HomeMy WebLinkAboutProject InformationLoad Short Form Job: 1388 Air Calcs, LLC Date: Dec 01, 2020 Zone 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynne@aircalcs.com Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Htg Clg Outside db (°F) 41 90 Method Inside db (°F) 70 75 Shielding /stories Design TD (°F) 29 15 Pressure /AVF Daily range - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 57 HEATING EQUIPMENT Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 12.8 kW 43766 Btuh 21 °F 1867 cfm 0.043 cfm/Btuh 0.60 in H2O Infiltration Blower door 3 (partial) / 2 50 Pa / 5422 cfm COOLING EQUIPMENT Make Lennox Trade LENNOX Cond ML14XC1-059-230A** Coil CBA27UHE-060-230*++TDR AHRI ref 10259431 Efficiency 12.5 EER,15.1 SEER Sensible cooling 39200 Btuh Latent cooling 16800 Btuh Total cooling 56000 Btuh Actual airflow 1867 cfm Air flow factor 0.050 cfm/Btuh Static pressure 0.60 in H2O Load sensible heat ratio 0.76 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) HtgAVF (cfm) ClgAVF (cfm) Cabana 55 2744 1087 119 54 Dining Room 181 2606 1483 113 74 Hallway 191 0 0 0 0 Kitchen 319 2350 4283 102 214 Laundry 69 520 199 23 10 M Bath 277 3741 1739 162 87 M Linen 34 0 0 0 0 M WIC 150 2382 865 103 43 Master Bedroom 371 8806 11952 382 597 Open To Below 767 19891 15675 862 783 Pantry 14 0 0 0 0 Stairs 34 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -F- wrightsoft" 2020-Dea0818:38A8 4 .• �Nh, u ,�m�„ Right-Sute®Universal 202121.0.02RSU27054 Page 1 aunenls\Wrightsoft HVAC\7466 Legends Dr MKS.rtp Calc= MJ8 Front Door faces: NE Zone d 2484 43079 37366 1867 1867 Other equip loads 1987 1055 Equip. @ 0.95 RSM 36654 Latent cooling 12447 TlITAI C '7AQA ACnaC AnInn IQC7 4QC7 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. * wrightsoft, 106K��„,...,,�•,U_M•, Rigft-Sute®Universal 202121.0.02RSU27054 aanerlts\WrigMsoft HVAC\7466 Legends Dr MKS.nQ Calc= MJB Front Door faces: NE 2020-Deo08 18:38AB Page 2 Air Calcs, LLC Load Short Form Zone 2 Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa Design. Information Htg Clg Infiltration Outside db (°F) 41 90 Method Blower door Inside db (°F) 70 75 Shielding /stories 3 (partial) /2 Design TD (°F) 29 15 Pressure /AVF 50 Pa / 5422 cfm Daily range - L Inside humidity (%) 30 50 Moisture difference (gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S018-230A** AHRI ref Coil CBA27UHE-018-230*++TDR AHRI ref 10259433 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating input 3.8 kW Sensible cooling 12600 Btuh Heating output 12846 Btuh Latentcooling 5400 Btuh Temperature rise 19 °F Total cooling 18000 Btuh Actual airflow 600 cfm Actual airflow 600 cfn Air flow factor 0.053 cfrnBtuh Airflowfactor 0.049 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.74 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) CIgAVF (cfm) Bath 2 55 495 304 26 15 Bath 3 114 216 314 11 15 Bed 2 219 2712 2776 144 135 Bed 3 221 2589 2767 138 135 Bed 4 173 2151 2167 114 105 Clst 23 0 0 0 0 Hall 126 0 0 0 0 Li nen 16 0 0 0 0 Loft 357 2099 3404 111 166 Upstairs 50 0 0 0 0 WIC 3 42 445 262 24 13 1n11r% A An fZor, 1140 1l it Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - wrightsoft, 2020-Deo-0818:38:48 ....... ,.• . �.wUmM , Right -Sate® Universal 2021 21.0.02 RSU27054 Pa9 e 3 aunents%WrigFtsoftHVAC\7466 Legends DrMKS.np Calc=MJB Front Doorfaoes:NE Zone 2 d 1435 11293 12333 600 600 Other equip loads 1174 624 Equip. @ 0.95 RSM 12361 Latent cooling 4639 TPITAI C` -1n2G I Mag Ia000 Cznn rnn Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrightsoft® 2020-Deo-08 18:38:48 k•a�„, .,„�.,Um,., Riglt-Sute®Uruversal202121.0.02RSU27054 Page curnents\Wrigltsoft HVAC17466 Legends Dr MKS.np Calc= MJ8 Frort Door faces: NE Air Calcs, LLC Building Analysis Zone 1 Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynne@aircalcs.com For: Location: St Lucie Co Intl, FL, US Elevation: 26 ft Latitude: 280N Outdoor: Dry bulb (OF) Daily range (OF) Wet bulb (OF) Wind speed (mph) Legacy N Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa Indoor: Heating Cooling Indoor temperature (OF) 70 75 Design TD (OF) 29 15 Relative humidity (%) 30 50 Heating Cooling Moisture difference (gr/Ib) 2.4 56.9 41 90 Infiltration: - 15 (L ) Method Blower door 77 Shielding / stories 3 (partial) / 2 15.0 7.5 Pressure /AVF 50 Pa / 5422 cfrn Heating Component Btuh/ft2 Btuh %of load Walls 2.9 8592 19.1 Glazing 19.7 7939 17.6 Doors 3.7 74 0.2 Ceilings 1.0 1090 2.4 Floors 2.8 7056 15.7 Infiltration 2.7 8309 18.4 Ducts 10019 22.2 Piping 0 0 Humidification 0 0 Ventilation 1987 4.4 Adjustments 0 Total 45066 100.0 Component Btuh/ft' Btuh % of load Walls 1.9 5410 14.1 Glazing 31.6 12771 33.2 Doors 3.7 75 0.2 Ceilings 1.5 1609 4.2 Floors 0 0 0 Infiltration 0.8 2561 6.7 Ducts 11140 29.0 Ventilation 1055 2.7 Internal gains 3800 9.9 Blower 0 0 Adjustments 0 Total 1 1 38421 1 100.0 Latent Cooling Load =12447 Btuh Overall U-value = 0.122 Btuh/ftz-°F Data entries checked. Glazing c a Glazing Floors Ceilirigs wr1ghtsoft- 2020-Deo•08 18:38:48 Right -Sate® Universal 2021 21.0.02 RSU27054 Page 1 ACCK aanents\WrightsoftHVAC7466 Legends Dr MKS.rkp Calc= MJ8 Front Door faces: NE Air Calcs, LLC Building Analysis Date: Dec 8 01, 2020 Zone 2 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynne@aircalcs.com For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Blower door Wet bulb (°F) - 77 Shielding / stories 3 (partial) / 2 Wind speed (mph) 15.0 7.5 Pressure /AVF 50 Pa / 5422 cfrn Heating Component Btuh/ft2 Btuh % of load Walls 2.4 2483 19.9 Glazing 9.2 1038 8.3 Doors 0 0 0 Ceilings 1.0 1422 11.4 Floors 0 0 0 Infiltration 2.7 3055 24.5 Ducts 3294 26.4 Piping 0 0 Humidification 0 0 Ventilation 1174 9.4 Adjustments 0 Total 1 112468 1 100.0 Component Btuh/ft2 Btuh % of load Walls 1.5 1588 12.3 Glazing 20.2 2273 17.5 Doors 0 0 0 Ceilings 1.5 2099 16.2 Floors 0 0 0 Infiltration 0.8 942 7.3 Ducts 3780 29.2 Ventilation 624 4.8 Internal gains 1650 12.7 Blower 0 0 Adjustments 0 Total 12957 100.0 Latent Cooling Load =4639 Btuh Overall U-value = 0.066 Btuhff--°F Data entries checked. Infiltration Gains M -Ofd- wrightsoft 2020-Deo0818:38:48 RigYt-Sate® Universal 202121.0.02 RSU27054 Page 2 cxznents\Wrightsoft HVAC\7466 Legends Dr MKS.np Calc= MJB Frort Door faces: NE p Component Constructions Job: 1388 Air Calcs, LLC Date: Dec 01, 2020 Zone 1 By-. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: Vieldlynna@aircaics.com For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Design, Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (T) 70 75 Elevation: 26 ft Design TD (T) 29 15 Latitude: 28°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (T) 41 90 Infiltration: Daily range (T) - 15 (L ) Method Blower door Wet bulb (T) - 77 Shielding / stories 3 (partial) / 2 Wind speed (mph) 15.0 7.5 Pressure /AVF 50 Pa / 5422 cfm Construction descriptions or area u-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuhtftk'F ft'"F/Btuh Btuw Btuh Btu AI Btuh Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh ne 449 0.109 5.1 3.15 1415 2.02 905 se 486 0.109 5.1 3.15 1530 2.02 978 sw 601 0.109 5.1 3.15 1894 2.02 1211 nw 486 0.109 5.1 3.15 1532 2.02 980 all 2022 0.109 5.1 3.15 6370 2.02 4075 Firm Wall, Stucco Ext, R-13 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2'k6" Wd Firm, ne 231 0.083 13.0 2.40 553 1.53 354 16" OC Stud se 256 0.083 13.0 2.40 614 1.53 393 sw 189 0.083 13.0 2.40 453 1.53 290 all 676 0.083 13.0 2.40 1621 1.53 1037 Partitions Firm Wall, 1/2" Gyp Bd Ext, R-19 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2'k6" 221 0.094 19.0 2.73 601 1.35 299 Firm, 16" CC Stud Windows Impact: Impact; NFRC rated (SHGC=0.21); 50%blinds 45°, medium; ne 26 0.330 0 9.57 249 17.6 458 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft nw 14 0.330 0 9.57 133 9.58 133 overhang (5.2 ft window ht, 1.5 ft sep.); 8 ft head ht nw 14 0.330 0 9.57 133 9.58 133 all 54 0.330 0 9.57 514 13.5 723 Impact: Impact; NFRC rated (SHGC=0.48); foreground = green grass ne 48 1.060 0 30.7 1476 36.4 1749 (0.23); 6 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.20); 50% blinds 45°, medium; ne 26 0.280 0 8.12 211 16.4 426 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (5.2 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; se 60 0.330 0 9.57 574 16.0 962 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (6 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; se 50 0.330 0 9.57 479 15.9 794 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (5 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.21); 50%blinds 45°, medium; sw 16 0.330 0 9.57 153 16.6 266 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (4 ft window ht, 1.5 ft sep.); 8 ft head ht Wrglhltsoft- 2020-Deo•0818:38:49 ,• • ,o,,o.. gym, M Right-&Re®Universal 2021 21.0.02 RSU27054 Page 1 aunents\Wrigrtsoft HVAQ7466 Legends Dr MKS.rkp Calc= MJ8 Frort Door faces: NE Impact: Impact; NFRC rated (SHGC=0.48); 50% blinds 45°, medium; sw 48 1.060 0 30.7 1476 18.4 884 foreground = green grass (0.23); 9 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.56); foreground = green grass sw 96 1.080 0 31.3 3007 55.3 5308 (0.23); 1.3 ft overhang (8 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.23); foreground = green grass nw 6 0.290 0 8.41 50 22.2 133 (0.23); 1.3 ft overhang (1.2 ft window ht, 1.5 ft sep.); 8 ft head ht Doors Fbrgls Door nw 20 0.127 7.0 3.69 74 3.73 75 Ceilings Attic, Metal Roof, R-30 Ceiling Ins, 1/2" Gyp Bd Int Fnsh 1100 0.034 30.0 0.99 1090 1.46 1609 Floors On Grade Depth, Tile Flr Fnsh 167 0.989 0 28.7 4775 0 0 80 0.989 0 28.7 2280 0 0 all 246 0.989 0 28.7 7056 0 0 �a '�" Wr ightsco 2020-Deo-08 18:38:49 M.•,�,kn ,on.e.�m�.•, Rigit-Sute®Universal 202121.0.02RSU27054 Paget aanents\Wrigttsoft HVAC\7466 Legends Dr MKS.rtQ Calc = MJ8 Front Door faces: NE Air Caics, LLC Component Constructions Zone 2 Air Caics, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vickilyrrie@aircalcs.com For: Location: St Lucie Co Intl, FL, US Elevation: 26 ft Latitude: 28°N Outdoor: Dry bulb (T) Daily range ff) Wet bulb (T) Wind speed (mph) Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa Indoor: Heating Cooling Indoor temperature (T) 70 75 Design TD (°F) 29 15 Relative humidity (%) 30 50 Heating Cooling Moisture difference (grAb) 2.4 56.9 41 90 Infiltration: - 15 (L ) Method Blower door 77 Shielding / stories 3 (partial) / 2 15.0 7.5 Pressure /AVF 50 Pa / 5422 cfm Construction descriptions Or Area U-value Insul R Htg HTM Loss Cig HTM Gain fN StuWft-°F ft"F/Btuh Btuw Btuh BtLM? Btuh Walls Frm Wall, Stucco Ext, R-13 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2'Sc6" Wd Frm, ne 285 0.083 13.0 2.40 683 1.53 437 16" OC Stud se 77 0.083 13.0 2.40 184 1.53 117 sw 323 0.083 13.0 2.40 774 1.53 495 nw 351 0.083 13.0 2.40 843 1.53 539 all 1035 0.083 13.0 2.40 2483 1.53 1588 Partitions (none) Windows Impact: Impact; NFRC rated (SHGC=0.21); 50%blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (5.2 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.20); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (5.2 ft window ht, 1.5 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.21); 50%blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1.3 ft overhang (3 ft window ht, 1.5 ft sep.); 8 ft head ht Doors (none) Ceilings Attic, Metal Roof, R-30 Ceiling Ins, 1/2" Gyp Bd Int Fnsh Floors (none) sw 31 0.330 0 9.57 299 16.9 527 nw 31 0.330 0 9.57 299 17.6 549 all 62 0.330 0 9.57 597 17.3 1077 ne 26 0.280 0 8.12 211 16.4 426 sw 24 0.330 0 9.57 230 16.2 388 1435 0.034 30.0 0.99 1422 1.46 2099 Wr ghtsoff - 2020-Deo•0818:38:49 �M.,.• .,.no-.n.ro.w„yUm�..> Right-Sute®Universal 202121.0.02RSU27054 Page aimerds\Wrigttsoft HVAC\7466 Legends Dr MKS.rLp Calc= MJ8 Front Door faces: NE Pro ect Summa Job: Air Calks LLC J rY Dec Date: Dec 01, zoso Zone 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyrm@aircalcs.com Project• • For: Leggacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Notes: Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 33060 Btuh Structure 26226 Btuh Ducts 10019 Btuh Ducts 11140 Btuh Central vent (62 cfm) 1987 Btuh Central vent (62 cfm) 1055 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 45066 Btuh Use manufacturer's data n Rate/swing multiplier Equipment load 0.95 36654 Btuh Infiltration sensible Method Blower door Latent Cooling Equipment Load Sizing Shielding / stories 3 artial) /2 Pressure /AVF 50 Pa 5422 cftn Structure 6848 Btuh Ducts 3190 Btuh Central vent (62 cfm) 2409 Btuh Heating Cooling Outside air Area (ftz) 2484 2484 Equipment latent load 12447 Btuh Volume (ft3) 33556 33556 Air changes/hour 0.47 0.27 Equipment Total Load (Sen+Lat) 49100 Btuh Equiv AVF (cfm) 261 151 Req. total capacity at 0.70 SHR 4.4 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-059-230A** AHRI ref Coil CBA27UHE-060-230*++TDR AHRI ref 10259431 Efficiency 100 EFF Efficiency 12.5 EER,15.1 SEER Heating input 12.8 kW Sensible cooling 39200 Btuh Heating output 43766 Btuh Latentcooling 16800 Btuh Temperature rise 21 OF Total cooling 56000 Btuh Actual airflow 1867 cIrn Actual airflow 1867 cfrn Airflowfactor 0.043 cfm/Btuh Airflowfactor 0.050 cfm/Btuh Static pressure 0.60 in H2O Static pressure 0.60 in H2O Space thermostat Load sensible heat ratio 0.76 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -�- wrightsoft ° 2020-Deo•08 18:38:49 RigFt-Sute®Universal 202121.0.02RSU27054 Page ACCk wmenlslWrigYtsoft HVAM7466 Legends Dr MKS.r p Calc = MJ8 Frort Door faces: NE Pro ect Summa Job: Air Calcs, LLC J rY Dec Date: Dec 01, zoso Zone 2 - By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Notes: Desfgn Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Structure 7999 Btuh Ducts 3294 Btuh Central vent (37 cfm) 1174 Btuh Outside air Humidification 0 Btuh Piping 0 Btuh Equipment load 12468 Btuh Infiltration Method Shielding / stories Pressure /AVF Blower door 3 artial)/2 50 Pa 15422 cfm Heating Cooling Area (ftz) 1435 1435 Volume (fF) 12915 12915 Air changes/hour 0.45 0.26 Equiv AVF (cfm) 96 56 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 3.8 kW 12846 Btuh 19 0 600 cfrn 0.053 cfm/Btuh 0.70 in H2O Sensible Cooling Equipment Load Sizing Structure 8552 Btuh Ducts 3780 Btuh Central vent (37 cfm) 624 Btuh Outside air Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 12361 Btuh Latent Cooling Equipment Load Sizing Structure 2150 Btuh Ducts 1064 Btuh Central vent (37 cfm) 1424 Btuh Outside air Equipment latent load 4639 Btuh Equipment Total Load (Sen+Lat) 16999 Btuh Req. total capacity at 0.70 SHR 1.5 ton Cooling Equipment Summary Make Lennox Trade LENNOX Cond ML14XC15018-230A** Coil CBA27UHE-018-230*++TDR AHRI ref 10259433 Efficiency 13.0 EER,16 SEER Sensible cooling 12600 Btuh Latentcooling 5400 Btuh Total cooling 18000 Btuh Actual airflow 600 cfm Air flow factor 0.049 cfm/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 0.74 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fd- =ightsoft- 2020-Deo•0818:38:49 - •.gym = Rigtt-S ite® Universal 202121.0.02 RSU27054 Page 2 ..aunents%Wrightsoft HVACV466 Legends Dr MKS.rup Calc= MJ8 Frort Door toes: NE Air Calcs, LLC Right-J® Worksheet Job: 1388 Zone 9 Date: Dec 01, 2020 By: Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlynne@aircalcs.com 1 Room name Zone 1 Cabana 2 Exposed wall 250.0 It 23.5 ft 3 Room height 13.5 It d 10.0 ft heat/cool 4 Room dimensions 6.5 x 8.5 It 5 Room area 2483.5 ftz 55.3 ft Ty Construction U-value Or HTM Area (q Load Area (fF) Load number (Btuhlftz°F) (Btu 1) or perimeter (ft) (Bivh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco E)d Impact, 0.109 0.330 ne ne 3.15 9.57 2.02 - 17.66 523 - " 26 449 0 1416 246 905 458 0 o 0 0 0 0 0 0 �C Impact 1.060 ne 30.74 36,44 48 0 1476 ' 1749 :. 