HomeMy WebLinkAboutProject Information9 Manual S Compliance Report Job: Lot 12 Block 5 Waterston...
wri htsoft Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Project Infor mat ion
For: ADAMS HOMES
5345 San Benedetto Place, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
design DB:
90.4OF
Sensible gain:
20903
Btuh Entering coil DB: 76.2OF
Outdoor design WB:
77.4OF
Latent gain:
4418
Btuh Entering coil WB: 63.2OF
Indoor design DB:
75.0 OF
Total gain:
25321
Btuh
Indoor RH:
50%
Estimated airflow:
947
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
SpIitASHP
Manufacturer:
Carrier
Model: 25HBC530A00300+FX4DNB031 L
Actual airflow:
947
cfm
Sensible capacity:
22369
Btuh
107%of load
Latent capacity:
4981
Btuh
113%of load
Total capacity:
27349
Btuh
108% of load SHR: 82%
Heating Equipment
Design Conditions
Outdoor design DB:
41.0 OF
Heat loss: 21676 Btuh Entering coil DB: 69.6OF
Indoor design DB:
70.0 OF
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier Model: 25HBC530A00300+FX4DNB031 L
Actual airflow: 947 cfm
Output capacity: 26638 Btuh 123% of load Capacity balance: 34 OF
Supplemental heat required: 0 Btuh Economic balance: -99 OF
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 947 cfm
Output capacity: 6.1 kW 96%of load Temp. rise: 20 OF
Meets all requirements ofACCA Manual S. FILE COPY
ti
wrightsoft- 2020-Oct-2811:00:19
CACnMa..•rmknwwm..owmwro Rigtt-Sute®Uriversal 201919.0.16 RSU23828 Page 1
ttaterstore1780AGL.np Calc=MJ8 Hosefaces:NW
Component Constructions Job: Lot 12 Block 5 Waterston...
wrightsoft® p Date: 06.07.12
Entire House By-. FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Project Info rmation
For: ADAMS HOMES
5345 San Benedetto Place, Fort Pierce, FL 34951
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 28 ON
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr4b)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (OF) -
15 (L
)
Method
Simplified
Wet bulb (OF) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions
or
Area u-value Insul R
Htg HTM
Loss Clg HTM
Gain
ft' BtuWftz°F ftz`F/Btuh
Btul/ft'
Btuh
BtuWt'
Btuh
Walls
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
n
17 0.201 4.1
5.83
99
4.06
69
ne
291 0.201 4.1
5.83
1698
4.06
1183
se
269 0.201 4.1
5.83
1571
4.06
1094
sw
383 0.201 4.1
5.83
2232
4.06
1555
w
17 0.201 4.1
5.83
99
4.06
69
nw
68 0.201 4.1
5.83
399
4.06
278
all
1046 0.201 4.1
5.83
6098
4.06
4247
16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw
ins, 1/2" gypsum
sw
117 0.049 19.0
1.42
166
2.59
303
board int fnsh
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, 214' wood frm, 16" o.c. stud
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n
thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.3 ft overhang w
(5.3 ft window ht, 0.8 It sep.); 6.67 ft head ht nw
all
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" ne
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang se
(5.3 ft window ht, 0.8 ft sep.); 6.67 It head ht
sw
all
10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" se
thk; NFRC rated (SHGC=0.70); 14.3 ft overhang (6.7 ft window ht, 0.8 ft
sep.); 6.67 ft head ht
Doors
11 JO: Door, mtl fbrgl type nw
11 DO: Door, wd sc type n
Ceilings
16B-3Oad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2"
gypsum board int fnsh
250
0.091
13.0
2.64
660
1.31
328
12
0.330
0
9.57
114
8.22
98
12
0.330
0
9.57
114
20.9
249
23
0.330
0
9.57
224
16.6
389
47
0.330
0
9.57
452
15.6
736
33
0.330
0
9.57
313
17.7
579
33
0.330
0
9.57
313
15.7
512
49
0.330
0
9.57
469
15.7
768
114
0.330
0
9.57
1095
16.2
1859
18
0.550
0
16.0
285
16.2
289
20
0.600
6.3
17.4
350
17.6
353
18
0.390
0
11.3
202
11.4
204
1972
0.032
30.0
0.93
1830
1.69
3332
41- wrightsoft- 2020-Oct-2811:00:19
�M,,..•, Wu.,,� ,., Right-StiteOUriversal201919.0.16 RSU23828 Page 1
aterstoml780AGL\Lot12Blk5Waterstone1780AGL.rtp Calc=W8 Hotsefaces:NW
Floors
22A-tpl: Bg floor, light dry soil, on grade depth 156 0.989 0 28.7 4465
- WrlghtsOfC® 2020-Oct-2811:00:19
�C% nM•t•��.+.�.•d�•-•.w•�•. Rig ht-Sute®Uriversa1201919.0.16RSU23828 Paget
aterstone1780AGL\Lot12Blk5Waterstore1780AGL.nQ Calc=W8 Hotsefaces:NW
Project Summary Job: Lot 12 Block 5 Waterston...
