HomeMy WebLinkAboutProject Information9 Manual S Compliance Report Job: Lot 12 Block 1 Waterston Wrl... htsoft Date: Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM For: ADAMS HOMES 5412 Lugo Street, Fort Pierce, FL 34951 D E ('' ® 8 2020 ST. Lucie County, Permitting Cooling Equipment Design Conditions Outdoor design DB: 90.4 °F Sensible gain: 26179 Btuh Entering coil DB: 76.8OF Outdoor design WB: 77.4OF Latentgain: 4767 Btuh Entering coil WB: 63.4OF Indoor design DB: 75.0 OF Total gain: 30946 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537A0030+FX4DNF037L Actual airflow: 1167 cfm Sensible capacity: 28372 Btuh 108% of load Latent capacity: 5061 Btuh 106% of load Total capacity: 33433 Btuh 108%of load SHR: 85% Heqting Equipment Design Conditions Outdoor design DB: 41.0 OF Heat loss: 90881 Btuh Entering coil DB: 62.3 OF Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537A0030+FX4DNF037L Actual airflow: 1167 cfm Output capacity: 34600 Btuh 38%of load Capacity balance: 52 OF Supplemental heat required: 56281 Btuh Economic Bala -99 OF Backup equipment type: Elecstrip,�„� Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 29% of load Temp. rise: 20 OF Meets all requirements ofACCA Manual S. t Wrightsoft, 2020-Nov-0909:13:04 Right-Sute®Uriversal 201919.0.16 RSU23828 Page 1 ACCA erstone1820CRGR1Lot12BIk1Waterstore1820CRGR.np Calc=MJ8 FrontDoorfaces: N wrightsoft° Component Constructions Ube Lot 12 Block 1 Waterston... Entire House By: ocs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Project Information For: ADAMS HOMES 5412 Lugo Street, Fort Pierce, FL 34951 Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area u-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuhfftz°F ftz'FBtuh Btuh(ft' Btuh Btu" Btuh Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh n 121 0.201 4.1 5.83 703 4.06 490 e 611 0.201 4.1 5.83 3561 4.06 2481 s 317 0.201 4.1 5.83 1846 4.06 1286 w 534 0.201 4.1 5.83 3113 4.06 2168 all 1582 0.201 4.1 5.83 9224 4.06 6425 Partitions 12C-Osw: Frm wall, 1 /2" gyp.bd ext, r-13 cav ins, 1 /2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 ft overhang (6.25 ft window ht, 0.8 ft sep.); 6.67 ft head ht 213-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft sep.); 6.67 It head ht 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl fan mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 9 ft overhang (6.7 ft window ht, 2 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, dr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang s (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht W all 10C-v: 2 glazing, clr low-e outr, air gas, vni fnn mat, dr innr, 1/4" gap, 1/8" s thk; NFRC rated (SHGC=0.70); 12 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 12 ft overhang (5.3 ft window ht, 0.5 ft sep.); 6.67 ft head ht 270 0.091 13.0 2.64 713 1.31 354 39 0.330 0 9.57 369 8.22 317 7 0.330 0 9.57 67 11.6 81 13 0.330 0. 9.57 128 9.72 130 49 0.330 0 9.57 469 22.4 1096 33 0.330 0 9.57 313 8.52 279 49 0.330 0 9.57 469 22.4 1096 131 0.330 0 9.57 1251 18.9 2470 18 0.550 0 16.0 285 16.2 289 33 0.330 0 9.57 313 8.52 279 wrightsoft- 2020-Nov-09 09:13:04 C% aM,»t• .. »�.