Loading...
HomeMy WebLinkAboutX Manual J 1 Air Calcs LLC Load Short Form Job: 1336 Date: Sep 29,2020 A H 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Blower door Inside db(°F) 70 75 Shielding/stories 3(partial)/1 Design TD(°F) 29 15 Pressure/AVF 50 Pa/0 cfm Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACX-047-230* AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259382 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 10.7 kW Sensible cooling 32900 Btuh Heating output 36400 Btuh Latent cooling 14100 Btuh Temperature rise 21 °F Total cooling 47000 Btuh Actual airflow 1567 cfm Actual airflow 1567 cfm Air flow factor 0.040 cfm/Btuh Air flow factor 0.050 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.75 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Laundry 138 3371 2125 135 107 Storage 16 0 0 0 0 Lin 7 0 0 0 0 Guest Bath 63 925 504 37 25 Back Hall 75 0 0 0 0 Bed 2 209 4444 2684 178 135 Hallway 141 0 0 0 0 Pantry 82 218 154 9 8 Foyer 71 2645 2018 106 101 Great Room 641 6912 8425 277 422 Bed 3 226 3529 2293 142 115 Rec Room 275 6883 4056 276 203 Cabana Bath 69 1833 823 74 41 Vestibule 81 2262 1816 91 91 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Jan-14 08:08:15 M.ek•ae„n„e a«awa.omPa, Right-Srite®Uriversal 2021 21.0.02 RSU27054 Page 1 ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Kit/Dining 566 6043 6345 242 318 A/H 1 d 2661 39065 31244 1567 1567 Other equip loads 1804 958 Equip.@ 0.95 RSM 30721 Latent cooling 10628 TOTALS 2661 40869 41349 1567 1567 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Jar04 08:08:15 AI.--I--- a«awa.Iom— Right-Sute®Uriversal 202121.0.02 RSU27054 Page 2 tHVAC\TBDNobleOaksLn-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs LLC Load Short Form Job: 1336 Date: Sep 29,2020 A H 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Blower door Inside db(°F) 70 75 Shielding/stories 3(partial)/1 Design TD(°F) 29 15 Pressure/AVF 50 Pa/0 cfm Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS018-230A** AHRI ref Coil CBA25UH-018-230** AHRI ref 202540456 Efficiency 100 EFF Efficiency 12.2 EER, 14 SEER Heating input 4.6 kW Sensible cooling 12600 Btuh Heating output 15544 Btuh Latent cooling 5400 Btuh Temperature rise 24 °F Total cooling 18000 Btuh Actual airflow 600 cfm Actual airflow 600 cfm Air flow factor 0.035 cfm/Btuh Air flow factor 0.052 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.73 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Master Bath 212 3850 2018 133 106 Wtr Clst 41 954 612 33 32 Master Bedroom 432 7727 5468 268 286 M Lin 11 0 0 0 0 His 70 125 93 4 5 Hers 77 1393 792 48 41 Office 209 3274 2487 113 130 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Jan-14 08:08:15 M.ew•ae„n„e a«awa.omPa, Right-Srite®Uriversal 2021 21.0.02 RSU27054 Page 3 tHVAC\TBD Noble OaksLn-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N A/H 2 d 1052 17323 11470 600 600 Other equip loads 574 305 Equip.@ 0.95 RSM 11233 Latent cooling 4418 TOTALS 1052 17898 15651 600 600 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Jar04 08:08:15 AI.--I--- a«awa.Iom— Right-Sute®Uriversal 202121.0.02 RSU27054 Page 4 tHVAC\TBDNobleOaksLn-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Job: 1336 Air Calcs, LLC Building Analysis Date: Sep 29,2020 A/H 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Blower door Wet bulb(T) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm amme Component Btuh/ft2 Btuh %of load Walls 3.1 6005 14.7 walls Ventilation Glazing 18.4 8969 21.9 Ducts Doors 0 0 0 Ceilings 1.6 4221 10.3 Floors 2.4 6288 15.4 Infiltration 3.4 7612 18.6 Glazing Ducts 5969 14.6 Piping 0 0 Infiltration Humidification 0 0 Ventilation 1804 4.4 Adjustments 0 Ceilings Total 40869 100.01Floors • • • Component Btuh/ftz Btuh %of load Walls 1.9 3779 11.7 Walls Ventilation Glazing 25.7 12553 39.0 Internal Gains Doors 0 0 0 Ceilings 1.2 3252 10.1 Floors 0 0 0 Infiltration 1.0 2267 7.0 Ducts Ducts 3974 12.3 Ventilation 958 3.0 Internal gains 5420 16.8 Glazing Blower 0 0 Infiltration Adjustments 0 Total 32202 100.01Ceilings Latent Cooling Load=10628 Btuh Overall U-value=0.233 Btuh/ft2--°F Data entries checked. wrightsoft- 2021-Jan-14 08:08:15 Right-SUte®Uriversal2021 21.0.02 RSU27054 Page 1 ACCA ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Job: 1336 Air Calcs, LLC Building Analysis Date: Sep 29,2020 A/H 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(°F) 41 90 Infiltration: Daily range(°F) - 15 ( L ) Method Blower door Wet bulb(°F) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm amme Component Btuh/ft2 Btuh %of load Walls 3.2 3411 19.1 Ventilation Glazing 14.3 2682 15.0 walls Ducts Doors 0 0 0 Ceilings 1.6 1669 9.3 Floors 3.2 3384 18.9 Infiltration 3.4 4286 23.9 Glazin Infiltration Ducts 1891 10.6 Piping 0 0 Humidification 0 0 Ventilation 574 3.2 Adjustments 0 Ceilings Total 17898 1 100.0 Floors Component Btuh/ft2 Btuh %of load Walls 2.0 2182 18.5 Ventilation Walls Internal Gains Glazing 23.9 4484 38.1 Doors 0 0 0 Ducts Ceilings 1.2 1285 10.9 Floors 0 0 0 Infiltration 1.0 1276 10.8 Ducts 1243 10.6 Infiltration Ventilation 305 2.6 Internal gains 1000 8.5 Blower 0 0 Glazing Ceilings Adjustments 0 Total 11775 100.0 Latent Cooling Load=4418 Btuh Overall