0 0 0 0 IW Frm Wall, Stucco Ext 0.083 ne 2.40 1.53 257 231 553 354 0 0 0 0 11 - L-G Impact 0280 ne 8.12 16.38 26 0 211 426 0 0 0 0 W , Blk Wall, Stuma E)d 0.109 se 3.15 2.02 646 486 1530 . 978 85 85 268 171 `-G Impact • 0.330 se 9.57 16.04 60 12 574 962 0 0 0 0 IW Frm Wall, Stucco EM 0.083 se 2.40 1.53 306 256 614 393 0 0 0 0 - �-G Impact ,, Blk Wall, Sluco6 E>d 0.330 0.109 se sw 9.57 3.15 15,88 2A2 50 761 12 601' 479, 1894 794 1 n -0 65 0 65 0 205 0 131 fW w1iImpact -" Impact 0.330 1.060 sw sw 9.57 30.74 16.61 18.41 16 48 5 96 153 1476 266 884 0 0 0 0 0 0 0 0 Impact 1.080 sw 31.32 5529 96 15 3007 5308 '_ 0 0 0 0 W Fmi Wall, Stucco E)d Impact 0.083 0.330 sw sw 2.40 0.00 1.53 0.00 189 0 189 0 453 0 290 0 0 0 0 0 0 0 0 0 I-G Impact_ Blk Wall, Stlioco E)d 0.330 0.109 0290 sw nw nw 0.00 ' 3.15 8A1 0.00 2.02 2222 0 Mo - 6 _ 0 486 ..;. 0 _, 0 ,1532 50 _ , 0 980 138 0 85 0 0 65 0 _ 0 205 0 0 131 0 V1/VbImpact Impact,.,, 0.330 nw 9.57 9.56 - 14 0 133 133 0 0 0 0 Impact 0.330 nw' 9.57 9.58 14.' 0 133 133 0 0 0 0 Fbrglsboo� AU7 nw 3.69 3.73 20 20 74 75 -' `' 20 20 74 75 WI Fnn Wall, Stuom E)d 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 �c Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P ' ' Frrn Wall, iW Gyp B 0.094 2.73 1,35 "221 221 601 299 0 0 0 0 C Atfir, Metal Roof, R 0.034 0.99 1 A6 1100 1100 1090 1609 55 55 , 55 81 F On Grade Depth, Tile 0.989 - 28.68 0.00 1717 167 4775 0 55 24 674 0 F On Grade Depth, Tile 0.989 2.8.68 0:00 818 80 2280 0 0 0 0 0 6 c) AED excursion 1525 -19 Envelope loss/gain 24751 19854 1480 670 12 a) Infiltration 8309 2561 626 193 b) Room ventilation 0 0 0 0 13 Internal gains Oaupants@ 230 5 1150 0 0 Appliances(other 2650 0 Subtotal (lines 6 to 13) 33060 26226 2106 763 Less e)temalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 33060 26226 2106 763 15 Dud loads 30% 42% 10019 11140 30% 42% 638 324 Total room load 43079 37366 2744 1087 Air required (dm) 1867 1867 119 54 Calculations ElDDroved bvACCAto meet all requirements of Manual J 8th Ed. _ -Pla- wrigF�tsoft 2020-Dec-0818:38:49 .4 Z7- "" ,, ._.,.._-"--- Right-Srite® Universal 2021 21.0.02 RSU27054 Page 1 aunents\Wrigltsoft HVAC\7466 Legends Dr MKS.rLp Calc= MJB Front Door faces: NE Air Calcs, LLC Right-M Worksheet Job: 1388 Zone 1 Date: Dec 01, 2020 By: Vicki Lynne Nisa Air Calks, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Dining Room Hallway 2 Exposed wall 19.0 It 4.0 ft 3 Room height 11.0 ft heatl000l 10.0 ft heaf/cool 4 Room dimensions 12.5 x 14.5 It 1.0 x 190.6 ft 5 Room area 181.3 ft' 190.6 ftz Ty Construction LI-value Or HTM Area M Load Area (M Load number (Btuhlft2-'F) (Btu or perimeter (ft) (13 h) or perimeter (ft) (Biuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1N Blk Wall; Stucco E)d ' 0.109 ' ne 3.15 2.02 138 112 351 225 0 0 0 0 Impact 0.330 ne 9.57, 17.60 26 0 249 458 0 0 0 0 L�__GG Impact' 1060 he 30.74 . 36.44 0 0 0 0 0 0 0 0 IW Frm Wall, Stuom Ext 0.083 ne 2.40 1.53 0 0 0 0 0 0 0 0 11 L_G Impact 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 W. L-G Blk Wall, StucooExt Impact 0.109 A.330 "se 'se 3.15 9.67 202 16.04 66 0 66 0 208 °to 133 0 0 0 0 0 0 0 0 0 IW L-G Frm Wall, Stucco IRA 0.083 se 2.40 1.53 0 6 0 0 0 0 0 0 Impact , 0.330 se 9.57 15.88 0 0 0 0 0 0 0 W II--- ^ _ Blk Wall, Stuom Ext 0.109 ' sw 3.15 2.02 0 0 0 0 .0 0 0 0 0 Impact 0.330 sw 9.57 16.61 0 0 0 0 6 0 0 0 Impact 1.060 sw 30.74 18.41, 0 0 0 0 0 0 0 0 �--G LLL--GGG Impact 1.080 sw 31.32 - 6529 0" 0, 0 0 0 0 0 0 W Frm Wall, Stucco Ext 0.083 sw 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact, 0.330 sw 0.00 0.00 0 0 0 0 0 0 0 0 W _ Blk Wall, Stucco Ext 0.109 :nw 3.15 2.62 0 0 0 0 0 6 0 0. Impact 0290 nw 8A1. 2222 '0 0 0 0 0 0 0 0 Impact 0.330 nw 957 9.58 0 0 0 0 0 0 0 0 Impact 0.330 nw .- 9.57 9.58 ._ 0 0 0 0 0 0 0 0 FbrglsiDoor 0.127 nw 369 3.73 0 0 0 0 0 0 0 0 W Frm Wall, Stucco Ext 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 L_G Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall, 1IY' Gyp B 0.694 - 2.73 1.35 6 6 15 7 40 40 109 54 C Attic, Metal Roof, R 0.034 0.99 1.46 6 6 6 9 21 21 21 31 F On Grade Depth, Tile, 0.989 , - 28.68 0.00 - 181 19 545 0 191 4 115 0 F On Grade Depth, Tile 0.989 28.68 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 13 -2 Envelope loss(gain 1374 846 245 83 12 a) Infiltration 542 167 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(Iines6to13) 1916 1013 245 83 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 84 28 -245 -83 14 Subtotal 2000 1041 0 0 15 Dud loads 30% 42% 606 442 30% 42%1 0 0 Total room load 2606 1483 0 0 Airrequired(cfm) 113 74 0 0 Calculations aDDroved WACCA to meet all recluirements of Manual J 8th Ed. -Fid- 2020-Deo-0818:38:49 """` '" "'"'"^` Right -Suite® Universal 2021 21.0.02 RSU27054 Page t aunents\Wrigh tsoft HVAC\7466 Legends Dr MKS.r p Calc= MJ8 Front Door faces: NE Air Calcs, LLC Right-J® Worksheet Job: 1388 Zone 1 Date: Dec 01, 2020 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden HammockLR Vero Beach, FL32966 Phone:772.800.8413 Email: vicidlynne@aircalcs.com 1 Room name Ktchen Laundry 2 Exposed wall 19.0 ft 5.5 It 3 Room height 10.0 It heatl000l 10.0 ft heatl000l 4 Room dimensions 1.0 x 318.8 ft 5.5 x 12.5 It 5 Room area 318.8 ft2 68.8 ft Ty Construction number U-value (BtuhffL-q Or HTM (Btuhlft2) Area (ft2) or perimeter (ft) Load (Btiuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V,U Blk Wall, Stucco Ext Impact Impact 0.109 0.330 1.060 ne ne' "ne. 3.15; 9.57 30.74 2.02 17:60 36A4 0 0 " 0 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 I� W Frm Wall, Stucco Ext 0.083 ne 2A0 1.53 0 0 0 0 0 0 0 0 11 L-G Impact 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 W Blk Wall, Stucco F)d 0.109 se 3:15 2.02 '0 0 0 0 0 0 0 0 L- G Impact 0.330 " se, , 9.57, 16;04 0, 0 0 0 0 0 0 0 Frm Wall, Stucco Eid 0.083 se 2AO 1.53 0 0 0 0 0 0 0 0 Impact. Blk Wall, Stucoo Exi 0.3130 0.109 se sw3.15 9.57 15.88 Z62 0 190 0 - . 174 0 548 0 351 0 0 0 0 0 0 0 0 -(i fW _ Impact '' 0.330 sw 9.57 16.61 16 2 163 266 - - 0 0 0 0 �--c� it---GG Impact 1:660 sw 30.74 18.41 0 0 0 0 0 0 0 0 Impact 1.080 'sw 31.32 5529 0 0 0 0 0 0 0 0 W Frm Wall, Stucco Ext 0.083 sw 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.330 sw 0;00 0.00 0 0 0 0 0 0 0 0 _ Blk Wall, Stucco Eud 0.109 riiiv 3.15 2.02 0 0 0 0 0 0 0 0 Impact 0290 nw 6A1 2222 0 0, 6- 0 0 :0 0 0 Impact Impact Florgis Door 0:330 0.330 0.1'27 nw nw' nw .. 9.57. 951 13.69 9.58 9:58 3.73 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 0 0 . 