FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: FP-TANAGER-20
Builder Name: GHO HOMES
Street: 3712 TANAGER PL
Permit Office: ST. LUCIE COUNTY
City, State, Zip: FORT PIERCE, FL, 34983
Permit Number.
Owner:
Jurisdiction:
Design Location: FL, ST LUCIE_CO INTL
County: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans)
9. Wall Types (2321.7 sgft.)
Insulation Area
2. Single family or multiple family Single-family
a. Concrete Block - Ext Insul, Exterior
R=4.1 2039.30 ft2
b. Frame - Wood, Adjacent
R=11.0 282.33 ft2
3. Number of units, if multiple family 1
c. N/A
R= ft2
4. Number of Bedrooms 3
d. NIA
R= ft2
5. Is this a worst case? No
10. Ceiling Types (2443.0 sgft.)
Insulation Area
a. Under Attic (Vented)
R=40.0 2443.00 ft
6. Conditioned floor area above grade (ft2) 2443
b. N/A
R= ft2
Conditioned floor area below grade (ft2) 0
c. NIA
R= ft2
11. Ducts
R ft2
7. Windows(330.3 sgft.) Description Area
a. Sup: Attic, Ret: Attic, AH: Mein
6 664
a. U-Factor: Dbl, U=0.62 330.33 ft2
SHGC: SHGC=0.26
b. U-Factor. N/A ft2
12. Cooling systems
kBtu/hr Efficiency
SHGC:
a. Central Unit
56.0 SEER:16.00
c. U-Factor: N/A ft2
SHGC:
13. Heating systems
kBtu/hr Efficiency
d. U-Factor: N/A ft2
a. Electric Strip Heat
30.1 COP:1.00
SHGC:
Area Weighted Average Overhang Depth: 0.000 ft.
Area Weighted Average SHGC: 0.260
14. Hot water systems
a. Propane
Cap: 50 gallons
8. Floor Types (2443.0 sgft.) Insulation Area
EF: 0.900
a. Slab -On -Grade Edge Insulation R=0.0 2443.00 ft2
b. Conservation features
b. WA R= ft2
Norte
c. N/A R= ft2
15. Credits
Pstat
Glass/Floor Area: 0.135 Total Proposed Modified Loads: 67.99
PASS
Total Baseline Loads: 77.55
I hereby certify that the plans and specifications covered by
Review of the plans and
S-r
this calculation are in compliance with the Florida Energy
speciflcatons covered by this
O�ZKE
Code. v
calculation indicates compliance
with the Florida Energy Code.
PREPARED BY: _
Before construction is completed
l "
--- -
DATE: .._... 7/9/2Q20 __
this building will be inspected for
6, �i
compliance with Section 553.908
, °
s is in compliance
I hereby certify that7Code.
Florida Statutes.
with the Florida
f''Op WE
OWNER/AGENT:_.
GOFFICIAL: . -..DATE:
- . "7 .. Zd.
DATE:
I -
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifles as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402A.1.2).