U-value=0.223 Btuh/112--°F Data entries checked. wrightsoft- 2021-Jan-14 08:08:15 Right-Suite®Universal 202121.0.02 RSU27054 Page 2 ACCA ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Component Constructions Job: 1336 p Date: Sep29,2020 A H 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Blower door Wet bulb(T) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd Ins,8"Thk, 1/2"Gyp Bd Int Fnsh ne 241 0.109 5.1 3.15 758 2.02 485 e 22 0.109 5.1 3.15 71 2.02 45 se 643 0.109 5.1 3.15 2026 2.02 1296 s 34 0.109 5.1 3.15 107 2.02 68 sw 400 0.109 5.1 3.15 1261 2.02 806 w 121 0.109 5.1 3.15 383 2.02 245 nw 307 0.109 5.1 3.15 968 2.02 619 all 1769 0.109 5.1 3.15 5573 2.02 3565 Partitions Fnn Wall, 1/2"Gyp Bd Ext,R-13 Cav Ins, 1/2"Gyp Bd Int Fnsh,2"A"Wd 185 0.080 13.0 2.33 432 1.16 214 Fnn, 16"OC Stud Windows Impact: Impact;NFRC rated(SHGC=0.25);foreground=green grass ne 10 0.400 0 11.6 116 25.3 253 (0.23);2 ft overhang(2 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);foreground=green grass ne 12 0.400 0 11.6 139 25.3 303 (0.23); 10 ft overhang(2 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.21);50%blinds 45°,medium; ne 30 0.640 0 18.6 557 21.9 657 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang se 54 0.640 0 18.6 1002 20.4 1104 (6 ft window ht,2 ft sep.);8.6 ft head ht all 84 0.640 0 18.6 1559 21.0 1761 Impact: Impact;NFRC rated(SHGC=0.31);foreground=green grass ne 48 0.790 0 22.9 1100 25.4 1218 (0.23); 10 ft overhang(8 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.31);foreground=green grass e 20 0.790 0 22.9 459 33.3 667 (0.23);6 ft overhang(6.5 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; se 20 0.400 0 11.6 232 17.9 358 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (4 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; se 25 0.400 0 11.6 290 18.5 463 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (5 ft window ht,2 ft sep.);8.6 ft head ht wrightsoft- 2021-Jan-14 08:08:15 --k=de-•,.ea«a-a. ,P=. Right-Sute®Universal 202121.0.02RSU27054 Pagel ACCk ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Impact: Impact;NFRC rated(SHGC=0.21);50%blinds 45°,medium; se 9 0.640 0 18.6 167 18.7 168 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (3 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.21);50%blinds 45°,medium; se 11 0.640 0 18.6 210 19.6 222 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang nw 11 0.640 0 18.6 210 21.9 248 (4 ft window ht,2 ft sep.);8.6 ft head ht all 23 0.640 0 18.6 421 20.7 470 Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; sw 20 0.400 0 11.6 232 14.8 296 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (2 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; sw 24 0.400 0 11.6 278 11.1 267 50%outdoor insect screen;foreground=green grass(0.23);20 ft overhang(6 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.37);foreground=green grass sw 120 0.810 0 23.5 2819 22.2 2668 (0.23); 15 ft overhang(10 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; w 41 0.400 0 11.6 476 11.1 456 50%outdoor insect screen;foreground=green grass(0.23); 14 ft overhang(6 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.31);foreground=green grass w 20 0.790 0 22.9 459 20.7 414 (0.23); 16.6 ft overhang(6.5 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.21);50%blinds 45°,medium; nw 12 0.640 0 18.6 223 21.9 263 50%outdoor insect screen;foreground=green grass(0.23); 18 ft overhang(4 ft window ht,2 ft sep.);8.6 ft head ht Doors (none) Ceilings DftCathCeil:Attic,Metal Roof,R-20 Roof Deck Ins, 1/2"Gyp Bd Int Fnsh 2661 0.405 21.0 1.59 4221 1.22 3252 Floors DftFlor.On Grade Depth,Tile Flr Fnsh 219 0.989 0 28.7 6288 0 0 wrightsoft- 2021-Jar04 08:08:15 --k-I.-III.-11.11...11 11-1 Right-Sute®Urrversal 2021 21.0.02 RSU27054 Page 2 ACCA ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Component Constructions Job: 1336 p Date: Sep29,2020 A H 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Blower door Wet bulb(T) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd Ins,8"Thk, 1/2"Gyp Bd Int Fnsh ne 250 0.109 5.1 3.15 788 2.02 504 se 197 0.109 5.1 3.15 619 2.02 396 sw 132 0.109 5.1 3.15 414 2.02 265 nw 504 0.109 5.1 3.15 1589 2.02 1017 all 1083 0.109 5.1 3.15 3411 2.02 2182 Partitions (none) Windows Impact: Impact;NFRC rated(SHGC=0.25);foreground=green grass ne 10 0.400 0 11.6 116 25.3 253 (0.23);2 ft overhang(2 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; ne 27 0.400 0 11.6 313 20.7 558 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (3 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.21);50%blinds 45°,medium; ne 30 0.640 0 18.6 557 21.9 657 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang sw 31 0.640 0 18.6 575 20.4 634 (6 ft window ht,2 ft sep.);8.6 ft head ht all 61 0.640 0 18.6 1132 21.2 1291 Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; nw 25 0.400 0 11.6 290 20.7 517 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (5 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.21);50%blinds 45°,medium; nw 11 0.640 0 18.6 210 21.9 248 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (4 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; nw 20 0.400 0 11.6 232 20.7 413 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (2 