HomeMy WebLinkAboutProject Information- - wrightsofto Manual S Compliance Report
Entire House
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Pfnre:407-333-2665
Job: Lot 18 Block 5 Waterston...
Date: NOVEMBER 3, 2010
By: DCS
For: ADAM HOMES DEC 0 8 170
5369 San Benedetto Place, Fort Pierce, FL 34951
ST. Lucie County, Permitting
Cooling Equipment
Design Conditions
design DB:
90.4 OF
Sensible gain:
20061
Btuh Entering coil DB: 76.9OF
Outdoor design WB:
77.4OF
Latent gain:
4176
Btuh Entering coil WB: 63.4OF
Indoor design DB:
75.0 OF
Total gain:
24238
Btuh
Indoor FIR
50%
Estimated airflow:
947
cfm
Manufacturer's.Performance Data at Actual Design Conditions
Equipment type:
SpIitASHP
Manufacturer:
Carrier
Model: 25HBC530A00300+FX4DNF031 L
Actual airflow:
947
cfm
Sensible capacity:
22733
Btuh
113%of load
Latent capacity:
4719
Btuh
113%of load
Total capacity:
27452
Btuh
113% of load SHR: 83%
Heating Eqvipment
Design Conditions
Outdoor design DB:
41.0 OF
Heat loss: 22365 Btuh Entering coil DB: 69.2 OF
Indoor design DB:
70.0 OF
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier Model: 25HBC530A00300+FX4DNF031 L
Actual airflow: 947 drn
Output capacity: 26672 Btuh 119% of load Capacity balance: 35 cF
Supplemental heat required: 0 Btuh Economic balance: -99 IF
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 947 cfm
Output capacity: 5.7 kW 87%of load Temp. rise: 19 OF
Meets all requirements ofACCA Manual S.
FILE C®P"
Wrightsoft, 2020-Nov-0910:47:52
��r• • „•� �•. �mpM RigfR-Sdte®Udversa1201919.0.16 RSU23828ACCK Page l
..aterstore1635BGL1Lot18BIk5Waterstore1635BGL.rLp Calc=MJ8 Housefaces: N
Project Su mma Job: Lot 18 Block 5 Waterston...
- - wrightsofte Date: NOVEMBER 3, 2010
Entire House By: DCS
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
For: ADAM HOMES
5369 San Benedetto Place, Fort Pierce, FL 34951
Notes: REVISED 3-26-12 SGT
REVISED 8-18-15 JA
L. S. 11-9-20 VW K
Mil-M19,111i
formation,
Weather: St Lucie Cc Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41
°F
Outside db
90
°F
Inside db 70
°F
Inside db
75
OF
Design TD 29
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Heating Summary
Sensible Cooling Equipment Load Sizing
Structure 17164
Btuh
Structure
13980
Btuh
Ducts 5201
Btuh
Ducts
6081
Btuh
Central vent (0 cfm) 0
Btuh
Central vent (0 cfm)
0
Btuh
(none)
(none)
Humidification 0
Btuh
Blower
0
Btuh
Piping 0
Btuh
Equipment load 22365
Btuh
Use manufacturer's data
y
Rate/swingg multipplier
Equipmentsensibleload
1.00
Btuh
Infiltration
20061
Method Simplified
Latent Cooling Equipment Load Sizing
Construction quality
Average
Fireplaces
0
Structure
3041
Btuh
Ducts
1135
Btuh
Central vent (0 cfm)
0
Btuh
Heatingg
Cooling
(none)
Area (ft2) 1635
1635
Equipment latent load
4176
Btuh
Volume (ft3) 15846
15846
Air changes/hour 0.38
0.20
Equipment Total Load (Sen+Lat)
24238
Btuh
Equiv. AVF (cfm) 100
53
Req. total capacity at 0.75 SHR
2.2
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Make Carrier
Trade CARRIER
Trade CARRIER
Model 25HBC53OA00300
Cond 25HBC53OA00300
AHRI ref 9154945
Coil FX4DNF031 L
AHRI ref 9154945
Efficiency 8.5 HSPF
Efficiency 12.5 EER,15
SEER
Heating input
Sensible cooling
21300
Btuh
Heating output 28200
Btuh @ 47-F
Latentcooling
7100
Btuh
Temperature rise 27
°F
Total cooling
28400
Btuh
Actual air flow 947
cfm
Actual air flow
947
cfm
Airflowfactor 0.042
cfm/Btuh
Airflowfactor
0.047
cfm/Btuh
Static pressure 0.40
in H2O
Static pressure
0.40
in H2O
Space thermostat
Load sensible heat ratio
0.83
Capacity balance point = 35 OF
Backup:
Input = 6 kW, Output =19353 Btuh, 100AFUE
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
r � wrigghtsoTt® 2020-Nov-0910.47:52
�* w�-•.�m� Rig ht-SUte®Uriversal201919.0.16 RSU23828 Page 1
ACCA aterstone1635BGL\Lot18BIMWaterstone16358GL.rip Calc=MJ8 House faces: N
+ wrightsoftg
Right-M Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
Job: Lot 18 Block 5 Waterston 16...