- .mom Right-StiteOUriversal 2019 19.0.16 RSU23828 Page 1 erstore1820CRGR1Lot12BIk1Waterstorte1820CRGR.rLp CaIc=W8 FrontDoorfaces: N 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr, innr, 1/4" gap, 1/8" w 7 0.330 0 9.57 66 21.8 151 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.8 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type n 20 0.600 6.3 17.4 355 17.6 359 Ceilings 16B-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1835 0.032 30.0 0.93 1703 1.69 3100 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 185 0.989 0 28.7 5306 0 0 wrightsoft 2020-Nov-09 09:13:04 .4CCi� Right-Sutera�Uriversal 201919.0.16 RSU23628 Page 2 erstone1B20CRGR1Lot12BIk1Waterstone1820CRGR.nQ Calc=MJ8 FrortDoorfaces: N wrightsoft. m Project Su mma Job: Lot 12 Block 1 Waterston... Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Project• • For: ADAMS HOMES 5412 Lugo Street, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch L. S. 11-9-20 VWK Design Information Weather: St Lucie Co Inti, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 23484 Btuh Structure 18541 Btuh Ducts 67398 Btuh Ducts 7639 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 90881 Btuh Use manufacturer's data y Rate/swing multiplier Equipment load 1.00 Infiltration sensible 26179 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh Heatingg Cooling Area (none) (ft2) 1820 1820 Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Airchanges/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 30946 Btuh Equiv. AVF (cfm) 116 61 Req. total capacity at 0.75 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC537AO030 Cond 25HBC537AO030 AHRI ref 10487322 Coil FX4DNF037L AHRI ref 10487322 Efficiency 8.5 HSPF Efficiency 12.5 EER,16 SEER Heating Input Sensible cooling 26250 Btuh Heating output 34600 Btuh @ 47°F Latent cooling 8750 Btuh Temperature rise 27 OF Total cooling 35000 Btuh Actual airflow 1167 cfm Actual airflow 1167 cfm Airflowfactor 0.013 cfm/Btuh Airflowfactor 0.045 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.85 Capacity balance point = 52 OF Backup: Input = 8 kW, Output = 25913 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed wrightsoft® �� .....,., ,...w,.__.,<e..,..�, Right-Su2020-Nov-0909:13:04 te®Uriversal 2019 19.0.16 RSU23828 Page 1 ..erstonel820CRGFVLotl2BIklWaterstore1820CRGR.rp Calc=MJ8 FrordDoorfaces: N -f wrightsoft, Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 12 Block 1 Waterston 18... Date: By: DCS 1 Room name Entire House BDRM2 2 Exposed wall 185.0 It 36.0 It 3 Room height 10.0 ft d 10.0 ft heaU000l 4 5 Room dimensions Room area 1835.0 ft2 13.0 x 13.0 It 169.0 ft2 Ty Construction number U-value (Btuh/ft2-'q Or HTM (Btuh/ftz) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blkvi211,s1ucaoexl -' 2A-2ov 28-2ty . 0201 0.330 0,330 -.n' , n n 5.83 957 957. ' 4.06 822 11.58 __-200 39 " 7 -" 121 0 0 703 _' 369 67 490 317 81 --_' ;_ m0 0 0 --. _,-O._.r_._ 0 0 p 0 . 0 O 0 - . 0 VN L-G y - I/-G I-G TV)J 2B 2fv Blk wall, stucco exl 2A-2ov_ st.o �__- _..._, Blk 'V all ext 10C v 2A 2ov y 2A2ov_ _ - ----_ Blk wall, stu000 ext 2A-2ov 0,330 0.201 - _ _ 0.330 0201 0.550 0.330 ..,_ 0.330 0.201 0.330 .n a _ _e... s s s :-_s_. w w 9.57 5.83 _9.57 5 83 1595 957 ,--_:9.57_ 5.83 9.57 .9.72 4.06 _ 22.35 4.06 1626 8.52 _._-8.52 4.06 21.79 13 „_;_-..:.20 660 _ - 49 400 18 33 _z_w_...._33 590 7 0 2Q 611 _._ _ 6 317 36 65 v, w_65 534 1 128 __.w_.,355__. 