REVIEWF-D FO CE
000E COMPLIANCE
cc 1,UC1IE COUN VT
719/2020 2:44 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017);;Mpliant Software , Page 1 of 4
' FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title:
FP-TANAGER-20
Bedrooms: 3
Address Type: Street Address
Building Type:
User
Conditioned Area: 2443
Lot #
Owner Name:
Total Stoles: 1
Block/Subdivision:
# of Units:
1
Worst Case: No
PlatBook:
Builder Name:
GHO HOMES
Rotate Angle: 0
Street: 3712 TANAGER PL
Permit Office:
ST. LUCIE COUNTY
Cross Ventilation: No
County: St. Lucie
Jurisdiction:
Whole House Fan: No
City, State, Zip: FORT PIERCE,
Family Type:
Single-family
FL, 34983
New/Existing:
New (From Plans)
Comment:
CLIMATE
/
Design Temp
lnt Design Temp Heating Design Daily Temp
V Design Location
TMY Site 97.5 % 2.5 %
Winter Summer Degree Days Molsture Range
FL, ST_LUCIE CO_INTL FL VERO_BEACH_MUNI 39 90
70 75 299 58 Medium
BLOCKS
Number
Name
Area Volume
1
Blockl
2443 23697.1
SPACES
Number
Name
Area Volume Kitchen Occupants
Bedrooms InfilID Finished Cooled Heated
1
Main
2443 23597.1 Yes 4
3 1 Yes Yes Yes
FLOORS
_ #
FloorType_
Space Perimeter R Value _
Area _ Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio Main 211 ft 0
2443 ft2 — 0 0 1
ROOF
/
Roof Gable Roof
Rad Solar SA Emitt Emitt Deck Pitch
V #
Type
Materials Area Area Color
Barr Absor, Tested Tested Insui. (deg)
1
Hip Composition shingles 2732 ft' 0 ft' Medium
N 0.4 N 0.9 No 0 26.6
ATTIC
/
V #
Type
Ventilation Vent Ratio (1 in)
Area RBS IRCC
1
Full attic
Vented 150 2443 fN N N
CEILING
_ _ _ #
_ Ceiling Type_
Space R-Value — Ins Type Area Framing Free Truss Type
1
Under Attic (Vented)
Main 40 Blown
2443 R2 0.1 Wood
7/9/2020 2:44 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 4
' Ff1RM Rdf1F,-9nl7 IMPI IT RI IMMARY f_NFMCI IST RFPCIRT
WALLS
Cavity Width Height
Sheathing Framing Solar
Below
VAdjacent
_.. #
Omt
To.. Wall Type _ .- __-
Space R.Value_ .. -Ft --An Ft In -_
Area- -
_R-Vatue-Fraction..-Absor. GradeJ.-
1
N
Exterior Concrete Block - Ext Insul
Main
4.1 1 5 9
4
13.2 ft'
0
0 0.3
0
_ 2
NE
Exterior Concrete Block - Ext Insul
Main
4.1 61 11 9
4
577.9 ft'
0
0 0.3
0
3
SE
Exterior Concrete Block - Ext Insul
Main
4.1 54 10 9
4
511,8 ft'
0
0 0.3
0
4
SW
Exterior Concrete Block - Ext Insul
Main
4.1 39 8 9
4
370.2 ft'
0
0 0.3
0
5
NW
Exterior Concrete Block - Ext Insul
Main
4.1 60 8 9
4
566.2 ft'
0
0 0.3
0
_ 6
-
Garage Frame - Wood
Main
11 30 3 9
4
282.3 ft'
0
0.25 0.3
0
DOORS
#
Omt Door Type Space
Storms
U Value
Width
Height
Area
Ft
In
Ft In
1
SW Wood Main
None
.39
3
8
24 ft'
WINDOWS
Orientation shown is the entered, Proposed orientation.