Date: NOVEMBER 3, 2010
By: DCS
1
Room name
Entire House
FAM
2
Exposed wall
158.9 It
35.9 ft
3
Room height
9.7 ft d
10.7 ft heat/cool
4
5
Room dimensions
Room area
1635.0 ft'
1.0 x 456.0 ft
456.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh/ft-9
(Btuht2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall; stu000 ext
2A-2om
26-2fv
_0.143
0.330
0.330
- n
h
n
- -4.15
957
0'57
822
- . 9.72
16
' 5
127
0.
0
Y ^ 5277
155
48
:-329
133
49
_70-31
0
5
"0
0
v -130
0
48
- 81
0
49
11
213-21v
0.330
0.600
n
n_
9.57
__ 1740
' • - , 9.72
.--_1758
'13
__�__?0
.0
_._..,__ _20
128
_352
13.0
356
13
._..� _.�20
.0
- -__ ._-20
, 128
_�_ : 352.
130
-____356
t-G
Blk wall, stuaa eM
2A-2ov
Blkwall,stu000eid ; •
0.143
0.330
0:143
a
a
s
4.15
9.57
4;15
2.59
22.43
` 2:59
384
16
� . 348
368
1
_ .__.265
1525
155
'y' 1100
952
_ _ 363
� � 687
0
0
�� 180
0
_ 0
- w 130
0
0
'• -- 538
0
0
336
10C-m ; ,
2A-20v'.
0.550
0.330
.0.330
s
s
s
15.95
- 9.57
9.57
1:64
-'8.52
• ; 8.52
' 18
: , . 16
, ' '- 16
18,
, a 16
16
- 287
' 155
' ' '. 16s
228,
138
- ` 138
"18
" , 16
., 0
18
^ , 16
0
• ' • 287
"' 155
': 0
228
138
0
2A-2ov-.�__.:.:
_.0.330
;,-s-
._.,_.'9.5T
_-8.52_._'r....-_32
_, __-_:32._._..__.310
___._276
_,._.__._16_.___.__i6.
_..:155._______.138
+
Blk wall, stucco ext
0.143
w
4.15
2.59
484
412
1710
1067
110
110
456
285
C
2A-2ov
2A-2ov
0.330
0.330
__0.091
0.032
w
w
:._
:. -
9.57
9.57
.. .2.64.;
21.93
22.43
7
65
1
3
_1Z4______.459
1784
66
620
1655
150
1453
.____228.
3014
0
0
_.__30
484
0
0
_ __ _30:_
484
0
0
_ ?9
450,
0
0
_ ___ _39
819
1.69
-_174__
1784
_.
F� ---
-1613-30ad .......
2? tph "_ .__
_-_ __.
0.989.
. _
_.-v..
__ , _0,93
_._28.68:
.
-0,00
_ _.
t835
_
_._ 159
___ _ 4558
:4
- _. -.
----_.__0
. _ ,_. ;
._. _ . _6
- - -__ -,
___ __36
_. _ r .
