FORM R405-2014
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: TACOMA_eMED_MDW 91 Builder Name: GHO Homes
Street: 2801 Bent Pine Dr. Permit Office:
City,State,Zip: Fort Pierce,FL,34951 Permit Number:
Owner: GHO Homes Jurisdiction:
Design Location: FL,Fort Pierce County:: St.Lucie(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(2265.7 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul,Exterior R=4.1 1971.70 ftz
b.Frame-Steel,Adjacent R=11.0 294.00 ftZ
3. Number of units,if multiple family 1 c. N/A R= ft'
4'Number of Bedrooms 3 d.N/A R= ft'
5. Is this a worst case? No 10.Ceiling Types (2727.9 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 2523.00 ftZ
6- Conditioned floor area above grade(ft') 2523 b.Knee Wall(Vented) R=19.0 204.92 ft'
Conditioned floor area below grade(ft') 0 c. R= ft
11.Duct
s R ft'
7. Windows(444.6 sqft.) Description Area a.Sup:Attic, Ret:Attic,AH:Main 6 504.2
a. U-Factor: Dbl,U=0.49 248.00 ft'
SHGC: SHGC=0.24
b. U-Factor: Dbl,U=0.53 96.00 ft' 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.25 a.Central Unit 60.0 SEER:16.00
c. U-Factor: Dbl,U=0.46 78.67 ft'
SHGC: SHGC=0.26 13.Heating systems kBtu/hr Efficiency
d. U-Factor: other(see details) 21.92 ft' a.Electric Strip Heat 60.0 COP:1.00
SHGC: other(see details)
Area Weighted Average Overhang Depth: 8.011 ft.
Area Weighted Average SHGC: 0.243 14.Hot water systems
8. Floor Types (2523.0 sqft.) Insulation Area a.Natural Gas Cap:50 gallons
a.Slab-On-Grade Edge Insulation R=0.0 2523.00 ft' b. Conservation features EF:0.600
b.N/A R= ft2 None
c. N/A R= ft' 15.Credits Pstat
Glass/Floor Area: 0.176 Total Proposed Modified Loads: 78.63 PASS
Total Baseline Loads: 81.12
1 hereby certify that the plans and specifications co red by Review of the plans and 04114E STgTF
this calculation are in compliance with the Flori nergy specifications covered by this V e = , p�
Code. calculation indicates compliance
with the Florida Energy Code. ti rrre, ::': :•• „��
PREPARED BY: Before construction is completed Cc
DATE: 7! /2 17 V this building will be inspected for
compliance with Section 553.908 , •
Ph
ereby certify that t ' it as ned, is in compliance Florida Statutes.
the Florida Energy Co e. OpWE
OWNER/AGENT: BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
- Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors,
tested in accordance with Section 803 of RESNET Standards, is not greater than 0.060 Qn for whole house.
7/6/2017 9:00 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5
L
FORM R405-2014
PROJECT
Title: TACOMA_eMED_MDW 91 Bedrooms: 3 Address Type: Street Address
Building Type: User Conditioned Area: 2523 Lot#
Owner: GHO Homes Total Stories: 1 Block/SubDivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: GHO Homes Rotate Angle: 270 Street: 2801 Bent Pine Dr.