3561 _ 469 1846 285 313 .___,Fk;313.__,:__-279 3113 66 130 `_ 359...__ 2481 1096 1286 289 279 2168 151 0 Q 130 _---. 0 136 0 16 100 0 0 v 4 130 -- - •---- 0 114 0 16 100 0 0 758 ... _._ 0. 663 0 156 583 0 0 528 ___ -0 461 0 139 406 0 P _._..12GOsw 2A-2ov _. _ _- 0.330 -w - --- 9.57 22,35 _ 49 _6 469 1096 0 _. 0 - - ---. 0 Q . 0 _ 0 C - Fs-_--..__0.989 166 30ad _ - _ 0.032 _ _.. 0.93 -�._28.68.__.__i0A0 1.69 , 1835 _ ._.1835 ry.1835 ° 185 1703 . 5306 r3100 0 169 _J69 - 169 736;__0. 157 __--_ _ _ _286 6 c) AED excursion 0 -98 Envelope loss/gain 19780 13955 3349 1723 12 a) Infiltration 3704 1035 721 201 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 0 0 Appliances/other 2400 0 Subtotal (lines 6 to 13) 23484 18541 4070 1924 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 23484 18541 4070 1924 15 Dud loads 287% 41 % 67398 7639 287 % 419.1 11680 793 Total room load 1 90881 26179 15750 2717 Air required (cfm) 1116.7 1167 202 121 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrightsoit° 2020-Nov-0909:13:04 Righ-Sute®Uriversal201919.0.16RSU23828 Pagel erslor)el820CRGR\Lotl2BIk1Waterstorel820CRGR.rLp Calc=MJB Frontloorfaces: N - F wrightsoft, Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 12 Block 1 Waterston 18... Date: By: DCS 1 Room name BATH 2 BDRM3 2 E posed wall 6.0 it 13.0 It 3 Roam height 10.0 It heat/cool 10.0 It heat/cool 4 Room dimensions 13.0 x 6.0 8 13.0 x 13.0 It 5 Room area 78.0 ftz 169.0 ftz Ty Construction U-value Or HTM Area (ft) Load Area (ftz) Load number (Btuh/ftz-`F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 ' Blk wall, stu000 e)d _ 2A 2ov 0,201 0.330 ,n:4.06 n` 957, • , °822 0 0 > 0 {; 0 0 0 0 0 w 0 0 `', 0 0 0 ' '2B-2N 0330 'n `: 957: 11,58 0 0 0 00 = 0 0 2B-2N " 0 330 n ,': 9 57 9 72 A 0 0 0 0 0 0 ,=0' 0' 11 '11.b__ __. ,wQ600 _n 77.40 17,68 , , -.,, 0 _ _' a. " ", �, _Q ___._ L � _,0 � _0 � V+! t Blk wall, stuoco e)d 0201 a 5.83 4.06 60 60 350 244 130 114 663 461 2A-2ov, 0.330 a 9.57 22.35 0 0 0 0 16 1. 156 365 vw I--G Blk wall sluoco ex[ ] OC v 2A _ 0201 0.550 6' s. 5 83 15 95; 4:06 1620 ' 0 A _ _ a 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2ov 0.330 s 957 852 00 0 0 0 1{—�G 2A 2ov_ _ �. �0.330 �, s- _ _9.57 8.52 0 - .w 0 f _ a «� 0 - ., _0 __. ,0 _..0 .1u. -'_«0 Z _..,�..0 Vt/ Blk wall, stucoo e)d 0.201 w 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 w 9.57 21.79 0 0 0 0 0 0 0 0 I��G 2A 2ov 0.330 w_ 9.57 22.35 0 0 0 0 0 0 0 0 Osw 0,091. C 1613-30ad 0.032 093 1.69 78 78 72 132 169 169 157 286 F 22A ipl 17- -w 0989 a 28.68 , ...m, 0 0.R �I8 12 = ] 0 &9 _ »._ e u. ._.-:-....,.....,i....k . R_..._.v..aF.... _ ._.-..,e,... _ ,......r>y. .ra..-_...._. ....v_....� ..r...er_ `' {+.rl C, ..«..�. i..... a.�G..... .�v-...,__ ..,., v_v.... ,._w.r...,... r F: _.. _. .w ..__._..._,« ,.s v._.._ _.ai..�t,w.. •.-_ ................. _.e... __, r ..-,r:..-..:::1 .+.x_u....«n. ..a_... _. ...._..-....4 .- �.. ...,.•vw...e „-......_... %z..+a. ... «.,.. ...a .�...-u_-..bx.+.,...i:....„... ....... hr,... .. .w...-. ,._ .. x�,..—. sm.......a .xa -,..., -.e. .L..e.a.- ...«.,s... .n ..... �. .._ .