_._,1030
6
c) AED excursion
445
-152
Envelope losstgain
13966
10136
3808
2446
12
a) Infiltration
3198
894
824
230
b) Room ventilation
0
01
0
0
13
Internal gains: Oocupants@ 230
5
1150
3
690
Appliances/other
1800
0
Subtotal (lines 6 to 13)
17164
13980
4632
3366
Less extemalload
0
0
0
0
14
Lesstransler
Redistribution
Subtotal
0
0
17164
0
0
13980
0
0
4632
0
0
3366
15
Duct loads
300X
6081
30 %
44 %
1403
1464
Total room load
Air required (cfm)
�435201
22365
947
20061
947
1
6035
256
4830
228
Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed.
+�1_ wr!R1 tsoTt� 2020-Nov-0910.47:52
� "" ""' Rigk-Sute®Universal 201919.0.16 RSU23828 Page 1
aterstore16358GULot1861k5Waterstone16358GL.nQ CaIc=MJB House faces: N
-9- wrightsoftm Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
Job: Lot 18 Block 5 Waterston 16...
Date: NOVEMBER 3, 2010
By: DCS
1
Room name
BR 4
BR 3
2
Exposed wall
11.0 ft
24.0 ft
3
Room height
8.9 ft heatbool
9.0 ft heat/cool
4
5
Room dimensions
Room area
1.0 x 140.5 ft
140.5 ftz
1.0 x 133.0 ft
133.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuht-fl
(Btuh/W)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
_
VN
(Blk wall sluao ext
2A 2om
262fv
2B2fv '°
]1J0, .,� .
Blk wall, stucco ext
_ `0143
0 330
g330'n.
0330
-__v 0600
0.143
� n ',
. n
m
.>0? ;
a
' 4.15.
957
957
957
J790
4.15
2 59
', 822
9.72
972
_ 1758
2.59
`0
0
0
0
_ ��0
0
_ .__ 0
0
;; 0
0
_ D
0
0
0
p`
0
�0
0
-�
0-"
0°U"
0
-- . u 0
0
0
0
0
_,wt _ »_-0
112
0
0
0
$
112
0
0
0
0
`0
464
.' 0
0
0`
"0
_ 0
290
I—G
2A-2ov
. _
Blk wall stucco eM , '
10cnf',
2A 2ov- r' =-
0.330
0143
.:0.550
D.330
a
s ,
, s �
s +
9S7
415
15.95'
�`9.57,
95
22.43
__
2.59
012.64
8:52
8.52
0
. 88
.Q
�b
0
' 72
0
0
0
298
0
0
0
186
0
0
0
0
- 80
0'
0
16
0
' ° 64
p
16
0
_ 265
0
155
0
165
0
138
ILIBlk
wall, stucco ext
_0.330
0.143
s,
w
x7_
957
4,15
852
2.59
%0
._. 16
0
0
0
___138
0
__ _
0
0
u0
0
._.. _ a,:_0
0
war:_12C,Osw_._�__.,..�.�,.>__.��0�1
C
2A-2ov
2A-2ov
16B-30ad
0.330
0.330
0032
w
w
,,....�
wt>.
9.57
9.57
_,2_64
0.93,
21.93
22.43
_. _.1.31:
1.69
7 -co
0
0
p 166
0
0
__...._,�.0.._.u._.:0
_ t166
0
0
154
0
0
280
0
0
16Q
0
0
>.__:._�,..�:>_.0
1.60
0
0
_ 148
-688
0
0
_-_....W.�,.O_
270
...._..,,_,_..,.,x_,_...._...z�.
o......_...say.,,
,.. ..�
.._.�-x:.
'v...._�..... w.a
..
_«.._�__
.-.., b...�
..............
... ii... .._
.,
.1:,... �.....e
a.,...._ .e
..._....-A f
..
6
c) AED excursion
-29
-43
Envelopeloss/gain
922
575
1720
820
12
a) Infiltration
201
56
439
123
b) Room venfilation
0
0
0
0
13
Internal gains: Occupants Ca) 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines6 to 13)
1123
632
2160
943
Less external load
0
0
0
0
Lesstransfer
0
0
0
0
14
Redistribution
Subtotal
0
1123
0
632
0
2160
0
943
15
Ductloads
30%
44%
340
275
30%
44%
654
410
Total room load
1464
906
2814
1353
Air required (cfm)
62
43
119
64
Calculations approved WACCA to meet all reauirements of Manual J 8th Ed.