Permit Office: Cross Ventilation: County: St. Lucie
Jurisdiction: Whole House Fan: City,State,Zip: Fort Pierce,
Family Type: Single-family FL, 34951
New/Existing: New(From Plans)
Comment:
CLIMATE
• IECC Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL VERO BEACH MUNI 2 39 90 70 75 299 62 Low
BLOCKS
Number Name Area Volume
1 Blockl 2523 23548.2
SPACES
Number _ Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 Main 2523 23548.2 Yes 4 3 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Main 242.75 ft 0 2523 ft' ____ 0.6 0 0.4
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Hip Barrel tile 2822 ft' 0 ftz Medium 0.75 No 0.9 No 0 26.6
/ ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 150 2523 ft' N N
CEILING
# Ceiling Type Space R-Value_ Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) Main 30 Blown 2523 ft' 0.11 Wood
2 Knee Wall(Vented) Main 19 Batt 204.92 ftZ 0.11 Wood
7/6/2017 9:00 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
FORM R405-2014
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below# Ornt To Wall Type
_ 1 S=>E Exterior Concrete Block-Int Insul Main 4.1 13 6 9 4 126.0 ft2 0 0.600000 0
2 SE=>NE Exterior Concrete Block-Int Insul Main 4.1 3 9 4 28.0 ft2 0 0.600000 0
_ 3 E=>N Exterior Concrete Block-Int Insul Main 4.1 2 6 9 4 23.3 ft2 0 0.600000 0
4 S=>E Exterior Concrete Block-Int Insul Main 4.1 7 9 9 4 72.3 ft2 0 0.600000 0
5 W=>S Exterior Concrete Block-Int Insul Main 4.1 10 9 4 7.8 ft2 0 0.600000 0
6 SW=>SE Exterior Concrete Block-Int Insul Main 4.1 3 9 4 28.0 ft2 0 0.600000 0
7 S=>E Exterior Concrete Block-Int Insul Main 4.1 9 11 9 4 92.6 ft2 0 0.600000 0
8 S=>E Garage Frame-Steel Main 11 24 4 9 4 227.1 ft2 0.23 0.01 0
9 E=>N Garage Frame-Steel Main 11 7 2 9 4 66.9 ft2 0.23 0.01 0
10 E=>N Exterior Concrete Block-Int Insul Main 4.1 39 8 9 4 370.2 ft2 0 0.600000 0
11 N=>W Exterior Concrete Block-Int Insul Main 4.1 27 9 4 252.0 ft2 0 0.600000 0
12 W=>S Exterior Concrete Block-Int Insul Main 4.1 7 7 9 4 70.8 ft2 0 0.600000 0
13 NW=>S Exterior Concrete Block-Int Insul Main 4.1 1 5 9 4 13.2 ft2 0 0.600000 0
14 N=>W Exterior Concrete Block-Int Insul Main 4.1 13 3 9 4 123.7 ft2 0 0.600000 0
15 E=>N Exterior Concrete Block-Int Insul Main 4.1 12 0 9 4 112.0 ft2 0 0.600000 0
16 N=>W Exterior Concrete Block-Int Insul Main 4.1 16 9 4 149.3 ft2 0 0.600000 0
17 W=>S Exterior Concrete Block-Int Insul Main 4.1 51 6 9 4 480.7 ft2 0 0.600000 0
18 NW=>S Exterior Concrete Block-Int Insul Main 4.1 2 4 9 4 21.8 ft2 0 0.600000 0
DOORS
# Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 S=>E Insulated Main None .14 3 8 24 ft2
2 S=>E Wood Main None .14 2 8 8 21.3 ft2
3 N=>W Insulated Main None .14 1 2 8 9.3 ft2
4 E=>N Insulated Main None .14 1 2.9 8 10 ft2
WINDOWS
Orientation shown is the entered orientation => changed to As Built rotated 270 degrees).
/ Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 S=>E 1 Metal Low-E Double Yes 0.49 0.24 36.0 ft2 2 ft 0 in 1 ft 1 in Drapes/blinds Exterior 5
2 SE=>NE 2 Metal Low-E Double Yes 0.49 0.24 12.0 ft2 7 ft 11 in 7 ft 11 in Drapes/blinds Exterior 5
3 S=>E 4 Metal Low-E Double Yes 0.46 0.26 8.0 ft2 8 ft 6 in 6 ft 9 in Drapes/blinds Exterior 5
4 S=>E 4 Metal Low-E Double Yes 0.46 0.26 9.7 ft2 8 ft 6 in 4 ft 1 in Drapes/blinds Exterior 5
5 SW=>SE 6 Metal Low-E Double Yes 0.49 0.24 12.0 ft2 9 ft 4 in 7 ft 11 in Drapes/blinds Exterior 5
6 SW=>SE 6 Metal Low-E Double Yes 0.46 0.26 3.8 ft2 9 ft 4 in 5 ft 7 in Drapes/blinds Exterior 5
I: 7 S=>E 7 Metal Low-E Double Yes 0.49 0.24 30.0 ft2 2 ft 0 in 3 ft 5 in Drapes/blinds Exterior 5
8 S=>E 7 Metal Low-E Double Yes 0.46 0.26 12.0 ft2 2 ft 0 in 1 ft 8 in Drapes/blinds Exterior 5
9 E=>N 10 Metal Low-E Double Yes 0.49 0.24 12.0 ft2 2 ft 0 in 1 ft 1 in Drapes/blinds Exterior 5
10 E=>N 10 Metal Low-E Double Yes 0.49 0.24 40.0 ft2 2 ft 0 in 1 ft 1 in Drapes/blinds Exterior 5
11 N=>W 11 Metal Low-E Double Yes 0.25 0.18 10.7 ft2 5 ft 4 in 3 ft 4 in Drapes/blinds Exterior 5
12 N=>W 11 Metal Low-E Double Yes 0.49 0.24 36.0 ft2 5 ft 4 in 3 ft 1 in Drapes/blinds Exterior 5
13 N=>W 11 Metal Low-E Double Yes 0.46 0.26 8.0 ft2 5 ft 4 in Oft 11 in Drapes/blinds Exterior 5
7/6/2017 9:00 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
FORM R405-2014
WINDOWS
Orientation shown is the entered orientation => changed to As Built rotated 270 de rees .
/ Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
14 W=>S 12 Metal Low-E Double Yes 0.49 0.24 24.0 ft' 17 ft 0 in 3 ft 7 in Drapes/blinds Exterior 5
15 W=>S 12 Metal Low-E Double Yes 0.46 0.26 5.3 ft' 17 ft 0 in 1 ft 5 in Drapes/blinds Exterior 5
16 N=>W 14 Metal Low-E Double Yes 0.53 0.25 96.0 ft' 14 ft 4 in 3 ft 1 in Drapes/blinds Exterior 5
17 N=>W 14 Metal Low-E Double Yes 0.46 0.26 16.0 ft' 14 ft 4 in Oft 11 in Drapes/blinds Exterior 5
18 E=>N 15 Metal Low-E Double Yes 0.25 0.18 11.2 ft' 32 ft 8 in 3 ft 4 in Drapes/blinds Exterior 5
19 N=>W 16 Metal Low-E Double Yes 0.49 0.24 40.0 ft' 2 ft 0 in 1 ft 1 in Drapes/blinds Exterior 5
20 W=>S 17 Metal Low-E Double Yes 0.49 0.24 6.0 ft' 2 ft 0 in 1 ft 2 in Drapes/blinds Exterior 5
21 W=>S 17 Metal Low-E Double Yes 0.46 0.26 12.0 ft' 2 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
22 SE=>NE 2 Metal Low-E Double Yes 0.46 0.26 3.8 ft' 7 ft 11 in 5 ft 7 in Drapes/blinds Exterior 5
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 688.988895 ft' 688.988895 ft' 77.5 ft 9.33 ft 0
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000415 2747.3 150.82 283.64 .303 7
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Strip Heat None COPA 60 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER: 16 60 kBtu/hr 1800 cfm 0.75 1 sys#1
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Natural Gas None Garage 0.6 50 gal 60 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft'
7/6/2017 9:00 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5
FORM R405-2014
DUCTS
/ ----Supply---- ----Return---- Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 504.2 ft Attic 126.05 Proposed Qn Main ---cfm 151.4 cfm 0.06 0.60 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
CoolingJan Feb Mar A r Ma rj Jun Jul rj Au Se ]Oct Nov Dec
Heatin HJan HFeb Mar APr MaY Jun IXI
Jul Au �Xj
Sep ]Oct H
Nov HDec
Ventin Jan Feb X Mar [X]A r [ Ma Jun Jul Aug Se [X]Oct Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
7/6/2017 9:00 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5
i
f
1
FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 97
The lower the EnergyPerformance Index, the more efficient the home.
