HomeMy WebLinkAboutAPPROVED FL Polyglass_2-3Ply_FlatRoof2/3/2021 Florida Building Code Online
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqu8obl%2fIZm6TpmvJBPDlAvtKGsHR4x0B30r8qfZppTJHg%3d%3d 1/2
BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications Contact Us BCIS Site Map Links Search
Product Approval
USER: Public User
Product Approval Menu > Product or Application Search > Application List > Application Detail
FL #FL16717-R10
Application Type Revision
Code Version 2020
Application Status Approved
Comments
Archived
Product Manufacturer POLYGLASS USA
Address/Phone/Email 1111 W. Newport Center Drive
Deerfield Beach, FL 33442
(954) 233-1330 Ext 242
malpert@polyglass.com
Authorized Signature Maury Alpert
malpert@polyglass.com
Technical Representative TECH REP
Address/Phone/Email 1111 West Newport Center Drive
Deerfield Beach, FL 33442
(866) 802-8017
uspolyglasstechnical@polyglass.com
Quality Assurance Representative QA REP
Address/Phone/Email 1111 West Newport Center Drive
Deerfield Beach, FL 33442
(888) 410-1375
uspolyglasstechnical@polyglass.com
Category Roofing
Subcategory Modified Bitumen Roof System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed the
Evaluation Report
Robert Nieminen
Florida License PE-59166
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 10/21/2022
Validated By John W. Knezevich, PE
Validation Checklist - Hardcopy Received
Certificate of Independence FL16717_R10_COI_2020_01_COI_NIEMINEN.pdf
Referenced Standard and Year (of Standard)Standard Year
ASTM D2178 2015
ASTM D4601 2012
ASTM D4897 2009
ASTM D6162 2015
ASTM D6163 2015
ASTM D6164 2011
ASTM D6222 2011
2/3/2021 Florida Building Code Online
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqu8obl%2fIZm6TpmvJBPDlAvtKGsHR4x0B30r8qfZppTJHg%3d%3d 2/2
ASTM D6509 2015
TAS 110 2000
TAS 114 2011
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
Date Submitted 10/02/2020
Date Validated 10/04/2020
Date Pending FBC Approval 10/12/2020
Date Approved 12/16/2020
Summary of Products
FL #Model, Number or
Name
Description
16717.1 Polyglass Modified
Bitumen Roof Systems
APP and SBS modified bitumen roof systems
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: No
Impact Resistant: N/A
Design Pressure: +N/A/-622.5
Other: 1.) The design pressure in this
application pertains to one system. Refer
to ER Appendix for all systems and
maximum design pressures. 2.) Refer to
ER Section 5 for Limits of Use. 3.) Refer
to FL1654 for non-HVHZ jurisdictions.
Installation Instructions
FL16717_R10_II_2020_10_01_FINAL_A1_ER_POLYGLASS_MODBIT_HVHZ_FL16717-
R10.pdf
Verified By: Robert Nieminen PE-59166
Created by Independent Third Party: Yes
Evaluation Reports
FL16717_R10_AE_2020_10_01_FINAL_ER_POLYGLASS_MB_HVHZ_FL16717-R10.pdf
Created by Independent Third Party: Yes
Back Next
Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida. :: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public-records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section 455.275(1),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have one. The emails
provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S., please click here .
Product Approval Accepts:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 1 of 83
APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE
TABLE DECK APPLICATION TYPE DESCRIPTION PAGE
1A Wood New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 6-12
1B Wood New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 12-14
1C Wood New, Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 14
1D Wood New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 15-17
1E Wood New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 17-21
1F Wood New or Reroof (Tear-Off) E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 21-25
1G Wood New, Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 25-32
2A Steel or Structural Concrete New, Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 33-35
2B Steel or Structural Concrete New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 36-40
2C Steel or Structural Concrete New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 41-42
2D Steel or Structural concrete New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Velociflex, Bonded Roof Cover 43-44
3A Structural Concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 45-57
3B Structural Concrete New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 58
4A Lightweight concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 59-63
4B Lightweight concrete New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 64
4C Lightweight concrete New or Reroof (Tear-Off) E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 65-68
5A Cementitious wood fiber Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 69-70
5B Cementitious wood fiber Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 70-71
5C Cementitious wood fiber Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 71
5D Cementitious wood fiber Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 72
5E Cementitious wood fiber Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 72
6A Existing gypsum Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 73-76
6B Existing gypsum New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 77
6C Existing gypsum New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 77
6D Existing gypsum New, Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 77
7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 78-83
7B Various Recover F Non-Insulated, Bonded Roof Cover 83
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 2 of 83
The following notes apply to the systems outlined herein:
1 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC HVHZ requirements to the satisfaction of the Authority Having
Jurisdiction. Deck-attachment details pertain to ‘as-tested’ conditions under Testing Application Standard TAS 114, Appendix J. The table below provides reference to various as-tested deck sub-assemblies and
associated maximum allowable design pressures.
