HomeMy WebLinkAboutFire Dept PermitSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
I FMO Permit # !B-21-24
Building Dept. SLC
Project Name Wolflube Warehouse & Offices _ 18LD6 Permit # 2012 0558
Address 4774 South Jenkins Road City Fort Pierce
Contractor Rf Concrete Construction
Address 664 Old Dixie Hwy City (Vero Beach
I
�-
State FL I Zip I32962 J Telephone (772)567-3356
Architect/Engineer I Telephone
Storage/Business Construction Type IIB -� Square Feet 15,676
Occupancy Type
Occupant Load 137 per plan Number of Stories I1 I Access Box l Required Access Key Switch
AFSPermit Required i FA Permit (Required _� FFPPermi:
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper LIL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code compliance.
10. Automatic fan shutdown is required for HVAC systemis that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. A separate review and permit is required for the installation or alterat!on of the fire alarm and fire sprinkEer systems,
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s)
shall be tied into the fire alarm systern.
I _ T Date 01-25-2021-�
Page of Reviewed by ;Tony Jerger