0 0 0 0 0 0 0 • W Frm Wall, Stucco Eud 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 L-G Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,10 Gyp B - 0.094 - 2.73 1.35 0 0 0 0 • 55 55 150 74 C A1tiG Metal Roof, R 0.034 0.99 1.46 10 10 9 14 33 33 33 48 F On Grade Depth, Tile 0.989 28.68 0.00 319 19 546 0 69 6 158 0 F On Grade Depth, Tile 0.989 - 28.68 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 46 -3 Envelope loselgain 1256 676 340 120 12 a) Infiltration 506 156 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Ooaupants@ 230 2 460 0 0 Appliances(other 1700 0 Subtotal (lines 6to 13) 1762 2992 340 120 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 42 14 58 20 14 Subtotal 1803 3006 399 140 15 Dud loads 30% 42% 547 1277 30% 42% 121 59 room load 2350 4283 520 199 ,-TTotal Airrequired (clim) 102 214 23 10 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -FW 2020-Dec-0818:38.49 .4CCA Right-Sute®Universal 2021 21.0.02RSU27054 Page canents\Wrigftsoft HVAC17466 Legends Dr MKS.r p Calc = MJ8 Front Door faces: NE Air Calcs, LLC Right-J® Worksheet Job: 1388 Zone 1 Date: Dec 01, 2020 By: Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicidlyrvre@aircalcs.com 1 Room name M Bath M Linen 2 Exposed wall I 29.5 ft 0 ft 3 Room height 11.0 ft heat/000l 10.0 ft heat/ocol 4 Room dimensions 20.6 x 13.5 ft 1.0 x 33.9 it 5 Room area 276.8 ftz 33.9 W Ty Construction U-value Or HTM Area Load Area (ft-) Load number (Btuhfi1--q (B or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall, Stu000 Ext 0.109 ne 3.15 2.02 88, 88 277 177 0 0 0 0 , Impact '0.330 ne 9.57' 17.60 0 0 0 0 0" D 0 0 Impact 1.060 ne 30.74 36A4 0 0 •'0 0 -' _ 0 0 0 0 IW Fnn Wall, Stucco End 0.083 ne 2.40 1.53 0 0 0 0 0 0 0 0 11 - L-G Impact 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 W Blk Wall, Stucco E)d 0.109 'se :.A5 ' 2.62 0 b 0 0 0 0 0 0 Impact 0.330 ab 9.67 16.04 0 0 0 0 0 0 0 0 W - L Frm Wall, Stucco Ext 0.083 se 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 se 9.57 15.88 0 0 0 0 0 0 0 0 -G W Blk Wall, Stucco Bd 0.109 sw 3.15 2.02 88 '88 277 171 0 0 0 0 Impact 0.330 sw 9.57 16.61 0 0 0 -0 0 6 0 0 Impact 1.060 sw 30.74 18A1 0 0 0 0 0 0 0 0 Impad 1.080 sw 31.32 5529 0 0 0 0- 0. 0 0 0 W Frm Wall, Stucoo Ext 0.083 sw 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact Blk Wall, Stu000 Ext 0.330 0:109 sw nw 0.00_ 3.15 0.00 2.02 0, , 149 0 143 0 449 0 •287 0 0 0 0 0 0 0 0 Impact' 0.290 nw 8.41 2222 6 0 50 133 0 0 0 0 Impact 0.330 nw 9.57 9.58 0 0 0 .. ... A 0 0 0 0 Impact FbrglsDoor' 0.330 0.127 nw nw 9:57 3.69 9.58 3.73 0 0 0 "' 0 0 0 0 0 '0 0 0 0 0 0 0 0 WI Frm Wall, Stucco Ext 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 - W-_ G Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P" Fmn Wall, "112° Gyp B 0.094 2.73 1.35 0 0 -0 0 6 0 0 0 C MQ Metal Roof, R 0.034 0.99 1.46 108 108 107 156 0 0 0 0 F On Grade Depth, Tile 6.966 - - 28.68 0.00 277 _ 30 M6 0 34 6 0 0 F On Grade Depth, Tile- 0.989 28.68 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 21 0 Envelope loss(gain 2007 954 0 0 12 a) Infiltration 864 266 0 0 b) Room ventilation 0 0 0 0 13 Internal gains Ooaipants @ 230 0 0 0 0 AppliancesAother 0 0 Subtotal (lines 6 to 13) 2871 1220 0 0 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2871 1220 0 0 15 Dud loads 30% 42% 870 518 30% 42%1 0 0 FTTotal room load F I 3741 1739 0 0 Air required (cm) 162 87 0 0 .j Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fid- 2020-Dec-0818:38:49 Aad A Right-Sute®Universal 2021 21.0.02 RSU27054 Page 4 aunerds\Wrightsoft HVAC\7466 Legends Dr MKS.np Calc= MJ8 Front Door faces: NE Air Calcs, LLC Right-J® Worksheet Zone 1 Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name MWC Master Bedroom 2 Exposed wall 24.5 It 41.5 ft 3 Room height 10.0 It heat/000l 11.0 It heaV000l 4 Room dimensions 12.0 x 12.5 It 22.5 x 16.5 It 5 Room area 150.0 ft 371.3 ftz Ty Construction U-value Or HTM Area (q Load Area (q Load number (Btuhlftz-°F) (B or perimeter (ft) (Btuh) or perimeter. (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W. Blk Wall, Stu000 E)d Impact 0.109 0.330 ne ne 3.15 9.57 2.02 17.60 0 0 0 0 0 0'' 0 0 0 0 0 0 0 0 0 0. Impact: 1060 ne 30.74 36.44 0 -0 -0 0 0 0 0 0 WI Fnn Wall, Stucco E)d 0.083 ne 2.40 1.53 0 0 0 0 0 0 0 0 11 L-G Impact. 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 W. Blk Wall, Stu' F-id ' 0:109 se 3.15 2.02 0 0 0 0 28 28 87 55 L Impact ;0.330 se_ 9.57 16.04 0 °. 0 0 0 -. 0 0 0 0 W Fnn Wall, Stucco E)d 0.083 se 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 se 9.57 15.88 01 0 0 0 0 0 0 0. IW _ WIE� Bilk Wall, Stu000 E)d ' 0.109 sw 3.15' 2A2 " ' 0 0 01 _ 0 248 152 477 ' 305 Impact 0.330 sw 9.57 16.61 0 0 0 0 0 0 0 0 Impact 1.060 sw 30.74 18.41 0. 0 0 .0 0 0 .0 ;0 Impact, 1.680 sw 31.32 5529 '0 0 0 0 96 7 3007 '5306 W Frm Wall, Stucco E)d 0.083 sw 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact Blk Wall, Stucco E)d Impad 0.330 0.109 0.290 sw nw nw 0.00 3.15 BAII 0.00 2.02 2222 0 .125 0 0 125 0 , . 0 394 -0 , ,., 0 252 , 0 _. 0 182 0 0 154 .0 0 484 0 0 310 0 Impact Impact 0.330 0.330 nw nw. 9.57 9.57• 9:58 9.58 0 0 0 0 :.: 0 ., 0 0 0 14 14 0 0 133 133 133 133 Fbrgls Door 0.127 nw 3:69 3.73 0 0 0 0 0 0 0 0 W Fnn Wall, Stu000 E)d 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 L= Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm.Wall,1a' Gyp B : 0.094 -- 2.73 1.35 120 120 32Z 162 0 '0 0 0 C Attic, Metal Root R, 0.034 0.99 1 A6 72 72 71 105 2 2 1 2 F _ On Grade Depth, Tile 0.989 28.68 000 - 150 25 703 0 371 42 1190 0 F On Grade Depth, Tile 0.989 28.68 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -15 1757 Envelope loss/gain 1495 505 5512 8003 12 a) Infiltration 333 103 1215 375 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6to13) 1828 607 6728 8378 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 30 10 14 Subtotal 1628 607 6758 8388 15 Dud loads 30% 42% 554 258 30% 42% 2048 3563 Total room load 2382 865 8806 11952 Air required (ctm) 103 43 382 597 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -FL4- wri htsoi t ^ 2020-Deo•08 18.38.49 g A "'""'" Right-Sute®Universal 2021 21.0.02 RSU27054 Page 5 aunerts\WrigitsoftHVAC\7466 Legends Dr MKS.rkp Calc= MJB Front Door faces: NE Air Cans, LLC Right-J® Worksheet Job: 1388 Zone 1 Date: Dec 01, 2020 Air Calcs, LLC By: Vicki Lynne Nisa 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynre@aircalcs.com 1 Room name Open To Below Pantry 2 Exposed wall 83.5 It 0 It 3 Room height 20.3 It heat/cool 10.0 ft heat1cool 4 Room dimensions 1.0 x 766.5 ft 2.5 x 5.5 It 5 Room area 766.5 ft 13.8 f 2 Ty Construction U-value Or HTM Area (" Load Area (" Load number (BtuhAt--F) (Btu or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Vp Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 298 '250 786 503 0 0 0 0 Impact 0.330 ne 9.57 17.60 0 "o - 0 0. 0 0 0 0 Impact, 1.060 ne 30.74 36.44 48 1476 1749 0 0 0 0 W Frm Wall, Stucco Ext 0.083 ne 2.40 1.53 257 _0 231 553 354 0 0 0 0 11 L-G Impact 0.280 ne 8.12 1638 26 0 211 426 0 0 0 0 W BIk Wall, Stucco Ext 0.109 se 3.15 2.02 367 307 967 , 619 0 0 0 6 " Impact , _ 0.33.0 se 9.57 16.04 ,60 6 `574 962 0 0 0 0 IW �-G Fmn Wall, Stucco Ext 0.083 se 2.40 1.53 306 256 614 n3 0 0 0 0 Impact 0.330 "se 9.57 15.88 50 6 479 794 0 0 0 W Blk Wall, Stucco Ext 0.109 sw '3.15 2.02 171 123 386 247 0 .0 0 0 0 Impact 0.330 "sry 0.57 16.61 0 0 0 0 0 0 0 0 L-IG Impact 1.060 sw 80.74 18.41 48 -48 1476 884 0 0 0 0 Impact 1.080 SN 31.32 55.29 " 0, 0 0 0 0 0 0 0 W �G Fnn Wall, Stucco Ext Impact 0.083 0.330 sw sw 2.40 0.00 1.53 0.00 189 0 169 0 453 0 296 0 0 0 6 0 0 0 0 0 L_ Impact 0.330 0.00 0:00 0 0 0 0 0 0 0 0 -G Blk Wall, Stucco Ext 0.109 _snr nw 3.15 2.02 0 0 0. _ 9 0 0 0 0 Impact 0.2910 8AI _ 2222 0 0 '0 0 0 0 0 0, lmpad ., 0.330 nw' 9.57 9.58 .. 