POLYGLASS AS-TESTED DECK ATTACHMENT DETAILS; TAS 114, APPENDIX J
TYPE TESTED SPAN (FT O.C.) TESTED FASTENING TESTED FASTENER SPACING
(INCH O.C.)
HIGHEST AS-TESTED ALLOWABLE
PRESSURE (PSF)
15/32-inch plywood 2 8d ring shank nails 6 -75.0
15/32-inch plywood 2 #10 wood screws 6 -90.0
15/32-inch plywood 2 #10 wood screws 4 -120.0
19/32-inch plywood 2 8d ring shank nails 6 -60.0
19/32-inch plywood 2 #10 wood screws 6 -127.5
22 ga., Type B, Grade 33 steel 6 Tek/5 screws 6 -112.5
22 ga., Type B, Grade 40 steel 6 5/8” puddle welds 6 -97.5
22 ga., Type B, Grade 40 steel 6 Traxx/5 screws with ¾” washers 6 -135.0
2 Unless otherwise noted, fasteners and stress plates shall be as follows. Fasteners shall be of sufficient length for the following engagements:
➢ Wood Deck: Firestone Insulation Fastening Plates with Firestone All-Purpose Fasteners; Firestone Pre-Assembled Fastener and Plate (consisting of 0.196-inch thread diameter fastener with 3-inch
diameter metal plate). Minimum 1-inch plywood penetration or wood plank embedment.
➢ Steel Deck: Firestone Insulation Fastening Plates with Firestone All-Purpose Fasteners or Firestone Heavy-Duty Fasteners; Firestone Pre-Assembled Fastener and Plate (consisting of 0.196-inch
thread diameter fastener with 3-inch diameter metal plate); Firestone Pre-Assembled Heavy-Duty Fastener and Plate (consisting of 0.275-inch thread diameter fastener with 3-inch
diameter metal plate); AP AccuTrac; HD AccuTrac. Minimum 0.75-inch steel penetration and engage the top flute of the steel deck.
➢ Structural Concrete: Firestone Insulation Fastening Plates with Firestone Heavy-Duty Fasteners or Firestone Concrete Drive Fasteners; Firestone Pre-Assembled Heavy-Duty Fastener and Plate (consisting
of 0.275-inch thread diameter fastener with 3-inch diameter metal plate); HD AccuTrac. Minimum 1-inch embedment into pilot hole in accordance with published installation
instructions.
3 Unless otherwise noted, insulation may be any one layer or combination of FBC Approved (Local or Statewide) board(s) that meet FBC HVHZ 1516 and, for foam plastic, FBC Chapter 26, when installed with the
roof cover.
4 If mechanical attachment to the structural deck through lightweight insulating concrete is proposed, field withdrawal resistance testing shall be performed to confirm equivalent or determine enhanced
fastening patterns and density. All testing and fastening design shall be in compliance with Testing Application Standard TA S 105 and Roofing Application Standard RAS 117 and/or RAS 137. Calculations shall
be prepared, signed and sealed by a qualified design professional.
5 Preliminary insulation attachment for System Type D: Minimum four fasteners per 4 x 8 ft board or minimum two fasteners per 4 x 4 ft board.
6 Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer’s published
instructions.
➢ Hot asphalt (HA): Full coverage at 25-30 lbs/square.
➢ DuPont INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c.
➢ H.B. Fuller Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ H.B. Fuller Millennium PG-1 Pump Grade Adhesive (M-PG1): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. Note: OlyBond Green may be used where OlyBond 500 is referenced.
➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive & Sealants Polyset CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c.
➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon-applied adhesive, board joints shall be staggered.
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 3 of 83
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one -half the specified ribbons spacing.
7 Unless otherwise noted, all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following
Maximum Design Pressure (MDP) limitations. In no case shall these values be used to ‘increase’ the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in
the tables, then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table.
➢ H.B. Fuller Millennium One Step Foamable Adhesive (M-OSFA): MDP = -157.5 psf (Min. 0.5-inch thick)
➢ H.B. Fuller Millennium PG-1 Pump Grade Adhesive (M-PG1): MDP = -157.5 psf (Min. 0.5-inch thick)
➢ OMG OlyBond 500 (OB500): MDP = -45.0 psf (Min. 0.5-inch thick Multi-Max FA-3)
➢ OMG OlyBond 500 (OB500): MDP = -187.5 psf (Min. 0.5-inch thick ISO 95+ GL)
➢ OMG OlyBond 500 (OB500): MDP = -315.0 psf (Min. 0.5-inch thick ENRGY 3)
➢ OMG OlyBond 500 (OB500): MDP = -487.5 psf (Min. 0.5-inch thick ACFoam II)
➢ ICP Adhesives & Sealants Polyset CR-20: MDP = -117.5 psf (Min. 1.0-inch thick)
8 Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
9 For mechanically attached components, the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1 PRIME design pressure determined in accordance with FBC HVHZ 1620
or Roofing Application Standard RAS 128. Elevated pressure zones shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria in accordance with
Roofing Application Standard RAS 117 or Roofing Application Standard RAS 137. *This extrapolation is not permitted for systems marked with an asterisk*
10 For assemblies marked with an asterisk*, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational
analysis is permitted for these systems.