wrightsoft® rY Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Promect, 1,r1form9tion
For: ADAMS HOMES
5345 San Benedetto Place, Fort Pierce, FL 34951
Notes: L. S. 10-28-20 VWK
Design Information
Weather: St Lucie Co Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41
OF
Outside db
90
OF
Inside db 70
OF
Inside db
75
OF
Design TD 29
OF
Design TD
15
°F
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure 18784
Btuh
Structure
17092
Btuh
Ducts 2893
Btuh
Ducts
3811
Btuh
Central vent (0 cfm) 0
Btuh
Central vent (0 cfm)
0
Btuh
none
e)
Humidifir.,ation 0
Btuh
Blower
0
Btuh
Piping 0
Btuh
Equipment load 21676
Btuh
Use manufacturer's data
y
Rate/swin multipplier
Equipmengsensible
1.00
Infiltration
load
20903
Btuh
Method Simplified
Latent Cooling Equipment Load Sizing
Construction quality
Average
Fireplaces
0
Structure
3230
Btuh
Ducts
1188
Btuh
Central vent (0 cfm)
0
Btuh
Heat' ngg
Area
Cooling
(none)
(ft2) 1780
1780
Equipment latent load
4418
Btuh
Volume (ft3) 15760
15760
Airchanges/hour 0.38
0.20
Equipment Total Load (Sen+Lat)
25321
Btuh
Equiv. AVF (cfm) 100
53
Req. total capacity at 0.75 SHR
2.3
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Make Carrier
Trade CARRIER
Trade CARRIER
Model 25HBC53OA00300
Cond 25HBC53OA00300
AHRI ref 9154945
Coil FX4DNB031 L
AHRI ref 9154945
Efficiency 8.5 HSPF
Efficiency 12.5 EER,15
SEER
Heating Input
Sensible cooling
21300
Btuh
Heating output 28200
Btuh @ 47OF
Latentcooling
7100
Btuh
Temperature rise 27
OF
Total cooling
28400
Btuh
Actual airflow 947
cfm
Actual airflow
947
cfm
Airflowfactor 0.044
cfm/Btuh
Airflowfactor
0.045
cfm/Btuh
Static pressure 0.40
in H2O
Static pressure
0.40
in H2O
Space thermostat
Load sensible heat ratio
0.83
Capacity balance point = 34 OF
Backup:
Input = 6 kW, Output = 20744 Btuh,100 AFUE
Calculations approved byACCAto meet all requirements of Manual J 8th Ed
wrightsoft' �� ^-°•"••-��°�^_�^•�^� Rigk-Su2020-Oct-2811:00:19
te@Uriversa12019 19.0.16 RSU23828 Page 1
aterstone1780AGL\Lot12Blk5Waterstone1780AGL.rLp Calc=MJ8 Hoisefaces:NW
-q- wrightsoft, Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 12 Block 5 Waterston 17...
Date: 06.07.12
By: RETCH
1
Room name
Entire House
LAU
2
E)posed wall
155.7 It
0 ft
3
Room height
8.8 It
8.0 ft heat/cool
4
Room dimensions
7.0 x 7.0 8
5
Room area
1792.0 ft2
49.0 82
Ty
Construction
U-value
Or
HTM
Area (ft')
Load
Area (ftz)
Load
number
(Btuh/ftz-cF)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W
Blk wall slu000 ext
0 201
n 'I
5 83
4:06
29
17
;99
69
"' 0
t 0
0
.2A 2ov_, , _ L __
_ �0330
_ n:
�___957_-,
'.822
w .2
_0
114
,__ , �w. 98
�_ Q
Q
_0
0
Blk wall, stucoo ext
0.201
ne
5.83
4.06
324
291
1698
1183
0
_ _ _v
0
0
- _ 0
2A 2ov
Y 0 330
ne
9.57
17.70
33
0
313
579
0
0
0
0
11
Blk wall sluiao ext
10C v
0201
01
se`
ses�
5.83
1595,
4.06
1620
320
18
269
18
1571
-285
1094
289
0
0
"4 "0
0
0
0
V p'
0
2A2ov,_ ti,_ A__,_�.
