HomeMy WebLinkAboutBuilding plans - T Gates - 603016-Rev1 - Digital Sealed1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET —BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON —HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS WITH SEAL WASHERS @ 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH.
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
NOTES:
SUB —GRADE SOILS:
—TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION
—BOTTOM OF CONCRETE FOOTING SHALL BE MINIMUM OF 12" BELOW UNDISTURBED OR
ENGINEERED GRADE
CONCRETE:
—MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
—ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
—MINIMUM GRADE 40 STEEL
—REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
—THE REBAR IS BENT COLD
—THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6—BAR DIAMETERS: AND
" —REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
—COVER:
—3" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF 4" FOR FINE
GROUT, AND }" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATION:
—METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
ROPrL—UP EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
DOOR CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
N DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
J"x54" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES
AND EVERY OTHER END —WALL POST
3" MINI DOUBLE
�BASERAIL
`IIIIII�� d6�da C a
= _ a 2,500 PSI 4" CONCRETE
SLAB WITH 10GA. W.W.F.
�2OR FIBER MESH
1
_MINIMUM SOIL BEARING" CO)N INUOUS#5 REAWITTH MINIMUM
CAPACITY 500 PSF(TYP.) 25" OVERLAP SPLICE
CONCRETE FOUNDATION/DOUBLE
BASE RAIL ANCHOR DETAIL
2 5" PLAN VIEW DOOR FRAMING
" RECESS
4 DOOR WIDTH
ELEVATION VIEW
DOOR FRAMING
RECESS
T
.75"J 'L6 DOOR WIDTH
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
MIN. 2,500 PSI 4" CONCRETE SLAB WITH 10GA. W.W.F. (OR
FIBER MESH) AND 12"02" REINFORCED FOOTER PERIMETER 12"02" REINFORCED FOOTER
SW+NGNG---------------------------------------------------------------------------------------------------------------------------------------- � ------------------------------------------------------------------------
DOOR
1
ROLL -UP
DOOR
III
ROLL-i UP
DOOiR
CODE VERSION IFBC 2020 7th Edition,lj
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
INO
SQUARE FOOTAGE
11,800 SQ. FT.
REVISIONS
REV
DESCRIPTON
DATE
I BY
1
IWINDSPEED
1 1/5/21
1 MTB
e1: MTB
12/15/20
N. 5105 Pine Tree Dr., Ft. Pierce
60'L X 30'W X 16'H
NO.64608 2
i STATE OF 44/
8/0
c Digitally signed
by Matthew
Baldwin
Date:2021.01.05
09:57:06-05'00'
Z Matthew T. Baldwin P.E.
Q Florida License #64608
w —I
Sheet: CA-1 OF 4
12
3F77__1__
ROLL -UP
DOOR
FRONT END WALL
ROLL -UP
DOOR
DOUBLE
REAR END WALL
ROLL -UP
DOOR
DOUBLE
D.C. MAX.
sWMciNc •�
DOOR
�� SWMGMc
DOOR
3'-111i
3'-111j"
3'-11
LEFT SIDE WALL PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
D.O. MAX.
3'-11
3'-11
3'-11
3'-11
3'-11
3'-11
3'-11
3'-11
^3'-11
3'-11
5-11
3'-11
3'-111j"
RIGHT SIDE WALL
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
VRATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,800 SQ. FT.
REVISIONS
REVI
DESCRIPTON
I DATE
I BY
1
IWINDSPEED
1 1/5/21
1 MTB
UKAWN ex: MTB
DATE: 12/ 15/20
LOCATION: 5105 Pine Tree Dr., Ft. Pierce
SIZE: 60'L X 30'W X 16'H
cn
LLw
0
z_
Q
LL
0
z
L_LJ
Matthew T. Baldwin P.E.
W Florida License #64608
U) Sheet:
CA-2 OF 4
SWING NG
DOOR
FRONT END WALL
RIGHT SIDE WALL
LEFT SIDE WALL
REAR END WALL
SWING NG
DOOR
ANY ELECTRONIC COPIES
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
IUTILITY. U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
VRATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
11,800 SQ. FT.
