HomeMy WebLinkAboutFL14911_R11_II_SWD050 SS 2018-10-11SILVER LINE BUILDING PRODUCTS CORP.
V1 SERIES170 SERIES SINGLE HUNG WINDOW (2127)
(IMPACT RA TED) (H VHZ)
GENERAL NOTES:
1. THE PRODUCT SHOWN HEREIN IS DESIGNED AND
MANUFACTURED TO COMPLY WITH THE CURRENT EDITION
FLORIDA BUILDING CODE (FBC), INCLUDING HVHZ AND HAS
BEEN EVALUATED ACCORDING TO THE FOLLOWING:
• TAS 201-94
• TAS 202-94
• TAS 203-94
• ASTM E330-02
• ASTM E1886-05
• ASTM E1996-06/09/12
• AAMA/WDMA/CSA 101/I.S.2/A440-08
2. ADEQUACY OF THE EXISTING STRUCTURAL
CONCRETE/MASONRY, 2X FRAMING, AND METAL FRAMING
AS A MAIN WIND FORCE RESISTING SYSTEM CAPABLE OF
WITHSTANDING AND TRANSFERRING APPLIED PRODUCT
LOADS TO THE FOUNDATION IS THE RESPONSIBILITY OF THE
ENGINEER OR ARCHITECT OF RECORD FOR THE PROJECT OF
INSTALLATION.
3. 1X AND 2X BUCKS (WHEN USED) SHALL BE DESIGNED AND
ANCHORED TO PROPERLY TRANSFER ALL LOADS TO THE
STRUCTURE. BUCK DESIGN AND INSTALLATION IS THE
RESPONSIBILITY OF THE ENGINEER OR ARCHITECT OF
RECORD FOR THE PROJECT OF INSTALLATION.
4. THE INSTALLATION DETAILS DESCRIBED HEREIN ARE
GENERIC AND MAY NOT REFLECT ACTUAL CONDITIONS FOR
A SPECIFIC SITE. IF SITE CONDITIONS CAUSE INSTALLATION
TO DEVIATE FROM THE REQUIREMENTS DETAILED HEREIN,
A LICENSED ENGINEER OR ARCHITECT SHALL PREPARE SITE
SPECIFIC DOCUMENTS FOR USE WITH THIS DOCUMENT IN
NON-HVHZ AREAS. IN HVHZ AREAS, ONETIME PRODUCT
APPROVAL TO BE OBTAINED FROM MIAMI-DADE RER OR
AHJ.
5. APPROVED IMPACT PROTECTIVE SYSTEM IS NOT REQUIRED
ON THIS PRODUCT IN AREAS REQUIRING IMPACT
RESISTANCE.
6. WINDOW FRAME MATERIAL: PVC
7. IN ACCORDANCE WITH THE CURRENT EDITION FBC, WOOD
COMPONENTS SHALL HAVE BEEN PRESERVATIVE TREATED
OR SHALL BE OF A DURABLE SPECIES AS DEFINED IN
CHAPTER 23.
8. GLASS MEETS THE REQUIREMENTS OF ASTM E 1300
GLASS CHARTS. SEE SHEET 1 FOR GLAZING DETAILS.
MAX OVERALL SIZE
CONFIG.
DESIGN
MISSILE
WIDTH
HEIGHT
PRESSURE
IMPACT RATING
52"
73"
O/X
+55 / -60 PSF
LMI/SMI
TABLE OF CONTENTS
SHEET
REVISION
SHEET DESCRIPTION
1
GENERAL NOTES & GLAZING DETAIL
2
ELEVATION & ANCHOR LAYOUTS
3
VERTICAL SECTIONS
4
HORIZONTAL SECTIONS
S
HORIZONTAL & VERTICAL SECTIONS, INSTALLATION NOTES &
REINFORCEMENT DETAILS
EXTERIOR
STEELSPACER
1/8" OR 3/32"
SETTING BLOCK
GLAZING DETAIL 1
43/64" O.A. I.G. LAMINATED GLASS
CONSISTING OF:
1/8" ANNEALED GLASS
7/32"STEEL SPACER
3/32" ANNEALED GLASS
0.090" SAFLEX PVB INTERLAYER BY
EASTMAN CHEMICAL COMPANY
3/32" ANNEALED GLASS
INTFRinR
MIN. GLASS
BITE 7/16"
U 995 SEALANT
NOTE:
ALL GLAZING CONFIGURATIONS SHALL COMPLY WITH
SAFETY GLAZING REQUIREMENTS OUTLINED IN
CURRENT FBC AND ASTM E 1300 GLASS LOAD
RESISTANCE.
