HomeMy WebLinkAboutBuilding plansFile Copy General Notes A. CONCRETE & FOUNDATION DESIGN: 1. ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSI MINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MWI UM, 31/2" NOMINAL THICKNESS. 3. FIBERMESH (3/4" PER CUBIC YARD MIN.) MEETING APPROPRIATE ACI AND ASTM REQUIREMENTS MAY BE USED IN LIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERMESH. 5. ALL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, #3 BARS MAY BE GRADE 40 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM. THICKNESS. 7. SOIL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 FSF. 8. THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,- ASTM C 150). AGGREGATES - #6 STONE, ASTM C 33 SIZE NO.67 LESS THAN 3/4". AIR ENTRAINING +/-1%- ASTM C 260. WATER REDUCING AGENT - ASTM C 494. CLEAN POTABLE WATER OTHER ADMIXTURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTITUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALLING OR OTHER DETERIORATION. B. MASONRY: I. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR 2. ALL MORTAR SHALL BE OF TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS F-O" IN HEIGHT. C. ALUMINUM: 1. ALL STRUCTURAL ALUMINUM SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF 6005-T5 FOR ALLOY WITH A MINIMUM THICKNESS OF 0.040" FOR SUPPORTING MEMBERS. 2. WHERE KICK PLATES ARE USED A MINIMUM THICKNESS OF 0.024" SHALL APPLY. 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO "PART I -A - SPECIFICATIONS FOR ALUMINUM STRUCTURES - ALLOWABLE STRESS DESIGN" OR "PART 1-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN" OF THE ALUMINUM DESIGN MANUAL 2010 PREPARED BY THE ALUMINUM ASSOCIATION, INC.WASHINGTON D.C. THE 2014 FLORIDA BUILDING CODE 5TH EDITION ( CHAPTER 16 STRUCTURAL DESIGN & CHAPTER 20 ALUMINUM). 4. WHERE ALUMINUM COMES INTO CONTACT WITH STEEL, OR PRESSURE TREATED LUMBER PROVIDE DIELECTRIC SEPARATION. 5. ALUMINUM MEMBERS SHALL BE STITCHED WITH NO LESS THAN #10 SMS 6" FROM THE ENDS AND 12" ON CENTER IF USING #12 SPACING MAY BE 24" ON CENTER 6. VINYUACRYLIC/GLASS PANELS SHALL BE REMOVABLE. THEY SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH". DECAL SHALL BE PLACED SO IT IS VISIBLE WHEN PANEL IS INSTALLED. (ACRYLIC/GLASS WINDBREAKERS INCLUDED) D. FASTENERS: I. ALL LAG BOLTS SHALL CONFORM TO STAINLESS STEEL TYPE. 300 18-8, WITH STANDARD FLAT WASHER UNLESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. 2. HEX BOLTS HAS TO BE ASTM A 325, PLATED WITH STANDARD FLAT WASHERS AND NUTS. 3. ALL CONCRETE SCREWS SHALL BE, SIMPSON, BILTI, RAWL, TAPCON,REDHEAD, DYNABOLT, OR APPROVED EQUAL. 4. ALL METAL TIES AND ASSOCIATED ACCESSORIES SHALL BE HOT DIPPED GALVANIZED, S. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF SX BOLT DIAMETER INTO STRUCTURAL FRAMING (G=.42 MIN.). 