_.�0330
„_se_`
_ ,» Q5.7.:
w ri15.67
._ .�33
,8
_ __ _313.
512
0
,0..._j0
W
16B-19ad
0049
sw
1.42
2.59
117
117
166
303
_�y.....w
0
__ _.__.._0
0
_ .�
0
0
Blkwall stuaoeM
0201
sw;,
583
4.06.
432
383
2232
�1555
0
0
_
0
_.b
0
0u49
12
:, • 469
. .a768
w. _._0
_ _ _A
_.. Lb
Blk wall, stucco e#
0.201
w
5.83
4.06
29
17
99
69
0
0
0
0
2A 2ov
11,0 33..
w
9 57
20 92
12
1
1141.
249
0
0
0
0
Blkwall stu000ext
2A 2ov
0201
O.336
nw
nw
583,
9 57
406
1661
112
23
�68
0
399
224
278
= 389
0
0
0
0
0
0
0
0
11J0 _
2600
nw:n
1740;
175$
.. 20
s..,_ 20_�350
_w
0,
.� _ 4
1
12C Osw
0.091
2.64
1.31
268
250
660
328
56
38
w__.�0_
101
_,�Q
50
11 DO
0.390
n
11.31
11.43
ry 18
18
204
18
18
202
204
�166-30ai ,_w ._ r
_: .0032.p
,-
093.
___ 169
__v1972
_202
,
F
22A tpl _
-
0.989
28 68
0.00
_
1792
156
4465
0
49
0
0
0
t
-
_ j
w
7-777-
". _.,. .... ..�
..,.�._...._ �«.;.::.:._....._... _.,::_:...-_
w�....:...._.ia.. _L..
_ ......,»
.._r..._..:a_.._.
.._._, .....,..,.`a_
_� ...,..... ,iw.
_...,. .,.,_�_.._..,......_..,._
.:, _....e,
..w.E__..,...w ,.. ..
:...c,.._..a....::.:
....... a...> ..... ...............
.......m.
�._
,�.. ...�..-..--,.. zw
_
71
6
c)AED..ion
171
_42
Envelope loss/gain
15603
11823
348
295
12
a) Infiltration
3181
889
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
6
1380
0
0
Appliances/other
3000
600
Subtotal (lines 6 to 13)
18784
17092
348
895
Less edernal load
0
0
0
0
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
18784
.17092
348
895
15
Duct loads
15 %
22 %
2893
3811
15 %
22 %
54
200
Total room load
21676
20903
402
1095
Air required (cfm)
947
947
18
50
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-�- wrigtitsot-t^
2020-Oct-2811:e 1
�"'A Right-Sute(a�Uriversal 201919.0.16 RSU23828 Page 1
aterstone1780AGL\Lotl2Blk5Waterstonel780AGL.np Calc=MJ8 Hoisefaces:NW
- F wrightsoft, Right-M Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Job: Lot 12 Block 5 Waterston 17...
Date: 06.07.12
By: FLETCH
1
Room name
BR3
BATH2
2
Exposed wall
13.0 It
0 ft
3
Room height
8.0 ft heaV000l
8.0 It heaYbool
4
Room dimensions
1.0 x 146.5 It
9.0 x 6.0 ft
5
Room area
146.5 ftz
54.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft')
Load
Area (ft')
Load
number
(Btuh/ftz-`F)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall stucco 6)d
0201
n
51
i4.06
0
0
0
0
0
0
0
.:. 0
0 330
_n .
