HomeMy WebLinkAboutFire Dept Permit SAINT LUCIE COUNTY FIRE DISTRICT
��t�GQUNrY,r PLAN REVIEW FORM
5160 N.W.Milner Drive
Port Saint Lucie,FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: wwwsicfd.com
Building Dept. SLC FMO Permit# 8-21-V
Project Name A-1 Truss Expansion Bldg 6 I BLDG Permit# i 2008-0498
Address 4451 St Luice Blvd City Ft Pierce
Contractor Proctor Construction
Address 2050 US HWy 1 Ste 200 City hero Beach
State FL Zip 132960 — i Telephone (772)234-8164
rchitect/Engineer Rama Prana Kristam Telephone (772)409-1003
ccupancy Type I Storage Construction Type lVB I Square Feet 3000
Tel
Occupant Load Number of Stories E1 :7]
Access Box Required Access Key Switch
AFS Permit T FA Permit I _j FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be.pdf only.
2. All revisions,including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers,Fire Alarms,and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE,2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1.Portable fire extinguishers from a licensed contractor are required.
2.Exit and emergency signs are required.
3.Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector
(
Page E of E Reviewed by IT€ ony Jerger I Date 01-27-2021