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE PROVIDED WITH PILOT HOLES HAVING A DIAMETER NOT GREATER THAN 70 PERCENT OF THE THREAD DIAMETER OF THE BbLT OR SCREW. ALL LAG BOLTS AND SCREWS SHALL BE INSERTED IN PILOT HOLES BY TURNING AND UNDER NO CIRCUMSTANCES BY DRIVING WITH A HAMMER 7. ALL EXPANSION ANCHORS SHALL BE DESIGNED IN ACCORDANCE WITH THE SPECIFIC MANUFACTURER'S REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER FASTENERS SHALL BEA MINIMUM OF SAE GRADE #5 OR BETTER ZINC PLATED. 8. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD, OR OTHERWISE NOTED ON PLANS 9. ALL FASTENERS SHALL COMPLY WITH ASTM A153. 10. ALL CONNECTORS SHALL COMPLY WITH ASTM A653 CLASS G-185. 11. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SHALL BE 3/4" AND MINIMUM CENTER -TO -EDGE SHALL BE 1/2" UNLESS NOTED OTHERWISE. E. REFERENCE STANDARDS: ASTM E 119 ASTM E 1300 ASCE 7 -10 AA ASM35, AND SPEC. FOR ALUMINUM PART 1-A, & 1-B ASTM C94 ASTM C150 ASTM C33 ASTM C260 ASTM C494 ASTM A615 ASTM A185 FLORIDA BUILDING CODE 2014 (CHAPTERS 16,20 AND 23) STH EDITION 2010 ALUMINUM DESIGN MANUAL F. ABBREVIATIONS: THE FOLLOWING LIST OFABBREVIATIONS IS NOT INTENDED TO REPRESENTALL THOSE USED ON THESE DRAWINGS, BUT 1. TO SUPPLEMENT THE MORE COMMON ABBREVIATIONS. 2. TYP--TYPICAL 3. SIM--SIMILAR 4 LON - UNLESS OTHERWISE NOTED CONT-- CONTINUOUS S. VIF-- VERIFY IN FIELD G. RESPONSIBILITY: 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD CONDITIONS. 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE 'SUNROOM' ROOM ADDITION ELEMENTS AS PROVIDED BY THE CONTRACTOR 4. ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND MANUFACTURER S. ANY DETAILS NOT SHOWN ARE TO BE ENGINEERED BYA LICENSED P.E. IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES, H. MISCELLANEOUS: 1. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 2, IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPATHE ENCLOSURE SHALL COMPLY WITH RESIDENTIAL SWIMMING BARRIER REQUIREMENTS OF THE FBC STH EDITION 3. R4501.17 IN ITS ENTIRETY, EMERGENCY ESCAPE & RESCUE OPENING PER FBC R310.1 SHALL BE VERIFIED BY CONTRACTOR& BUILDING OFFICIAL 4. DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY CONTRACTOR 5. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL HAVE EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, ENSURE BON DING AGENT IS USED FIRST. 5. SCREENING MATERIAL SHALL BE 18X14XO.013 OR EQUIVALENT DENSITY SCREEN MESH ONLY UNLESS NOTED ON DRAWING S-2. 7. 1"12"1045 NON-STRUCTURAL MEMBERS SHALL BE ATTACHED TO HOST WITH 1/4" DIAMETER 1-3/4' EMBEDMENT & 24" O.C. MASONRY SCREW FOR CONCRETE & EQUIVALENT SIZE WOOD SCREW WHEN IN WOOD & #10 X 1/2" EMBEDMENT SMS OR TEN SCREWS IN ALUMINUM MEMBERS TYPICAL. DESCRIPTION: SUNROOM it OR III WALLS ONLY DESIGN DATA: CONUEALK FASTENERS OR ARE THE RESPONSIBIP OF THE GON'TRACTOR OF RCORD IKESE PLANS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY DC NECESaiRY IN.ORDERTO COMPLY 6NITH ALL I?PIPPLICAYLI CODES, 1. ULTIMATE DESIGN WIND SPEED VW3, (3 SECOND GUST): 160 MPH NOMINAL DESIGN WIND SPEED Vasd: 130 MPH 