2801 Bent Pine Dr., Fort Pierce, FL, 34951
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul,Exterior R=4.1 1971.70 ft2
b. Frame-Steel,Adjacent R=11.0 294.00 ft2
3. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 3 d. N/A R= ft2
10.Ceiling Types Insulation Area
5. Is this a worst case? No a. Under Attic(Vented) R=30.0 2523.00 ft2
6. Conditioned floor area(ft2) 2523 b. Knee Wall(Vented) R=19.0 204.92 ft2
7. Windows- Description Area c. N/A R= ft2
a. U-Factor: Dbl,U=0.49 248.00 ft2 11.Ducts R ft2
SHGC: SHGC=0.24 a.Sup:Attic,Ret:Attic,AH: Main 6 504.2
b. U-Factor: Dbl,U=0.53 96.00 ft2
SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: Dbl,U=0.46 78.67 ft2 a.Central Unit 60.0 SEER:16.00
SHGC: SHGC=0.26
d. U-Factor: other(see details) 21.92 ft2 13.Heating systems kBtu/hr Efficiency
SHGC: other(see details) a.Electric Strip Heat 60.0 COP:1.00
Area Weighted Average Overhang Depth: 8.011 ft.
Area Weighted Average SHGC: 0.243
8. Floor Types Insulation Area 14.Hot water systems
a.Natural Gas Cap:50 gallons
a.Slab-On-Grade Edge Insulation R=0.0 2523.00 ft2EF:0.6
b. N/A R= ft2
c. N/A R= ft2 b. Conservation features
None
15.Credits Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building qHE S7
Construction through the above en rgy saving features which will be installed (or exceeded) gpFo
in this home before final inspectio Otherwise, a new EPL Display Card will be completed
based on installed Code complia features. ,,,,� --: :;: r• ;;;:
x
Builder Signature: Date:
Address of New Home: Z Q City/FL Zip: E, - p/Le rt, g'S
3 ySSI CDUW-Eto
'Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
7/6/2017 9:00 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
Buildin Analysis Job: Tacoma Lot-91
g J Date: 7-5-17
Entire House By: Skyetec
Project • •
For: GHO Homes
2801 Bent Pine Dr., Fort Pierce, FL 34951
Design C• • •
Location: Indoor: Heating Cooling
St Lucie Co Intl, FL, US Indoor temperature(°F) 70 75
Elevation: 26 ft Design TD (°F) 29 15
Latitude: 28°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 24.4 56.9
Dry bulb(T) 41 90 Infiltration:
Daily range (T) - 15 ( L ) Method Simplified
Wet bulb(T) - 77 Construction quality Average
Wind speed (mph) 15.0 7.5 Fireplaces 0
•
Component Btuh/ftz Btuh % of load
Walls 4.1 7739 18.1
Glazing 14.4 6095 14.3
Doors 11.3 1018 2.4
Ceilings 0.9 2278 5.3
Floors 2.9 7238 16.9
Infiltration 2.0 4282 10.0
Ducts 10471 24.5
Piping 0 0 _
Humidification 0 0
Ventilation 3646 8.5
Adjustments 0
Total 42767 100.0
Component Btuh/ft2 Btuh % of load
Walls 2.5 4774 11.6 .�
Glazing 22.6 9601 23.3 . ..
Doors 11.4 1028 2.5
Ceilings 1.0 2577 6.2
Floors 0 0 0 t
Infiltration 0.5 1137 2.8
Ducts 12756 30.9
Ventilation 1936 4.7
Internal gains 7470 18.1
Blower 0 0
Adjustments 0 a.