+..r..s..., .,...m _._ �.._.H.w t_.. _..-...—.-....v...._.._.-r r+...w� ..._. .,e., -:.- .. ....._.._.._. ,c.. ... A.`.. n ;+sc.. 4,.... _...»a ..w2.L�. M..;.zn..... .u.....k...�. _... ,..-a... .. ..._....-.,r. ... .�v�:w .. . _�._>...�-.�dA.,...-... .n.te_ .�.-..:..,.. G.... -.-..�., - _....,.._w - sJr. �...._ ..:- .:. ...»...__ f.....�_x ............ -...- /v.,�...,...� ._ . v._� _F ....,.4 ,. _.... - u,, i � .y�..._.�........-_�.,..._._.. .....»...,........ i .. ,_.....,�_ _,...,.... .._...,��s. � v...,.v.....,«..1 ..�>....a-... .mac.. _.___-�.... ._...,_.�. ....,.�, �_�- 4 ..., ,,u .,,..w. >_-,....s..y ._:. _ s,,,-.._,. ,a.<... _...,... . ... ...,,w-.... a. .,� .,.....ry..,. _. ....<r '�ti a�....:�a.F ..r,.,7-.u.... .:x_,:..r,,.,,.,. _........... _....,., ..... . ,�... W 77 .... .�.. .....,5,... _wz. ,.. 6 c) AED excursion -20 52 Envelope lossigain 594 356 11349 1164 12, a) Infiltration 120 34 260 73 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 714 389 1609 1237 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 714 389 1609 1237 15 Ductloads 287% 41% 2050 160 287% 41 % 4617 509 Total room load 2764 550 6226 1746 Air required (dm) 35 24 80 78 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -P�&- 2020-Nov-09 09:13:04 "° Right-Suite®Uriversal 201919.0.16 RSU23828 Page 2 erstone1820CRGRLot12BIk1Waterstone1820CRGR.rup CaIc=MJB FrortDoorfaces: N -qd- wrightsoft, Right -A Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 12 Block 1 Waterston 18... Date: By: DCS 1 Room name DINING/FOYER DEN/BDRM4 2 Exposed wall 18.0 It 31.0 It 3 Room height 10.0 8 heaU000l 10.0 ft heat/wol 4 Room dimensions 1.0 x 276.0 ft 13.0 x 13.0 ft 5 Room area 276.0 ft2 169.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area 2 Load number (Btuh/ft2-� (Btuh/t2) or perimeter (ft) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk wall stu000 ext 2A 2ow" 0 201 0330 + n ,' � n °' 5,83 9.57 4.06 822 7,0 'o 29 " 0 ; 170 0 119 0 130 39 . 91 " , 0 ' 533 369 371' 317 28.2fv , 0330 ,n° 9S7 11.687 0 67 81 0 �,0 0 2B-2W 0 330 n. 9 57 972 13 0 128 130-- 0 0. 0 0 600. h - - 1740, Y_ -35 __. .,1359 V}J Blk wall; stu000 ext 0.201 a 5.83 4.06 110 77 451 314 130 130 758 528 _ 2A toy, _^ _ Blk wall stucco ext OC v 2A2ov _ 0330 0 201 0 550 a s s 9.57 5 83 15 95 22.35 4 06 1620 33 0 A �2 0 0 313 0 0 730 0 0 0 0 4� r 0 0 0 0° 0 0 0 0 0 0 '0 -;-ilt 2A 2ov,.._ _ _�� 0330 _A _0.336 s _sw 9.57 _-14.57_ 8.52,0 _ 8.52 _ ` -.,._ O 0 _n . 0 0 _ w e._>0 0 ��� _ .„0 0 f _ 9 0 .. 0 0 _ 0 ___ .-._:0 Blk wall, slucoo ext 2A-2ov 0.201 0.330 w w 5.83 9.57 4.06 21.79 0 0 0 0 0 0 0 0 50 0 50 0 291 0 203 0 2A 2ov 0.330 w 9.57 22.35 0 0 0 0 0 0, 0 0 .d _ s_.. _.2 64. 13i µ 7092 u 0 _ 0 . 0 0. C 1613-30ad 0.032 0.93 1.69 276 276 256 466 169 169 157 286 '276-.'.� 18 _�• 516 _,_x 0 _ . 169 :�: .$J. . __.8$9 ..0. j ._.- - .. n _ � e,-r v._....u�.._. +.-..._ e_ ........ .-... «..�.«a ... ,.. _ rye. __...� ... ._,.3... _. _„... _s ...,......r -.,r..� . _.., wr ..,.v.,,. v..._,., � .....t r c ........_.... �. - ._.. _. _...-.._..... .,_. ....... _ _.. .._.a._ .x, ..,... ._. �._ ......_. _.rvy.,_.. _. ..� ,.cue,_.. ._ .v __._. _ ........... .. _M.... A.. ,.y_,aR...� .. ._ - ::__...._ter.:. _..::.....,:..