- wrightsoft ° ACGA Right-SuteC�U iversal 201919.0.16 RSU23828 2020-Nov-0910:47:52
Page 2
...aterslonel635BGL\Lotl813MWaterstonel635BGL.rulo Calc=MJ8 House faces: N
-AL
F wrightsoft9
Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
Job: Lot 18 Block 5 Waterston 16...
Date: NOVEMBER 3, 2010
By: DCS
1
Room name
DIN
BATH
2
E)posed wall
12.0 It
6.0 It
3
Room height
11.0 8 heat/000l
8.5 It heaticool
4
Room dimensions
1 9.0 x 12.0 8
8.0 x 6.0 It
5
Room area
108.0 82
48.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft)
Load
Area (ft)
Load
number
(Btuh/ft2-9
(Btuh/ t2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
-
Blkvall,stu000e#
6.143
n
2A-2om
0.330
n
9.57
822
0
0
0
0
0
0
0
.0
11
2B-2fv
2B-2fv
11J0_
0,330
0,330
-0,800,
n
n'
__n_
9.57
957,
.. 17.4Q
9.72
•:- 9.72
�.. 17.58
0
0
____0
0
0
_ _.._...__,0
0
0
_-------0
0
0
- :_°0
0
0
__.__- Q
0
6
0
0
0
.-Q
0
0
____. _
VI/
__----._Q.
124
0
. o
Blk wall, stucco ext
2A-2ov
0.143
0.330
a
a
4.15
9.57
2.59
22.43
0
0
._ ._ 0
0
0
_ .4 _- 0
0
0
.0
0
_., 0
n_-. 0
48
0
. _ _ __ 0
48
0
. _ _ ._ 0
199
0
0
-G
_ . _.--.
�.w...•.
IOC-rri. „ , ..
2A2ov', '.
2A-26u
.2A2ov..__:.. _y_:..__.__._-:0.330,__s:.
Blk wall, stucco ext
0.55Q
.0.330
0330
0.143
s
s
s
w
15.95
9.57
6.57
_.-.-957_
4.15
'� 12.64
8.52
8:52
a8.52_._
2.59
0
_ 0
0
..___A
120
0
0
0
_ .a__.._0,.
88
'0
0
0
.--__0
363
°:� ti ,- - 0
0
0,
__._._0
227
0
°0
0
..-_:__..0
0
0
, p
0.
_._.0
0
0
-` 0
0
__0
0
0
0
0
_...- __0.
0
2A-2ov
2A-2ov
0.330
0 330
w
w
9.57
9.57
21.93
22.43
0
32
0
2
0
310
0
726
0
0
0
0
0
0
0
0
P _ _1.31
_�
_
C
16B-30ad
0.032
0.93
1.69
118
118
110
199
55
55
51
93
0,989.�._.
_28.8-
___,:0,00',---
108
_ _. _-,_12
---_..344.__
_-0
_-� �48
._ ..__6
_ _ 172_,__.
0-
6
c) AED excursion
367
-11
Envelope loss(gain
1127
1520
422
206
12
a) Infiltration
275
77
110
31
b) Roomventilation
0
0
0
0
13
Internal gains: Occupants Qn 230
1
230
0
0
Appliancesrother
0
0
Subtotal (lines 6 to 13)
1401
1827
532
237
Less external load .
0
0
0
0
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1401
1827
532
237
15
Ductloads
30%
449/.
425
795
30%
44-/.l
161
103
Total room load
1826
2621
693
340
Air required (cfm)
77
124
29
16
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-rk=10"tsolFt- 2020-Nov-0910:47:52
.4C�P. """" "'"" Right-SuteOUriversal2019 19.0.16 RSU23828 Page 3
aterstore1635BGULot18BIk5Waterstore1635BGL.rup Calc=W8 House faces: N
-EL
F wrightsoft9
Right-M Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
Job: Lot 18 Block 5 Waterston 16...