11 For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance in accordance with Testing Application Standard TAS 105. A qualified design
professional shall review the data for comparison to the minimum requirements for the system. Should the fastener resistance be less than that required, a revised fastener spacing – prepared, signed and
sealed by a qualified design professional in accordance with Roofing Application Standard RAS 117 or Roofing Application Stan dard RAS 137 – may be submitted to the Building Official for review and
acceptance.
12 Refer to FBC HVHZ 1521 for requirements and limitations regarding recover installations. For bonded insulation or membrane over existing substrates in a re-roof (tear off) or recover installation, the existing
deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance
shall be conducted on mock-ups of the proposed new roof assembly. For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting
project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with Testing Application Standard TAS 124.
13 For Structural Concrete Deck or Recover Applications using System Type C-1, C-2, D-1 or D-2, the insulation is optional. Alternatively, an FBC HVHZ Approved insulation board or coverboard may be used as a
separation layer. Board products shall be preliminarily attached prior to roof cover installation (Note 5 herein). The separator component shall be documented as meeting FBC HVHZ 1516 and, for foam plastic,
FBC Chapter 26, when installed with the roof cover in Recover applications.
14 Lightweight insulating concrete (LWIC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC is referenced, refer to current
LWIC FBC HVHZ Product Approval for specific deck construction and limitations. Unless otherwise noted, for systems where spe cific LWIC is not referenced, the minimum design mix shall be 300 psi. In all
cases, the minimum top-coat thickness is 2-inches. For LWIC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. For “pre-existent” LWIC references, listings were established through
testing over lightweight concrete cast using only foaming agent (ASTM C896), water and Portland cement (ASTM C150), with no proprietary additives, in accordance with procedures adopted by Miami -Dade
BCCO (FBC CER1592). Use of these listings in new construction or re-roof (tear-off) applications is at the discretion of the Designer or Record and Authority Having Jurisdiction.
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 4 of 83
15 For bonded membrane applications, unless otherwise noted, refer to the following.
MEMBRANE / ADHESIVE COMBINATIONS
REFERENCE LAYER MATERIAL APPLICATION
BP-AA
(Base and Ply sheets,
Asphalt-Applied)
Base Ply One or more plies Polyglass G2 Base, FBC Approved ASTM D4601, Type II Hot Asphalt at 20-40
lbs/square Ply One or more plies Polyglass Ply IV, Polyglass Ply VI, FBC Approved ASTM D2178, Type IV or VI
Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
SBS-CA1
Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield HT PG350 at 1.5-2.0
gal/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex
S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed)
SBS-CA2
Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP Polyplus 35 at 1.5-2.0
gal/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex
S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed)
SBS-AA
(SBS, Asphalt-Applied)
Base Ply or Ply One or more plies Elastobase (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex S6, Elastoflex
S6 HP, Elastoshield HT Hot Asphalt at 20-40
lbs/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G,
Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed)
Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
SBS-TA
(SBS, Torch-Applied)
Base Ply or Ply One or more plies Elastobase (sand/poly), Elastobase (poly/poly), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield HT
Torch-Applied Cap Ply
Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6
G, Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (poly-film backed), Polyfresko G SBS FR (poly-film
backed)
SBS-SA-H
(SBS, Self-Adhering, Hybrid Systems) Base Ply Elastobase SA Self-adhering (followed
by torch-applied sheet)
SBS-SA
(SBS, Self-Adhering)
Base Ply One or more plies Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Elastoflex SA V Plus FR, Elastoflex SA Base HD
Self-Adhering Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyreflect
Note: Unless otherwise noted, permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein,
Elastobase (poly/sand) or Elastobase (poly/poly).
APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2.0
gal/square
APP-TA
(APP, Torch-Applied)
Base Ply or Ply One or more plies Polyglass Base, Polyflex, Polybond Torch-Applied Cap Ply Polyflex, Polyflex G, Polyflex G FR, Polybond, Polybond G, Polyfresko G, Polyfresko G FR
APP-SA-H
(APP, Self-Adhering, Hybrid Systems) Base Ply Polyflex SA Base Self-adhering (followed
by torch-applied sheet)
APP-SA
(APP, Self-Adhering)
Cap Ply Polyflex SA P, Polyflex SA P FR, Polyfresko G SA, Polyfresko G SA FR, Polykool
Self-Adhering Note: Unless otherwise noted, permissible membrane substrates for APP-SA are limited to the SBS-SA Base Ply options herein,
Elastobase (poly/sand) or Elastobase (poly/poly).