__.9.57.,
822
w0
0
_0
Blk wail, stucco ext
0201
ne
5.83
, 4.06
104
88
511
356
0
0
0
0
2A2ov
0330
ne
9.57
1770
16
0
156
289
0
0
0
0
1 1
Blk wall stucco ext
10Cv
0201
0550
se rt
sen
5 83
1595
r 4.06
16.20
0
0
0
0
0
0
0
0
0
0
0
0
0
0'
7A2ov0330
0w
_.0a
w,1-0u�_._�
`0_
0
�4
0
•.,:0
W
16B 19ad
0049
sw
1.42
2.59
0
0
0
0
0
0
0
�0
.
Blk wall stucco ext
0201
sw
5 5 83
4 06
"0
0
0
0
0
0
`' p
.2A2ov _..
__. _v0330
sw
_957,.
,166Z
z _0.0
_. -0.0,_°_
Blk wall, stucco ext
0.201
w
5.83
4.06
0
0
0
0
0
0
0
0
2A 2ov
0.330
w
9.57
20.92
0
0
0
0
0
0
0
0
'Blkwall stuomext
2A 2ov
0201
0.360
nw
nw
583
967
406
16 61
0
0
0
0
0
0
0
0
0
0
A
0
0
0
0
0
�9.600
12C Osw
0.091
2.64
1.31
104
104
274
136
0
0
0
0
11D0 -__
0390
n
1131,
1143
0
0
0
0
0
0
0
0
L30ad,:._
_., 0032
._ .(_
_..0
,y
F
22A 1pl
0.989
28.68
0.00
147
13
373
0
54
0
0
0
v
- �-
x _ ._
-71
Fn
c) AED
excursion
_48
-77
6
-4
Envelope loss/gain
1451
983
50
87
12
a) Infiltration
243
68
0
0
b) Room ventilation
0
0
0
0
13
internal gains: Occupants@ 230
0
0
0
0
Appliances/other
300
0
Subtotal (lines 6 to 13)
1693
1351
50
87
Less external load
0
0
0
0
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1693
1351
50
87
15
Dud loads
15%
22%
261
301
15%
22%
8
19
Total room load
1954
1652
58
107
Air required (cfm)
851
75
3
5
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-r�&- wrightsoft^
2020-Oct-2811:e 2
�A Right-SuteCNUriversal 201919.0.16 RSU23828 Page 2
aterstone1780AGLLot12Blk5Waterstone1780AGL.rup Calc= W8 House faces: NW
-�- wrightsoft9 Right-M Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 12 Block 5 Waterston 17...
Date: 06.07.12
By: FLETCH
1
Room name
BR2
MBR
2
3
4
5
Exposed wall
Room height
Room dimensions
Room area
13.0 ft
8.0 8 heaticool
1.0 x 137.5 ft
137.5 ftz
32.5 It
8.0 It heaV000l
1.0 x 270.5 ft
270.5 ftz
Ty
Construction
number
U-value
(Btuh/ftz-9
Or
HTM
(Btuh/ftz)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
1 1
yy11- -
!-G
BIk wall, shioco eM _ ~
2A2dv__: _ _ _�..
Blk wall, stucco ext
2A 2ov�
Blk wall, stucco ext
10C v
n2A2ov .._ _
166-19ad
Blkwall stu000eM
2A2ov y ..,__..._
Blk wall, stucco ext
Blkwall stu000ext
2A 2ov
12C-Osw
11DO__-_f__ _
16630adw
22A_tal_
0201
-_-0.330
0.201
0.330
- 0201
0550
_.._.0.33.0..._se.1567,_512
0049
0201
------ _0330
0.201
0.330
0201
0.330
u ___.060.0
0.091
0390
0032
._ 0989
n`
_-n-_
ne
se
-se-
se
sw
sw'
-sw:
w
_, w.
nw
nw
_ nw,
-
n
_ _.
_._.._
a.._ 583
___'057
5.83
9.57
5.83
1595
1.42
5f33:
,., .9.57;__,.
5.83
9.57
583
9.57
17A0.
2.64
11.31,
0.93.
�2868
v 4.Ofi
�122
4.06
17.70
4:06
1620
2.59
4.06
15:67
4.06
20.92
4.06
16.61
17.58
1.31
1143
__. , 1,69
0.00373
- ... 0v.0
.---_--_-0
104
16
, 0
0
0
0
_..; 0
0
_ ._0
0
0
0
0
_-__._._0
_._,__ __138
_ ....... _.. 0
88
_.__„ __ 0
0
0
0
0
_..._.._ 0_.._._
0
__...0
0
0
_.-.._.._0
0
__0
138
. .O
�. 0
511
__ 156
0
0
0
0
_0.__
0
_. ,.._ 0
0
0
^_-� 0.