Date: NOVEMBER 3, 2010
By: DCS
1
Room name
M BR
Krr
2
6posed wall
15.0 ft
0 ft
3
Room height
11.0 ft heat/cool
10.0 ft heat/cool
4
5
Room dimensions
Room area
1.0 x 200.0 It
200.0 ft'
1.0 x 127.5 ft
127.5 ftz
Ty
Construction
number
U-value
(BtuhrltZfl
Or
HTM
(Btuh/ft2)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Area (ft)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
MRS
Heat
Cool
6
-
Blk uvall, slucao ext
2A-2om
2B-2iv"
- - 0143
; 0.330
0.330
- . n "
'n
n
-415
957,
957
; 2.59
. s ; 922
9.72
7,-0
. 0
0
O
; 0
0
-- 0
z 0
0
_ ------- _. O
0
0
_ ,_0
0.
6
.. - _- _:0
0
0
O
. 0
0'
; 0
0
0
2B 2fv
0:330
n
957
' 9.72
0
0.
0
0
0
0
0
0
V�I
_ �-G
0
0
- - - 0
0
0
Blk wall, stucco eM
2A 2ov-
Blk wall; studoo ext
10C-m , ,_ ".'
2A-2ov' ,. ..
0.143
0.330
0,143
0.550
0.330
a
-_e _
„ s
, s
. 's
4.15
__.._ 9.57
4.15
15.95
'9.57.
2.59
22.43
v, 2:59
. 12.64
8.52
0
_ 0
___. 0
0
0
0
_ 0
0
0
,, „. •. 0
0
0
,0
0
0
0
_ 0
0
0
0
0
_ _ 0
0
0
0
0
_-0
0
.0
0
0
----__-- 0
0
0
0
2A-2ov
2A-2ov__--_._____..
Blk wall, stucco ext
0.330
__....._ _0.330
0.143
s
._.s..,.__.__9.5Z:..',-.8.52
w
0.57
4.15
8.52
2.59
" 0
_..._____ 0
150
0
_._._____0
118
0
..._._:_-'.0
488
0
____.___0
304
0.
__ .____.0
0
0
.--_------A
0
0
�._--_-._0
0
0
0
C._._
2A-2ov
2A-2ov
16B-30ad__. ... _ _
0.330
0.330
_ 0032
_0989
w
w
._; .
",_.r ..
9.57
9.57
0.93
,..._2868'w6
21.93
22.43
.._>1.69
0
32
_ 224
0
2
224
0
310
0
_ 208
30
0
726
--.�.. 0
.. 378
0
_ 0
-- --128
_28
0
0
_ 128
0'0
0
0
118
0
0
215
o
6
c) AED excursion
355
-61
Envelope loss/gain
1436
1765
118
154
12
a) Infiltration
343
96
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
1
230
0
0
Appliances/other
0
1200
Subtotal (lines 6to 13)
1779
2090
118
1354
Less edemalload
0
0
0
0
14
Lesstransfer
Redistribution
Subtotal
0
0
1779
0
0
2090
0
0
118
0
0
1354
15 1
Dud loads
30 %
44 %
539
909
30%1
44 %
36
589
Total roam load
2318
3000
1
1
154
1943
Air required Pm)
98
142
7
92
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-4d- wrigF�tsoft- .2020-Nov-0910:47:52
AC�A Right-Sute®Uriversal201919.0.16RSU23828 Page
aterstone1635BGLU,ot18BMWaterstone1635BGL.np Calc=MJ8 Hoisefaces: N
- F wrightsoft,
Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
Job: Lot 18 Block 5 Waterston 16...
Date: NOVEMBER 3, 2010
By: DCS
1
Room name
BR 2
UTIL
2
Exposed wall
16.0 ft
0 ft
3
Room height
8.5 it heat/cool
8.0 ft heaUcool
4
Room dimensions
12.0 x 16.0 ft
1.0 x 48.0 ft
5
Room area
192.0 ftz
48.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh/ftzF)
(Btuh/ft)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
-
Blkwallstuoceext}
2A2om`�..
0.143
"0.330
`
n��
• m_
�4:15
9.57,
'2.59
,`e , 822
,._
' „ •°0
a0
_k.