/
Wall
Overhang
#
Omt ID Frame Panes NFRC
U-Factor SH_GC_ Imp
Area
Depth
Separation
Int Shade
Screening
1
no 2 Metal Double (Clear)
Yes
0.62 0.26 N
43.3 ft'
0 ft 0 in
0 ft 0 in
None
None
2
ne 2 Metal Double (Clear)
Yes
0.62 0.26 N
128.0 ft'
0 It 0 in
0 ft 0 in
None
None
3
se 3 Metal Double (Clear)
Yes
0.62 0.26 N
14.0 ft'
0 ft 0 in
0 ft 0 in
None
None
4
se 3 Metal Double (Clear)
Yes
0.62 0.26 N
30.0 ft'
0 ft 0 in
0 ft 0 in
None
None
5
sw 4 Metal Double (Clear)
Yes
0.62 0.26 N
72.0 ft'
0 ft 0 in
0 It 0 in
None
None
6
sw 4 Metal Double (Clear)
Yes
0.62 0.26 N
8.0 It,
0 ft 0 in
0 ft 0 in
None
None
7
sw 4 Metal Double (Clear)
Yes
0.62 0.26 N
16.0 ft'
0 ft 0 in
0 It 0 in
None
None
8
nw 5 Metal Double (Clear)
Yes
0.62 0.26 N
12.0 ft'
0 ft 0 In
0 ft 0 in
None
None
9
NW 5 Metal Double (Clear)
Yes
0.62 0.26 N
7.0 ft'
0 ft 0 in
0 ft 0 In
None
None
GARAGE
#
Floor Area Ceiling Area
Exposed Wall Perimeter
Avg. Wall Height
Exposed Wall Insulation
1
661 ft' 661 ft'
64 It
9.3 ft
1
INFILTRATION
#
Scope
Method SLA
CFM 50 Et.A EgLA
ACH
ACH 50
1 Wholehouse Proposed ACH(50) .000431
2764.7 151.78 285.44
.1615
7
HEATING SYSTEM
#
System Type Subtype
Speed Efficiency
_ Capacity
-
_ Block
Ducts
1
Electric Strip Heat/ None
COPA
30.07 kBtu/hr
1
sys#1
7/9/2020 2:44 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 4
' FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
COOLING SYSTEM
# System Type
Subtype
Subtype Efficiency
Capacity
—Air Flow _SHR
Block_
Ducts
1 Central Unit/
Split
Singl SEER: 16
56 kBtu/hr
cfm
0.7
1
sys#1
HOT WATER SYSTEM
V. # System Type
SubType
Location
EF_ Cap
Use
• SetPnt —
_ Conservation
1 Propane
None
Garage
0.9 50 gal 60.9 gal
120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector
Storage
Cart # Company Name
System Model # Collector Model
# Area
Volume
FEF
None None
ft2
DUCTS
/ — Supply ---
— Return—
Air
CFM 25 CFM25
HVAC #
V # Location R-Value Area
Location
Area Leakage Type
Handler
TOT OUT
ON
RLF
Heat Cool
1 Attic
6 664 ft2
Attic
362 W Default Leakage
Main
(Default) (Default)
1 1
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
Heating Jan Feb
Mar
Apr I
Apr
j M:, n Jut
JXJ
May JuJul
n Aug
Aug
�j Sep
Sep
Oct
Oct(
Nov
Nov
H Dee
Dec
Venting Jan Feb
X Mar
n
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2 3
4 5 6
7
8 9
10
11
12
Cooling (WD) AM
78
78 78
78 78 78
78
78 80
80
80
80
PM
80
80 78
78 78 78
78
78 78
78
78
78
Cooling (WEH) AM
78
78 78
78 78 78
78
78 78
78
78
78
PM
78
78 78
78 78 78
78
78 78
78
78
78
Heating (WD) AM
66
66 66
66 66 68
68
68 68
68
68
68
PM
68
68 68
68 68 68
66
68 68
68
66
66
Heating (WEH) AM
66
66 66
66 66 68
68
68 68
68
68
68
PM
68
68 68
68 68 68
68
68 68
68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction Space
Default 8 Ibs/s .ft,
0 112
Oft
0.3
Main
719/2020 2:44 PM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 4
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 88
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition
1. New (From Plans)
12. Ducts, location & insulation level
a) Supply ducts R
6.0
2. Single-family or multiple -family
2. Single-family
b) Return ducts R
6.0
c) AHU location
Main
3. No. of units (if multiple=family)
3. 1
4. Number of bedrooms
4. 3
13. Cooling system: Capacity
56.0
a) Split system SEER
16.0
5. Is this a worst case? (yes/no)
5. No
b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area (sq. ft.)