0 0 0 0 0 0 0 0 Impact 0.330 'nw 9.57 .958 0 0 0 0 0 0 0 0 ,. D Fbrgls Door 0.127 nw 3.69 3.73 0 0 0 0 0 0 0 0 W Frm Wall, Stucco Ext 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 L-G Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall, 1t2" Gyp B 6.094 - 273 1:35 0 0 6 0 0_ 6 0 0 C Attic, Metal Roof, R 0.034 0.99 146 793 793 786 1160 0 0 0 0 F On Grade Depth, Tile 0.989 - 28.68 0.00 0 0 0 0 14 0 0 0 F On Grade Depth, Tile 0.989 28.68 0.00 818 80 2280 0 0 0 0 0 6 c) AED excursion -271 0 Envelope losstgain 11041 8109 0 0 12 a) Infiltration 4224 1302 0 0 b) Roomventilation 0 0 0 0 13 Internal gains Occupants@ 230 3 690 0 0 Appliancesother 900 0 Subtotal (lines6to 13) 15265 11001 0 0 Less external load 0 0 0 0 Less transrer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 15265 11001 0 0 15 Dud loads 30% 42% 4626 4673 30% 42%1 0 0 Total room load 19891 15675 0 0 Air required (dim) 862 783 0 0 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed. _ -Fk- 2020-Dea0818:38:49 .4CCA -' - " Right -Suite® Universal 2021 21.0.02 RSU27054 Page 6 aunentsUrightsofttiVAM7466 Legends Dr MKS.rkp Calc = MJ8 Front Door faces: NE Air Calcs, LLC Right-J® Worksheet Zone 1 Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name Stairs Wtrcist 2 Exposed wall O ft O ft 3 Room height 10.0 It heat/tool 10.0 It heat/cool 4 Room dimensions 8.5 x 4.0 It 3.5 x 6.5 It 5 Room area 34.0 ftz 22.8 ft Ty construction U-value Or HTM Area (fl Load Area (M Load number (Btuh/ff--°F) (B or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VL2Blk Wall, Stuom Ext 0.109 ne 3.16 2.02 , 0 0 6 0 0 0 0 0 Impact„ 0.330 .rie 9.57 17.60 0 0 0 0 0 0 0 0 impact, 1.060 he 30:74 36.44 0 0 0 0 0 0 0 6 WI Frm Wall, Stuom Ext 0.088 ne 2A6 1.53 0 0 6 0 0 0 0 0 11 r-G Impact 0280 ne 8.12 16.38 0 0 0 0 0 0 0 0 V,V Blk Wall, Stucco Ex( 0,109 ', se 3.15 2.62 6 0 0 0 0 0 0 0 L--,G Impact 0.330. "se 9.57 16.04 0 0 0 0 0 0 0, 0 WI Frm Wall, Stucco Ext 0.083 se 2A0 1.53 0 0 0 0 0 0 0 0 �-G Impact Blk Wall, stucco E6d Impact Impact 0.330 0.109 0.330 1.060 se sw swv " 9.57 3.15 9.57 k74 15.88 2.02 16.61 18A1 0 0 0 0 0 0 0 0 0 ' 0 0 0 0 0 0 0 0 0 0 6 0 ',0 0 0 0 0. 0 0 0 0 0 0 WI ' - Impact 1.080 1sN 31.32 5529 0 0 0 0 0 0 0 0 W, Frm Wall, Stucco Ext 0.083 sw 2A0 1.53 0 0 6 0 0 0 0 0 Impact 0.330 sw 0.00 0.00 0 0 0 0 0 0 0 0 L�-GG Impact 0.330 sw 0.00 0.00 0 0. 0 0 0 0 0 0 Blk Wall, Stucco F>d 0.1 o9 ' nw 3.15 2.02 0 0 0 6 0 0 0 0 Impact 0290 nw 8A1 2222 0 0:• 0 0 0 0 0 0 Impact 0:330 •nw 9.57 9.58 0 0 0 0 0 0 0 0 Impact 0.330 nw 9.57 9.58 0 0 0 0 0 0 0 0 Fbrgls Door 0.127 _fiw 3.69 3.73 0 0 0 0 0 0 0 0 WI Frm Wall, Stucco E)d 0.083 nw 0.00 0.00 0 0 0 0 0 0 0 0 - �c Impact 0.330 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,1 /2" Gyp B 0.094 2.73 1.35 0 0 0 0 0 0 0 0 C. Attic, Metal Roof, R 0.034 0.99 1A6 0 0 0 0 0 0 0 0 F On Grade Depth, Tile 0.989 28.68 0.00 34 0 _ 0 0 23 0 0 0 F On Grade Depth, Tile 0.969 28.68 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 0 0 0 -1 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains Occupants@ 230 0 0 0 0 Appliances/other 0 50 Subtotal (lines 6 to 13) 0 0 0 49 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 30 10 14 Subtotal 0 0 30 59 15 Duct loads 30% 42% 0 0 30% 42% 9 25 Total room load 0 0 39 84 Air required (dm) 0 0 2 4 Calculations aDDroved bvACCA to meet all requirements of Manual J 8th Ed. _Right -Sute®Uruversa12021 21.0.02 RSU27054 2020-Dec-0818:38:49 Page 7 aanents\Wrigttsoft HVAC\7466 Legends Dr MKS.rtp Calc= MJB Front Door faces: NE Air Calcs, LLC Right-M) Worksheet Zone 2 Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlynre@aircaics.com Job: 1388 Date: Dec 01, 2020 By- Vicki Lynne Nisa 1 Room name Zone 2 Bath 2 2 Exposedvell 127.5 It 6.5 It 3 Room height 9.0 It d 9.0 it heat/cool 4 Room dimensions 8.5 x 6.5 it 5 Room area 1435.0 ft 55.3 W Ty Construction U-value Or HTM Area (M Load Area (M Load number (Btuhlft;°F) (Btu or perimeter (ft) (Btirh) or perimeter (it) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W, Blk Wall, Stucco 6d, Impact Impact 0.109 0.330 1,060 he, ne. hi 0.00 0.00 0.00 0.00. obo '0.00 0 0 ' 0 0 0 0 0 0 0 0 0 0 0 0 0' 0 0 0 0 0 0 0 0 0 II_�, 11 IW - r-G Frm Wall, Stucco Ext Impact 0.083 0.280 ne ne 2AO 8.12 1.53 16.38 311 26 285 0 683 211 437 426 0 0 0 0 0 0 0 0 W, Blk Wall, Stuow E)d, 0.109 se `0.00 0.00 . 0 0 0 0 0 0 0 0 L-G Impact 0.330 se "_' 0.00 0.00 0 0 0 0 0. 0 0 0 W Frm Wall, Stvcoo Ext 0.083 se 2.40 1.53 77 77 184 117 0 0 0 0 Impact Blk Wall, Stucco Ed 0.330 0.109 se- sw 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W Impact Impact " Impact 0.330 1.060 1.080 sw sw sw 0.00 10.00 0.00 0.00 0.00 0.00 0 0 0 0- 0 0 0 0 0 0 0 0 :0 0 •. 0 0 0 0 0 0 0 0 0 0 WI Frm Wall, Stu000 6d 0.083 sw 2.40 1.53 378 323 774 495 0 0 0 0 - Impact 0.330 sw 9.57 16.18 24 10 230 388 0 0 0 0 I-G Impact 0.330 sw 9.57 16.90 31 7 299 527 0 0 0 0 BIk Will, Stucco E>d 0.109 .'nw 0.00 o.00 0 0 0 0 ' 0 0 0 0 Impact 0290 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact, Impad Fbrgls Door 0.330 0.330 0.127 nw riw nw 0.00 0.00 -0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 `0 0 0 0 0 0 0 0 0 0 0 0 0 0 D WI - r--G Frm Wall, Stucco End Impact 0.083 0.330 nw nw 2.40 9.57 1.53 17.60 383 31 351 0 843 299 539 549 59 0 59 0 140 0 90 0 P Fmi Wall,10 Gyp B 0.094 - 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Metal Rcof, R 0.034 0.99 1.46 1435 1435 1422 2099 55 55 55 81 F On Grade Depth, Tile , 0.989 - 0.00 0.00 0• 0 0 0 0 0 0 0 F On Grade Depth, Tile 0.989 0.00 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 382 -8 Envelope lossrgain 4944 5961 195 163 12 a) Infiltration 3055 942 156 48 b) Room ventilation 0 0 0 0 13 Internal gains: Ooajpants@ 230 0 0 0 0 Appliancestother 1650 0 Subtotal (lines 6 to 13) 7999 8552 351 211 Less e)dernal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 7999 8552 351 211 15 DUdloads 41% 44% 3294 3780 41% 44% 145 93 Total room load 11293 12333 495 304 Air required (dm) 600 600 26 15 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -Fk- 2020-Deo•0818:38:49 .RC - "'""'" .1.11 -., RighFSuite®Universal 2021 21.0.02 RSU27054 Page 8 aunents\Wrigttsoft HVAC\7466 Legends Dr MKS.rkp Calc= MJ8 Front Door faces: NE Air Calcs, LLC Right-JO Worksheet Zone 2 Air Calm, LLC 7550 Hidden Hammock Lr\ Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircatcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name Bath 3 Bed 2 2 Exposed wal I O ft 22.0 ft 3 Room height 9.0 It heat/000l 9.0 It heat/cool 4 Room dimensions 1.0 x 113.5 ft 1.0 x 219.0 It 5 Room area 113.5 ft' 219.0 ft' Ty Construction U-value Or HTM Area (ftF) Load Area (fl Load number (BtuhAF--'F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 Blk Wall,Stuoco Ext 0.109 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact 0.330 ne 0.00 0.00 0 0 "- 0 0 0 0 0 0 Impact 1.060 -ne 0.00 0.00 0 0 0 0 0 0 0 0, W Fnn Wall, Stucco E)d 0.083 ne 2.40 1.53 0 0 0 0 0 0 0 0 11 L-G Impact 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 W. Blk Wall, Stucoo E)d 0.109 ,se 0.00 0.00 0 0 0 ,0 0 0 0 0 L-G Impact 0.330 se 0.00 0.00 0 0 0 0 0 0 0 0. W� L-G Frm Wall, Stucoo bd On se 2.40 1.59 0 0 0 0 27 27 65 41 Impact ._ Blk Wall, Stucco E)d 0.330 '0:109 ,se "sw 0.00 0.00 0.00 •0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WI -" Impact 0.330 sw 0.00 0.00 0" 0 0 0 0 0 0 0 Impact 1.060 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact, 1.080 "sw 0.00 0.00 0 0. 