2. RISK CATEGORY 1 3. WIND EXPOSURE B 4. WIND PRESSURES: SUNROOM/ENCLOSED ROOM -160 OLT ROOF: N/A WALLS: +30.4/-33.0 PSF @ ZONE 4 WALLS: +30.4/-40.7 PST @ ZONE 5 INTERNAL COEFFICIENT: +/-.18 S. FACTOR APPLIED TO SCREEN WIND LOADS FOR 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH: N/A 6. FACTOR APPLIED TO SCREEN WIND LOADS FORALLOWABLE STRESS DESIGN: 0.6 7. LIVE LOAD: 3001b. VERTICAL DOWNLOAD ON PRIMARY SCREEN ENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREEN ENCLOSURE PURLINS. 8. EXISTING 4" CONCRETE SLAB AND FOOTER W/ WIREMESH (HOUSE FOUNDATION) SHALL BE ADEQUATE TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE. 9. SCREEN ROOF TYPE: L 10. SOLIOROOFTYPE: N/A ALUMINUM STRUCTURAL MEMBERS HOLLOW SECTIONS 2 x 2:------ =-------------------------------- 2" x 2" x 0.046" 3 x 2--------------------------------------3" x 2" x 0.050„ 2 x 3------------------------------------2" x Y x 0.- 2 x 3:--------------------------------------2" x 3" x 0.070" 2 x 4---------------------------------------2" x 4" x 0.050„ 2 x 5:--------------------------------2„ x 5" x 0.050" OPEN BACK SECTIONS 1 x 2r-------------------------------------- I" x 2" x 0.040" 1 x 3---------------------------------------1„ x 3" x C.045" SNAP SECTIONS 2 x 2 Snap:-------------------------2" x 2" x 0.045" 2 x 3 Snap:-------------------------2" x 3"x 0.050" 2 x 4 Snap:------------------------------- 2" x 4" x 0.045" SELF MATING (SMB 2 x 4 SMB:-------------- 2" x 4" x 0.044" x 0.100" 2 x 5 SMB:-------- 2" x 5" x 0.050" x 0.118" 2 x 6 SMB:---------------------- 2" x 6" x 0.050" x 0.120" 2 x 7 SMB:-------------- 2" x 7" x 0.057" x 0.120" 2 x 8 SMB: - ------- ------- 2" x 8" x 0.072" x 0.224" 2 x 9 SMB:--------------------- 2" x 9" x 0.072" x 0.224" 2 x SO SMB:------ ---------- 2" x 10" x 0.092" x 0.374" > NI a� S . L Cx1E rOUNTYv4TRUILPnO ]f)11'ISIO\ F V VTVAN z D FOR Q1vIPLIA SCE xnVl.-„ D-ITE PLANS AND E 1 T MUST BE KEPT ON JOB 011 NO ]INSPECTION WILL BE 4IADE, RECFE 6VrD APR 2 0 2017 PERMITTING St. Lucia County, FL 1 HEREBY CERTIFY THAT I HAVE REVIEWED THIS PLAN AND FOUND IT TO BE IN COMPLIANCE WITH ASCE7-10, & FBC 2014 STH EDITION .......... Q' i 2C/�C0 Cps !L •� 0... 20 � �.eWd A\ � /� • �F �" �(i=ems Ci j %EA T2SEAL ENGINEER OF RECORD David W. Smith P.E. FLORIDA LICENSE NUMBER: 53608 Thomas L. Hanson P.E. FLORIDA LICENSE NUMBER: 38654 Mark Ronald Dunn, Jr. P.E. FLORIDA LICENSE NUMBER: 73968 Joel Falardeau P.E. FLORIDA LICENSE NUMBER: 70667 Erik Stuart P.E. FBC Plans & Engineering Services, Inc. 6272 Abbott Station Drive Unit 101 Zephyrhills, 0. 33542 Phone:(813)788-5314 Fax:1-(866)-824-7894 Email: erb@fbcplans.com Website:w .fbcplansxom C.O.A.