„ 0
�� 0
0,0
0
0
0
;;�`0'
",0
0
0.
<,
2B 2fv .. � °"
, ,0.330
_ n -
�9 57�
: 9.72
A0
z 0
0
0
"� 0
0
:0
t 0
2B2N
0330
n'.
957
9.72
0
0
0
0
0
0
0
0
w_ ,a_0600
_0�
17!IQ.
17
�__�_� 0
W O
_0
_._i0
�_ �0
_,_.. 0.
0
9
y/
I-C
Blk wall, stucco ext
0.143
a
4.15
2.59
128
112
464
289
0
0
0
0
,
''
2A-2ov_
:Blk wal 1, stucco ext
0.330
0.143
0.550
e._,
- s
s,,,
957,
4.15
15.95
2243
... 2 59,
° 12.64,
16
0
0
_ 1
0
��_0
,. 155
,.` , Q
363
0
0
0
0
o
0,
, 0
,p
p
0
.0,
0'
2A 2ov. "
0.330
s'"
9.57
8.52
'. 0
0
0
0
0
- "0
0
A
'
,2A
0,330
s
�9.57"`
0
• , ':'', _ p
00
�0
2A-2ov _° _ .. ._.: .
_. . 0.330
., a .
., :..'957_
.::8.52
w. H __.
Blk wall, stucco ext
0.143
w
4.15
2.59
0
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
21.93
0
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
22.43
0
0
0
0
0
0
0
0
P „
,12ti.OsyY:m._1.27
C
168 30ad
0.932
-__.
0.93
1.69
219
219
371
48
48
45
81.
,
.989
k
_ _204
_ y
.. _
_
r
-7r
-
... ..,.
..,._,...,....+ _�._... ....-�..
-..._... ,_n.
..-
.,....-....
_:,,..-x.'c
_. ..v ._
,,._.�...._.
...ems.....
..._._
Wn
�1,`_,E_
_......_.,.
_.._.�.
_�. �._.....
ti
. -
..
:..
F
-
-
6
c) AED excursion
56
-32
Envelope losstgain
1534
1205
171
112
12
a) Infiltration
293
82
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: OccupantsQa 230
0
0
0
0
Appliancestother
0
600
Subtotal (lines 6 to 13)
1827
1287
171
712
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1827
1287
171
712
15
Ductloads
30%
44%
554
560
30%
44%
52
310
Total room load T2381
1847
1
223
1022
Air required (cfm)
101
87
9
48
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-r�F- 2020-Nov-0910:47:52
...... ' '"'"""" ^ " Right-SLite@Uriversal 20l9 l9.0.16 RSU23828 Page 5
aterstonel635BGLIotl813MWaterstone1635BGL.np CaIc=MJB House faces: N
+ wrightsofV
Right-M Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665
Job: Lot 18 Block 5 Waterston 16...
Date: NOVEMBER 3, 2010
By: DCS
1
Room name
MBATH
MWIC
2
Exposed wall
33.0 ft
6.0 ft
3
Room height
8.0 ft heatbool
8.0 ft heal/cool
4
5
Room dimensions
Room area
1.0 x 135.0 It
135.0 ft2
1.0 x 47.0 It
47.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh/ftz-'l
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
_
Blkvvall,stu000ext ,
2A-2om
26-2fv ''
-_.__._._
0.143
0.330
0.330
n
n
ft
___0-_
4.15
9.57
9.57
_ _ ____._
� ' '2b9
.822
' 9.72
.----.__
112
16
0
. _-----96
0
0
'7 397
155
0
246
133
0
,._. __._
0
0
0
0
0
0
0
0
26-2tv
Blk wall, stuaoo ext
2A-2oY_ _ _- .._
Blk wall; stu000;ext
0.330
_,_0.600-0'..__1740:
0.143
_ 0.330
A.143
n
a
_
a ..
s
9.57
4.15
_ 9.57
. '4.15
"- 9.72
_ 1Z.58
2.59
22.43
•--2.59
0
-------0
48
0
__.._ _ _ 0
0
----00
48
._... _-._-0
_ 0
0°
199
__. _ _- _0
0
0
- =
124
-0._
- .- _- 0
0
- --- _0
48
_ _
0
0
- �.._:-
48
0
._ -A
199
_. o
0
----�.