6. 2443
d) Room uniVPTAC EER
e) Other
7. Windows, type and area
a) U-factor:(weighted average)
7a. 0.620
b) Solar Heat Gain Coefficient (SHGC)
7b. 0.260
14. Heating system: Capacity
30.1
c) Area
7c. 330.3
a) Split system heat pump HSPF
b) Single package heat pump HSPF
8. Skylights
c) Electric resistance COP
1.0
a) U-factor:(weighted average)
8a. NA
d) Gas furnace, natural gas AFUE
b) Solar Heat Gain Coefficient (SHGC)
8b. NA
e) Gas furnace, LPG AFUE
f) Other
9. Floor type, insulation level:.
a) Slab -on -grade (R-value)
9a. 0.0
b) Wood,.raised (R-value)
9b.
15. Water heating system
c) Concrete, raised (R-value)
9c.
a) Electric resistance EF
b) Gas fired, natural gas EF
10. Wall type and insulation:
c) Gas fired, LPG EF
0.90
A. Exterior:
d) Solar system with tank EF
1. Wood frame (Insulation R-value)
10A1.
e) Dedicated heat pump with tank EF
2. Masonry (Insulation R-value)
10A2. 4.1
f) Heat recovery unit HeatRec%o
B. Adjacent:
g).Other
1. Wood frame (Insulation R-value)
10131. 11.0
2. Masonry (Insulation R-value)
1062.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level
a) Ceiling fans
a) Under attic
11a. 40.0
b) Cross ventilation
No
b) Single assembly
11b.
c) Whole house fan
No
c) Knee walls/skylight walls
11c.
d) Multizone cooling credit
d) Radiant barrier installed
11d. No
e) Multizone heating credit
f) Programmable thermostat
Yes
"Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has compli d with the
Florida Building Code, Energy
Conservation, through the above energy
saving features which will be'instdiled (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed bas don installed code compliant features.
Builder Signature:
Date: :7/q / 7,.D 2,0
Address of New Home: 3712 TAN OERPI
City/FL Zip: FORT PIERCE, FL 34983
7/9/2020 2:44:44 PM EnergyGauge®
USA 6.0.04 (Rev. 1) - FlaRes2017
FBC 6th Edition (2017) Compliant Software
Page 1 of 1
-- wrightsoft. Load Short Form
Entire House
Project
For: PSL-TANGER-20
3712 TANAGER PL, FORT PIERCE, FL 34983
Job:
Date: Jun 30, 2020
By:
Design -Information
Htg Clg Infiltration
Outsidedb (OF) 43 91 Method Simplified
Ins ide'db(OF) 70 72 Construction quality Semi -tight
Design TD (°F) 27 19 Fireplaces 0
Daily range - L.
Inside humidity (%) 30 50
Moisture difference (gr/lb) 0 65
HEATING EQUIPMENT
Make
Trade
Model
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
100 EFF
8.8 kW
30073 Btuh
14 OF
1900 cfm
0.062 cfm/Btuh
0 in H2O
COOLING EQUIPMENT
Make Lennox
Trade 16ACX SERIES
Cond 16ACX=060-230A
Coil CBA25UHV-060-230
AHRI ref 202540573
Efficiency 12.0 EER,
16 SEER
Sensible cooling
39200 Btuh
Latent cooling
16800 Btuh
Total cooling
56000 Btuh
Actual air flow
1900 cfm
Air flow factor
0.049 cfm/Btuh
Static pressure
0 in H2O
Load sensible heat ratio
0.71
ROOM NAME
Area
(ft2)
Htg load
(Btuh)
Clg load
(Btuh)
Htg'AVF
(cfm)
Clg AVF
(cfm)
MASTER SUITE
305
4815
4562
297
222
HIS WIC
40
681
464
42
23
MASTER BATH
166
1828
2119
113
103
HER WIC
74
63
259
4
13
DEN
201
4278
4506
263
219
FOYER
69
1502
1943
93
95
DINING
175
2567
3489
158
170
MECH
24
375
627
23
31
UTILITY
68
123
791
8
38
BATH 2
58
1020
924
63
45
BED 2
180
1757
2383
108
116
BED 3
178
1803
2398
111
117
BATH 3
58
1698
1132
105
55
NOOK
73
2277
2103
140
102
KITCHEN
l_1E5C AT M R A
2118
AAG
655
CAOM
2338
OCGn
40
13413
114
AAC
'Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
r 2020Jul-07 12:05:11
-+ - wrightSOft' Right-SuiteO Universal2012 12.1.05 RSU02818 Page 1
'�vCil1. C:1UserslJasontDocuments\WrightsoR WACIPSL-TANAGER-20.rup Calc = MJ8 Front Door faces: SW
U I ILI I'Y I71HLL
PANTRY
fL
39
Lt55
33,
z1v
194
-10
2
19+
9
Entire House
2442
30848
39072
1900
1900
Other equip loads
0
0
Equip. @ 0.95 RSM
37313
Latent cooling
16066
Irr% Al Q
I nAAn
I 9AOAD.