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 5 of 83
16 Vapor barrier options for use over structural concrete deck followed by bonded insulation carry the following MDP limitations. The lesser of the MDP listings below vs. those in Table 3A applies.
VAPOR BARRIER OPTIONS; STRUCTURAL CONCRETE DECK; FOLLOWED BY ADHESIVE-APPLIED INSULATION PER TABLE 3A:
OPTION
# PRIMER VAPOR BARRIER INSULATION ADHESIVE MDP
(PSF)* TYPE (NOTE 15) APPLICATION
C-VB-1. PG100 Elastoflex SA V Plus Self-Adhering D-IS or CR-20, 12-inch o.c. -60.0
C-VB-2. PG100 Polyglass Base Torch-applied D-IS or CR-20, 12-inch o.c. -75.0
C-VB-3. PG100 Elastoflex SA P Self-Adhering D-IS, 12-inch o.c. -75.0
C-VB-4. PG100 Elastoflex SA P Self-Adhering M-OSFA, 12-inch o.c. -157.5
C-VB-5. PG100 Elastoflex SA P Self-Adhering CR-20, 12-inch o.c. -270.0
C-VB-6. PG100 Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Elastoflex SA V
Plus FR Self-Adhering M-OSFA, M-PG-1, OB500 or CR-20, 12-inch
o.c. -290.0
C-VB-7. PG100 SBS-TA (with sanded-top-surface) Torch-applied M-OSFA, M-PG-1, OB500 or CR-20, 12-inch
o.c. -290.0
17 The following surfacing may be applied to the Cap Ply without adverse effect on the system wind load performance. Refer to current Florida Product Approval for approved Polyglass and KM Coatings roof coatings
for application limitations and a Roofing Materials Directory for fire ratings associated with coating usage.
SURFACING OPTIONS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS
OPTION # SURFACING FLORIDA HVHZ PRODUCT APPROVAL
SURF-1. PG 300 17-1031.01
SURF-2. PG 600 17-1031.01
SURF-3. PG 650 17-1031.01
SURF-4. PG 700 20-0611.01
SURF-5. PG 700 QS 20-0611.01
SURF-6. PG 800 17-1031.01
SURF-7. Polyplus 60 17-1031.01
SURF-8. Polyplus 65 17-1031.01
SURF-9. PolyBrite 60-FC 20-0611.01
SURF-10. PolyBrite 70 20-0611.01
SURF-11. PolyBrite 70 QS 20-0611.01
SURF-12. PolyBrite 75 20-0611.01
SURF-13. PolyBrite 71 HS 20-0611.01
SURF-14. PolyBrite 90 19-0610.02
SURF-15. PolyBrite 90.1 19-0610.02
SURF-16. PolyBrite 95 19-0610.02
SURF-17. PolyBrite 95.1 19-0610.02
SURF-18. KM Acryl 15 17-1031.01
SURF-19. KM Acryl 15 QS 17-1031.01
SURF-20. KM Acryl 25 17-1031.01
SURF-21. KM Acryl 25 QS 17-1031.01
SURF-22. KM Acryl 40 HS 17-1031.01
SURF-23. KM Acryl 85 17-1031.01
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 6 of 83
SURFACING OPTIONS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS
OPTION # SURFACING FLORIDA HVHZ PRODUCT APPROVAL
SURF-24. KM PS#250 17-1031.01
SURF-25. KM PS#220 17-1031.01
SURF-26. Turbo-Set 19-0820.05
18 “MDP” = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC (HVHZ) 1620 and Roofing Application Standard RAS 128 for determination of design
wind loads.
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-1.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 18-inch o.c.
in two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
W-2.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 18-inch o.c.
in two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
W-3.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 12-inch o.c.
in two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-52.5
W-4.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 12-inch o.c.
in two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 7 of 83
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-5.
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase
P (sanded-top),
Elastovent,
CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or
GAFGLAS #75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. in 4-inch
lap and 8-inch o.c.
in three (3), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-6.
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase
P (sanded-top),
Elastovent,
CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or
GAFGLAS #75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. in 4-inch
lap and 8-inch o.c.
in three (3), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-7.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-8.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-9.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
8-inch o.c. in 4-inch
lap and 8-inch o.c.
in four (4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 8 of 83
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-10.
Min.
15/32-
inch
plywood
Polyglass G2 Base Simplex MAXX
Cap
9-inch o.c. in 4-inch
lap and 9-inch o.c.
in four (4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-82.5
W-11.
Min.