__..:.., 6 c) AED excursion -42 -91 Envelope loss/gain 2441 2249 2997 1614 12 a) Infiltration 360 101 621 173 b) Roomventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 1 230 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 2801 2580 3618 1788 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2801 2580 3618 1788 15 Ductloads 12870/6 41 / 8040 1063 2870/6 41 % 10383 736 Total room load 10841 3643 14001 2524 Air required (cfm) 139 162 180 113 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 2020-Nov-09 09:13:04 Rigtt-SLite@Uriversal 20l9 l9.0.16 RSU23828 Page 3 ...erstone1820CRGR\Lot1213Ik1Waterstone1820CRGR.rup Calc=MJ8 Frort Door faces: N - - wrightsoft, Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 12 Block 1 Waterston 18... Date: By: DCS 1 Room name FAMILY RM MSTR BDRM 2 3 4 5 Exposed wall Room height Room dimensions Room area 13.0 ft 10.0 It heaV000l 13.0 x 22.0 ft 286.0 ft2 41.0 ft 10.0 ft heat/cool 14.0 x 17.0 ft 238.0 ftz Ty Construction number U-value (Btuh/ft2-4q Or HTM (Btuh/112) Area (ft') or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (it) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 _ -_.. V►/ I _ VV��II F--G Blk vtall stucco ex`t 2A-2ov .. ' 26-2fv 2B-2fv 11J0 _ _ - _-- Blk wall, stu000 ext 2A_2oy - - - - Blk wall, stucdo ext 1007v 2A 2ov ', - - - 0201 0,330 0.330 00 --.__.._0.600 0.201 0.330 020f 0.550 0.330 _.. n. n n n _-n-_ a ,_-e s , s s 5 83 9.57 9.57 9.67 1740' 5.83 _ 9.57 4.06 822 11.58 9.72 __ 17i58 4.06 ._ _ 22.35 4:06 1620 8.52 0 . ' 6 0 6 �_..-0 0 _. _0 ' 130 18 0 ___ 0 , :,, ^ . 0 0 r, 0 _ _Q 0 0 '. __.. 0 , ,. , -6. =, 0 0 _v_..__ _0.----__-0 0 0 285 0 0 0 .0 0 0 289 0 ' 0 0 0 0 -_.-----.9. 100 0 16 0 . 0 0 0, ___._:0 0 0 0 0 0 0 0 6 100 124 '0 16 583 �- 721 0 156 406 -- 502 0 139 "5:83 15.95 -9.57 . ; 79 18 0 11_GG __._.G Vt/ C LW_..., 2A2ov-::--.._-.,_. Blk wall, stucco ext 2A-2ov 2A 2ov _._ 16B 30ad _--_._.0.330 0.201 0.330 0.330 091. 0.032 __s.- w w w _A;.. . _.-__957 5.83 9.57 9,57 _ -9 0.93 28.68238. -852 4.06 21.79 22.35 131. _ 1.69 .__._-._ 33 0 0 0 ._0 286 33 0 0 0 _ 0 286 _ ..> ;_:313 0 0 _ 0 _. w . 0 265 _--_--_279 0 0 ___ 0 . _. __ . _0 - 483 _._._._._0 170 0 16 ., _._ _._�0 238 __0 154 0 _ - -1 <0 238 _ _. -_�0 896 0 156 _.._._0. 221 _-,._ -0 624 0 -_ _ - _365 402 . _ 6 c) AED excursion -103 4 Envelopeloss/gain 1699 1271 3909 2443 12 a) Infiltration b) Room ventilation 260 0 73 0 821 0 229 0 13 Internal gains: Occupants@ 230 3 690 1 230 Appliances/other 0 600 Subtotal (lines 6 to 13) 1959 2033 4730 3502 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 287% 41 % 0 0 0 1959 5623 0 0 0 2033 8381 2879/6 41%1 0 0 0 4730 13575 0 0 0 3502 1443 Total room load Air required (cfm) 7583 97 2871 128 18304 235 4945 . 220 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -r�- wrightsoTt^ 2020-Nov-09 09:13:04 "" ^ Rigtt-Sdte®Uriversal 201919.0.16 RSU23828 Page 4 ...erstone1820CRGR\Lotl2BIk1Walerstonel820CRGR.rtp Calc=W8 FrontDoorfaces: N -- wrightsoft, Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 12 Block 1 Waterston 18... Date: By. DCS 1 Room name fA BATH M WIC 2 wall 12.0 ft 0 ft 3 Room height 10.0 ft heat/000l 10.0 It heat/000l 4 Room dimensions 1.0 x 119.0 ft 7.0 x 7.0 It 5 Room area 119.0 ft2 49.