ft window ht,2 ft sep.);8.6 ft head ht Impact: Impact;NFRC rated(SHGC=0.25);50%blinds 45°,medium; sw 34 0.400 0 11.6 389 18.9 634 50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang (6 ft window ht,2 ft sep.);8.6 ft head ht Doors (none) wrightsoft- 2021-Jan-14 08:08:15 --1-de-•,.e a«a-a. ,P=. Right-Sutee Universal 2021 21.0.02 RSU27054 Page 3 ACCk ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Ceilings DftCathCeil:Attic,Metal Roof,R-20 Roof Deck Ins, 1/2"Gyp Bd Int Fnsh 1052 0.405 21.0 1.59 1669 1.22 1285 Floors DftFlor.On Grade Depth,Tile Flr Fnsh 118 0.989 0 28.7 3384 0 0 t -1l Wrightsoft- 2021-Jan-1408:08:15 11 Right-Sute®UNversal 2021 21.0.02 RSU27054 Page 4 tHVAaTBDNobleOaksLn-PereiraRes-VCC.np Calc=MJ8 Front Door faces:N Project Summary Job: 1336 Air Calcs, LLC 1 ry Date: Sep 29,2020 A/H 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project • • For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 33095 Btuh Structure 27270 Btuh Ducts 5969 Btuh Ducts 3974 Btuh Central vent(57 cfm) 1804 Btuh Central vent(57 cfm) 958 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 40869 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 30721 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding/stories 3(ppartial)/1 Pressure/AVF 50 Pa/0 cfi71 Structure 5975 Btuh Ducts 2466 Btuh Central vent(57 cfm) 2187 Btuh Heating Coolingg Outside air Area(ft�) 2661 2661 Equipment latent load 10628 Btuh Volume(ft3) 30859 30859 Air changes/hour 0.46 0.26 Equipment Total Load(Sen+Lat) 41349 Btuh Equiv.AVF(cfm) 239 134 Req.total capacity at 0.70 SHR 3.7 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond 14ACX-047-230* AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259382 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 10.7 kW Sensible cooling 32900 Btuh Heating output 36400 Btuh Latent cooling 14100 Btuh Temperature rise 21 °F Total cooling 47000 Btuh Actual airflow 1567 cfm Actual airflow 1567 cfrn Air flow factor 0.040 cfm/Btuh Air flow factor 0.050 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.75 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr1Q"tsoft- 2021-Jan-14 08:08:15 ^.,.I•I �.,.I�---..°..,,­r., Right-Sute®Universal 2021 21.0.02 RSU27054 Page 1 ACCk ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Project Summary Job: 1336 Air Calcs, LLC 1 ry Date: Sep 29,2020 A/H 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project • • For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 15432 Btuh Structure 10227 Btuh Ducts 1891 Btuh Ducts 1243 Btuh Central vent(18 cfm) 574 Btuh Central vent(18 cfm) 305 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 17898 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 11233 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding/stories 3(ppartial)/1 Pressure/AVF 50 Pa/0 cfi71 Structure 2914 Btuh Ducts 808 Btuh Central vent(18 cfm) 696 Btuh Heating Cooling Outside air Area(ft�) 1052 1052 Equipment latent load 4418 Btuh Volume(ft3) 11372 11372 Air changes/hour 0.71 0.40 Equipment Total Load(Sen+Lat) 15651 Btuh Equiv.AVF(cfm) 134 75 Req.total capacity at 0.70 SHR 1.3 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS018-230A** AHRI ref Coil CBA25UH-018-230-** AHRI ref 202540456 Efficiency 100 EFF Efficiency 12.2 EER, 14 SEER Heating input 4.6 kW Sensible cooling 12600 Btuh Heating output 15544 Btuh Latent cooling 5400 Btuh Temperature rise 24 °F Total cooling 18000 Btuh Actual airflow 600 cfm Actual airflow 600 cfm Air flow factor 0.035 cfm/Btuh Air flow factor 0.052 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.73 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr1Q"tsoft- 2021-Jan-14 08:08:15 ^.,.I•I �.,.I�---..°..,,­r., Right-Sute®Universal 2021 21.0.02 RSU27054 Page 2 ACCk ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name A/H 1 Laundry 2 E)posed wal I 219.3 It 25.5 ft 3 Room height 11.6 It d 10.0 It heat/000l 4 Room dimensions 1.0 x 138.3 ft 5 Room area 2660.6 fF 138.3 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 341 241 758 485 0 0 0 0 Impact 0.400 ne 11.60 25.29 10 0 116 253 0 0 0 0 Impact 0.400 ne 11.60 25.29 12 0 139 303 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 30 0 557 657 0 0 0 0 Impact 0.790 ne 22.91 25.38 48 0 1100 1218 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 42 22 71 45 0 0 0 0 Impact 0.790 e 22.91 33.28 20 18 459 667 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 762 643 2026 1296 115 97 306 196 Impact 0.400 se 11.60 17.90 20 13 232 358 0 0 0 0 Impact 0.400 se 11.60 18.52 25 13 290 463 0 0 0 0 Impact 0.640 se 18.56 18.70 9 8 167 168 0 0 0 0 Impact 0.640 se 18.56 19.57 11 7 210 222 0 0 0 0 Impact 0.640 se 18.56 20.44 54 23 1002 1104 18 4 334 368 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 34 34 107 68 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 564 400 1261 806 0 0 0 0 Impact 0.400 sw 11.60 14.79 20 25 232 296 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 24 48 278 267 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 120 240 2819 2668 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 182 121 383 245 0 0 0 0 Impact 0.400 w 11.60 11.13 41 82 476 456 0 0 0 0 Impact 0.790 w 22.91 20.67 20 40 459 414 