15/32-
inch
plywood
Polyglass G2 Base,
Elastobase,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. in 4-inch
lap and 6-inch o.c.
in five (5) equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-90.0
W-12.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
6-inch o.c. at 2-inch
lap and 6-inch o.c.
in two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-90.0
W-13.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. in 4-inch
lap and 6-inch o.c.
in four (4), equally
spaced, staggered
center rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
Min. 0.25-inch Dens
Deck, Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof
Board
D-IS,
OB500, CR-
20 or M-
OSFA
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0*
SELF-ADHERING BASE PLY:
W-14.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 18-inch o.c.
in two, equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-45.0*
W-15.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 12-inch o.c.
in two, equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 9 of 83
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-16.
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase
P (sanded-top),
Elastovent,
CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or
GAFGLAS #75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. in 4-inch
lap and 8-inch o.c.
in three (3), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
W-17.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
W-18.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. in 4-inch
lap and 6-inch o.c.
in four (4), equally
spaced, staggered
center rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
(Optional) Additional
layers of base
insulation
D-IS,
OB500, CR-
20 or M-
OSFA
SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-19.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 18-inch o.c.
in two, equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -45.0*
W-20.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at 2-inch
lap and 12-inch o.c.
in two, equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 10 of 83
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-21.
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase
P (sanded-top),
Elastovent,
CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or
GAFGLAS #75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. in 4-inch
lap and 8-inch o.c.
in three (3), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -60.0
W-22.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -60.0
W-23.
Min.
15/32-
inch
plywood
Polyglass G2 Base,
Elastobase,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
8-inch o.c. in 4-inch
lap and 8-inch o.c.
in four (4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -67.5
W-24.
Min.
15/32-
inch
plywood
Polyglass G2 Base Simplex MAXX
Cap
9-inch o.c. in 4-inch
lap and 9-inch o.c.
in four (4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -82.5
W-25.
Min.
15/32-
inch
plywood
Polyglass G2 Base,
Elastobase,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. in 4-inch
lap and 6-inch o.c.
in five (5) equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -90.0
W-26.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
6-inch o.c. at 2-inch
lap and 6-inch o.c.
in two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 11 of 83
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-27.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. in 4-inch
lap and 6-inch o.c.
in four (4), equally
spaced, staggered
center rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
(Optional) Additional
layers of base
insulation
D-IS,
OB500, CR-
20 or M-
OSFA
APP-
SA-H
(Optional)
APP-TA APP-TA -60.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-28.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -45.0*
W-29.
Min.
15/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 12-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -52.5
W-30.
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase
P (sanded-top),
Elastovent,
CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or
GAFGLAS #75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at three
(3), equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -60.0
W-31.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 12 of 83
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-32.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at four (4),
equally spaced,
staggered center
rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
(Optional) Additional
layers of base
insulation
D-IS,
OB500, CR-
20 or M-
OSFA
SBS-SA-
H
(Optional)
SBS-TA SBS-TA -60.0*
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten (Note 11) Attach Type
Attach
(Notes
6,7,8)
Type
Attach
(Notes
6,7,8)
Base Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-33.
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-
2-7/8) with Dekfast #14, OMG 3”
Round Metal Plate with OMG
HD, OMG Flat Bottom Plate
(Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
10-inch o.c. in 4-
inch lap and 10-inch
o.c. in three (3),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-52.5
W-34.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot
asphalt
BP-AA or
SBS-AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-35.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 13 of 83
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten (Note 11) Attach Type
Attach
(Notes
6,7,8)
Type
Attach
(Notes
6,7,8)
Base Ply Ply Cap Ply
W-36.
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-
2-7/8) with Dekfast #14, OMG 3”
Round Metal Plate with OMG
HD, OMG Flat Bottom Plate
(Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
9-inch o.c. in 4-inch
lap and 9-inch o.c.
in four (4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-82.5
SELF-ADHERING BASE PLY:
W-37.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-38.
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-
2-7/8) with Dekfast #14, OMG 3”
Round Metal Plate with OMG
HD, OMG Flat Bottom Plate
(Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
10-inch o.c. in 4-
inch lap and 10-inch
o.c. in three (3),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt APP-SA-H (Optional)
APP-TA APP-TA -52.5
W-39.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. in 4-
inch lap and 12-inch
o.c. in two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt APP-SA-H (Optional)
APP-TA APP-TA -60.0
W-40.
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-
2-7/8) with Dekfast #14, OMG 3”
Round Metal Plate with OMG
HD, OMG Flat Bottom Plate
(Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
9-inch o.c. in 4-inch
lap and 9-inch o.c.
in four (4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt APP-SA-H (Optional)
APP-TA APP-TA -82.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 14 of 83
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten (Note 11) Attach Type
Attach
(Notes
6,7,8)
Type
Attach
(Notes
6,7,8)
Base Ply Ply Cap Ply
W-41.
Min.
19/32-
inch
plywood
Elastobase,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot
asphalt
Min. 0.25-inch Dens
Deck, Dens Deck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot
asphalt SBS-SA-H (Optional)
SBS-TA SBS-TA -60.0
TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck (Note
1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-42.