Silver Line
byAndei4efi
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, NJ 08902
W
U
_j
(D ^
Z m e
Z_ N
N
N �
o m m n
n o
N
N
p2f N
wLu
o m
Q m? a
m
0 0
° a
W O
(n
F z
Q J
w w
3
O Z
J a
ccZ
Z a a a x 3
Z u
N
H Z
o o E
W
l7
N W
Z 0
J w 3
N ?
} m M
=
m
r-I
m
<C
w
J
W
�
a
REMARKS
BY
I DATE
AND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFIC
SITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATE
FROM THE REQUIREMENTS DETAILED HEREIN, A LICENSED
ENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFIC
DOCUMENTS FOR USE WITH THIS DOCUMENT.
Digitally signpoft{l-IJ44 fF.,Norero, P.E
Dat :'e 8 V. A •'38. '
:�•N .7 7
OF ; tYZ
OT O 4DQ':'• w.�`
�
HERME� / IwoRFkb� •E.�
FLORIDA P.E. No 73778
BUILDING DROPS, INC
398 E. DANIA BEACH BLVD. / 338
DANIA BEACH, FL 33004
FBPE CERT. OF AUTHORIZATION No. 29578
FL #:
FL14911
DATE: 01.23.18
DWG. BY: CHK. BY:
FIRHFN
SCALE: NTS
DWG. #: SW D050
SHEET:
OF 5
a
a
MAX. O.A FRAME
HEIGHT 73"
MAX
HEIGH
MAX
HEIGH
MAX. O.A FRAME
WIDTH 52"
NAAV r% 1 n
ELEVATION
SINGLE HUNG WINDOW
3" MAX. 6" MAX.
FROM O.C.
CORNERS
6" MAX.
O.C.
3" MAX.
FROM
CORNERS
In
"X"
ANCHOR LAYOUT
NAIL FIN - SINGLE HUNG WINDOW
6.25" MAX.
FROM f
CORNERS
NOTE:
ALL FASTENERS ABOVE
THE MEETING RAIL IN
THE INTERIOR JAMB
TRACK MUST BE FLAT HEAD
12.50" MAX.
O.C.
6.25" MAX.
FROM
CORNERS
.'X'.
ANCHOR LAYOUT
THROUGH FRAME - SINGLE HUNG WINDOW
Silver Line
brAnderseri
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, N108902
w
F
U
0
Z M e
a
N N
<
Na
d o a m o
W
v m
LL
\
0
m
w0
u
N 0
Z
(D m m o m 3
O Z
N
Q
Z a z a x 3
p m
W
Z
0
J w 3
0= Z
LU 0
~
m
I =
�
m
J
W
w
a
Lli
J
Lu
F
a
REMARKS
BY
I DATE
AND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFIC
SITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATE
FROM THE REQUIREMENTS DETAILED HEREIN, A LICENSED
ENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFIC
DOCUMENTS FOR USE WITH THIS DOCUMENT.
```���Illlttllllff`
�.� E S 'i
:�•N .7 7
OF
OT O
// d
HEdkki 1k111AFtW �1.
FLORIDA P.E. No 73778
BUILDING DROPS, INC
398 E. DANIA BEACH BLVD. N 338
DANIA BEACH, FL 33004
FBPE CERT. OF AUTHORIZATION No. 29578
FL #:
FL14911
DATE: 01.23.18
DWG. BY: BY:
CHK.
HR HFN
SCALE: NTS
DWG. #: SW D050
SHEET:
a
OF 5
H
C7
w
2
w
Q
LL
w
X
Q
FXTFRI(1R
SEE GLAZING
DETAIL, SHEET 1
INTFRI(1R
SEE GLAZING
DETAIL, SHEET 1
A VERTICAL SECTION
��3j NAIL FIN
w
2
w
Q
LL
w
X
Q
2
SEE GLAZING
DETAIL, SHEET 1
INTFRI(1R
SEE GLAZING
DETAIL, SHEET 1
g VERTICAL SECTION
3 THRU FRAME
Silver Line
brAnderseri
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, N108902
w
U m
J
(D^
Z M E
0
Z
_ N
N
Z
vi N o
m n
d o o
v
0
Q
LLI \
Lu
S
_
F
== m n o
O
w 0
N Q
w
N
W w v
(D m m rn m
O Z
Q
Z Z Z Q LL 3
U_
o0o
Q
m
N
DC z
H
w
J w
3
w
>
} C�
2
CID
r
>
<
w
m
<<Q
w
J
a
w
LZ
REMARKS
BY
I DATE
AND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFIC
SITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATE
FROM THE REQUIREMENTS DETAILED HEREIN, A LICENSED
ENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFIC
DOCUMENTS FOR USE WITH THIS DOCUMENT.