_. _0
_-L-0
356
289
- 6
0
0
0
0
_ . _ 0
0
0
0._-'R
0
_ _._. 0
__.. _232
_---_. -0
--__.__0,
116
0
-'' 144
0
0
- _._.._0
0
.__-. __0
0
0
0
_ _.0
�.T 271
____.._A
116
0
_ _.-1] T
0
0
._ 0.
0
0
.._ ._.-. _6
0
_0
0
_. _ 0
_--_ _271
676
0
---.649
0
0
_0
0
0
_---,__._. 0
0
0
_0
_ .252
471
0
0
0
_-, 0
0
0
0
0
_ 0.
0
_ .0
_ ..__.458
tV►/
I G
.
W
V►/
G
Vl/
R
__.
C - --__
0
__ 0
.� __ 128
_
excursion
--
-39
6
c) AED
150
Envelope loss/gain
1168
838
2822
2043
12
a) Infiltration
b) Room ventilation
243
0
68
01
607
0
170
0
13
Internal gains: Occupants@ 230
Appliancesbther
0
0
300
1
230
600
Subtotal (lines 6 to 13)
1411
1206
3429
3043
14
15
Less external load
Less transfer
Redistribution
Subtotal
Ductloads
15%
22%
0
0
0
1411
217
0
0
0
1206
269
15/
22%
0
0
0
3429
528
0
0
0
3043
679
Total room load
Air required (dm)
1628
71
1475
67
3957
173
3721
169
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
-* wr➢gF+tsoiFt AGE Right-Su2020-Oct-2811:00:19
te®Uriversa12019 19.0.16 RSU23828 Page 3
aterstone178OAGL1Lot12Blk5Waterstone178OAGL.np Calc=W8 Hoisefaces:NW
-FF wrightsoft, Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 12 Block 5 Waterston 17...
Date: 06.07.12
By: FLETCH
1
Room name
IVBATH
WIC
2
3
Exposed wall
Room height
21.0 ft
8.0 ft heaUcool
7.5 ft
8.1 It heat/cool
4
5
Room dimensions
Room area
1.0 x 116.0 It
116.0 ft2
1.0 x 87.0 8
87.0 ft2
Ty
Construction
number
U-value
(Btuhfit-'F)
Or
HTM
(Btuh12)
Area (ft2)
or perimeter (ft)
Load
(Btuh)
Area (ft')
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/PiS
Heat
Cool
6
11
Vy
! _-G
V)/
IG
__
W
yV►!l
_ C
tVI/
-mil]
--G
q
---.D-
Blk wall'siu000 eM _--
2A2ov • _ _ __
Blk wall, stuom ext
2A 2ov
Blkwall 66&i xt
10C v
1613-19ad
Blk wall' stucco eM
2A2ov.. en,
Blk wall, stucco ext
2A 2ov _
BIk wall stti000 ext
2A 2ov
12C-Osw
-11 D0- - _ --
166 30atl-- __-.._ _....�
'-- - 0201
._ _ __0330
0201
_ _ 0330
0201
0.550
0.049
0 201
:0330
0.201
0330
-0201
0330
0.091
---- 0.390
0,032
-ri
_ _n.
ne
._ne
se
se
sw
sw
_sw_:
w
w
nw
nw'
-. nw-
_ n
_ __.
5.83
-9.57
5.83
9.57
583
15.95
1.42
5 83
_.k._9.57_
5.83
957
5 83'
9.57
. 1740
2.64
- 11.31_
_. 0.93.
_ 4.06
4.06
17.70
� 4.06
1620
2.59
4 06
1_._1507.+
4.06
20.92
4.06
16.61
1758
1.31
_ . 11_.43
�_, 1.69
-'____ r_ O
_ _ _ __ 0
0
0
-� ' �112
0
0
- 56
. .a_._0
0
0
V 0
0
_ 0
0
-- 0
_____ 116
..-_-.-__ 0
0
_ 0
0
0
_ ,0_
0
0
_. 0
0
0
0
60
;___:____._0
0
0-____-,
0
0
,_._ 0
0
- _
0
0
_ 0
_ 0
0
0
60
_..-. _.__0
0
0
0
0
�___-_0
0
- _0..__.