Min. 19/32-
inch
plywood
Min. 1.5-inch ENRGY
3, H-Shield or
Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #12 or Trufast 3”
Metal Insulation Plate with Trufast
DP
1 per
1.3 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-43.
Min. 15/32-
inch
plywood
Min. 2-inch
Polytherm, ACFoam
II, ENRGY-3,
EnergyGuard Polyiso
Insulation, H-Shield
or Multi-Max FA3
Dekfast #14 with Dekfast Hex (aka,
Dekfast PLT-H-2-7/8), OMG #14 HD
with OMG 3” Galvalume Steel Plates
or Trufast #14 HD with Trufast 3-
inch Insulation Plates
1 per
1.0 ft2
Min. 0.25-inch Dens Deck Prime
or SECUROCK Gypsum Fiber Roof
Board
Hot asphalt SBS-AA, SBS-
TA, APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-75.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-44.
Min. 15/32-
inch
plywood
Min. 2-inch
Polytherm, ACFoam
II, ENRGY-3,
EnergyGuard Polyiso
Insulation, H-Shield
or Multi-Max FA3
Dekfast #14 with Dekfast Hex (aka,
Dekfast PLT-H-2-7/8), OMG #14 HD
with OMG 3” Galvalume Steel Plates
or Trufast #14 HD with Trufast 3-
inch Insulation Plates
1 per
1.0 ft2
Min. 0.25-inch Dens Deck Prime
or SECUROCK Gypsum Fiber Roof
Board
Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 15 of 83
TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-45.
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board
Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8),
OMG #14 HD with OMG 3” Galvalume Steel Plates or
Trufast #14 HD with Trufast 3-inch Insulation Plates
1 per 1.8 ft2 SBS-AA, SBS-
TA, APP-TA
(Optional) SBS-
AA, SBS-TA,
APP-TA
SBS-AA, SBS-
TA, APP-TA -45.0
W-46.
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board
Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8),
OMG #14 HD with OMG 3” Galvalume Steel Plates or
Trufast #14 HD with Trufast 3-inch Insulation Plates
1 per 1.0 ft2 SBS-AA, SBS-
TA, APP-TA
(Optional) SBS-
AA, SBS-TA,
APP-TA
SBS-AA, SBS-
TA, APP-TA -75.0
W-47.
Min. 19/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 0.5-inch Structodek High Density
Fiberboard Roof Insulation or min.
0.25-inch Dens Deck, Dens Deck
Prime or SECUROCK Gypsum-Fiber
Roof Board
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12
DP 1 per 1.3 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -82.5
SELF-ADHERING BASE PLY:
W-48.
Min. 15/32-
inch
plywood
One or more
layers, any
combination, min.
1-inch, loose laid
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board optionally primed
with POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast
Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or
OMG #14 Roofgrip with OMG 3 in. Round Metal Plate,
OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat
Bottom Plate or Trufast #14 HD Fasteners with Trufast
3” Metal Insulation Plate
1 per 2.0 ft2 SBS-SA None SBS-SA -45.0
W-49.
Min. 15/32-
inch
plywood
One or more
layers, any
combination, min.
1-inch, loose laid
Min. 0.25-inch Dens Deck Prime
optionally primed with POLYBRITE
745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate or Accutrac
Flat Bottom Plate or Trufast #14 HD Fasteners with
Trufast 3” Metal Insulation Plate
1 per 2.0 ft2 SBS-SA None SBS-SA -45.0
W-50.
Min. 15/32-
inch
plywood
One or more
layers, any
combination, min.
1-inch, loose laid
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board optionally primed
with POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast DF-#14
with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate or Accutrac
Flat Bottom Plate or Trufast #14 HD Fasteners with
Trufast 3” Metal Insulation Plate
1 per 1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-TA or
APP-TA
-45.0
W-51.
Min. 15/32-
inch
plywood
One or more
layers, any
combination, min.
1-inch, loose laid
Min. 0.25-inch Dens Deck Prime
optionally primed with POLYBRITE
745 or WB3000
OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or
Trufast #14 HD Fasteners with Trufast 3” Metal
Insulation Plate
1 per 1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-TA or
APP-TA
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 16 of 83
TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
W-52.
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 0.25-inch Dens Deck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof Board
Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8),
OMG #14 HD with OMG 3” Galvalume Steel Plates or
Trufast #14 HD with Trufast 3-inch Insulation Plates
1 per 1.0 ft2 SBS-SA (Optional) SBS-
TA, APP-TA
SBS-TA, APP-
TA -60.0
W-53.
Min. 19/32-
inch APA
rated
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max FA3,
Polytherm or Ultra-Max optionally
primed with POLYBRITE 745 or
WB3000
Trufast Versa Fasteners (min. ¾” penetration) & Plates;
2 screws per plate installed 180° into the holes of the
plate
1 per 1.3 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-67.5*
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 180 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-54.
