prescriptive Method B ALL CLIMATE ZONES
Compliance with Method B of Chapter 11 of the Florida Building Code, Residentia( or Subchapter 13-6 of the Florida Building Code, Building may be demonstrated by the use
of Form 1100B for single -and multiple -family residences of three stories or less in height, additions to existing residential buildings, renovations to existing residential
buildings, new heating, cooling, and water heating systems in existing buildings, and site -added components of manufactured homes and manufactured buildings.To comply,
a building must meet or exceed all of the energy efficiency requirements on Table 11 B-1 and all applicable mandatory requirements summarized in Table 11 B-2 of this form. If
.. G:1A:.....:....................A....:4h H.:.......1h A t+ -, ,+;11 nn.. h, „".1"r RA"fhn,i A of r`hantnr 11-Cnhrhnnfar 14.f, of Tha nnnli-hla -da _
PROJECT NAME:
Aft BUILDER:
AND ADDRESS:
ERMITTING 11 /1 L
f� Si'• Lucie Courl�y
FFICE:
OWNER: Oy PERMIT NO.:1 I I I I
JURISDICTION NO.: Q
1. New construction including additions which incorporate any of the following features cannot comply using this method: skylights or othernonvertical root glass, glass areas
in excess of 16 percent of conditioned floor area, and electric resistance heat (See Notes to Table 11 B-1 on page 2).
2. FlII in all the applicable spaces of the "To Be Installed" column on "Table 11 B-1 with the Information requested. All "To Be Installed" values must be equal to or more efficient
than the required levels.
3. Complete page 1 based on the "To Be Installed" column information.
4. Read "Minimum Requirements for All Packages", Table 11 B-2 and check each box to indicate your intent to comply with all applicable items.
5. Read, sign and date the "Prepared By" certification statement at the bottom of page 1. The owner or owners agent must also sign and date the form.
Please Print CK
1. New construction, addition, or existing building
2. Single-family detached or multiple -family attached
3. If multiple -family -No. of units covered by this submission
4. Is this a worst case? (yes/no)
5. Conditioned floor area (sq. ft.)
6. Glass type and area:
a. U-factor
b. SHGC
c. Glass area
7. Percentage of glass to floor area
8. Floor type, area or perimeter, and insulation:
a. Slab -on -grade (R-value)
b. Wood, raised (R-value)
c. Wood, common (R-value)
d. Concrete, raised (R-value)
e. Concrete, common (R-value)
9. Wall type, area and insulation:
a. Exterior: 1. Masonry (Insulation R-value)
2. Wood frame (Insulation R-value)
b. Adjacent: 1. Masonry (Insulation R-value)
2. Wood frame (Insulation R-value)
10. Ceiling type, area and insulation:
a. Under attic (Insulation R-value)
b. Single assembly (Insulation R-value)
11. Air distribution system: Duct insulation, location
Test report required if duct in unconditioned space
12. Cooling system:
(Types: central, room unit, package terminal A.C., gas, none)
13. Heating system:
(Types: beat pump, elec. strip, nat. gas, LP -Gas, gas h.p., room or PTAC, none)
14. Programmable thermostat installed on HVAC systems:
15. Hot water system:
(Types: elec., nat. gas, LP -gas, solar, heat rec., ded. heat pump, other, none)
1. ¢Ot7f'
2FM
.�
3. N /lA
5. G�iO St.
6a.
6b.
6c. 1 1� sq. ft.
7. •i8 %
Be. R= lin.ft.
8b. R= sq. ft.
8c. R= sq. ft.
8d. R= sq.ft.
8e. R= q.ft.
9a-1. R= sq.ft.
9a-2. R= sq.ft.
9b-1. R= sq.ft.
9b-2. R= sq.ft.
10a. R= sq.ft.
IOb. R= sq.ft.