I G,],]7A
I AAAA
I AAA
V IMI-Q G'f'TL JVV'tV JJJ(.7 1Q VV. I. aVV
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020Jul-07 12:05:11
..:ij:, + wrightSOft` Right -Suite) Universal 201212.1.05 RSU02818 Page
ACCk C:\UsersUasonlDocumentslWrighlsoft HVAMPSI.-TANAGER•20.rup Calo= MJ8 Front Door faces: SW
+�+ wrightsoft° Project Summary
Entire House
For: PSL-TANGER-20
3712 TANAGER PL, FORT PIERCE, FL 34983
Notes:
Design Information
Weather: Vero Beach Municipal AP, FL,, US
Job:
Date: Jun 30, 2020
By:
Winter Design Conditions Summer Design Conditions
Outside db 43 OF Outside db 91 OF
Inside db 70 OF Inside db 72 OF
Design TD 27 OF Design TD 19 OF
Daily range L
Relative humidity 50 %
Moisture difference 65 gr/lb
Heating Summary -
Structure 25219 Btuh
Ducts 5620 Btuh
Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh
Piping 0 Btuh
Equipment load 30848 Btuh
Infiltration
Method
Construction quality
Fireplaces
Simplified
Semi -tight
0
Heating Cooling
Area (ft?)
2442 2442
Volume (fP)
23785 23785
Air changes/hour
0.22 0.11
Equiv. AVF (cfm)
87 44
Heating Equipment Summary
Make
Trade
Model
AHRI ref
Efficiency
100 EFF
Heating input
8.8
kW
Heating output
30073
Btuh
Temperature rise
14
OF
Actual air flow
1900
cfm
Air flow factor
0.062
cfm/Btuh
Static pressure
0
in H2O
Space thermostat
Sensible Cooling Equipment Load Sizing
Structure 29140 Btuh
Ducts 9931 Btuh
Central vent (0 cfm) 0 Btuh
Blower 0 Btuh
Use manufacturer's data n
Rate/swing multiplier 0.95
Equipment sensible load 37313 Btuh
Latent Cooling Equipment Load Sizing
Structure
13379
Btuh
Ducts
2687
Btuh
Central vent (0 cfm)
0
Btuh
Equipment.latent load
16066
Btuh
Equipment total load
53379
Btuh
Req. total capacity at 0.70 SHR
4.4
ton
Cooling Equipment Summary
Make Lennox
Trade 16ACX SERIES
Cond 16ACX-060-230A
Coil CBA25UHV-060-230
AHRI ref 202540673
Efficiency 12.0 EER,
16 SEER
Sensible cooling
39200
Btuh
Latent cooling
16800
Btuh
Total cooling
56000
Btuh
Actual air flow
1900
cfm
Air flow factor
0.049 •cfm/Btuh
Static pressure
0
in H2O
Load -sensible heat ratio
0.71
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wri htsOft' 2020-Jul-0712:05:11
g Right-Suile®Universal 2012 12.1,05 RSU02010 Page 1
C:1UsersXJason%DocumentslWrighlsoft 1-1VAMPSL-TANAGER-20.rup Calc = MJB Front Door faces: SW
GHO HOME5
Ff-TANAGEK-20
3712 TANAGER P L
FORT PIERCE, FL 34965