124
0.
_ .__.�. _0
VIl
----G_...
10C-m . .•
2A-2ov :'
2A-2ov
Blk wall, stuomo ext
0.550
0.330
0330
0.143
s
s,
s
w
15.95,
0,57!
9:57
__,_.,-9.57_
4.15
,, 12.64,
`8:52,
:.- 8:52
_M-8.52
2.59
0
; . 0
0
_._ --..- 0
104
0
0
0
_ _ _ ..___0
97
a; 0;
0
'0
__.. _ _ w0
403
0•
0
0
... ._,0
251
0
0
0
_-__- .._..__0
0
0
0
0
-_.- __w_0
0
0
r . „ 0
0-
_____0
0
0
0:
0
_:_. _ _._.0
0
2A-2ov
2A-2ov
0.330
0.330
w
w
9.57
9.57
21.93
22.43
7
0
1
0
66
0
150
0
0
0
0
0
0
0
0
0
C _
12C Osw.^.'___ __
16B-30ad _
?2A.fpl.._ -.:_
. _.._0.091
.,0.032-
0.989
_ _
-___
_�
_.
.-_.2:64
_ 0.93
28:68
__..1;31
1_69
_ 0,00
_ _- _ _
. _0
135
._ _. -135
- _--___
0
135
_. __-_33
_ _.�
:__. _0:
125
-----_-946
_ _
._ __0
___228
--- _ 0
. --- _
_- 47
_ _ 47
. _.r..
_
44
172
. _- _
_ _ _ _79
_ __ 0
._ _47.
-_ _ B
6
c) AED excursion
4
-10
Envelope loss/gain
2292
1139
415
194
12
a) Infiltration
604
169
110
31
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
0
0
0
0
Applianoesiother
0
0
Subtotal (lines 6 to 13)
2896
1308
525
224
Less external load
0
0
0
0
14
Lesstransfer
Redistribution
Subtotal
0
0
2896
0
0
1308
0
0
525
0
0
224
15
Ductloads
30%
44%
877
569
30%
449/.
159
98
Total room load
Air required (dm)
3773
160
1877
89
684
29
322
15
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-r+- wrigF+tsolFt^ 2020-Nov-0910:47:52
Right-Sute®Uriversal 2019 19.0.16 RSU23828 Page 6
aterstone1635BGL\Lot18BIk5Waterstone1635BGL.rup Calc=MJ8 House faces: N
Duct System Summa Job: Lot 18 Block 5 Waterston...
-- wrightsoft� Date: NOVEMBER 3, 2010
Entire House By: DCS
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665
Project -Information
For: ADAM HOMES
5369 San Benedetto Place, Fort Pierce, FL 34951
External static pressure
Pressurelosses
Available static pressure
Supply/return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.40
in H2O
0.06
in H2O
0:34
in H2O
0.170 / 0.170
in H2O
0.256
in/100ft
947
cfm
133
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.256 in/100ft
947 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH
h 693
29
16
0.414
4.0
Ox 0
VI Fx
12.1
70.0
BR 2
h 2381
101
87
0.319
6.0
Ox 0
VI Fx
21.7
85.0
st1
BR 3
h 2814
119
64
0.404
6.0
Ox 0
VI Fx
14.1
70.0
BR4
h 1464
62
43
0.462
6.0
Ox0
VIFx
3.6
70.0
DIN
c 2621
77
124
0.414
6.0
Ox 0
VI Fx
12.1
70.0
FAM
h 6035
256
228
0.429
9.0
Ox 0
VI Fx
9.2
70.0
Krr
c 1943
7
92
0.445
6.0
Ox0
VIFx
6.3
70.0
M BATH
h 3773
160
89
0.256
7.0
Ox 0
VI Fx
32.7
100.0
s12
M BR
c 3000
98
142
0.274
7.0
Ox 0
VIFx
24.2
100.0
st2
M W IC
h 684
29
15
0.260
4.0
Ox'0
VI Fx
30.7
100.0
st2
UTIL
c 1022
9
48
0.327
4.0
Ox 0
MR
19.1
85.0
sti
Supply Trunk Detail Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FR
(fpm)
(in)
(in)
Material
Trunk
st2
PeakAVF
287
245
0.256
649
9.0
0 x 0
VinIFIX
st1
sti
PeakAVF
397
381
0.256
506
12.0
0 x 0
VinIFIX
-�- wrightsoft' 2020-Nov-0910:47:53
Right-SuteOUriversal201919.0.16 RSU23828
Page 1
aterstone1635BGL1Lot18BMWaterstone1635BGL.np CaIc=MJ8 Hoisefaces: N
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(Cfm)
Cig
(Cfm)
TEL
(ft)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb1
Ox 0
947
947
0
0
0
0
Ox 0
VIFx
1 wrightsoft®
2020-Nov-0910:47:53
Right-StiteC�Uriversa1201919.0.16RSU23828XCX Page2
aterstore1635BGL�Lot1BBIk5Waterstore1635BGL.nQ Calc=W8 Hoisefaces: N
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 18 Block 5 Waterstone 1635 BGL Builder Name: ADAM HOMES
Street: 5369 San Benedetto Place Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
Y
U
Owner: Jurisdiction: 661000
w
Design Location: FL, ST_LUCIE_CO_INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation,
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the drywall.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind pupona and wwrona.