8
- 0
0
0
0
0
0
6
0
-- 0
244
0
0
0
0
_-.----0.
0
0
..... _---- -- 0
0
-0
- f12
0
0
56
_:___0
0
0
0
0
_. _. 0
0
- - _ 0
___.__116
653
0
0
326
w_.. _.0
955
0
0
227
v ..- ._
0
0
`- 0,
0
_ 0
0
- - 0
76
0
0
350,
0
0
0-
0
�_-.- Q
0
- - 0
--___215
0
0
0
-0
_ __ 0
0
_0
- --108
6
c) AED e.rsion
_44
_19
Envelope loss/gain
1689
834
646
373
12
a) Infiltration
b) Room ventilation
392
0
110
0
140
0
39
0
13
Internal gains: Occupants@ 230
Appliances/other
0
0
0
0
0
0
Subtotal (lines 6 to 13)
2081
944
786
412
14
15
Less external load
Less transfer
Redistribution
Subtotal
Ductloads
159/6
22°/
0
0
0
2081
321
0
0
0
944
210
15%
22%1
0
0
0
786
121
0
0
0
412
92
Total room load
Air required (dm)
2402
105
1154
52
907
40
503
23
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-4*wrightsoFt^ 2020-Oct-2811:00:19
Right-Sute®Uriversal 2019 19.0.16 RSU23828 Page 4
...alerstonel780AGL\Lotl2Blk5Waterstonel780AGL.np Calc=MJ8 Hoisetaces:NW
-- wrightsoft, Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 12 Block 5 Waterston 17...
Date: 06.07.12
By: FLETCH
1
Room name
FAMIHALL(S)
KIT
2
3
Exposed wall
Room height
24.0 ft
9.5 ft heat/cool
17.0 ft
9.5 It heaU000l
4
5
Room dimensions
Room area
1.0 x 451.0 ft
451.0 ftz
1.0 x 290.0 It
290.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ft)
Load
number
(Btuh/ftz-cq
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
V►/
VI/
Blkwallstu000ext
Blk wall, stu000 ext
0201
0.201
n
._n_;
ne
683
9.57:
5.83
406
._822...._
4.06
=`0
a_
0
-0
_0:00_._.�_0----__.__0__
0
0
0
00
0
0
0
0
.0
0
�.-.
0
0
11
I-G
2A 2ov
Blkvuall stuoaoext _
0.330
0201
_ ne
se
9.57
583
17.70
406
0
64
0
46
0
0
0
0
0
_._ 0
0
W
'10C v
1613-19ad
Bik wall stu000 ext _
2A2ov_0.330
0.560
____-0.330._se_
0.049
0 201
se
sw
sw
__sw_
1595
__957
1.42
583
... _. 9.5Z
1620
2.59
4 06
__,1 .67
18
..__T.0__L_0
57
128
____._:_
18
57
95
_ _._ 8
285
_,-__,__0
81
" 556
_----__313
289
147
" 387
_.,____512
0
60
96
� D
0
60
96
_-__� ,___0
0
85
560
_u ____0
0
155
-'390
_. Q-
0
0
_ -40
VI/
�-G
Elk wall, stu000 ext
2A 2ov
0.201
0.330
0201
w
w
nw
5.83
9.57
583
4.06
W.
4.06
0
0
0
0
0
" 0
0
0
0
0
0
- 0
0
0_
.� 20
0
_ 0
116
0
0
` 81
-BlKwallu000eid
__--.
R
2A 2ov
11 J0 --- _.._w..
12C-Osw
11DO
0.330
_-__.__0600
0.091
0390
nw
._nw_
n_
9.57
_?1.40,
2.64
1131
16.61
i758
1.31
11.43
=769
0
_ __0
0
_0
0
_.�__0
0
0
0
__: 0
0
_0
0
_ 0
0
0
909
0
108
0_
0
0
285
0
0
142
_0
108
0
0.00
451
24
688
0
_ _ 290
_ - 17
488
_
_
___,-------0-
6
c) AED excursion
13
-135
Envelope loss(gain
2691
2445
2204
1570
12
a) Infiltration
581
162
458
128
b) Room ventilation
0
0
0
0
13
Internal gains: Oocupants@ 230
4
920
0
0
Applianoesiother
0
1200
Subtotal (li nes 6 to 13)
3272
3527
2662
2898
14
151
Less extemalload
Lesstransfer
Redistribution
Subtotal
Ductloads
15%
22%
0
0
0
3272
504
0
0
0
3527
787
15%
22%
0
0
0
2662
410
0
0
0
2898
646
Total room load
Air required (dm)
3776
165
4314
195
3071
134
3544
161
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed.