-#29054 DATE: 03-21-2017 DRAWN BY: DRAYTON REVISION: DATE: RO 1 RO 2 RO 3 PROJECT ADDRESS: THOMAS 80 GOLF DR PORT SAINT LUCIE, FL 34952 CONTRACTOR: ARROYO ENTERPRISES, INC. NOTES S-1 op SLIDING WINDDW - FL 15428 SLIDING DOOR - FL 15441 KICK PAN - FL 7561 MULLION - FL 15532 1 ELEVATION SIDE WALL NOTE SHALL NOT BLOCK/EFFECT EGRESS, PLAN VIEW �r 9-5 • •t ' 4_6.. J 4'-BY2 { 4'-6Y2„ IFG-S SPECS TYP. ApR 2 0 2017 PERMITTING St. Lucie County, FL 1 H ,K IJT LEKInY IHAII HAVE KEVIEWEV THIS PLAN AND FOUND IT TO BE IN COMPLIANCE WITH ASCE7-10, &FBC 2014 STH EDI'nQN v 44/� � O•' Uj �� a t'� ENGINEER OF RECORD David W. Smith P.E. Thomas L. Hanson P.E. FLORIDA LICENSE NUMBER. 38654 Mark Ronald Dunn, Jr. P.E. FLORIDA LICENSE NUMBER. 73968 Joel Falardeau RE Erik Stuart P.E. FLORIDA LICENSE NUME FBC Plans & Engineering Services, Inc. 6272 Abbott Station Drive Unit 101 Zepbyrbills, f133542 Phone;(813)788.5314 Fax: 1-(866)-824-7894 Email: erb@fbcplanscom Website:w .fbcplans.com C.OA. - #29054 DATE: 03-26-2017 DRAWN BY: DRAYTON REVISION: DATE: R01 RO 2 RO 3 RO 4 PROJECT ADDRESS: THOMAS 80 GOLF DR PORT SAINT LUCIE, FL 34952 CONTRACTOR: ARROYO ENTERPRISES, INC. ELEVATIONS S2 File Copy I HEREBY CERTIFY THAT I HAVE REVIEWED THIS PLAN AND FOUND IT TO BE IN 7-7 COMPLIANCE WITH ASCE 7-10, & / 1/4"0x 2"-1/2 MASONRY ANCHOR EXISTING MASONRY .p, C a. FBC STH EDITION(2014) RESIDENTIAL& *",AITo' y EXISTING BUILDING. IF WOOD SUBSTITUTE IDENTICAL SOLID WALL GROUTED �� � ry G V _ e P WOOD SCREW OR LAG 6"FROM OO 000NNECTION R �,.' �,�, u I. TOP & BOTTOM & @ 24" D.C. D n (9 �yryj�qp p'®Q }� y r' 1"X3"OPEN BACK OR RECEIVING CHANNEL 00 A?� 7 J 24'll m��V ` i °•® °°•°� eAy •" E/ 1/4"0A21/2 ENSONRYSCREW 3"PROM PER i'ePIT?IisiG a v •:\5 END & @ 24" O.C. / 2°X_END BEAM 4. _L Cit; 'v L'L'D?S.'� F; 'T 2[/c �� O,(C Q Ut -.. (SEE SHEET S-2 FOR SIZE) (L ° U AO Z, 6 / 2"x2"x1/B%BEAM DEPTH" iJ O• �� e LU r / RECEIVING CHANNEL ���,``° _ W/(1)1/4"X3"CONCRETE 1'X3"OPEN BACK W • Q °• a ANCHOR INTOWALL& °• GJ 1"X3"OPENBACK (4)*12 x 3/4"EMS EACH ® 0 °• SIDE INTO BEAM ✓' /�=r_�U,�® NOTE: WHEN ATTACHING TO WOOD STRUCTURES, WOOD LAGSCREW (2)#lOxl-1/2"SMS MIN MA ANCHOR DESIGNS SHALL BE OF IDENTICAL SIZE AND EMBEDMENT AS THAT ( � �AL OP SONRYANCHOR SCREWS. THRU SCREW BOSS OF VIX3"OPEN BALK S2 END BEAM TO HOST STRUCTURE —DETAIL ENGINEER OF RECORD H1 OPEN BACK TO HOST STRUCTURE DETAIL scaLE: HISs-s �NT3David W. Smith P.E. S_3 FLORIDA LICENSE NUMBER: 53608 UPRIGHT 3/E"0 L Thomas L. Hanson P.E. Sc rew crew SECONDARY ANGLE MIN Column Anchor Concrete Sc FLORIDA LICENSE NUMBER: 38654 (4)#10 X3/4"EMS 0.125" THICK (NOT Size B Min. Spa WOOD CONCRETE FASTENING SECONDARY REQUIRED FOR ZX3 ANGLE TO COLUMN MEMBER) 3X32X3 0" 2" SPACING MEMBER EACH SIDE) 2x4 1 3" (MIN)(TYF) 3/8"0X3"LAGSCREW Mark Ronald Dunn, Jr. PRIMARY 2"X 2" 2x5 1 3" *EACH SONRY SCREW IP X 0.125" ANGLE 2%6 1 4" NCRETE) INTO PRIMARY P.E. jB)-3/8"OLGNLREFE SCREW I (2)#I0X3/4"SMS FASTEN 2x7 1 5 ANGLE AND @24"O.C. ANCHOR INTO SECONDARY COLUMN TO PRIMARY ANGLE 2x8 2 IS) -1/4" 0 X 2" LAGWEEN COLUMNS (TYP FLORIDA LICENSE NUMBER; 73968 ANGLE(TYP EACH. SIDE)(SEE O (TYP EACH SIDE) 2x9 4 SCREW (MASONRY SIDE) TABLE) O 2X10 2 4.5 SCREW IF CONCRETE) VX 2'X Joel Falardeau