Min. 19/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max FA3,
Polytherm or Ultra-Max optionally
primed with POLYBRITE 745 or
WB3000ENRGY 3, H-Shield or
Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast
Galvalume Steel 3” Round Insulation Plate (aka, Dekfast
PLT-R-3) with Dekfast #12, OMG 3 in. Galvalume Plate
(non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip
or Trufast 3” Metal Insulation Plate with Trufast
DPDekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast
#12 DP or Trufast 3” Metal Insulation Plate with Trufast
DP
1 per 1.3 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-67.5*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-55.
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board
Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8),
OMG #14 HD with OMG 3” Galvalume Steel Plates or
Trufast #14 HD with Trufast 3-inch Insulation Plates
1 per 1.8 ft2 APP-SA-H (Optional) APP-
TA APP-TA -45.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-56.
Min. 15/32-
inch
plywood
One or more
layers, any
combination, min.
1-inch, loose laid
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board optionally primed
with POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast
Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or
OMG #14 Roofgrip with OMG 3 in. Round Metal Plate,
OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat
Bottom Plate or Trufast #14 HD Fasteners with Trufast
3” Metal Insulation Plate
1 per 2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0
W-57.
Min. 15/32-
inch
plywood
One or more
layers, any
combination, min.
1-inch, loose laid
Min. 0.25-inch Dens Deck Prime
optionally primed with POLYBRITE
745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate or Accutrac
Flat Bottom Plate or Trufast #14 HD Fasteners with
Trufast 3” Metal Insulation Plate
1 per 2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 17 of 83
TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
W-58.
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 0.25-inch Dens Deck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof Board
Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8),
OMG #14 HD with OMG 3” Galvalume Steel Plates or
Trufast #14 HD with Trufast 3-inch Insulation Plates
1 per 1.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -60.0
W-59.
Min. 19/32”
APA rated
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max FA3,
Polytherm or Ultra-Max optionally
primed with POLYBRITE 745 or
WB3000
Trufast Versa Fasteners (min. ¾” penetration) & Plates;
2 screws per plate installed 180° into the holes of the
plate*
1 per 1.3 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -67.5*
W-60. Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 180 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
W-61.
Min. 19/32-
inch
plywood
(Optional) One or
more layers, any
combination,
loose laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max FA3,
Polytherm or Ultra-Max optionally
primed with POLYBRITE 745 or
WB3000
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast
Galvalume Steel 3” Round Insulation Plate (aka, Dekfast
PLT-R-3) with Dekfast #12, OMG 3 in. Galvalume Plate
(non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip
or Trufast 3” Metal Insulation Plate with Trufast DP
1 per 1.3 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -67.5*
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-62. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P,
Elastovent, Polyglass G2 Base,
CertainTeed Glasbase,
Firestone MB Base, JM Perma-
Ply 28 or GAFGLAS #75
OMG Flat Bottom Plates (square) with
Roofgrip #14, Dekfast Hex (aka, Dekfast PLT-H-
2-7/8) with Dekfast #14 or Trufast 3” Metal
Insulation Plate with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two (2), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -52.5
W-63. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P or
Elastovent
OMG Flat Bottom Plates (square) with
Roofgrip #12
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two (2), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 18 of 83
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-64.
Min. 19/32-inch
APA rated
plywood
One or more
layers, any
combination
Loose-laid Elastobase, Elastobase P or
Elastovent
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-AA,
SBS-TA, APP-
TA
-67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-65.
Min. 19/32-inch
APA rated
plywood
One or more
layers, any
combination
Loose-laid Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
APP-TA APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-66. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Polyglass G2 Base, Elastobase,
Elastobase P or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac)
with Roofgrip #14 or Trufast 3” Metal
Insulation Plate with Trufast #14 HD.
10-inch o.c. in 4-inch lap and 10-
inch o.c. in three (3), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -75.0
W-67. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polyglass Base
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac)
with Roofgrip #14 or Trufast 3” Metal
Insulation Plate with Trufast #14 HD.
10-inch o.c. in 4-inch lap and 10-
inch o.c. in three (3), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -75.0
W-68.
Min. 15/32-inch
(existing) or
min. 19/32-inch
(new) APA
rated plywood
One or more
layers, any
combination
Loose-laid Elastobase, Elastobase P or
Elastovent
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
9-inch o.c. at min. 2-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-AA,
SBS-TA, APP-
TA
-90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-69.
Min. 15/32-inch
(existing) or
min. 19/32-inch
(new) APA
rated plywood
One or more
layers, any
combination
Loose-laid Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
9-inch o.c. at min. 2-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
APP-TA APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 19 of 83
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-70. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Polyglass G2 Base, Elastobase,
Elastobase P or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac)
with Roofgrip #14 or Trufast 3” Metal
Insulation Plate with Trufast #14 HD.
