1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM.COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET -BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON -HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN. INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION CIOI.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET -BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER, RECEIVED
6. ROOF AND WALL SHEATHING SECURED WITH M72-14x3/4" SELF-DRIWNG SCREWS WITH SEAL WASHERS O 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH 012-14x3/4" SELF-DRIWNG SCREWS. 1011
B. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER. Baia Q
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,50OLB TENSILE STRENGTH.
10. 12 OR 14GA, FRAMING IS 2.5'x2.5' TUBE STEEL. NIPPLES ARE 2.25"x2.25' TUBE STEEL persllttln9 Department
ROL —UP St. Lucie County
ROLL -UP
D R DOOR
CONCRETE WEDGE ANCHOR WITHIN e'
OF EACH POSf/iR1155 ALOND SIDES AND
EVERT o1HER ENO -WALL POST
2" MIN. ASE RAIL EMBEDMENT
MIN.
GRADE _
= �����
~I I ll I I MINIMUM SOIL
BEARING CAPACITY EXISTING 4"
500 PSF (TYP.) CONCRETE SLAB Z
0
LL_
EXISTING CONCRETE/BASE RAIL
ANCHOR DETAIL
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY
BOCC
FIl.E COPY
EXISTING CONCRETE SLAB
I
I
OI
w
II
o
o
CARRMANIVIARM
CODE IRF-ORMATIO
CODE VERSION
BC 2020 7th Edition
SCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II-B
RISK CATEGORY
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
ult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+ - 0.18
IMPORTANCE FACTOR
1,0
ROOF DEAD LOAD
tOPSF
ROOF LIVE LOAD
OPSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR UVE LOAD
5OPSF
'R'RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,200 S0. FT.
REVISIONS
REV
DESCRIPTON
DATE
BY
°NA ar. WM
DATE 12/28/20
ag�625 Silver Oak Dr., Port St. Lucie
SQE 401 X 30-W X 14-H
Q5
'I
>
z
f,'
12/30/20
MottheW T. BaldWin P.E.
Florida License #64608
Sheet.
a
CA-1 OF 4
+
'
.A• at'
d-0
CARl '4i R1
�.
•_om
r;
P-o•
Rou_uv
MR
CODE INFORMATION
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II-B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150m h
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+ - 0.18
IMPORTANCE FACTOR
1.0
'_o•
ROOF DEAD LOAD
1OPSF
ROOF UVE LOAD
OPSF OR 3001b P.L.
FRONT/REAR(MIRRORED)
END WALL
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
WRATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 1,200 SQ. FT.
REVISIONS
REV DESCRIPTON DATE BY
DRAWN W' MTB
DATE 12/28/20
LaG 0%25 Silver Oak Dr., Port St. Lucie
s¢E: 401 X 30•W X 14'H
LEFT SIDE WALL
`7
' oc Alai.
D.C. Aw
D.C. Aw
§
SONGING
MR
(n
W_
0
Z_
W
O
Z
�
12/30/20
W
Matthew T. Baldwin P.E.
Florida License #6460a
RIGHT SIDE WALL Sheet: CA-2 OF `t
CARPOMANYWHEtE
CODE INFORMATION
------"'-------- --- -----"-""""""" CODE VERSION FBC 2020 7th Edition
ASCE-7-16
MANUFACTURER CARPORTS ANYWHERE
. — ...................................... BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE II—B
4 RISK CATEGORY I
"_"— " -uv FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
--- OCCUPANCY UTILITY, U
WIND SPEED ult-150mph
EXPOSURE B
.___. ................................................................. ENCLOSURE ENCLOSED
INTERNAL PRESSURE COEFF. + — 0,18
IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD 1OPSF
-0. ROOF LIVE LOAD OPSF OR 3001b P.L.
FLOOR DEAD LOAD 1OPSF
FRONT/REAR(MIRRORED) END WALL FLOOR LIVE LOAD 50PSF
'R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 1,200 SQ. FT.
REVISIONS
REV DESCRIPTON DATE BY
DM B` MTB
DATE. 12/28/20
Loc�`na%625 Silver Oak Dr., Port St. Lucie
5IM: 40'L X 30'W X 14'H
LEFT SIDE WALL
V
4 W �I
Y 0 �1Y
oa�No W
12/30/20
MattheW T. BaldWin P.E.
W Florida License 64608
RIGHT SIDE WALL
Sheet. CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)112-14x4" SELF —DRILLING
NIPPLE TO
BASE RAIL
POST TO BASE RAIL
CONNECTION
2%2"x2" 16 GA.
ANGLE CUP
SECURED WITH (4)
#12-14xj"
SELF —DRILLING
SCREWS
NON—STRUCTURAL
HEADER OR WINDOW
RAIL TO POST DETAIL
SELF —DRILLING SCREWS
a 10" O.C. MAX., 3"
MAX. FROM CORNERS
EXTERIOR
DOOR FRAME TO POST
CONNECTION
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14x4" SELF —DRILLING
2%2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14rt2"
SELF —DRILLING SCREWS
END POST TO BASE RAIL
CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP SECURED
WITH (4) #12-14x4" SELF -DRILLING
SCREWS
VARIES
TO
STD. MAX. SPACIN
3" MIN.
STD. MAX. SP CING
_ VARIES J
SIDE WALL ROLL —UP
DOOR/FRAME OUT
HEADER DETAIL
kLL PER MANUFACTURERS INSTRUCTIONS
#14x1"
SELF —DRILLING
SCREWS ® 6" 0
MAX. & 6" MAX.
FROM CORNERS
ROLL —UP DOOR TO
POST CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF —DRILLING SCREWS
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR
WINDOW RAIL DETAIL
MINIMUM 6" TS
NIPPLE. NIPPLE
SECURED TO WALL
POST WITH
(4)#12-141
SELF —DRILLING
SCREWS
POST TO TRUSS
CONNECTION
TO
1 "x2.�" 16 GA.
U—CHANNEL BRACE, MIN.
24" UP TO 7' POST, MIN
48" OVER 7' POST. MIN.
45' TO MAX. 60' FROM
HORI2. (EXCLUDE
END —WALLS). SECURED
WITH (4)#12-14)j"
SELF —DRILLING SCREWS.
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14)4" SELF —DRILLING
SCREWS
BOX EAVE RAFTER TO
POST CONNECTION DETAIL
Design Pressures -
150
mph Basic Wind Speed
Zone
Roof
Wall
1
2n
2r
2e
3r
3e
4
5
9.6
10.1
9.6
9.6
14.8
14.8
14.8
17.9
-11.5
-36,6
-29.2
-11.5
-63.8
-53.6
-16.6
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14q
SELF —DRILLING SCREWS
OR DOUBLE TS
HEADER CONNECTION
DETAIL OPTION 1
26 GAUGE ROOF SHEATHING
SECURED WITH (1)#12-14)j"
SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-14k1" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
NIPPLE
TRUSSED RAFTER
CONNECTION DETAIL
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SCREWS 14xj" SELF —DRILLING
mom
Cmm
OR DOUBLE TS
HEADER CONNECTION DETAIL
OPTION 2
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1—R1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL21450.3
SERIES 3100
VERSION
TYPE
SPEED
FLOOR DEAD LOAD I10PSF
FLOOR LIVE LOAD 5OPSF
PER
SHELTER
S0. FT.
I0°'E 12/28/20
mG.no%25 Silver Oak Dr., Port St. Lucie 1
1— 40-L X 30-W X 14-H II
12/30/20
_J Matthew T. Baldwin P.E.
a Florida License #64608
LrQ Sheet_ CA-4 OF 4