HomeMy WebLinkAboutCarports Anywhere - N Figuereo - 402014 - Digital Sealed 1.29.211. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND
CLADDING, AND BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL,
INGRESS/EGRESS, PROPERTY SET —BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS
ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON —HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY I) CAPABLE OF
SUPPORTING DEAD LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY
ADDRESSED HEREIN, INCLUDING DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS
LIST, AND NOT PROVIDED AND INSTALLED BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE
STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE
RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-143/4" SELF —DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED
WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH.
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
SUB —GRADE SOILS:
—TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2020 FLORIDA BUILDING CODE, 7TH EDITION
—BOTTOM OF CONCRETE FOOTING SHALL BE MINIMUM OF 12" BELOW UNDISTURBED OR
ENGINEERED GRADE
CONCRETE:
—MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
—ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
—MINIMUM GRADE 40 STEEL
—REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
—THE REBAR IS BENT COLD
—THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6—BAR DIAMETERS: AND
—REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
—COVER:
—3" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 11" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF }" FOR FINE
GROUT, AND I" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATION:
—METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
4"x54" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES
AND EVERY OTHER END —WALL POST
2" MIN. BASE RAIL
GRADE
I° 2,500 PSI 4" CONCRETE
V
SLAB WITH 10GA. W.W.F.
OR FIBER MESH
MINIMUM SOIL BEARING CO)N INU USA WITH MINIMUM
CAPACITY 500 PSF(TYP.) 25" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR DETAIL
MIN. 2,500 PSI
4"
CONCRETE
SLAB WITH
10GA. W.W.F. (OR
FIBER MESH)
--------------------------------------------------------------------------------------------------------------------------------------------------------------
AND
12"x12"
REINFORCED
FOOTER PERIMETER
12"02" REINFORCED FOOTER
- --------------------------------------
m
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
ENCLOSURE
OPEN
INTERNAL PRESSURE COEFF.
+/— 0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1800 SQ. FT.
REVISIONS
REVI
DESCRIPTON
I DATE
I BY
""""'" o,: MTB
DATE: 1/22/21
LocAn01�340 West Midway Road, Ft. Pierce
SIZE: 40'L X 20'W X 14'H
q /
o ENSF ����
NO.64608 2
i �•:• STATE OF 4
/"OII 1110`
O
Digitally signed
L� by Matthew
z Baldwin
Date:2021.01.22
15:45:41-05'00'
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AN
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
z MottheW T. BOIdWin P.E.
Q Florida License #64608
ci
Sheet: CA-1 OF 4
—11 3'-11
—11J" 3'-11
LEFT/RIGHT SIDE WALL
12
�3
DOUBLE POST
(TYP.)
20'-0"
FRONT/REAR END WALL
RIqk�LI i1l ►
CODE VERSION IFBC 2020 7th Edition,11
MANUFACTURER
M 1G-/- V
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-150moh
O
ENCLOSURE
OPEN
INTERNAL PRESSURE COEFF.
+/— 0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
800 SQ. FT.
0
Z
IW
�
3» 3 3„ 3» 3„ 3
—113'-11� 3'-11� 3'-113'-113'-11
A 0'-0 4 4 4 w
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES k V) Sheet:
MTB
1/22/21
340 West Midway Road, Ft. Pierce
40'L X 20'W X 14'H
Matthew T. Baldwin P.E.
Florida License #64608
CA-2 OF 4
0
FRONT/REAR END WALL
CODE VERSION IFBC 2020 7th Edition,11
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150moh
ENCLOSURE
INTERNAL PRESSURE COEFF
IMPORTANCE FACTOR
ROOF DEAD LOAD
ROOF LIVE LOAD
FLOOR DEAD LOAD
FLOOR LIVE LOAD
"R"RATING OF WALLS,FLOOR,
MODULES PER BUILDING
HURRICANE PROTECTION US
HURRICANE SHELTER USAGE
SQUARE FOOTAGE
+/— 0.0
1.0
1OPSF
20PSF OR 3001b P.L.
1OPSF
50PSF
ROOF N/A
1
AGE NO
NO
800 SQ. FT.
MTB
1/22/21
340 West Midway Road, Ft. Pierce
40'L X 20'W X 14'H
AO'—O" -I Matthew T. Baldwin P.E.
IW Florida License #64608
LEFT/RIGHT SIDE WALL PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED ANDw
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES pm(/) Sheet: CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
Vill \ NIPPLE TO
BASE RAIL NIPPLE T
BASE RAI
POST TO BASE RAIL
CONNECTION
TO TRU
16 GA. U—CHANNEL
BRACE, MIN. 24" UP TO
7' POST, MIN. 48" OVER
6 7' POST. MIN. 45' TO
MAX. 60' FROM HORIZ.
(EXCLUDE END —WALLS).
SECURED WITH
(4)# 12-14xi"
SELF —DRILLING SCREWS.
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xj" SELF —DRILLING
SCREWS
BOX EAVE RAFTER TO
POST CONNECTION DETAIL
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xi" SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" D.C. MAX.))
MAx:
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xi" SELF —DRILLING
SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xj"
SELF —DRILLING SCREWS
END POST TO BASE RAIL
CONNECTION
4" WELD
2' O.C. MAX.
DOUBLE POST
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-14x1" SELF —DRILLING
SCREWS TO EACH RAFTER.
26 GAUGE ROOF SHEATHING
SECURED WITH (1)#12-14xi"
SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-14x1" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
MAX.
EAVE & RIDGE REINFORCED ROOF PANEL CONNECTIO
(RIDGE 3r AND EAVE 3ej
Design Pressures -
150
mph Basic Wind Speed
Zone
Roof
Wall
1
2n
2r
2e
3r
3e
4
5
15.6
20.2
15.6
15.6
22.2
22.2
22.2
25.3
-18.9
-53.7
-36.6
-18.9
-71.2
-61.0
-23.9
-29.9
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
Hampton Rib Roof Panel
FL27402.1 —R1
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
INONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-150mph
ENCLOSURE
OPEN
INTERNAL PRESSURE COEFF.
+/— 0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
800 SQ. FT.
REVISIONS
REV
I DESCRIPTON
I DATE
I BY
DRAWN BY: MTB
DATE: 1 /22/21
L0111IN 340 West Midway Road, Ft. Pierce
SIZE: I 40'L X 20'W X 14'H
cn
J_
Q
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w w
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES Sheet:
Matthew T. Baldwin P.E.
Florida License #64608
CA-4 OF 4