Building Dept. SLC
Project Name Indian River Spirits
Address 3196 North Kings Hwy
Contractor
mpson Remodeling & Home Repair
SAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
3871 39th Street City ;Vero Beach
— I
;Florida Zip 132960
itect/Engineer (MBVEngineering
FMO Permit # ; B-21-20
BLDGPermit # 1'2012-0517
City IFt. Pierce _
r
Telephone t
i(772)564-8008
Telephone 1(772)569-0035
Occupancy Type Industrial Construction Type VB Square Feet 110,000
Occupant Load 110 per plans Number of Stories j 1 Access Box +Required Access Key Switch
AFS Permit Required FA Permit JRequlred FFP Permit
I
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper LIL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Place exit lights over exit doors. Emergency lights are equired.
2. A separate review and permit is required for the installation or alteration of the fire alarm and fire sprinkler systews-.
3. Portable fire extinguishers from a licensed contractor are required.
4. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s)
shall be tied into the fire alarm system.
Pagel of j1— Reviewed by -� Date 01-21-2021