```�I%11111IIIIIff`
% E O
,`� ••��� .... ICI
L� E s • p 'i
:�•N .7 7
OF ; tYZ
OT O
O L E� `e`�1
HEdI. 1lF! 114RFkb��1.�
FLORIDA P.E. No 73778
BUILDING DROPS, INC
398 E. DANIA BEACH BLVD. # 338
DANIA BEACH, FL 33004
FBPE CERT. OF AUTHORIZATION No. 29578
FL #:
FL14911
DATE: 01.23.18
DWG. BY: [CEH�KBY:
FIR HFN
SCALE: NITS
DWG. #: SW D050
SHEET
I
OF 5
SECTION FOR
BLOCK & TACKLE
BALANCEI
INTERIOR
SEE GLAZING
SEE GLAZING
_ — / EXTERIOR
D. L.O.
MAX. FRAME WIDTH
C HORIZONTAL SECTION
4 UPPER SASH
SEE GLAZING SEE GLAZING
DETAIL SHEET 1 INTERIOR DETAIL SHEET 1N
EXTERIOR
D. L.O.
MAX. FRAME WIDTH
p HORIZONTAL SECTION
4 LOWER SASH
SECTION FOR
r-CONSTANT FORCE
4NCERS
Silver Line
byAndi rts&ri
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, N108902
w
U
-i
z M
E
z_ N
N rl
z
d o o
v
W
O
�
m
O m- a m
w O
w
w w
in Q
J
(D m m
O Z
F-
Z
z Z a
z LL 3
N�
m o o m
�C z
J w 3
w
O
} [�
_
=
m
>
o
w
<<Q
w
J
a
F
w
F-
a
REMARKS
BY
I DATE
AND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFIC
SITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATE
FROM THE REQUIREMENTS DETAILED HEREIN, A LICENSED
ENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFIC
DOCUMENTS FOR USE WITH THIS DOCUMENT.
```���Illlttllllff`
,`� ••��� .... ICI
L� E s • p 'i
:�•N .7 7
OF
HE114RFkb�•E.�
FLORIDA P.E. No 73778
BUILDING DROPS, INC
398 E. DANIA BEACH BLVD. # 338
DANIA BEACH, FL 33004
FBPE CERT. OF AUTHORIZATION No. 29578
FL #:
FL14911
DATE: 01.23.18
DWG. BY: CHK. BY:
FIRHFN
SCALE: NTS
DWG. #: SW D050
SHEET
11
OF 5
a
MIN. SUBSTRATE
EDGE DISTANCE BY OTHERS
MIN.
EMBEDMENT
PERIMETER SEALANT1/4" MAX. }
BY OTHERS SHIM SPACE
EXTERIOR IA INTERIOR
q VERTICAL SECTION
6 THROUGH FRAME (HEAD)
79 1/4" MAX.
SUBSTRATE\ SPACE
BY OTHERS
INTERIOR
rorm
Evil Ild Pilral ?I
FXTFRInR
1/4" MAX.
SHIM SPACE
INTFRInR �
PERIMETER SEALANT
BY OTHERS
EXTERIOR
--SUBSTRATE
BY OTHERS
SCREW IN THE INTERIOR
CHANNEL
MIN.
EDGE DISTANCE
SCREW IN THE EXTERIOR
CHANNEL
MIN.
EMBEDMENT
g HORIZONTAL SECTION
6 THROUGH FRAME (JAMB)
MIN. EMBEDMENT
w 1u
0 U
Z
wQ
SUBSTRATE
BY OTHERS
—7
1/4" MAX.
SHIM SPACE
INTERIOR
C HORIZONTAL SECTION
6 NAIL FIN (HEAD)
REINFORCEMENT DETAILS
�{ �— 0.34"
0.83" 0.87"
� 0.13"
0.77" 0 91,
INTERIOR } 0.46"
0.45" 0.06" 0.87"
O1 LOCK RAIL TOP 2 LOCK MEETING RAIL O BOTTOM LIFT RAIL & SASH
ALUMINUM ALUMINUM ALUMINUM
MIN. EDGE
DISTANCE
p HORIZONTAL SECTION E VERTICAL SECTION
6 NAIL FIN (JAMB) 6 MEETING STILE
INSTALLATION NOTES:
1. ONE (1) INSTALLATION ANCHOR IS REQUIRED AT EACH ANCHOR LOCATION SHOWN.
2. THE NUMBER OF INSTALLATION ANCHORS DEPICTED IS THE MINIMUM NUMBER OF ANCHORS TO BE USED FOR PRODUCT INSTALLATION OF THE
MAXIMUM SIZE LISTED.
3. INSTALL INDIVIDUAL INSTALLATION ANCHORS WITHIN A TOLERANCE OF ±1/2 INCH THE DEPICTED LOCATION & SPACING IN THE ANCHOR LAYOUT
DETAILS (I.E., WITHOUT CONSIDERATION OF TOLERANCES). TOLERANCES ARE NOT CUMULATIVE FROM ONE INSTALLATION ANCHOR TO THE NEXT.