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 331 307 968 619 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 11 0 210 248 0 0 0 0 Impact 0.640 nw 18.56 21.90 12 0 223 263 0 0 0 0 P Frm Wall,1/2"Gvp B 0.080 2.33 1.16 185 185 432 214 140 140 327 162 C DftCathCeil 0.405 1.59 1.22 2661 2661 4221 3252 138 138 219 169 F DftRor 0.989 28.68 0.00 2661 219 6288 0 138 26 731 0 6 c)AED excursion 2528 29 Envelope loss/gain 25484 19584 1917 924 12 a) Infiltration 7612 2267 388 116 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Appliances/other 4500 500 Subtotal(lines 6 to 13) 33095 27270 2306 1540 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 550 316 14 Subtotal 33095 27270 2856 1855 15 Dud loads 18% 15% 59691 3974 18% 15%1 515 270 FFTotal room load 39065 31244 3371 2125 Air required(ctm) 1567 1567 135 107 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..tHVAC\TBD Noble„...w.............. Right-Suite@ Universal 202121.0.02RSU27054 Pagel Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Storage Lin 2 E)posed wal I O ft O ft 3 Room height 10.0 It heat/000l 10.0 ft heat/000l 4 Room dimensions 4.5 x 3.5 ft 2.0 x 3.5 ft 5 Room area 15.8 ft2 7.0 ft Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.790 e 22.91 33.28 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 17.90 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 18.70 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 20.44 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 14.79 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 w 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.790 w 22.91 20.67 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 P Frm Wall,1C2"Gvp B 0.080 2.33 1.16 0 0 0 0 0 0 0 0 C DflCafhCeil 0.405 1.59 1.22 16 16 25 19 7 7 11 9 F DftRor 0.989 28.68 0.00 16 0 0 0 7 0 0 0 6 c)AED excursion -1 0 Envelope loss/gain 25 18 11 8 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 25 18 11 8 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution -25 -18 -11 -8 14 Subtotal 0 0 0 0 15 Duct loads 18% 15%1 01 0 18% 15%1 0 0 Total room load 0 0 0 0 Air required(ctm) 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 2 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Guest Bath Back Hall 2 E)posed wal I 5.5 ft 10.0 ft 3 Room height 10.0 ft heat/000l 10.0 ft heat/000l 4 Room dimensions 11.5 x 5.5 ft 6.5 x 11.5 ft 5 Room area 63.3 ft2 74.8 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 20 20 63 40 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.790 e 22.91 33.28 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 55 46 145 93 0 0 0 0 Impact 0.400 se 11.60 17.90 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 18.70 9 4 167 168 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 20.44 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 14.79 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 w 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.790 w 22.91 20.67 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 35 24 75 48 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 11 0 210 248 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gvp B 0.080 2.33 1.16 0 0 0 0 45 45 105 52 C DftCathCeil 0.405 1.59 1.22 63 63 100 77 75 75 119 91 F DftRor 0.989 28.68 0.00 63 6 158 0 75 10 287 0 6 c)AED excursion 26 55 Envelope loss/gain 570 364 858 535 12 a) Infiltration 186 55 186 55 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 756 420 1044 591 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 28 20 -1044 -591 14 Subtotal 784 440 0 0 15 Duct loads 18% 15% 141 64 18% 15%1 0 0 FFTotal room load 925 504 0 0 Airrequired(ctm) 37 25 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 3 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 2 Hallway 2 E)posed wal I 21.5 It 0 It 3 Room height 12.0 It heat/000l 12.0 It heat/000l 4 Room dimensions 13.5 x 15.5 It 1.0 x 141.0 It 5 Room area 209.3 fF 141.0 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 162 122 384 246 0 0 0 0 Impact 0.400 ne 11.60 25.29 10 0 116 253 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 30 0 557 657 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.790 e 22.91 33.28 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 17.90 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 18.70 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 20.44 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 14.79 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 w 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.790 w 22.91 20.67 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 96 96 302 193 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gvp B 0.080 2.33 1.16 0 0 0 0 0 0 0 0 C DftCathCeil 0.405 1.59 1.22 209 209 332 256 141 141 224 172 F DftRor 0.989 28.68 0.00 209 22 617 0 141 0 0 0 6 c)AED excursion -113 -9 Envelope loss/gain 2308 1492 224 163 12 a) Infiltration 870 259 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 0 Subtotal(lines 6 to 13) 3179 2001 224 163 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 586 342 -224 -163 14 Subtotal 3765 2343 0 0 15 Dud loads 18% 15%1 6791 341 18% 15%1 0 0 Total room load 4444 2684 0 0 Air required(ctm) 178 135 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 