REVISIONS
REVI
DESCRIPTON
I DATE
I BY
1
IWINDSPEED
1 1/5/21
1 MTB
uw+WN ex: MTB
DATE: 12/ 15/20
LOCATION: 5105 Pine Tree Dr., Ft. Pierce
SIZE: 60'L X 30'W X 16'H
cn
w
0
z
w
Matthew T. Baldwin P.E.
w Florida License #64608
U) Sheet:
CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING SC) 12 14xj" SELF —DRILLING
SCREWS
" NIPPLE TO /_2"x2"x2" 16 GA. ANGLE CLIP
T BASE RAIL NIPPLE TO T SECURED WITH (4) #12-14x"
BASE RAI O SELF —DRILLING SCREWS
POST TO BASE RAIL
CONNECTION
2"x2"x2" 16 GA.
ANGLE CLIP
SECURED WITH (4)
# 12-14xi"
SELF —DRILLING
SCREWS
NON—STRUCTURAL
HEADER OR WINDOW
RAIL TO POST DETAIL
#12-14xi"
SELF —DRILLING SCREWS
® 10" O.C. MAX., 3"
MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS
VERTICALLY
EXTERIOR
DOOR FRAME TO POST
CONNECTION
END POST TO BASE RAIL
CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP SECURED
WITH (4) #12-14xj" SELF —DRILLING
SCREWS
FF
ES NIF
TO TR
TD. MA�3SPM SPACING
I
D. MAX. SP*CING
' VARIES
SIDE WALL ROLL —UP
DOOR/FRAME OUT
HEADER DETAIL
PER MANUFACTURERS INSTRUCTIONS
#14x1"
SELF —DRILLING
SCREWS ® 6" O.C.
MAX. & 6" MAX.
FROM CORNERS
ROLL —UP DOOR TO
POST CONNECTION
TO TRU
BOX EA
POST COl`
Design Pressures -
150
mph Basic Wind Speed
Zone
Roof
Wall
1
2n
2r
2e
3r
3e
4
5
9.6
10.3
9.6
9.6
15.2
15.2
15.2
18.3
-11.8
-37.5
-29.9
1 -11.8
1
-65.4
1 -54.9
1 -17.0
1 -23.1
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF —DRILLING SCREWS
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR
WINDOW RAIL DETAIL
MINIMUM 6" TS
NIPPLE. NIPPLE
SECURED TO WALL
POST WITH
(4)# 12-14xi"
SELF —DRILLING
SCREWS
POST TO TRUSS
CONNECTION
GA. CHANNEL
B MI
BRACE, MIN. 24" UP TO
7' POST, MIN. 48" OVEF
7' POST. MIN. 45' TO
MAX. 60' FROM HORIZ.
(EXCLUDE END —WALLS).
SECURED WITH
(4)# 12-14xi"
SELF —DRILLING SCREWS.
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
RAFTER TO
JECTION DETAIL
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xj"
SELF —DRILLING SCREWS
SINGLE OR DOUBLETS
HEADER CONNECTION
DETAIL OPTION 1
26 GAUGE ROOF SHEATHING
SECURED WITH (1)#12-14xi"
SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
'e MAX
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-140" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
4" WELD
2' O.C. MAX.
DOUBLE POST/
LE
: R�
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
12-14xi" SELF —DRILLING
EWS
SINGLE OR DOUBLETS
HEADER
HEADER CONNECTION DETAIL
OPTION 2
NIPPLE
TRUSSED RAFTER
CONNECTION DETAIL
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 —R1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL21450.3
SERIES 3100
i 1p 0EL
!► i ►
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
INONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-150mph
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
11,800 SQ. FT.
REVISIONS
REV I DESCRIPTON DATE I BY
1 IWINDSPEED 1/5/21 1 MTB
C" J
MTB
12/15/20
5105 Pine Tree Dr., Ft. Pierce
60'L X 30'W X 16'H
Matthew T. Baldwin P.E.
Florida License #64608
Q
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w w
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES 0
Sheet: CA-4 OF 4