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (f2) Load number (Btuh/t2-9 (Btuh/112) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 ".Blkwall,stticooext 2A 2ov 0201 0 330 '0330 n ` = n 'ri; r 583 9.57 4,06 ,.899 �0 p = 0 0 - 0 0.r - 0 0,' 0' ,y.0 D 3';,.0; ;p 2B-21v '• 957, '1158 0 0 0 0 0 0 s0 0' 26-2fv . 0.330 n' 9 57 9 72 0 0 0 0 ., 0 ; 0 0 0` Q600 175800 V?/ L Blk wall, stu000 ext 0.201 a 5.83 4.06 0 0 0 0 0 0 0 0 __G 2A 2ov 0.330 a 9.57 22.35 0 0 0 0 0_ 0 0 0 Blk wall stu000 ext 10C v 2A 2ov 0201 0.550 s' s 6.83 15.95 °4.06 1620 0 70 0 0 0 0 ' v M 0 0 " _ 0 0 0 0 0 0 0 0 0330 s' 9.57 8.52 0 0 0 0 0 0 0 tI :2A2ov mom. ____._.0.330 ___s .>___A57_.� °_8.52 _ _ 0 _. _ .m 0 ' _ 0 .w 0.___ �.e ,._. Blk wall, stu000 ext 2A-2ov 0.201 0.330 w w 5.83 9.57 4.06 21.79 120 7 113 1 659 66 459 151 0 0 0 0 .D 0 0 KM:.O 0 0 2A 2ov __,-, 0.330 _w _ 9.57 2225 0 0 0 0 - 0 0 0 0 0091 264, 131 - C _ 166-30ad _ _Y _ �a 0.032 0.93 1.69 119 119 110 201 49 49 45 83 F._.._.. 22A-Qpl_ _ _ _._ _._;..,0989 R. _..a,2868 . ._.0.00 . 719 _.._r12 ..__;: 344 r: _..0 _.49 _ ° ...0 _.._0 ... _., d _.. _.� _ .�..-_.._... .... _...-..._..., t„_......-..., ». .�._.,.... ._.._ _,.....», _. _.w, _. .�., 7. ....-....:.. ..._ .. _._., ...H., ..._..._.,. mow..... ....,. .� ., ....... ......K ,,,._. __.._. .. ..,,..... .•: _..�. .w-... _ 6 c) AED exarsien 53 -4 Envelope loss(gain 1180 864 45 79 12 a) Infiltration 240 67 0 0 b) Roomventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 1420 931 45 79 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1420 931 45 79 15 Ductloads 287% 41% 4076 384 287% 41%1 131 32 Total room load 5496 1315 176 'I'llAir required (cfm) 71 59 2 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrigfmtsolFt- 2020-Nov-09 09:13:04 "tLA Right-Suite®Uriversal 201919.0.16 RSU23828 Page 5 erstone1820CRGR\Lot12BIk1Waterstone1820CRGR.np Calc=MJ8 FrontDoorfaces: N - wrightsoft, Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 12 Block 1 Waterston 18... Date: By: DCS 1 Room name KrrCHENMOOK LAUNDRY 2 3 Exposed wa l Room height 15.0 It 10.0 ft heal/cool 0 ft 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 246.0 ft 246.0 ft2 6.0 x 6.0 ft 36.0 112 Ty Construction number U-value (BtuhRtz-'F) Or HTM (Btuh/t2) Area (ft') or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 . Blkwall;sfu000eM_ __._ 2A-2ov, ., ,.. 26 2(v 2B-2fv .' 11J0„_�_-�.__ Bk wall, stu000 ext 2A-2ov, - - - Bwall, slk tucco 6d 10C-v 2A 2ov 2A2ov_____ Blk wall, stucco ext 2A-2ov 2A-2ov 166-30ad •22A.>pl_ __.... _____-. 0.201 0.330 0.330 0.330 •-_--•-0,600._n_-_ 0.201 -- 0:; 0 0201 0.550 0.330 __0.330 0.201 0.330 _0.330 0.032 _ ._0989 n n 'n n a -e_. s s s __s- w w w ._ ,583 9.57 - 957 9.57 17.40. 5.83 957 5.83 15.95 057 _.-u9.57_ 5.83 9.57 . 9.57 0.93 _ _ 2868. 822 11.58 9.72 4.06 22.35 4A6 1620 8.52 .._-:852 4.06 21.79 22.35 1.69 .. .0.00 . 0 0 0 0 0 0 0 0 __-_____0 150 0 33 246 `__.._246 ; 0 0 0•. 0-�0 -..- 0 0 0 ------_._.�0 117 0 _..... 2 1_40 246 - ._.,]5 L ..0 . -, 0 O 0 .w00 0 0 0 0 _ _ 0 0 0 0 __.____._0 476 0 _ ...__ 730 w _ 183 416 _._ _..,d0 0 0 0' ___ 0 "0 0 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 T ' - 0 0 0 0 0 _ 0 33 `. 0 0 0, 0 0 _ __ 0 - 0 0 0. 0 0 0 61_ , _..__0. __ �.