0 0 0 0 0 0 W L-G Fan Wall, Stu000 E)d Impact 0.083 0.330 sw sw 2.40 9.57 1.53 16.18 0 0 0 0 0 0 0 0 146 0 108 0 260 0 166 0 L-G Impact 0.330 sw 9.57 16.90 0 0 0 0 31, 4 299 527 'N. Blk Wall, Stucco E)d Impa(f 0.169 0.290 pw nw, 0.00 0.00 0.00 0.06 0 0 0 0 0 0 0 0 0 0 0 0, 0 0 0 0 Impact Impact FbrglsDoor, 0.330 0330 0:127 nw nw nw 0.00 0.00 0.00 0.00 0.00 0.00 0 ' 0 Jo 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 W Frm Wall, Stucco Ext 0.083 nw 2.40 1.53 0 0 0 0 32 32 76 48 L-G Impact 0.330 nw 9.57 17.60 0 0 0 0 0 0 0 0 P Frm Wall,112' Gyp B 0.094 - 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Metal Roof, R 0,034 - 0.99 1 A6 114 114 113 166 219 219 217 320 F On Grade Depth; Tile - . 0:989 - 0.00 0.00 0 0 0 0 0 0 0 0 F On Grade Depth, Tile 0.989 - 0.00 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion -6 172 Envelope loss/gain 113 160 916 1276 12 a) Infiltration 0 0 527 162 b) Room ventilation 0 0 0 0 13 Internal gains Occupants@ 230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13) 113 160 1443 1689 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 41 58 478 237 14 Subtotal 153 218 1921 1925 15 Duct loads 41% 44% 63 96 41% 44%1 791 851 Total room load 216 314 2712 2776 Air required (dm) 11 15 144 135 Calculations aDDroved bvACCA to meet all requirements of Manual J 8th Ed. _ �d- wrigtitsoR� 2020-Dec-0818:38:49 ACCA _,..,,•._�wmw„ Right -Sate® Universal 202121.0.02 RSU27054 Page 9 cunents\WrigttsoftHVAC\7466 Legends Dr MKS.rup Calc= MJ8 Front Door faces: NE Air Caics, LLC Right-J® Worksheet Zone 2 Air Calks, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynm@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name Bed Bed 2 Exposed wall 30.0 ft 25.0 ft 3 Room height 9.0 ft heaV000l 9.0 ft heat/cool 4 Room dimensions 13.0 x 17.0 It 1.0 x 172.8 ft 5 Room area 221.0 ft2 172.8 W Ty Construction number U-value (Btuhd2_-F) Or HTM (B Area (ft� or perimeter (ft) Load (Btuh) Area (ft-) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 BIk Wall, Stucco E)d Impact 0.109 0.330 ne ne 0,00 0.00 0.00 0.00 6, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact 1.060 ne' 0.00 0.00 0 0 0 0 .0 0 0 0 IW Frm Wall, Stucco Ext 0.083 ne 2.40 1.53 117 117 281 180 122 96 226 147 11 �-G Impact 0.280 ne 8.12 16.38 0 0 0 0 26 0 211 426 1N L� BIk MII, Stu'o EA Impact '''0.166 0.330 se ' se', 0.00 0.00 0.00 '0.00 0 0 0 0 6 0 0 0 0 0 0 0 0 ' 6 0 0 W Frm Wall, Stucco Ext 0.083 se 2.40 1.53 0 0 0 0 50 50 119 76 Impact 0.330 se 0.00 0.00 0 0 0 0_ 0 0 0 0 _ BIk Wall, Stucco E)d Impact b.109 ' 0.330 sw sW b.00 0.00 0.00 0.00 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0. 0 Impact 1.060 sni ;0.00 '0.00 0 0 0 0 0 0 0 0 Impact, 1.080 sw 0.00 '0.00 0 0 0 0. 0 0 0 0 W Frm Wall, StuooD E)d 0.083 sw 2.40 1.53 0 0 0 0 0 0 0 0 Impact 0.330 sw 9.57 16.18 0 0 0 0 0 0 0 0 Impad 0.330 sw 9.57 16.90 0 0 0 0 0. 0 0 0 W. BIk Wall, Stucco Eid Impact 0.109 ,:0290 nw -nW 0.00 0.00 0.00 -0.00 0 0-_ 0 .0 0 0 - -0 0 0 0 0 0 0 0 0 0 Impact 0.330 ?nw 0:00 - 0.00 0 . °' 0 0 0 0, 0 0 0 Unpad 0.330 nw 0.00 ' 0.00 0 0 0 0 6 0 0 0 D Fbrgls Door 0:127 "nw 0.00 0.010 ." 0. 0 0 0 0 0 0 0 , Frm Wall, Stucco EA 0.083 nw 2.40 1.53 153 122 292 187 54 54 130 83 - L-G Impad 0.330 nw 9.57 17.60 31 0 299 549 0 0 0 0 P" Frm Wall, 12" Gyp 6 0.099 ° - 0.00 0.00 - • 0 0 6 - :0 0 0 0 0 C AtbQMetal Roof, R 0.034 0.99 1.46 221 .221 219 323 173 173 171 253 F On Grade Depth, Tile 0.989 -- 0.00 0.00 0 0 6 0 0 0 0 0 F On Grade Depth, Tile 0.989 0.00 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 173 -8 Envelope lossrgain 1091 1412 860 976 12 a) Infiltration 719 222 599 185 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 250 250 Subtotal (lines 6 to 13) 1809 1884 1459 1410 Less external load 0 0 0 0 Lesstransrer 0 0 0 0 Redistribution 25 35 65 93 14 Subtotal 1834 1919 1524 1503 15 Ductloads 41% 44% 755 848 41% 44% 628 664 Total room load 2589 2767 2151 2167 Air required (dm) 138 135 114 105 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fl=§-- wq?lwtsolrr^ 2020-Deo•0818:38:49 AC�A """"Right-Sute®Universal2021 21.0.02 RSU27054 Page 10 aanerds\Wrightsoft HVACV466 Legends Dr MKS.r p Calc = MJ8 Front Door faces: NE Air Calcs, LLC Right-J® Worksheet Zone 2 Air Calm, LLC 7550 Hidden Hammock Ln Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name Clst Hall 2 Exposed wall 10.0 ft 0 It 3 Room height 9.0 It heaUcool 9.0 It heaVcool 4 Room dimensions 6.5 x 3.5 It 1.0 x 125.9 It 5 Room area 22.8 ft2 125.9 ftz Ty Construction U-value Or HTM Area (fF) Load Area (M Load number (BtuhA?-°F) (B or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 W Blk Wall, Stucco E)d 0.109 ne 0.00 0.00 0 0 0" 0 0 0 0 0 Impact Impad 0.330 1.060 ne :,ne 0.00 0.00 0,00 0:00 0 0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 IW ,„_ Frm Wall, Stucco E)d 0.083 ne 2.40 1.53 0 0 0 0 6 0 0 6 11 L_G Impad 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 1N Blk Wall, Stucco Ext 0.109 - se 000 0.00 0 0, 0 0 0 0 0 0 L G Impact 0.330 'se 0.00 0.00 0 0 0 0 0 0 0 0 IW Frm Wall, Stucco E)d 0.083 se 2.40 1.53 0 0 0 0 6 0 0 0 - L-G Impact Blk Wall, Stucco E)d 0.330 0.109 , se sw : 0.00 0.06 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 W Impact 0.330 0.330 sw 0 0.00 0 0 0 0' 0 0 0 0 Impact 1.060 sw 0.00. 0.00 0 0 0 0 0 0 0 0 Impact 1.080 sw 0.00 0.010 0 0 0 0 0 0, 0 0 --G------GGGG W Frm Wall, Stucco EA 0.083 sw 2.40 1.53 59 59 140 90 6 0 0 0 Impact 0.330 sw 9.57 16.18 0 0 0 0 0 0 0 0 Impact 0.330 sw, 9.57 16.90 0 0 0 0 0 0 0 0 Blk Wall, Stucco 6d 0.109 nw 0.00 0.00 - 0 0 0 0 0 0 0 0 Impact 0260 nw 0.00 0.00 0 0 0 0 1 0 0 0 0 Impact 0:330 nw 0.00 0.00 0 0 0 0 .0 6 0 0 Impact0.390 `nw 0.00 0.00 0 0 0 0 0 0 6 0 Fbrgls Door 0:127 nw 0:00 0.00 0 0 0 0 0 0 0 0 IW Frm Wall, Stuom E)d 0.083 nw 2.40 1.5332 32 76 46 0 0 0 0 - r-G Impact 0,330 nw 9.57 17.60 0 0 0 0 0 0 0 0 P Frm Wall;1r2" Gyp B 0.094 0.00 6.00 0 0 0 0_ 0 0 6 0 C Attic, Metal R 0.034 -- 0.99 1.46 23 23 23 33 126 126 125 184 F -Roof, On Grade Depth, Tile 0.989 •- ROO 0.00 0 0 0 0 0 . 0 0 - 0 F On Grade Depth, Tile 0.989 0.00 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -9 -7 Envelope losstgain 238 163 125 178 12 a) Infiltration 240 74 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianoes/other 0 0 Subtotal (lines 6 to 13) 478 237 125 178 Less odemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -478 -237 -125 -178 14 Subtotal 0 0 0 0 15 Dudloads 41% 44% 0 0 41% 44%1 0 0 Total room load 0 0 0 0 Air required (chn) 0 0 , 0 0 Calculations aDDroved bvACCA to meet all requirements of Manual J 8th Ed. -F#d- 2020-Dec-0818:38:49 "'" "^ ^" Right -Suite® Universal 2021 21.0.02 RSU27054 Page 11 ..o.unentslWrightsoft HVAC17466 Legends Dr MKS.np Calc= MJS Front Door faces: NE Air Calcs, LLC Right-M Worksheet Zone 2 Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name Linen Loft 2 E)posed wal I O ft 20.0 It 3 Room height 9.0 It heaV000l 9.0 It heat/cool 4 Room dimensions 8.0 x 2.0 It 1.0 x 356.9 It 5 Room area 16.0 ft 356.9 ft' Ty Constudion U-value Or HTM Area (ft2) Load Area (n Load number (Btuh/ftz°F) (B or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco E)d 0.109 ne no 0.00 0 0 6 0 0 0 0 0. Impad '. 