Total 41280 100.0
Latent Cooling Load= 12655 Btuh
Overall U-value= 0.115 Btuh/ft2-°F
Data entries checked.
+ wrightsoft' 2017-Jul-17 16:56:08
14CCA Right-Suite®Universal 2017 17.0.04 RS000269 Page 1
...oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJ8 Front Door faces: E
Coal onent Constructions Job: Tacoma Lot-91
p Date: 7-5-17
Entire House By: Skyetec
Project • •
For: GHO Homes
2801 Bent Pine Dr., Fort Pierce, FL 34951
Design C• • •
Location: Indoor: Heating Cooling
St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75
Elevation: 26 ft Design TD (T) 29 15
Latitude: 28°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 24.4 56.9
Dry bulb(T) 41 90 Infiltration:
Daily range (°F) - 15 ( L ) Method Simplified
Wet bulb(T) - 77 Construction quality Average
Wind speed (mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' Btuh/W-T ft'-°F/Btuh Btuh/W Btuh Btuh/ft' Btuh
Walls
13A-4ocs:Blk wall,stucco ext,r-4 ext bd ins,8"thk, 1/2"gypsum n 421 0.143 4.0 4.15 1745 2.59 1089
board int fnsh ne 13 0.143 4.0 4.15 55 2.59 34
e 208 0.143 4.0 4.15 864 2.59 539
se 19 0.143 4.0 4.15 78 2.59 49
s 549 0.143 4.0 4.15 2278 2.59 1422
sw 21 0.143 4.0 4.15 85 2.59 53
w 369 0.143 4.0 4.15 1530 2.59 955
nw 32 0.143 4.0 4.15 134 2.59 83
all 1632 0.143 4.0 4.15 6768 2.59 4224
Partitions
12B-Osm:Frm wall,stucco ext,r-11 cav ins, 1/2"gypsum board int 264 0.122 11.0 3.54 934 2.01 531
fnsh,2"x4"metal frm, 16"o.c.stud
12C-Osw:Frm wall,stucco ext,r-13 cav ins,2"x4"wood frm,16"o.c. 14 0.091 13.0 2.64 37 1.31 18
stud
Windows
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, 1/4" n 3 0.490 0 14.2 39 10.2 28
thk:2 glazing,Or low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, n 12 0.490 0 14.2 171 10.2 123
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45',medium;50% s 6 0.490 0 14.2 89 10.2 64
outdoor insect screen; 1.5 ft overhang(3 ft window ht, 1 ft sep.);6.67 ft w 3 0.490 0 14.2 39 23.7 65
head ht
all 24 0.490 0 14.2 337 11.8 280
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, 1/4" n 40 0.490 0 14.2 568 10.2 409
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, ne 10 0.490 0 14.2 136 19.4 186
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45',medium;50% a 20 0.490 0 14.2 278 24.2 473
outdoor insect screen; 1.5 ft overhang(5 ft window ht, 1 ft sep.);6.67 ft e 20 0.490 0 14.2 284 24.2 483
head ht
w 40 0.490 0 14.2 568 24.2 967
all 129 0.490 0 14.2 1835 19.5 2518
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr,1/4"gap, 1/4" ne 4 0.490 0 14.2 54 19.4 74
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45",medium;50% e 6 0.490 0 14.2 85 23.1 139
outdoor insect screen; 1.5 ft overhang(2 ft window ht, 1 ft sep.);6.67 ft head ht s 12 0.490 0 14.2 171 10.2 123
all 22 0.490 0 14.2 310 15.4 336
wri htsoft 2017Jul-1716:56:08
9 Right-Suite®Universal 2017 17.0.04 RS000269 Page 1
...oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJ8 Front Door faces: E
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, 1/4" e 6 0.460 0 13.3 80 24.0 144
thk:2 glazing,cir low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.26);50%blinds 45°,medium;50%