4. SHIM AS REQUIRED AT EACH INSTALLATION ANCHOR WITH LOAD BEARING SHIM(S). MAXIMUM ALLOWABLE SHIM STACK TO BE 3/8 INCH. SHIM
WHERE SPACE OF 1/16 INCH OR GREATER OCCURS. SHIM(S) SHALL BE CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER.
5. FOR MASONRY OR CONCRETE OPENINGS, 1X WOOD BUCK MAY BE USED (OPTIONAL AS LONG AS THE MINIMUM EMBEDMENT AND EDGE
DISTANCE REQUIREMENTS ARE STILL MET WITHIN THE CORRESPONDING HOST SUBSTRATE. SEE GENERAL NOTE #3 ON SHEET 1 FOR MORE
INFORMATION.
6. MINIMUM EMBEDMENT AND EDGE DISTANCE EXCLUDE WALL FINISHES, INCLUDING BUT NOT LIMITED TO STUCCO, FOAM, BRICK VENEER, AND
SIDING.
7. INSTALLATION ANCHORS AND ASSOCIATED HARDWARE MUST BE MADE OF CORROSION RESISTANT MATERIAL OR HAVE A CORROSION RESISTANT
COATING.
8. FOR HOLLOW BLOCK AND GROUT FILLED BLOCK, DO NOT INSTALL INSTALLATION ANCHORS INTO MORTAR JOINTS. EDGE DISTANCE IS MEASURED
FROM FREE EDGE OF BLOCK OR EDGE OF MORTAR JOINT INTO FACE SHELL OF BLOCK.
9. INSTALLATION ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND ANCHORS
SHALL NOT BE USED IN SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM STRENGTH SPECIFIED BY THE ANCHOR MANUFACTURER.
ANCHOR SCHEDULE
MIN. EDGE
METHOD
SUBSTRATE
ANCHOR SCHEDULE
MIN EMBEDMENT
DISTANCE
#8 WOOD SCREW
WOOD: MIN. SG = 0.55
PAN HEAD
1.5"
0.75"
NAILING FIN
3 THREADS MIN
METAL: 18 GAUGE Steel,
#8 TEK SCREW
MIN. Fy = 33KSI
PENETRATION BEYOND
0.50"
METAL
#10 PAN HEAD IN
EXTERIOR CHANNEL
1.51,
0.75"
WOOD: MIN. SG = 0.55
#10 FLAT HEAD IN THE
INTERIOR CHANNEL
1.5"
0.75"
3 THREADS MIN
#10 PAN HEAD IN
PENETRATION BEYOND
0.501,
METAL: 18 GAUGE Steel,
EXTERIOR CHANNEL
METAL
THROUGH FRAME
MIN. Fy = 33KSI
#10 FLAT HEAD IN THE
3 THREADS MIN
INTERIOR CHANNEL
PENETRATION BEYOND
0.50"
METAL
3/16" ITW TAPCON
CONCRETE: fc=3000PSI
FLAT HEAD
1.25"
1.75"
MASONRY: CMU per ASTM
3/16" ITW TAPCON
C90 MIN. 2000 PSI
FLAT HEAD
1.25"
1.75"
Silver Line
byAndi ris&i
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, N108902
w
Z
U
J
E
z_ (V
u06J
vi 0 uW~ie o a
N v
(n
N w H
J I-w
d
0
o o
?-a
LL
w
�
a 0 0
UZ�
m m v m
�umn-o
OC
Hzz
O
w O
L') p
cr w
wua�N9
(7 m m o
O Z
j 2
Z Z z Q LL 3
06 u
o o m
C{ Z
W m
ZNZ
CD
}
N
=
0 z w
r-I
>
N =CIO
o
lu
<<Q
a
REMARKS
BY
I DATE
AND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFIC
SITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATE
FROM THE REQUIREMENTS DETAILED HEREIN, A LICENSED
ENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFIC
DOCUMENTS FOR USE WITH THIS DOCUMENT.
```���Illlttllllff`
O ''e
:�•N .7 740
OF
OT O 4UQ'�'�
O
HE lF! ljvfktb� •E.�
FLORIDA P.E. No 73778
BUILDING DROPS, INC
398 E. DANIA BEACH BLVD. # 338
DANIA BEACH, FL 33004
FBPE CERT. OF AUTHORIZATION No. 29578
FL #:
FL14911
DATE: 01.23.18
DWG. BY: CHK. BY:
I I HFN
SCALE: NTS
SW D050
SHEET
10. FOR INSTALLATION ANCHORS ABOVE THE MEETING RAIL IN THE INTERIOR JAMB TRACK, USE FLATHEAD ANCHORS.
OF 5