11a. R=
11b.Test report attached? Yes
12a. Type: Adj Pbm is
12b. SEER/EER:
12c. Capacity: 1 f7 40
13a. V114
13b. HSPF/COP/AFUE:
13c. Capacity:
14. Yes No
15a. Type: N /A
15b. EF: cal / A
I hereby certify that the plans ecifications co red by the calculation are in compliance with Review of plans and specifications covered by this calculation indicates compliance with the Florida
the Florida Energy Code. Energy Code. Before construction Is completed, this building will be inspected for compliance in
accordance with Section 553.908, F.S.
PREPARED BY: DATE:
BUILDING OFFICIAL:
I hereby certify thi bu' ng sin co m a e wd le Flo a Energy Code:
OWNER AGENT: DATE: ATE:
2007 FLORIDA BUILDING CODE -BUILDING 13-D.23
APPENDIX 13-D
* TABLEii11-1
MINIMUM REQUIREMENTS (See Note 1) All Climate Zones
BUILDING COMPONENT
PERFORMANCE CRITERIA
INSTALLED VALUES:
U-Factor = 0.65
U-Factor =
Windows (see Note 2):
SHGC = 0.35
SHGC =
%of CFA<=16%
%Of CFA=
Exterior door type
Wood or insulated
Type:
Walls — Ext. and Adj. (see Note 3):
Frame
R-13
R-Value =
Mass (see Note 3)
Interior of wall:
R-6
R-Value =
Exterior of wall:
R-4
R-Value =
Electric resistance heat See Note 10
Not allowed
Ceilin s see Notes 3 & 4
R=30
R-Value =
Floors: Slab -on -grade
No requirement
R-Value =
Over unconditioned spaces see Note 3
R-13
Hot water systems (storage type)
Electric (see Note 5):
40 gal: EF = 0.92
Gallons =
50 gal: EF = 0.90
EF =
Gas fired (see Note 6):
40 gal: EF = 0.59
Gallons =
50 al: EF=0.58
EF=
Air conditioning s stems see Note
SEER =13.0
SEER =
Heat pump systems (see Note 8)
SEER =13.0
SEER =
HSPF = 7.7
HSPF =
Gas furnaces
AFUE = 78 %
AFUE =
Oil furnaces
AFUE = 78 %
AFUE =
Programmable thermostat see Note 10
Must be Installed on all HVAC systems.
Installed? Yes No
Ductwork: (see Note 9)
Location:
Unconditioned space'
R-6, TESTED
Unconditioned space
Conditioned space
NA
R-Value =
Unvented attic assembly per R806.4 with insulation at the roof plane
R-4.2
Test report
Conditioned space
R-Value =
No test report required)
Air Handler location:
Unconditioned attic' or garage
Requires test report
Location:
Conditioned space or
Test report
Unvented attic assembly per R806.4 with insulation at the roof plane
I No duct test required
(1) Each component present in the As -Built home must meet or exceed each of the applicable performance criteria in order to comply with this code using this method; 011E
erwise Method A compliance must be used.
(2) Windows and doors qualifying as glazed fenestration areas must comply with both the maximum (}Factor and the maximum SHGC (Solar Heat Gain Coefficient) criteria
and have a maximum total window area equal to or less than 16% of the conditioned floor area (CIA); otherwise Method A must be used for compliance. Exceptions: 1. Ad-
ditions of 600 square feet (56 m2) or less may have maximum glass to CIA of 50 percent. 2. Renovations with new windows under 2 foot overhang whose lower edge does
not extend further than 8 feet from the overhang may have tinted glazing or double -pane clear glazing. Replacement skylights installed in renovations shall be doublepaned
or single paned with a diffuser.
(3) R-Values are for insulation material only as applied in accordance with manufacturers' installation instructions. For mass walls, the "interior of wall" requirement (R-6)
must be met except if at least 50% of the R-4 insulation value required for the "exterior of wall" is installed exterior of, or integral to, the wall.