0330 ne 0.00 0.00 -,0 0 -0 0 0 0 0 0 Impad 1.060 ne 0.00 0.00 0 0 0 0 0 0 0 0 IW Frm Wall, Stucco E)d 6.083 ne 2AO 1.53 0 6 0 0 0 0 0 0 11 L-G Impad 0.280 ne 8.12 16.38 0 0 0 0 0 0 0 0 W Blk Wall, Stucco E)d 0.169 se" 0.00 0.00 0 0 0 6 0 0 0 0 Lin Impact, 0,330 se 0.00 0.00 _ 0 0 1 0 0 0 0 0 0 IW �-G Frm Wall, Stucco E)d 0.083 se 2AO 1.53 0 0 0 0 0 0 0 0 Impact 0.330 se 0.00 O.OD 0 0 0 0 0 0 0 0 W Blk Wall, Stucco E)d 0.109 sw. . 0.00 0.00 0 b 0 0 0 0 0 0 Impact0.330 §wv 0.00 0.00 0 A 6 0 0 0 0 0 sw"' 0.00• 0.00 0 0 0 0 0 0 0 0 ImpaImpact1.060 mpad 1.08,0 6,V 0.60 0.00 0 0 0 0 0 0 0 0 W Frm Wall, Stucco E)d 0.083 sw 2.40 1.53 6 0 0 6 180 156 374 239 Impact 0.330 sw 9.57 16.18 0 0 0 0 24 5 230 388 Impact 0.330 sw 9.57 16.90 0 0 0 0 0 0 0 BIk Wall, Stucco E)d 6.109 , nw, 0.00 0.00 0 0 0 6 .0 0 D 0 0 Impad 0.290 , nw. ' 0.00 , 0.00, 0 0 6 0 , 0 0 0 0. Impad 0.330 , nw 0.00 0.00 0 0 0 0 0 .0 0 0 Impact0.330 nw. 0.00 0.00 0 0 0 0 0 6 0 0 FbrgIsDoor '. 0:127 riw obo 0.00 0 0 .0 , 0 0 0 0 0 W Frm Wall, Stu000 E)d0.083 nw 2AO 1.53 0 0 0 0 0 0 0 0 L_G Impact 0.330 nw 9.57 17.60 0 0 0 0 0 0 0 0 P Frm Wall,1/2" Gyp B 0.094 .- 0.00 0.00 .0 0 0 0 6 0 0 0 C AtBG Metal Roof, R 0.034 0.99 1.46 16 16 16 23 357 357 354 522 F On Grade Depth, Tile 0.989 0.00 10.00 1 0 0 0 0 0 0 0 0 F On Grade Depth, Tile 0.989 0.00 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -1 92 Envelope loss/gain 16 23 958 1242 12 a) Infiltration 0 0 479 148 b) Room ventilation 1 0 0 1 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 900 Subtotal (lines 6 to 13) 16 23 1437 2290 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -16 -23 50 70 14 Subtotal 0 0 1486 2360 15 Ductloads 41% 44% 0 0 41% 44% 612 1043 Total room load 0 0 2099 3404 Air required (dm) 0 0 111 166 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - w1r10F2tso4`t- 2020-Deo•0818:38:49 --�A Right-SuteOUniversal 2021 21.0.02 RSU27054 page 12 aunerds\WrigksoftHVAC\7466LegendsDrMKS.nQ Calc=MJ8 Front Door faces'. NE Air Calcs, LLC Right-J® Worksheet Zone 2 Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlynne@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name Upstairs WIC 3 2 Exposed wall 0 It 6.0 It 3 Room height 9.0 It heat/cool 9.0 ft heaV000l 4 Room dimensions 10.0 x 5.0 ft 7.0 x 6.0 It 5 Room area 50.0 ftz 42.0 ft2 Ty construction number U-value (Btuh/tz°F) Or HTM (Btuh/ft) Area (ft) or perimeter (ft) Load (Btuh) Area (M or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 Blk Wall, Stucco Ext Impact 0.109 0.330 ne ne 0.00 0.00 0.00 0.00 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 Impact 1.080 ne 0.00. 0.00 0. 0 0 0 0_ 0 0 0 11 WI L-G Frm Wall, Stucco Ext Impact0.280 0.089 ne ne 2.40 8:12 1.53 16.38 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W L_G BIk Wall, Stucco Ext Impact. 0.109 0.330 "se se 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 " . 0 0 0 0 0 0 0. W Fnn Wall, Stucco Ext 0.083 se 2A0 1.53 0 0 0 0 0 0 0 0 -- L--G Impact0330 Blk Wall, Stucco Ext 0.109 se SN 0.00 0.00 0.00 0.00 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 W Impact Impact ' 0.330 1.060 1.080 sw sw sw 0.00 0.00 0.00 0.00' 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L�Impad �j I-G Frm Wall, Stucco Ext Impact 0.083 0.330 sN sw 2AO 9.57 1.53 16.18 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impad Blk Wall,`Stucoo Ext Impact'. Impact Impact„ Fbrgls Door 0.330 0.169 0200 0.330 0.330 0.127 sw nw nW, nw nvv : "tiv✓. 9.57 0.00 0.00 0.00 0.00 0.00 16.90 0.00 0.'00 0.00 0.0o 0.00 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 „ 0 0 0_ 0 0 ",0 0 0 0 0 0 0 ' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W W. W Fnn Wall, Stucco Ext Impact. 0.083 0.330 nw nw 2AO 9.57 1.53 17.60 0 0 0 0 0 0 0 0 54 0 54 0 130 0 83 0 P Fnn Wall,10 Gyp B, 0 09,4 - 0,00 0.00 0 0 D 0 0 0 0 0 C F AtbG Metal Roof, R , On Grade Depth, Tile . 0.034 0.989 - - ,. 0,99 0.00 1.46 0.00 50 0 50 0 50 0 73 0 4.2 . 0 42 0 42 0 61 0 F On Grade Depth, Tile 6.989 0.o0 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -3 -7 Envelope loss/gain 50 71 171 138 12 a) Infiltration 0 0 144 44 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliancesuother 0 0 Subtotal (lines 6 to 13) 50 71 315 182 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -50 -71 0 0 14 Subtotal 0 0 315 182 15 Dud loads 41% 44%1 0 0 41% 44%1 1301 80 FTTotal room load 0 0 445 262 Ajr required (cfm) 0 0 24 13 Calculations EIDDroved bvACCAto meet all requirements of Manual J 8th Ed. -Fid- wrigFmtssoft" 2020-Deo-0818:38:49 Right -Suite@ Universal 2021 21.0.02 RSU27054 Page 13 ACCA asnents\Wrigttsoft HVAC\7466 Legends Dr MKS.nQ Calc= MJ8 Front Door faces: NE Air Calcs, LLC Right-JO Worksheet Zone 2 Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa 1 Room name WIC 4 2 Exposed wall 8.0 It 3 Room height 9.0 It heat/cool 4 Room dimensions 8.0 x 5.0 It 5 Room area 40.0 ftz Ty Construction U-value Or HTM Area (q Load Area Load number (Btuh/ft;°F) (Btu or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W ` Blk Wall, Stucco Eid Impact - Impact 0.109 0.330 1.060 he .ne . ne. 0.00 0.00 0.00 0.00 0.00 `0,00 0 10 0 0 01 0 0 0 0 0 0 0 _ W Frm Wall, Stucco Ext 0.083 ne 2A0 1.53 72 72 173 110 11 L_G Impact 0.280 ne 8.12 16.38 0 0 0 0 W. Blk Wall, Stucco E)d, • 0.109 se 0.00 0.00 0 0 0 0 L-G Impact • . 0.330 'se 0.00 O.OD - 0 0 01 0 fW �--G Fnn Wall, Stucco E)d 0.083 se 2AO 1.53 0 0 0 0 Impact. 0.330 se 0.00 0.00 0 0 0 0 fW - _ __ Blk Wall, Stucco E)d Impact Impact 0.109 0.330 1.060 sw sw sw 0.00 0.00 0.00 . 0:00 0:00 0.00 0 0 0 0 0 , 0 0 0 0 . ` 0 0 0 Impad 1,080 sw' 0.00 0.00 ,. 0 0, 0 0 W Frm Wall, Stu000 Ext 0.083 sw 2AO 1.53 0 0 0 0 Impact 0.330 sw 9.57 16.18 0 0 0 0 Impact 0.330 sv 9.57 16.90 0 0 0 0 1N Blk,Wall, Stucco E)d Impad 6.109 0290 nw nw, 0.00 0,00 0.00 0.00 0 0 0 0 0 0 0 b Impact `0.330 nw 0.00 0.00 0 0 0 0 9 Impad Fbrgls Door ; 0.330 0.127 nw ' nw 0.00 0:00 '0.00 0:00 0 0 0 0 0 0 0 0 �j Frm Wall, Stu000 Ext 0.083 nw 2.40 1.53 0 0 0 0 Impact 0.330 nw 9.57 17.60 0 0 0 0 --G P Frrn Wall, 10Gyp13 0.094 - ono 0.00 0 0 0 0 C At6c Metal Roof, R 0;034 - 0.99 1.46 40 40 40 59 F On Grade Depth, Tile Ob89 - 0.00 0.00 9 0 . 0 0 F On Grade Depth, Tile 0.989 - 0.00 0.00 0 0 0 0 6 c) AED excursion -8 Envelope loss(gain 212 161 12 a) Infiltration 192 59 b) Room ventilation 0 0 13 Internal gains: Oooupants@ 230 0 0 Applianceslother 0 Subtotal (lines 6 to 13) 404 220 Less extemalload 0 0 Less transfer 0 0 Redistribution 11 15 14 Subtotal 415 235 15 Dud loads 41% 44% 171 104 Total room load 585 339 Air required (dim) 31 16 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -FP- 2020-Deo•0818:38:49 �� � Right -Suite® Universal 2021 21.0.02 RSU27054 Page 14 cuments\Wrightsoft HVACV466 Legends Dr MKS.rup Calc= MJ8 Front Door faces: NE Air CaIcs, LLC Duct System Summary ate: 1388 c801, 2020 Zone 1 By: Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlyme@aircalcs.com Project• • For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.60 in H2O 0 in H2O 0.60 in H2O 0.515 / 0.085 in H2O 0.102 in/100ft 1867 chi 591 ft Cooling 0.60 in H2O 0 in H2O 0.60 in H2O 0.515/0.085 in H2O 0.102 in/100ft 1867 cfin Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Cabana h 2744 143 65 0.102 8.0 Ox 0 VIFx 97.7 410.0 st8 Dining Room h 2606 136 