wr➢gF�#sort^ 2020-Oct-2811:00:19
ACCK Righ-Sute®Uriversal 201919.0.16 RSU23828 Page 5
aterstonel780AGLtLotl2Blk5Walerstonel78OAGL.nQ Calc=MJ8 Hosefaces:NW
-�- wrightsoft9 Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 12 Block 5 Waterston 17...
Date: 06.07.12
By. FLETCH
1
Room name
DIN/FOY
2
3
Bposed wall
Room height
27.7 It
9.5 8 heat/cool
4
5
Room dimensions
Room area
1.0 x 190.5 ft
190.5 ftz
Ty
Construction
number
U-value
(Btuft tz-fl
Or
HTM
(Btuh/ftz)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Area
or perimeter
Load
Heat
Cool
Gross
N/F/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
__..
W
Vj/
�--G
-G
R
_ -.__...
F.__�__
Blk wall, siu000 ex[
2A-2ov_
Blk wall, slu000 ext
2A 2ov_ -
Blkwallmoext4.06
100v
2A 2ov_ :_
16B-19ad
Blkwall shi000ext
:2A2ou_ .,v _..__..
BIk wall, stuoco ext
2A2ov _-
Blkwalt tu000ext
2A 2ov
12C-Osw
_11p0-__.
22Adpl _ r__
- 0201
0201
0.330
0550
_ _-..._0.330
0.049
-0201
_m._.u:_0330
0.201
_�0330
0201
0330
_0600
0.091
0.390
.-__ 0.032
0.989
n-_-
ne
" ne
se
.. se"..
sw
sw
.sw.",
w
w_
'nw
nw
,- riw.
-
" n-
..__ _
57.
5.83
_ 9.57
15.95.
1.42
583
957_
5.83
9.57
5.83
9.57
17,40.
2.64
- 11.31_
..._.._ 0233.
28.68
4.06
17.70
1620
2.59
406
4.06
20.92
4.06
16.61
.- 1758
1.31
11.43
�.-.._1.69
- 0.00
0
._� _ ,0
0
- _« 0
0
- 0
�76
17
1.
48
0
---_.--
0
-
,_-___227,
28
0
0
0
0
_ 441
99
114
283
224
0
0
- .0
. - 210
764
0
__---.-.--
0
0
0
92
29
12
_.-72
23
0
0
-- -
_.__,..�..227,
191
0
0
_ 0
69
249
197
' 389,
_�0
0
--
._' 383
0
----___.>..
_--.-------
- ---
- ___-.---
6
c) AED
excursion
337
Envelope loss/gain
2534
2354
12
a) Infiltration
b) Room ventilation
518
0
145
0
13
Internal gains: Occupants@ 230
1
230
Appliances/other
O
Subtotal (lines 6 to 13)
3051
2729
14
151
Less e)dernalload
Lesstransfer
Redistribution
Subtotal
Duct loads
15%
220/6
0
0
0
3051
470
0
0
0
2729
609
Total room load
Air required (dm)
3521
154
3337
151
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
�" L-4:- wrigF+tsoTt^ 2020-Oct-2811:00:19
A Right-Sute®Uriversal 201919.0.16 RSU23828 Page 6
..aterstone1780AGLIot12Blk5Waterstone1780AGL.np Calc=MJ8 Hosefaces:NW
wrightsoft. Duct System Summary Job: Lot 12 Block 5 Waterston...