P.E. O 1"X2"BASE MEMBER INTO SECONDARY ANGLE MEMBER BASE(TYP EACH SIDE) (TYP EACH SIDE](SEE MCHSIDETYPANCHOR SPA q TABLEBELOWFOREAcx slDe7 FLORIDA LICENSE NUMBER: 70667 (MIN)(TYP)(S6E TABLE) (1)-3/8"O CONCRETE SCREW QUANTITY)RIMARY 2"X 2"ErLk Stuart P.E. d ANCHOR INTO PRIMARY SECONDARYANGLE0.125"ANGLEANGLE AND @ 1/4" 0 CONCRETE (MIND.125"THICK)FLORIDA LICENSE NUMBER: 77605 3"(MIN) SCREWANCHOR@ 2)#IOX3/4"SMS 24" O.C. BETWEEN COLUMNS (4)#10X3/4"SMSASTENING COLUMN FBC Plans&En ineerin(TYP EACH SIDE) FASTENING SECONDARYO PRIMARY ANGLEg g NOTES: ANGLE TOCOLUMN(TYPTYP EACH SIDE) Services, Inc. 1. NUM HER OF ANCHORS"B" IS EACH SIDE I NTO THE SECONDARY ANGLE AND DOES NOT I NCLUDE THE ANCHOR EACH SIDE]oumn INTO THE IX2. NOTES: 6272 Abbott Station Drive Unit 101 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL HE 2-3/4" AT AT ALL UPRIGHT 1. NUMBER OF LAG SCREWS IS EACH SIDE AND DOES NOT INCLUDE THE LAG SCREW INTO THE Zephyrhills, fl. 33542 LOCATIONS. ALL SCREW LENGTHS AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED 1X2. Phone: (813)78B-5314 EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 2. LAG SCREW DESIGNS ARE BASED ON AN ALLOWABLE WITHDRAWAL LOAD OF 410 LB. AND Fax: 1-(866)-824-7894 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON FASTENERS APPROVED ON THE S-1 NOTES PAGE. AN ALLOWABLE LATERAL LOAD OF 185 LB. FOR WOOD WITH SPECIFIC GRAVITY, G=O.SS. Email: erb@fbcplans.com 4. 2X3 W/IX2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. 3. ALL LAG SCREWS SHALL BE FULLY INSTALLED INTO WOOD MEMBERS FORTHE ENTIRE Website: www.Pocplans.com LENGTH OF THE SCREW. C.OA. - #29054 POST OR SMB CONCRETE BASE CONNECTION (NOTE: CONNECTION SHALL BE USED FORTOP & BOTTOM WHEN APPLICABLE) Gl COLUMN OR POST WOOD BASE OR LEDGER CONNECTION DRAWN BY: S-3 SfALe. n.Ts. - G COLUMN OR POST CONCRETE BASE OR LEDGER CONNECTION REVISION: DATE: $-3 sul.e:N.rs. RO 1 RO 2 (4)#10x1H'SMSINTD SCREW BOSSES OPTINAL RO 3 ANGLE CLIPS OR RE[EIVMG CHANNEL W/ OPTION #1 «lox'/°° sms EA LEc PROJECT ADDRESS: RECEIVING CHANNEL 060 MIN. (O SCREW AWACHEUT02-M CHAIR THOMAS INTO SCREW BOSSES RAILW/a10x3/4"SMs3' FROM ENO &@ 13" O.C. iit COMPOSITE MATERIAL 80 GOLF DR .ArracxED w/a1Gx324°oc PORT SAINT LUCIE, FL 34952 2"X2"OR 2"X3" INTERNAL MEMBER CE1ViNG COMPOSITE PANEL DEC. CHANNEL#10X3/4" ATTACRRPTOFDUNDATION -- UPWGHTORBEAM W 14'x23/4-TAPCONS OR• MATINGDR &6"FROMENOSLEGNTOGITOR PU4"EA. NICUMINU MATING OR @24 f ATTMEMBER W/(1] nox CONTRACTOR: LEG INTO GIRT OR PURLIN- HOLLOW 0.062"ANGLE CLIPSw 2 MEMBE 2/4'@ a10X( /O 3/4"®24°O.F COMPOSITE FANEMSEC NINE •jUPRnUTTORBEAM 3NAPORR SELF #12x3/4"SMS EA LEG) • ATTACHEDTO RECEIVING MArmcOn ARROYO ENTERPRISES, INC. CHANNELw/(1)atnx HOLLOW 3/4" W 24' O.C. UPRIGHT A BEAM -SNAP OR SELF MATING OR KICK PLATE ATTACHED ALUMINUM MEMBER . DETAILS HOLLOW SCALE: : NTS H CHAIR RAIL CONNECTION H1 RECEIVING CHANNEL TO COMPOSITE MATERIAL TO UPRIGHT `' J S_? IELE:N.T.S� S'-4, SCALE: NT$ J ✓