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings,
a. In addition, inspection of log walls shall be in accordance with the provisions of [CC-400.
11/9/2020 11:00 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
FORM R405-2017
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the
residential Simulated Performance Method shall include:
❑ This checklist
❑ A Form R405 report that documents that the Proposed Design complies with Section
R405.3 of the Florida Energy Code. This form shall include a summary page
indicating home address, a -ratio and the pass or fail status along with summary
areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual
completing the compliance report (one page) and an input summary checklist that can
be used for field verification (usually four pages/may be greater).
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO for the Performance Method:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -
one page)
❑ A completed Envelope Leakage Test Report (usually one page)
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
Form R405 Duct Leakage Test Report (usually one page)
11/9/2020 10:59:35 AM EnergyGauge@ USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: 661000
Permit #:
�z - -
Job Informatlow'
Builder: ADAM HOMES Community: Lot: 18
Address: 5369 San Benedetto Place
City: Fort Pierce State: FL Zip: 34951
I�11C Leakage=Test=,ReSl11tS Passrng-results must meet ertherjthe Performance; Prescr►ptiVe,.orERl Method >
0 PRESCRIPTIVE METHOD The binding or dwelling undshall beYfested,and verified as having an arr, leakage rate of notexceeding 7 air,
changes pef hour at'a pressure of 0.2 inch w g: -(50 Pascals) rn..Clim a Zones 1 and2
: ;PERFORMANCE orER1 METHOD ,The buildmg•or dwe0ng umtshall be tested and;venfied'as hamng'an air leakage rate.ofnot'ezceeding
=the selected ACH(50) value as 'shown on Form R405-2017 (Performahce) or R406 2017;(ERI} *section labeled as infiltration, sub-section,'AGH50.
' ACH(50) specified orr Form R405 20 f7 Energy Calc (Performance) or R406 20i7 (ER!) 7.000
K
x 60 _ 15860 = Method for calculating building volume:
CFM(50) Building Volume ACH(50)
O Retrieved from architectural plans
[—] PASS 0 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
fiestmgCornpany x
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition, Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
11/9/2020 11:00:42 AM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
777
5369 San Benedetto Place Permit Number:
Fort Pierce , FL , 34951
MANDATORY REQUIREMENTS See individual code sections for full details.
V
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal enveldom building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 Instal lationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
El R402.4.3 Fenestration air IeakagdtVindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
11/9/2020 11:00 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory) Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
❑ pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
11/9/2020 11:00 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or RA 0
otherwise.
R403.7 Heating and cooling equipment (Mandatory).
❑ R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
11/9/2020 11:00 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
11/9/2020 11:00 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
EjR403.11 Portable spas (Mandatoryhe energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404:1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps.
Exception: Low -voltage lighting.
R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights.
11/9/2020 11:00 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5