89 0.218 7.0 Ox 0 VIFx 31.8 205.0 st3 Kitchen c 2141 61 128 0.109 7.0 Ox 0 VIFx 68.3 405.0 st8 Kitchen -A c 2141 61 128 0.109 7.0 Ox 0 VIFx 69.8 405.0 st8 Laundry h 520 27 12 0.222 4.0 Ox 0 VIFx 26.7 205.0 st3 M Bath h 3741 195 104 0.222 8.0 Ox 0 VIFx 27.5 205.0 st3 M WIC h 2382 124 52 0.226 7.0 Ox 0 VIFx 23.5 205.0 st3 Master Bedroom c 5976 229 358 0.144 12.0 Ox 0 VIFx 51.8 305.0 st7 Master Bedroom -A c 5976 229 358 0.143 12.0 Ox 0 VIFx 55.1 305.0 st7 Open To Below h 4973 259 235 0.157 9.0 Ox 0 VIFx 69.3 260.0 St6 Open To Below -A h 4973 259 235 0.154 9.0 Ox 0 VIFx 74.4 260.0 St6 Open To Below-B h 4973 259 235 0.154 9.0 Ox 0 VIFx 75.7 260.0 St6 Open To Below•D h 4973 259 235 0.152 9.0 Ox 0 VIFx 80.1 260.0 st6 Wtrclst c 84 2 5 0.144 4.0 Ox0 VIFx 53.9 305.0 st7 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st6 PeakAVF 1034 940 0.152 741 16.0 0 x 0 VinlFlx st2 st2 PeakAVF 1034 940 0.152 741 16.0 0 x 0 VinIFIX st8 PeakAVF 265 322 0.102 410 12.0 0 x 0 VinIFIX st7 st7 PeakAVF 725 1043 0.102 590 18.0 0 x 0 VInIFIX st3 st3 PeakAVF 1206 1300 0.102 736 18.0 0 x 0 VinIFIX BoWltalic values have been manually overridden Wrlghtsoft- 2020-Deo-0818:38:51 Right -Suite® Universal 2021 21.0.02 RSU27054 Page 1 aurtents\WrigttsoftHVAC\7466 Legends Dr MKS.r p Calc= MJ8 Frort Door faces: NE Return Branch Detail Table. Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) M FR (fpm) (in) (in) Opening (in) Matl Trunk rb6 Ox 0 643 897 83.2 0.102 507 18.0 Ox 0 VIFx rt2 rb3 Ox 0 1597 1343 70.6 0.120 508 24.0 Ox 0 VIFx r12 Name Trunk Type Htg (Cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt2 PeakAVF 2240 2240 0.102 1027 20.0 0 x 0 VinIFIX Bolditalic values have been manually overridden wrightsoft ^�• 1 e4•/no4Nbe Na/�axrry Compury Rigft-Sute®Universal 2021 21.0.02 RSU27054 ,ACC,k ...cments\Wrigttsoft HVAC\7466'Legends Dr MKS.np Calc= MJ8 Front Door faces: NE 2020-Dec-08 18:38:51 Page 2 Air Calcs, LLC Duct System Summary Zone 2 Air Calm, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com For: External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.517 / 0.183 in H2O 0.112 in/100ft 600 cfm 626 ft Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.517 / 0.183 in H2O 0.112 in/100ft 600 cfm Name Design (Btuh) Htg (cim) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bathe h 495 32 18 0.219 4.0 Ox 0 VIFx 26.5 210.0 st1 Bath c 314 14 18 0.227 4.0 Ox 0 VIFx 17.5 210.0 st1 Bed 2 h 2712 173 162 0.217 8.0 Ox 0 VIFx 28.8 210.0 st1 Bed 3 h 2589 165 162 0.213 7.0 Ox 0 VIFx 33.3 210.0 st1 Bed 4 h 2151 137 127 0.113 7.0 Ox 0 VIFx 48.5 410.0 st5 Loft c 1702 67 99 0.150 6.0 Ox 0 VIFx 34.4 310.0 st4 Loft -A c 1702 67 99 0.150 6.0 Ox 0 VIFx 35.5 310.0 st4 wlc 3 h 445 28 15 0.220 4.0 Ox 0 VIFx 25.1 210.0 st1 WIC h 585 37 20 0.112 4.0 Ox0 VIFx 52.6 410.0 st5 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st5 PeakAVF 174 146 0.112 500 8.0 0 x 0 VinIFIX st4 st4 PeakAVF 308 345 0.112 439 12.0 0 x 0 VinIFIX st1 st1 PeakAVF 720 720 0.112 674 14.0 0 x 0 VinIFIX wr ghtsoft- ,..•,�•. •m�. Right-Sute®Universal202121.0.02RSU27054 ACCK cLoenhs\WrightsoftHVAC\7466LegendsDrMKS.np Calc=MJB Front Door faces: NE 2020-Dec•08 18:38:51 Page 3 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (Cfm) (Cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb7 Ox 0 148 217 161.9 0.113 491 9.0 Ox 0 VIFx rt1 rb2 Ox 0 206 164 159.6 0.114 466 9.0 Ox 0 VIFx rt1 rb1 Ox 0 173 162 163.3 0.112 391 9.0 Ox 0 VIFx rt1 rb5 Ox 0 193 177 1 151.1 0.121 438 9.0 Ox 0 VIFx I rt1 Return Trunk Detail Table Name Trunk Type Htg (Cfm) Cig (Cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 720 720 0.112 516 16.0 0 x 0 VinIFIX wrightsoft- / � 1o•�k�>�,� M�m�.m RigFfiSute®Universal 202121.0.02RSU27054 Cumenls\Wrigftsoft HVAC\7466 Legends Dr MKS.np Calc= MJ8 Front Door faces: NE 2020-Deo•08 18:38:51 Page 4 Manual S Compliance Report Job: 1388 Air Calcs, LLC p Date: Dec 01, 2020 Zone 1 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlyrm@aircalcs.com • • • For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Design Conditions Outdoor design DB: 90.4°F Outdoor design WB: 77.4°F Indoor design DB: 75.0°F Indoor RH: 50% Sensible gain: 38421 Btuh Latent gain: 12447 Btuh Total gain: 50868 Btuh Estimated airflow: 1867 cfirn Entering coil DB: 76.6°F Entering coil WB: 63.7°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1-059-230A**+CBA27UHE-060-230*++TDR Actual airflow: 1867 cfm Sensible capacity: 39200 Btuh 102% of load Latent capacity: 16800 Btuh 135% of load Total capacity: 56000 Btuh 110% of load SHR: 70% Design Conditions Outdoor design DB: 41.0°F Heat loss: 45066 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1867 ctin Output capacity: 12.8 kW 97% of load Meets all requirements ofACCA Manual S. -- wrightsoft� w« amMM Right-SLAe®Universal202121.0.02RSU27054 cunenlss\Wrigltsoft HVAC\7466 Legends Dr MKS.rLQ Calc= MJ8 Front Door faces: NE Entering coil DB: 68.5°F Temp. rise: 50 °F 2020-Dec-08 18:38:51 Page 1 Air CaIcs, LLC Manual S Compliance Report Zone 2 Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com For: Legacy IV Model, MKS Construction 7466 Legends Dr, Port St Lucie, FL 34986 Design Conditions Job: 1388 Date: Dec 01, 2020 By: Vicki Lynne Nisa Outdoor design DB: 90.4°F Sensible gain: 12957 Btuh Entering coil DB: 77.3°F Outdoor design WB: 77.4°F Latent gain: 4639 Btuh Entering coil WB: 64.4°F Indoor design DB: 75.0°F Total gain: 17595 Btuh Indoor RH: 50% Estimated airflow: 600 cfm Manufacturer's Performance Data atActual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1S018-230A**+CBA27UHE-018-230*++TDR Actual airflow: 600 dim Sensible capacity: 12600 Btuh 97% of load Latent capacity: 5400 Btuh 116% of load Total capacity: 18000 Btuh 102% of load SHR: 70% Design Conditions Outdoor design DB: 41.0°F Heat loss: 12468 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elec strip Manufacturer: Model: Actual airflow: 600 ch Output capacity: 3.8 kW 103% of load Meets all requirements ofACCA Manual S. Entering coil DB: 67.6°F Temp. rise: 50 °F v -F' Wrightsoft- 2020-Deo-0818:38.51 M:* . ,.-'-, -', Right-SUte®Universal 202121.0.02RSU27054 Page 2 ACCA a anents\WrigHsoft HVAC\7466 Legends Dr MKS.nQ Calc= MJ8 Front Door faces: NE Level 2 30Wx9IH 30WxSl'H - x8".a, 411wx3PH 491Mz30H . ° 1730rm° . Clst • • 12x12 ex4 • • Warm173 99cfm • ti t 5'e'Wx6O'H 12x42 •. .) . ,r _ / • ^ . 259 cfdi . -. mom. _• Bed a Loft;. . ,. ..., � tWr 1axr . g; . . , • .' SX8" "` • 2r7'dm' Bath 3 . 3t' 12x12.� a°. - ax4 259cfm \ .. r tactm'u 9 : 28cfm1 „7; �T 12x12— pfm .. ... .. ... A. .peen ToBelow 5IIWr59'H y. ' e 7 Bed 3' ... ;. .. .... .. .. 12x$"mod Linen "_ 12x81. •12><12 .- 137cim i 165ctm. WC 4 . .. 92x12 ' -',12x12 .. -259cfm,- 2.59eft ,e 216 chn `8 4'° .. , _ .. :. .. .. . 4vy ..i., ,, - .. ,37C6n 16' sEp i15er 5awx57H Bed Job #: 1388 Performed by Vicki Lynne Nisa for: Legacy IV Model 7466 Legends Dr Port St Lucie, FL 34986 ISUWx52'H I Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com 13UWX57H I Scale: 1 : 141 Page 1 Right -Suite® Universal 2021 21.0.02 RSU27054 2020-Dec.08 18:37:55 oft HVAC\7466 Legends Dr MKS.rup Job #: 1388 Performed by Vicki Lynne Nisa for: Legacy N Model 7466 Legends Dr Port St Lucie, FL 34986 Level 7 Air Caics, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircaics.com Scale: 1 : 141 Page 2 RightSuite® Universal 2021 21.0.02 RSU27054 2020-Dec-0818:37:56 ...oft WACX7466 Legends Dr MKS.rup