outdoor insect screen; 1.5 ft overhang(2 ft window ht, 1 ft sep.);6.67 ft se 4 0.460 0 13.3 51 13.0 50
head ht all 10 0.460 0 13.3 131 19.7 194
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr,1/4"gap, 1/4" e 15 0.460 0 13.3 200 26.0 390
thk:2 glazing,cir low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.26);50%blinds 45",medium;50%
outdoor insect screen; 1.5 ft overhang(5 ft window ht,3 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr,1/4"gap,1/4" e 8 0.490 0 14.2 114 10.2 82
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50%
outdoor insect screen; 10 ft overhang(2 ft window ht,3 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr,1/4"gap, 1/4" e 15 0.490 0 14.2 207 24.9 363
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45•,medium;50%
_outdoor insect screen; 1.5 ft overhang(5 ft window ht,3 ft sep.);6.67 ft se 10 0.490 0 14.2 136 19.7 189
head ht
all 24 0.490 0 14.2 343 22.8 552
2 glazing,cir low-e outr,air gas,vnl frm mat,clr innr,1/4"gap, 1/4" e 8 0.490 0 14.2 114 18.8 151
thk:2 glazing,cir low-e outr,air gas,vnl frm mat,cir innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45•,medium;50%
outdoor insect screen; 10 ft overhang(8 ft window ht,5 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr,1/4"gap,1/4" s 5 0.490 0 14.2 68 10.2 49
thk:2 glazing,cir low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50%
outdoor insect screen;7.5 ft overhang(1.6 ft window ht,1 ft sep.);6.67
ft head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, 1/4" s 18 0.490 0 14.2 256 10.2 184
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50%
outdoor insect screen;7.5 ft overhang(6 ft window ht,3 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr,1/4"gap, 1/4" w 10 0.460 0 13.3 128 10.1 97
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.26);50%blinds 45°,medium;50%
outdoor insect screen;6 ft overhang(1.6 ft window ht,1 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,air has,vnl frm met,clr innr,1/4"gap, 1/4" w 19 0.460 0 13.3 256 10.1 194
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,cir innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.26);50%blinds 45°,medium;50%
outdoor insect screen;15 ft overhang(1.6 ft window ht,1 ft sep.);6.67
ft head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap, 1/4" w 37 0.490 0 14.2 526 20.0 742
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45",medium;50%
outdoor insect screen;6 ft overhang(6 ft window ht,3 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr,1/4"gap, 1/4" w 96 0.530 0 15.4 1476 26.2 2515
thk:2 glazing,clr low-e outr,air gas,vnl frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.25);50%blinds 45°,medium;50%
outdoor insect screen;1.5 ft overhang(8 ft window ht,3 ft sep.);6.67 ft
head ht
Doors
11DO:Door,wd sc type n 23 0.390 0 11.3 256 11.4 259
• e 22 0.390 0 11.3 249 11.4 251
w 23 0.390 0 11.3 256 11.4 259
n 23 0.390 0 11.3 256 11.4 259
all 90 0.390 0 11.3 1018 11.4 1028
Ceilings
16D-30td:Attic ceiling,tile,slate,concrete roof mat,r-30 cell ins, 1/2" 2455 0.032 30.0 0.93 2278 1.05 2577
gypsum board int fnsh
wri htSOftw 2017Jul-1716:56:08
�� 9 Right-Suile®Universal 2017 17.0.04 RS000269
..oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJ8 Front Door faces: E Page 2
Floors
22A-cpm:Bg floor,heavy dry or light damp soil,on grade depth,carpet 111 1.180 0 34.2 3790 0 0
fir fnsh
22A-tpm:Bg floor,heavy dry or light damp soil,on grade depth,tile fir 101 1.180 0 34.2 3448 0 0
fnsh
Wrl htsoft, 2017-Jul-1716.56:08
9 Right-Suite®Universal 2017 17.0.04 RS000269
�� Page 3
...oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJB Front Door faces: E
Pro ect Summary Job: Tacoma Lot-91
1 1 Date: 7-5-17
Entire House By: Skyetec
Project Information
For: GHO Homes
2801 Bent Pine Dr., Fort Pierce, FL 34951
Notes:
Design Information
Weather: St Lucie Co Intl, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 41 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 29 °F Design TD 15 °F
Daily range L
Relative humidity 50 %
Moisture difference 57 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 32296 Btuh Structure 28524 Btuh
Ducts 10471 Btuh Ducts 12756 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 42767 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load 39381 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 8817 Btuh
Ducts 3839 Btuh
Heating Cooling Central vent (0 cfm) 0 Btuh
Area(ft') 2455 2455 Equipment latent load 12655 Btuh
Volume(ft') 25191 25191
Air changes/hour 0.32 0.16 Equipment total load 52036 Btuh
Equiv.AVF (cfm) 134 67 Req. total capacity at 0.80 SHR 4.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Rheem
Trade Trade RHEEM; RUUD
Model Cond RA1660AJ1
AHRI ref Coil RH1T6024STAN
AHRI ref 7943714
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input 12.3 kW Sensible cooling 46400 Btuh
Heating output 41975 Btuh Latent cooling 11600 Btuh
Temperature rise 20 °F Total cooling 58000 Btuh
Actual air flow 1900 cfm Actual air flow 1900 cfm
Air flow factor 0.044 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.77
Bold/Italic values have been manually overridden
Calculations approved by AC CA to meet all requirements of Manual J 8th Ed.
t +� wrightsoft- 2017-Jul-1716:56:08
Ptak Right-Suite®Universal 2017 17.0.04 RS000269 Page 1
...oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJ8 Front Door faces: E
N
V '\
Tocoma
12 z 12 _. I`. 8Z
206 dm y
Nook 8 x 8
Master Suite
I,
34 dm i.
• lox 10 - 30x 18
Ox16—j - L-
138 dm 138 dm aedrlxlm 3
8',10.9 8',9,7N 9',10.3N�_ /7',5.5ft
\ 12x 12� tOx 10
4".1.7If 215 dm 105 dm
18 dmm 6x6
6z -His_ - 14
12x 12 1
4dm _ --12x12
4 59k � 166dm � r ..;...
Great Room --18",420 -
9',8.5 ft
rt
6 x 6 115
10 x 10
11 dm i 6x6 \ \ 279',10.0N 18'13.5ft 113 dm
II 12",24.6N ggI
31 dm � �•� � - ''��10",13.a f�room 2 Schedule
4',5.5 ft �-Master Bath 5',6.411 3V, b
F lox 10 Exhaust Fan F
eo it
4ncrn, 0 412 12
---=-- _._ .`.--- - -- © Range Vent O
6 x 6 8",6.1N
9".18.1 N - _ 46 dm Y 44 dm - Dryer Vent D
6,6
12x12 12x12
193 dm 1 Foyer Rheem Equipment
18".10.9If
D pen 16'.73.3N —_ 5.0 Ton 16SEER RHIT60 AHU
-- -
Dinning
5.0 Ton 16 SEER RA1660 Cond
6x6
20',1.8 rt 33 dm
- -- 4',4.3 ft
T metal dud for 6 x 6
12 z 12
combustion air,this ff 18 dm
dud it to terminate !I 5.0 Ton
to the roof with a
roof cap.. ''..