__ 1�I _ L-G Vl/ C F __ ..a _ 0 0 0 __ ___- 0 684 0 313 =369 228 _. _430 0 0 " b 0 0 _.__«�.___.- 0 0 0 __- _ 9 _ _ _ 60 36 .mr.. _36 36 0 7 7- 6 c)AED...!on 284 -36 Envelope lossIgain 2025 2090 192 104 12 a) Infiltration 300 84 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Ocaipants@ 230 0 0 0 0 Applianceslother 1200 600 Subtotal (lines 6 to 13) 2325 3374 192 704 Less extemalload 0 0 0 0 14 Lesstransfer Redistribution Subtotal 0 0 2325 0 0 3374 0 0 192 0 0 704 15 Duct loads 287% 41% 6672 1390 2879/6 41%1 550 290 Total room load Air required (dm) 8997 116 4764 212 742 10 994 44 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -r}.t'- wrigFatsoft- 2020-Nov-09 09:13,04 .4�GP. Right-SuteOUriversal 201919.0.16 RSU23828 Page 6 erstone1820CRGR�Lotl2BIk1Waterstore1820CRGR.np Calc=MJB FronlDoorfaces: N ® Duct System Summary Job: wrightsoft y ry Date: Entire House By: DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY, SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM For: ADAMS HOMES 5412 Lugo Street, Fort Pierce, FL 34951 Heating Cooling External static pressure 0.40 in H2O 0.40 in H2O Pressure losses 0.06 in H2O 0.06 in H2O Available static pressure 0.34 in H2O 0.34 in H2O Supply/return available pressure 0.170/0.170 in H2O 0.170/0.170 in H2O Lowest friction rate 0.300 in/100ft 0.300 in/100ft Actual air flow 1167 cfm 1167 cfm Total effective length (TEL) 113 ft Supply Branch Detail Table Lot 12 Block 1 Waterston... DCS Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 2764 35 24 0.394 4.0 Ox 0 VI Fx 16.3 70.0 BDRM 2 h 15750 202 121 0.366 8.0 Ox 0 VI Fx 22.9 70.0 BDRM3 h 6226 80 78 0.433 5.0 Ox0 VIFx 8.6 70.0 DEN/BDRM4 h 14001 180 113 0.409 7.0 Ox0 VIFx 13.2 70.0 DINING/FOYER c 3643 139 162 0.444 7.0 Ox 0 VIFx 6.5 70.0 FAMILYRM c 2871 97 128 0.330 8.0 Ox 0 VIFx 17.9 85.0 st1 KRrCHEN/NOOK c 4764 116 212 0.323 8.0 Ox0 VIFx 20.1 85.0 st1 LAUNDRY c 994 10 44 0.316 4.0 Ox 0 VIFx 22.7 85.0 st1 M. BATH h 5496 71 59 0.317 5.0 Ox 0 VIFx 22.2 85.0 sti KWIC c 111 2 5 0.318 4.0 Ox 0 VIFx 21.9 85.0 sti MSTR BDRM h 18304 235 220 0.300 8.0 Ox 0 VI Fx 28.2 85.0 st1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 530 669 0.300 625 14.0 0 x 0 VinlAx wrightsoft, 2020-Nov-0909:13:05 �M •k• F. ,„a•...�m� •. Rig id-Sute®Uriversal 201919.0.16 RSU23828 Page 1 ACCA erstorel820CRGR\Lotl2BIklWaterstore1B20CRGR.rp CaIc=MJ8 FrortDoorfaces:N Return Branch Detail: Table Name Grille Size (in) Htg (Cfm) Clg (Cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matt Trunk rbi Ox0 1167 1167 0 0 0 0 Ox 0 VIFx - wrightsoft, 2020-Nov-09 09:13:05 <M,,.k•,�,�n,„,,.. �m�.. Riglt-SUte®Ulversal201919.0.16RSU23828 Page 2 erstore1820CRGR\Lotl2BIklWaterstorel820CRGR.rrp Calc=MA Frort Door faces: N 2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 12 Block 1 Waterstone 1820 CRGR Builder Name: ADAMS HOMES Street: 5412 Lugo Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 W Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawlsspace walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class,l vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extgntl behind piping and wiring, Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants. shall not be used to fill voids between fire sprinkler cover plates and walls or ce4lings. a. In addition, inspection of log walls shall be in accordance with the provisions of ]CC-400. 