(4) Attic knee walls shall be insulated to same level as ceilings and shall have a positive means of maintaining insulation in place. Such means may include rigid insulation
board or air barrier sheet materials adequately fastened to the attic sides of knee wall framing materials.
(5) For other electric storage volumes, minimum EF = 0.97 - (0.00132 * volume).
(6) For other natural gas storage volumes, minimum EF = 0.67 - (0.0019 * volume).
(7) For all conventional units with capacities greater than 30,000 Btu/hr. For Small -Duct, High -Velocity units, Space Constrained units, and units with capacities less than
30,000 Btu/hr see Table 13-607.AB.3.2A of the Florida Building Code, Building or Table N1107.AB.3.2A of the Florida Building Code, Residential
(8) For all conventional units with capacities greater than 30,000 Btu/hr.. For Small -Duct, High -Velocity units, Space Constrained units, and units with capacities less than
30,000 Btu/hr see Table 13-607.AB.3.2B of the Florida Building Code, Building, or Table N 11 07.AB.3.2B of the Florida Building Code, Residential
(9) All ducts and air handlers shall be either located in conditioned space or tested by a Class 1 BERS rater to be "substantially" leak free. "Substantially leak free" shall mean
distribution system air leakage to outdoors no greater than 3 cfm per 100 square feet of conditioned floor area at a pressure differential of 25 Pascal (0.10 in. wc.) across the
entire air distribution system, including the manufacturer's air handler enclosure. Exception: New or replacement ducts installed onto an existing air distribution system as
part of an addition or renovation. Such ducts shall either be insulated to R-6 or be installed in conditioned space.
10) The prohibition on electric resistance heat and the requirement for programmable thermostats do not apply to additions, renovations, and new heating systems installed
in existing buildings.
TABLE 11B-2 MINIMUM REQUIREMENTS FOR ALL PACKAGES
COMPONENTS
SECTION
REQUIREMENTS
CHECK
Exterior Joints & Cracks
N1106.AB.1.2
To be caulked, asketed, weather-stripped or otherwise sealed.
Exterior Windows & Doors
N1106.AB.1.1
Max .3 cfm/s .ft. window area; .5 cfmtsq.ft. door area.
Sole & Top Plates
N1106.AB.1.2.1
Sole plates and penetrations through top plates of exterior walls must be sealed.
Recessed Lighting
N1106.AB.1.2A
Type IC rated with no penetrations two alternatives allowed).
Multistory Houses
N1106.AB.1.2.5
Air border on perimeter of floor cavity between floors.
Exhaust Fans
N1106.AB.1.3
Exhaust fans vented to unconditioned space shall have dampers, except for combustion devices with integral
exhaust ductwork.
Water Heaters
N1112.AB.3
Comply with efficiency requirements in Table N7112.AB.3. Switch or clearly marked circuit breaker electric or cutoff
as must be provided. External or built-in heat trap required for vertical pipe risers.
Swimming Pools & Spas
N1112.AB.2.3.4
Spas & heated pools must have covers (except solar heated). Noncommercial pools must have a pump timer. Gas
spa & pool heaters must have minimum thermal efficiency of 78%. Heat pump pool heaters shall have a minimum
COP of 4.0.
Hot Water Pipes
N1112.AB.5
Insulation Is required for hot water circulating systems(including heat recovery units).
Shower Heads
N1112.AB.2.4
1 Water flow must be restricted to no more than 2.5 gallons per minute at 80 psig.
HVAC Duct Construction,
Insulation &Installation
N1110.AB
All ducts, fittings, mechanical equipment and plenum chambers shall be mechanically attached, sealed, Insulated
and installed in accordance with the criteria of Section N1110.AB. Ducts in attics must be Insulated to a minimum of
R6.
HVAC Controls
N1107.AB.2
Separate readily accessible manual or automatic thermostat for each system.
13-D.24 2007 FLORIDA BUILDING CODE -BUILDING