4 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Pantry Foyer 2 E)posed wal I O ft 9.5 It 3 Room height 10.0 It heat/000l 13.0 It heat/000l 4 Room dimensions 1.0 x 81.6 ft ft 9.5 x 7.5 5 Room area 81.6 ft2 71.3 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 124 64 200 128 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 12 0 139 303 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 48 0 1100 1218 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.790 e 22.91 33.28 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 17.90 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 18.70 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 20.44 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 14.79 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 w 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.790 w 22.91 20.67 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gvp B 0.080 2.33 1.16 0 0 0 0 0 0 0 0 C DftCathCeil 0.405 1.59 1.22 82 82 129 100 71 71 113 87 F DftFlor 0.989 28.68 0.00 82 0 0 0 71 10 272 0 6 c)AED excursion -5 -100 Envelope loss/gain 129 94 1824 1637 12 a) Infiltration 0 0 417 124 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 129 94 2241 1761 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 55 40 0 0 14 Subtotal 185 135 2241 1761 15 Dud loads 18% 15% 33 20 18% 15%1 404 257 Total room load 218 154 2645 2018 Air required(ctm) 9 8 106 101 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 5 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Great Room Bed 3 2 E)posed wal I 21.0 It 21.5 It 3 Room height 13.0 It heat/000l 10.0 It heat/000l 4 Room dimensions 1.0 x 641.4 It 1.0 x 226.4 It 5 Room area 641.4 fF 226.4 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.790 e 22.91 33.28 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 155 119 375 240 Impact 0.400 se 11.60 17.90 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 18.70 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 20.44 0 0 0 0 36 8 668 736 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 273 153 482 308 60 60 189 121 Impact 0.400 sw 11.60 14.79 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 120 120 2819 2668 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 w 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.790 w 22.91 20.67 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gvp B 0.080 2.33 1.16 0 0 0 0 0 0 0 0 C DflCathCeil 0.405 1.59 1.22 641 641 1018 784 226 226 359 277 F DftRor 0.989 28.68 0.00 641 21 602 0 226 22 617 0 6 c)AED excursion 1949 121 Envelope loss/gain 4921 5709 2209 1495 12 a) Infiltration 921 274 726 216 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 900 250 Subtotal(lines 6 to 13) 5842 7344 2935 1961 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 14 10 55 40 14 Subtotal 5856 7354 2990 2002 15 Dud loads 18% 15% 10561 1072 18% 15%1 539 292 FFTotal room load 6912 8425 3529 2293 Airrequired(ctm) 277 422 142 115 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 6 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Rec Room Cabana Bath 2 E)posed wal I 48.5 It 13.5 It 3 Room height 11.0 It heat/000l 10.0 ft heat/000l 4 Room dimensions 1.0 x 275.1 It 1.0 x 69.0 It 5 Room area 275.1 fF 69.0 tt Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 35 35 110 71 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.790 e 22.91 33.28 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 187 167 526 337 100 89 280 179 Impact 0.400 se 11.60 17.90 20 6 232 358 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 18.70 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 11 4 210 222 Impact 0.640 se 18.56 20.44 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 165 145 457 292 0 0 0 0 Impact 0.400 sw 11.60 14.79 20 13 232 296 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 w 11.60 11.13 0 0 0 0 0 0 0 0 Impact 0.790 w 22.91 20.67 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 182 170 534 342 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 12 0 223 263 0 0 0 0 P Frm Wall,1/2"Gvp B 0.080 2.33 1.16 0 0 0 0 0 0 0 0 C DftCathCeil 0.405 1.59 1.22 275 275 436 336 69 69 109 84 F DftRor 0.989 28.68 0.00 275 49 1391 0 69 14 387 0 6 c)AED excursion -119 27 Envelope loss/gain 4031 2105 1097 583 12 a) Infiltration 1800 536 456 136 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 900 0 Subtotal(lines 6 to 13) 5831 3541 1553 718 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 0 0 14 Subtotal 5831 3541 1553 718 15 Dud loads 18% 15% 10521 516 18% 15%1 280 105 FFT-o tal room load 6883 4056 1833 823 required(ctm) 276 203 74 41 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 7 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 aH 1 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Vestibule Kit/Dining 2 E)posed wal I 10.6 It 32.2 It 3 Room height 10.0 It heat/000l 12.0 ft heat/000l 4 Room dimensions 1.0 x 81.0 ft 1.0 x 565.6 ft 5 Room area 81.0 ft2 565.6 fF Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 22.91 25.38 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 3.15 2.02 42 22 71 45 0 0 0 0 Impact 0.790 e 22.91 33.28 20 9 459 667 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 150 125 394 252 