11/9/2020 9:29 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 FORM R405-2017 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the residential Simulated Performance Method shall include: ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page) and an input summary checklist that can be used for field verification (usually four pages/may be greater). ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report (usually one page) 11/9/2020 9:27:28 AM EnergyGauge@ USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition Jurisdiction: 661000 Permit #: Job Information Builder: ADAMS HOMES Community: Lot: 12 Address: 5412 Lugo Street City: Fort Pierce State: FL Zip: 34951 Air Leakage.TeSt Results Passing results must meet either the Performance, Prescriptive, orERIMethod, O PRESCRIPTIVt METHOD -The building or.dwelling;unit shall be tested and venfied`as,having an air leakage rate of,not,exceeding,7 air changes per hour at a pressure of 0.2 inch w.g `,(50.Pascals) in Climate Zones PERFORMANCE or' METHOD -The bwldmg or dwelling unit shall be tested and verified as having an air leakage rate of'not exceeding the selected ACH{50)-value, as shown on Form R465=2017,(Perf6rmance) or R406 2017 (ERI), section labeled as ihiiitiaiion,a sub -section ACH50. ACH(50) specified on Form R405-2017-Energy Calc (Performance) • r R406-2017 (ERf): 7.000 x 60 _ 18200 — Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans 1-1 PASS • Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 11/9/2020 9:29:16 AM EnergyGauge@ USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 6th Edition (2017) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods FADDRESS: 5412 Lugo Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS See individual code sections for full details. V SECTION R401 GENERAL EjR401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal enveldibr- building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. R402.4.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. Fi R402.4.3 Fenestration air IeakagdNindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 11/9/2020 9:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) - All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. EJ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 "C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory) Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 11/9/2020 9:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). ❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60oC). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. EJ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 11/9/2020 9:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. El intermittent Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. ❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 11/9/2020 9:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatoryhe energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps. Exception: Low -voltage lighting. R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights. 11/9/2020 9:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5