Date: 06.07.12
Entire House By-. FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Project• •
For: ADAMS HOMES
5345 San Benedetto Place, Fort Pierce, FL 34951
External static pressure
Pressurelosses
Available static pressure
Supply/ return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.40
in H2O
0.06
in H2O
0.34
in H2O
0.170 / 0.170
in H2O
0.312
in/100ft
947
cfm
109 ft
Supply Branch Detail Table
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.312 in/100ft
947 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH2
c 107
3
5
0.460
4.0
Ox 0
VI Fx
3.9
70.0
BR2
h 1628
71
67
0.420
5.0
Ox0
VIFx
11.0
70.0
BR3
h 1954
85
75
0.443
5.0
Ox 0
VIFx
6.7
70.0
DIWFOY
h 3521
154
151
0.374
7.0
Ox 0
VIFx
20.9
70.0
FAMMALL(S)
c 4314
165
195
0.434
8.0
Ox 0
VI Fx
8.3
70.0
KIT
c 3544
134
161
0.381
7.0
Ox 0
VI Fx
19.1
70.0
LAU
c 1095
18
50
0.456
4.0
Ox 0
VIFx
4.5
70.0
MBATH
h 2402
105
52
0.312
6.0
Ox 0
VI Fx
24.0
85.0
sti
MBR
h 3957
173
169
0.322
7.0
Ox0
VIFx
20.7
85.0
st1
W Ic
h 907
40
23
0.333
4.0
Ox 0
VI Fx
17.1
85.0
st1
Supply Trunk Detail Table
Name
Trunk
Type
Htg
(cfm)
Cig
(cfm)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
st1
PeakAVF
317
244
0.312
719
9.0
0 x 0
VinlFlx
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Cig
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mal
Trunk
rb2
Ox 0
947
947
0
0
0
0
Ox 0
VIFx
^ * wrights* CM,
14L Right-SuteOUriversal201919.0.16 RSU23828
XCK aterstone1780AGL\Lott2Blk5Waterstore1780AGL.nQ Calc=MJB Hoisetaces:NW
2020-Oct-2811:0020
Page 1
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 12 Block 5 Waterstone 1780 AGL Builder Name: ADAMS HOMES
Street: 5345 San Benedetto Place Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
U
Owner: Jurisdiction: 661000
W
Design Location: FL, ST_LUCIE_CO_INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the drywall.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
I
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates gnd walls or cp4lffinas-
a. in addition, inspection or log walls shall be in accordance with the provisions of !CC-400.
10/28/2020 11:36 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
FORM R405-2017
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the
residential Simulated Performance Method shall include:
❑ This checklist
❑ A Form R405 report that documents that the Proposed Design complies with Section
R405.3 of the Florida Energy Code. This form shall include a summary page
indicating home address, a -ratio and the pass or fail status along with summary
areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual
completing the compliance report (one page) and an input summary checklist that can
be used for field verification (usually four pages/may be greater).
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO for the Performance Method:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -
one page)
❑ A completed Envelope Leakage Test Report (usually one page)
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
Form R405 Duct Leakage Test Report (usually one page)
10/28/2020 11:35:45 AM EnergyGauge@ USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: 661000
Permit #:
Job Information
Builder: ADAMS HOMES Community: Lot: 12
Address: 5345 San Benedetto Place
City: Fort Pierce State: FL Zip: 34951
Air Leakage Test, - Results Passing results must meet either the Performance, Prescriptive, or ERI Method
eTIhVEtt METTH-ODJhe hall -beand verified'as having an air leakage rate of �riot�exceeding 7 air
Q
t
changes. sure of 0 2building
inch wwe1150,Pas ahs mate
p p 9• ( ) ones 1 and 2,
0 PERFORMANCE or ERI METHOD -The building or• dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the elected ACH(50) value, as shown on Form R405-201;7,(performance) or R406-2017- (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405 201 Z'Energy Ca/c (Performance) or R406 2017 (ERI): 7.000
x 60 _ 15664 Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
F1PASS Code
0 software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testin&Companyp':. _ .
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
10/28/2020 11:37:05 AM EnergyGaugeO USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 5345 San Benedetto Place Permit Number:
Fort Pierce , FL , 34951
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal enveld'* building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air IeakagdNindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
10/28/2020 11:36 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls. SECTION R403 SYSTEMS
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1, Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w,g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
�R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory) Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
❑ pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
10/28/2020 11:36 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
EiR403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60'C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
El R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment (Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
10/28/2020 11:36 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
El intermittent
Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -Fred heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste-heat-recoyery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
ElR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters Fred by natural or LP gas shall not have continuously burning pilot lights.
10/28/2020 11:36 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5
❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatofte energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps.
Exception: Low -voltage lighting.
R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights.
10/28/2020 11:36 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5