Impact 0.400 se 11.60 17.90 0 0 0 0 0 0 0 0 Impact 0.400 se 11.60 18.52 0 0 0 0 25 6 290 463 Impact 0.640 se 18.56 18.70 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 19.57 0 0 0 0 0 0 0 0 Impact 0.640 se 18.56 20.44 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 34 34 107 68 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 66 42 132 85 Impact 0.400 sw 11.60 14.79 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 11.13 0 0 0 0 24 24 278 267 Impact 0.640 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.810 sw 23.49 22.23 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 3.15 2.02 64 44 138 88 119 78 245 157 Impact 0.400 w 11.60 11.13 0 0 0 0 41 41 476 456 Impact 0.790 w 22.91 20.67 20 20 459 414 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 18 18 57 36 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gvp B 0.080 2.33 1.16 0 0 0 0 0 0 0 0 C DftCathCeil 0.405 1.59 1.22 81 81 129 99 566 566 897 691 F DftRor 0.989 28.68 0.00 81 11 304 0 566 32 923 0 6 c)AED excursion 165 502 Envelope loss/gain 1559 1478 3799 2978 12 a) Infiltration 358 107 1305 388 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 2 460 Appliances/other 0 1700 Subtotal(lines 6 to 13) 1917 1585 5103 5526 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 16 12 14 Subtotal 1917 1585 5119 5538 15 Duct loads 18% 15% 346 231 18% 15% 923 807 FFTotal room load 2262 1816 6043 6345 Airrequired(ctm) 91 91 242 318 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 8 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 AM 2 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name A/H 2 Master Bath 2 E)posed wal I 118.0 It 29.5 ft 3 Room height 10.8 It d 10.0 ft heat/000l 4 Room dimensions 1.0 x 211.8 ft 5 Room area 1051.8 fF 211.8 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 317 250 788 504 155 128 404 258 Impact 0.400 ne 11.60 25.29 10 0 116 253 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 20.67 27 0 313 558 27 0 313 558 11 Impact 0.640 ne 18.56 21.90 30 0 557 657 0 0 0 0 Impact 0.790 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 e 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 197 197 619 396 15 15 47 30 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 196 132 414 265 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 18.94 34 14 389 634 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 sw 18.56 20.44 31 13 575 634 0 0 0 0 Impact 0.810 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 w 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 561 504 1589 1017 125 115 363 232 Impact 0.400 nw 11.60 20.67 20 0 232 413 10 0 116 207 Impact 0.400 nw 11.60 20.67 25 0 290 517 0 0 0 0 Impact 0.640 nw 18.56 21,90 11 0 210 248 0 0 0 0 Impact 0.640 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Fmi Wall,1/2"Gvp B 0.080 0.00 0.00 0 0 0 0 0 0 0 0 C DftCathCeil 0.405 1.59 1.22 1052 1052 1669 1285 212 212 336 259 F DftRor 0.989 28.68 0.00 1052 118 3384 0 212 30 846 0 6 c)AED excursion 569 -49 Envelope loss/gain 11147 7951 2425 1496 12 a) Infiltration 4286 1276 996 297 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 1000 0 Subtotal(lines 6 to 13) 15432 10227 3421 1792 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 9 7 14 Subtotal 15432 10227 3430 1799 15 Duct loads 12% 12% 1891 1243 12% 12%1 420 219 FFTotal room load 17323 11470 3850 2018 Airrequired(dm) 600 600 133 106 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..t HVAC\TBD Noble w.............. Right-Suite@ Universal 2021 21.0.02 RSU27054 Page 9 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 AM 2 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Wtrclst Master Bedroom 2 E)q)osed wal I 6.5 It 52.0 ft 3 Room height 10.0 It heat/000l 11.0 ft heat/cool 4 Room dimensions 9.0 x 4.5 It 1.0 x 432.0 It 5 Room area 40.5 ft' 432.0 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 20.67 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 e 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 116 116 364 233 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 20 20 63 40 176 112 351 225 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 18.94 0 0 0 0 34 7 389 634 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 sw 18.56 20.44 0 0 0 0 31 7 575 634 Impact 0.810 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 w 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 45 34 106 68 281 256 805 515 Impact 0.400 nw 11.60 20.67 0 0 0 0 0 0 0 0 Impact 0.400 nw 11.60 20.67 0 0 0 0 25 0 290 517 Impact 0.640 nw 18.56 21.90 11 0 210 248 0 0 0 0 Impact 0.640 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gvp B 0.080 0.00 0.00 0 0 0 0 0 0 0 0 C DftCathCeil 0.405 1.59 1.22 41 41 64 49 432 432 685 528 F DftRor 0.989 28.68 0.00 41 7 186 0 432 52 1491 0 6 c)AED excursion 74 513 Envelope loss/gain 630 480 4951 3799 12 a) Infiltration 219 65 1930 575 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 500 Subtotal(lines 6 to 13) 850 545 6881 4873 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 3 2 14 Subtotal 850 545 6884 4876 15 Duct loads 12% 12%1 104 66 12% 12%1 844 593 FFTotal room load 954 612 7727 5468 Airrequired(ctm) 33 32 268 286 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..tHVAC\TBD Noble