f
Garage
_ I
r
Job #: Tacoma Lot- 91 Scale: 1 : 143
Performed by Skyetec for: Page 1
GHO Homes Right-Suite®Universal 2017
2801 Bent Pine Dr. 17.0.04 RS000269
Fort Pierce, FL 34951 2017-Jul-1716:56:14
...s\Skytec\Tacoma Lot-91 GR E.rup
Duct System Summary Job: Tacoma Lot-91
y Date: 7-5-17
Entire House By: Skyetec
• Project Information
For: GHO Homes
2801 Bent Pine Dr., Fort Pierce, FL 34951
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0.18 in H2O 0.18 in H2O
Available static pressure 0.32 in H2O 0.32 in H2O
• Supply/return available pressure 0.196/ 0.124 in H2O 0.196/ 0.124 in H2O
Lowest friction rate 0.086 in/100ft 0.086 in/100ft
Actual air flow 1900 cfm 1900 cfm
Total effective length (TEL) 371 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk
Bath 2 h 1385 62 33 0.124 5.0 OX 0 VIFx 18.3 140.0 St2
Bath 3 h 1977 88 34 0.086 6.0 Ox 0 VIFx 46.9 180.0 st5
Bedroom 2 h 2910 129 113 0.102 7.0 OX O VIFx 31.4 160.0 st4
Bedroom h 2725 121 105 0.090 7.0 Ox0 VIFx 38.4 180.0 st5
Den h 5235 233 193 0.121 9.0 OXO VIFx 31.4 130.0 SO
Dinning h 3337 148 148 0.131 8.0 Ox 0 VIFx 19.4 130.0 SO
Foyer h 1708 76 48 0.131 5.0 Ox0 VIFx 19.4 130.0 SO
Great Room c 4670 117 215 0.101 9.0 OXO VIFx 34.3 160.0 st4
Great Room-A c 4670 117 215 0.088 9.0 Ox 0 VIFx 43.1 180.0 st5
Hers c 78 3 4 0.096 4.0 Ox 0 VIFx 39.5 165.0 st3
His h 1095 49 18 0.094 4.0 Ox 0 VIFx 43.8 165.0 st3
Kitchen c 4077 46 188 0.102 9.0 Ox0 VIFx 32.9 160.0 st4
MECH-A h 730 32 18 0.188 4.0 Ox0 VIFx 4.3 100.0
Master Bath h 1434 64 31 0.094 5.0 Ox 0 VIFx 44.3 165.0 st3
Master Suite-A h 3627 161 138 0.090 8.0 Ox 0 VIFx 48.8 170.0 st3
Master suite-B h 3627 161 138 0.092 8.0 Ox 0 VIFx 47.6 165.0 st3
Nook h 5731 255 206 0.089 10.0 Ox 0 VIFx 41.2 180.0 st5
Utility c 960 15 44 0.131 4.0 Ox 0 VIFx 14.4 135.0 st2
WC h 534 24 11 0.094 4.0 Ox 0 VIFx 43.4 165.0 st3
Bold/italic values have been manually overridden
wri htsoft, 2017-Jul-1716:56:08
CA 9 Right-Suite®Universal 2017 17.0.04 RS000269 Page 1
..oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJ8 Front Door faces: E
SupplyDetail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk
st5 Peak AVF 581 560 0.086 543 14.0 0 x 0 VinlFlx st4
st3 Peak AVF 461 340 0.090 587 12.0 0 x 0 VinlFlx st1
st1 Peak AVF 918 730 0.090 657 16.0 0 x 0 VinlFlx
st4 Peak AVF 873 1075 0.086 608 18.0 0 x 0 VinlFlx st2
st2 Peak AVF 950 1152 0.086 652 18.0 0 x 0 VinlFlx
TableReturn Branch Detail
Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Matl Trunk
rb8 Ox0 461 340 143.8 0.086 261 1&0 Ox 0 VIFx rst3
• rb4 Ox 0 1439 1560 118.0 0.105 591 22.0 Ox 0 VIFx rst4
TableReturn Trunk Detail
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk
rst3 Peak AVF 1900 1900 0.086 871 20.0 0 x 0 VinlFlx
rst4 Peak AVF 1439 1560 0.105 883 1&0 0 x 0 VinlFlx rst3
Bold/italic values have been manually overridden
wri htsoftA 2017-Jul-17 16:age 2 9 Right-Suite®Universal 2017 17.0.04 RS000289 Page 2
...oad Calculations\Skytec\Tacoma Lot-91 GR E.rup Calc=MJ8 Front Door faces: E