w.............. Right-Suite@ Universal 202121.0.02RSU27054 Page10 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 AM 2 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name MI-in His 2 E)q)osed wal I O ft O ft 3 Room height 10.0 it heat/000l 10.0 it heat/000l 4 Room dimensions 2.5 x 4.5 it 5.0 x 14.0 it 5 Room area 11.3 it' 70.0 ft Ty Consh'ucton U-value Or HTM Area (fl) Load Area (fl) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 25.29 0 0 0 0 0 0 0 0 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 20.67 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.790 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 e 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 18.94 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 sw 18.56 20.44 0 0 0 0 0 0 0 0 Impact 0.810 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco IDA 0.109 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 w 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 nw 11.60 20.67 0 0 0 0 0 0 0 0 Impact 0.400 nw 11.60 20.67 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gvp B 0.080 0.00 0.00 0 0 0 0 0 0 0 0 C DflCathCeil 0.405 1.59 1.22 11 11 18 14 70 70 111 86 F DttRor 0.989 28.68 0.00 11 0 0 0 70 0 0 0 6 c)AED excursion 0 -2 Envelope loss/gain 18 13 111 83 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 18 13 111 83 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution -18 -13 0 0 14 Subtotal 0 0 111 83 15 Duct loads 12% 12%1 0 0 12% 12% 14 10 Total room load 0 0 125 93 Air required(ctm) 0 0 4 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..tHVAC\TBD Noble„...w.............. Right-Suite@ Universal 202121.0.02RSU27054 Page 11 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 1336 AM 2 Date: Sep 29,2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Hers Office 2 E)posed wal I 11.0 It 19.0 It 3 Room height 10.0 It heat/000l 12.0 It heat/000l 4 Room dimensions 7.0 x 11.0 It 13.5 x 15.5 It 5 Room area 77.0 ft' 209.3 fF Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 162 122 384 246 Impact 0.400 ne 11.60 25.29 0 0 0 0 10 0 116 253 Impact 0.400 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 ne 11.60 20.67 0 0 0 0 0 0 0 0 11 Impact 0.640 ne 18.56 21.90 0 0 0 0 30 0 557 657 Impact 0.790 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 a 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 e 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 66 66 208 133 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 se 0.00 0.00 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 s 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 sw 11.60 18.94 0 0 0 0 0 0 0 0 Impact 0.400 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.640 sw 18.56 20.44 0 0 0 0 0 0 0 0 Impact 0.810 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.400 w 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.790 w 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 110 100 315 202 0 0 0 0 Impact 0.400 nw 11.60 20.67 10 0 116 207 0 0 0 0 Impact 0.400 nw 11.60 20.67 0 0 0 0 0 0 0 0 Impact 0.640 nw 18.56 21.90 0 0 0 0 0 0 0 0 Impact 0.640 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,1CZ"Gvp B 0.080 0.00 0.00 0 0 0 0 0 0 0 0 C DflCathCeil 0.405 1.59 1.22 77 77 122 94 209 209 332 256 F DftRor 0.989 28.68 0.00 77 11 315 0 209 19 -145 0 6 c)AED excursion 93 -60 Envelope loss/gain 869 595 2142 1484 12 a) Infiltration 371 111 769 229 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 500 Subtotal(lines 6 to 13) 1241 706 2911 2213 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 6 4 14 Subtotal 1241 706 2917 2218 15 Duct loads 12% 12% 1521 86 12% 12%1 357 270 FFTotal room load 1393 792 3274 2487 Airrequired(ctm) 48 41 113 130 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Jan-14 08:08:15 �� ..tHVAC\TBD Noble w.............. Right-Suite@ Universal 202121.0.02RSU27054 Page12 Oaks Ln-Pereira Res-VCC.r p Calc=MJ8 Front Door faces: N Air Calcs LLC Duct System Summary Job: 1336 Date: Sep 29,2020 A H 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.528/0.172 in H2O 0.528/0.172 in H2O Lowest friction rate 0.133 in/100ft 0.133 in/100ft Actual airflow 1567 cfm 1567 cfm Total effective length(TEL) 524 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Bed 2 h 4444 214 162 0.230 8.0 Ox 0 VI Fx 24.6 205.0 st3 Bed 3 h 3529 170 138 0.198 8.0 Ox 0 VI Fx 56.3 210.0 st2 Cabana Bath h 1833 88 50 0.136 6.0 Ox 0 VI Fx 79.0 310.0 st5 Foyer h 2645 127 121 0.135 7.0 Ox0 VIFx 75.7 315.0 st6 Great Room-A c 4213 166 253 0.133 9.0 Ox 0 VI Fx 80.3 315.0 st6 Great Room-B c 4213 166 253 0.138 9.0 Ox 0 VI Fx 67.6 315.0 st6 Guest Bath h 925 45 30 0.232 4.0 Ox0 VIFx 22.5 205.0 st3 Kit/Dining c 3172 145 191 0.205 8.0 Ox0 VIFx 47.4 210.0 st2 Kit/Dining-A c 3172 145 191 0.199 8.0 Ox0 VIFx 55.0 210.0 st2 Laundry h 3371 162 128 0.237 7.0 Ox0 VIFx 17.5 205.0 st3 Pantry h 218 10 9 0.207 4.0 Ox0 VIFx 45.1 210.0 st2 Rec Room h 3441 166 122 0.137 8.0 Ox 0 VI Fx 74.2 310.0 st5 Rec Room-A h 3441 166 122 0.134 8.0 Ox 0 VI Fx 83.7 310.0 st5 Vestibule c 1816 109 109 0.137 7.0 Ox0 VIFx 76.2 310.0 st5 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st5 PeakAVF 528 403 0.134 673 12.0 0 x 0 VinlFlx st2 st6 PeakAVF 460 628 0.133 588 14.0 0 x 0 VinlFlx st2 st2 PeakAVF 1459 1560 0.133 883 18.0 0 x 0 VinlFlx st3 PeakAVF 421 320 0.230 771 10.0 0 x 0 VinlFlx wrightsoft® 2021-Jan-14 08:08:17 A� M;.ek „n"e a«awa.=mP=. Right-Sute®Uriversal 2021 21.0.02 RSU27054 Page l ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb7 Ox 0 331 244 129.1 0.133 422 12.0 Ox 0 VI Fx rt2 rb1 Ox0 170 138 90.3 0.191 487 8.0 Ox 0 VIFx rt2 rb2 Ox 0 214 162 93.1 0.185 484 9.0 Ox 0 VIFx rt2 rb4 Ox 0 1165 1336 89.4 0.193 506 22.0 Ox 0 VI Fx rt2 TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt2 PeakAVF 1880 1880 0.133 862 20.0 0 x 0 VinlFlx Bolditalic values have been manually overridden wrightsoft® 2021-Jan-14 08:08:17 A —=ek=Iae,•.--1awa.=—— Right-Sute®Uriversal 2021 21.0.02 RSU27054 Page 2 ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs LLC Duct System Summary Job: 1336 Date: Sep 29,2020 A H 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.465/0.235 in H2O 0.465/0.235 in H2O Lowest friction rate 0.117 in/100ft 0.117 in/100ft Actual airflow 600 cfm 600 cfm Total effective length(TEL) 597 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Hers h 1393 58 50 0.119 5.0 Ox0 VIFx 65.1 325.0 st4 His c 93 5 6 0.119 4.0 Ox0 VIFx 66.4 325.0 st4 Master Bath h 3850 160 127 0.183 8.0 Ox 0 VI Fx 33.6 220.0 st1 Master Bedroom c 1823 107 114 0.117 7.0 Ox 0 VI Fx 71.3 325.0 st4 Master Bedroom-A c 1823 107 114 0.120 7.0 Ox 0 VI Fx 63.4 325.0 st4 Master Bedroom-B c 1823 107 114 0.177 7.0 Ox 0 VI Fx 42.6 220.0 st1 Office c 2487 136 156 0.183 7.0 Ox0 VIFx 33.9 220.0 st1 wtr clst h 954 40 38 0.183 4.0 Ox 0 VI Fx 34.0 220.0 st1 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st4 PeakAVF 277 284 0.117 521 10.0 0 x 0 VinlFlx st1 st1 PeakAVF 720 720 0.117 674 14.0 0 x 0 VinlFlx TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb6 Ox0 477 449 200.3 0.117 446 14.0 Ox 0 VIFx rt1 rb3 Ox0 243 271 178.1 0.132 496 10.0 Ox 0 VIFx rt1 wrightsoft® 2021-Jan-14 08:08:17 A� M;.ek „n"e a«awa.=mP=. Right-Sute®Uriversal 2021 2l.O.O2 RSU27054 Page 3 ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt1 PeakAVF 720 720 0.117 516 16.0 0 x 0 VinlFlx wrightsoft® 2021-Jar04 08:08:17 A —=ek=Iae,•.--1awa.=—— Right-Sute®Urrversal 2021 21.0.02 RSU27054 Page 4 ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Manual S Compliance Report Job: 1336 p Date: Sep29,2020 A H 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 32202 Btuh Entering coil DB: 75.7°F Outdoor design WB: 77.4°F Latent gain: 10628 Btuh Entering coil WB: 63.6°F Indoor design DB: 75.0°F Total gain: 42831 Btuh Indoor RH: 50% Estimated airflow: 1567 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: 14ACX-047-230*+CBA27UHE-048-230*++TDR Actual airflow: 1567 ch Sensible capacity: 32900 Btuh 102%of load Latent capacity: 14100 Btuh 133%of load Total capacity: 47000 Btuh 110%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 40869 Btuh Entering coil DB: 68.7°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1567 cfm Output capacity: 10.7 kW 89%of load Temp.rise: 50 °F Meets all requirements ofACCA Manual S. wrightsoft® 2021-Jan-14 08:08:17 A II,-=Iae,-"e--.,I—— Right-Sute®Universal 2021 21.0.02 RSU27054 Page l ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Manual S Compliance Report Job: 1336 p Date: Sep29,2020 A H 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Pereira Residence,Villadelta Construction Corp,LLC TBD Noble Oaks Ln,Port St Lucie,FL 34952 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 11775 Btuh Entering coil DB: 75.6°F Outdoor design WB: 77.4°F Latent gain: 4418 Btuh Entering coil WB: 63.4°F Indoor design DB: 75.0°F Total gain: 16193 Btuh Indoor RH: 50% Estimated airflow: 600 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: 14ACXS018-230A**+CBA25UH-018-230** Actual airflow: 600 ch Sensible capacity: 12600 Btuh 107%of load Latent capacity: 5400 Btuh 122%of load Total capacity: 18000 Btuh 111%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 17898 Btuh Entering coil DB: 68.9°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 600 ch Output capacity: 4.6 kW 87%of load Temp.rise: 50 °F Meets all requirements ofACCA Manual S. wrightsoft® 2021-Jan-14 08:08:17 A II,-=Iae,-"e--.,C­ Right-Sute®Universal 202121.0.02RSU27054 Page ACCP. ...tHVAC\TBD Noble Oaks Ln-Pereira Res-VCC.rup Calc=MJ8 FrontDoorfaces: N Level 1 N R R. 6 j M3sfer Behoan _6 / �me l 24 om .16 e - 12x12 4Ndm t14 � 1 253rhn ] KNgnrg 91 tlm 6. Gim[Room Res �10x6 8" 9" 6 R tOxb 6" / �ry4 d~ 1146n 12x12 �bx4 9•• 253ctrn Bed3 12.12 10 Qm � 14 1n1 fin He Ma 2x6 6 9 ] ]1 do - 1Octrn �WIrCM M n c�s1 a�n 214tln Fme< 6 lazsem 2,8 e dz11 smra� un am`Rei 1ss m,� 1s6 em 12x6 214ifm IaWry Matz BatM1 12.8 82 rfm 4 16" u G_2, G_1 m VILLADELTA CONSTRUCTION CORP.LLC CRC 058035 oRaoE�_a°�Ed�pAE9n'"..'��°MNs Pronto PLans,LLC. m C_omplete Dra{tiny.Services `o Pereira Residence E eesee.« Enter address here Ns16�s,�or,oF,R�6 PRo�Ec,s6P.R�6R„z6�sP66N,6 Palls��� 711772-, Job#: 1336 Air Caics, LLC Scale: 1 : 211 Performed by Vicki Lynne Nisa for: Page 1 Pereira Residence 7550 Hidden Hammock Ln Right-Suite®Universal 2021 TBD Noble Oaks Ln Vero Beach, FL 32966 21.0.02 RSU27054 Port St Lucie,FL 34952 Phone:772.800.8413 2021-Jan-14 08:08:41 vickilynne@aircalcs.com e Oaks Ln-Pereira Res-VCC.rup