9-inch o.c. in 4-inch lap and 9-
inch o.c. in four (4), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -90.0
W-71. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polyglass Base
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac)
with Roofgrip #14 or Trufast 3” Metal
Insulation Plate with Trufast #14 HD.
9-inch o.c. in 4-inch lap and 9-
inch o.c. in four (4), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -90.0
W-72. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P or
Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast
3” Metal Insulation Plates
6-inch o.c. at 4-inch lap and 6-
inch o.c. in three (3), equally
spaced, staggered center rows
(Optional) BP-AA
or SBS-AA SBS-AA -90.0
W-73. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P or
Elastovent
OMG #12 Standard Roofgrip or OMG #14
Heavy Duty with OMG 3” Round Metal Plates
or OMG Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-
inch o.c. in three (3), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA, APP-TA
SBS-AA, SBS-
TA or APP-TA -90.0
W-74. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polyglass Base
OMG #12 Standard Roofgrip or OMG #14
Heavy Duty with OMG 3” Round Metal Plates
or OMG Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-
inch o.c. in three (3), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -90.0
W-75.
Min. 15/32-inch
(existing) or
min. 19/32-inch
(new) APA
rated plywood
One or more
layers, any
combination
Loose-laid Elastobase, Elastobase P or
Elastovent
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-AA,
SBS-TA, APP-
TA
-105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-76.
Min. 15/32-inch
(existing) or
min. 19/32-inch
(new) APA
rated plywood
One or more
layers, any
combination
Loose-laid Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
APP-TA APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-77. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P or
Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast
3” Metal Insulation Plates
6-inch o.c. at 4-inch lap and 6-
inch o.c. in five (5), equally
spaced, staggered center rows
(Optional) BP-AA
or SBS-AA SBS-AA -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 20 of 83
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-78. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P or
Elastovent
OMG #12 Standard Roofgrip or OMG #14
Heavy Duty with OMG 3” Round Metal Plates
or OMG Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-
inch o.c. in five (5), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA, APP-TA
SBS-AA, SBS-
TA or APP-TA -120.0
W-79. Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polyglass Base
OMG #12 Standard Roofgrip or OMG #14
Heavy Duty with OMG 3” Round Metal Plates
or OMG Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-
inch o.c. in five (5), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -120.0
SELF-ADHERING BASE PLY:
W-80. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P (poly-
film top)
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two, equally spaced,
staggered center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-52.5*
W-81. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P (poly-
film top)
OMG Flat Bottom Plates (square) with
Roofgrip #12
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two, equally spaced,
staggered center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0*
W-82.
Min. 19/32-inch
APA rated
plywood
One or more
layers, any
combination
Loose-laid Elastobase, Elastobase P (poly-
film top)
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-83. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P (poly-
film top)
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two, equally spaced,
staggered center rows
APP-SA-H APP-TA -52.5*
W-84. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P (poly-
film top)
OMG Flat Bottom Plates (square) with
Roofgrip #12
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two, equally spaced,
staggered center rows
APP-SA-H APP-TA -60.0*
W-85.
Min. 19/32-inch
APA rated
plywood
One or more
layers, any
combination
Loose-laid Elastobase, Elastobase P (poly-
film top)
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
APP-SA-H APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-86. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P (poly-
film top)
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
SBS-SA-H SBS-TA -52.5*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 21 of 83
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-87. Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase, Elastobase P (poly-
film top)
OMG Flat Bottom Plates (square) with
Roofgrip #12
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
SBS-SA-H SBS-TA -60.0*
W-88.
Min. 19/32-inch
APA rated
plywood
One or more
layers, any
combination
Loose-laid Elastobase, Elastobase P (poly-
film top)
Trufast Versa Fasteners (min. ¾” penetration)
& Plates; 2 screws per plate installed 180° into
the holes of the plate, parallel to the width-
direction of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
SBS-SA-H SBS-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
NO BASE PLY:
W-89. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two
(2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -45.0*
W-90. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -52.5
W-91.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Elastobase (sanded top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -60.0
W-92.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Elastobase (poly-film top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-TA, APP-TA -60.0
W-93.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Polyglass Base Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None APP-TA -60.0
W-94.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Elastobase (poly-film top)
Simplex MAXX Cap
Note: MAXX Caps are to be primed with
PG100 or ASTM D41 primer
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-SA, APP-SA -60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 22 of 83
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-95. Min. 19/32-inch plywood
Elastobase, Elastobase P,
Elastovent,Polyglass G2 Base,
CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in three
(3), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -60.0
W-96. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in three
(3), equally spaced, staggered center rows None SBS-SA, APP-SA -60.0
W-97. Min. 15/32-inch plywood
Polyglass G2 Base,
Elastobase, Elastobase P or
Elastovent
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in four
(4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -67.5
W-98. Min. 15/32-inch plywood Polyglass Base 32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in four
(4), equally spaced, staggered center rows None APP-TA -67.5
W-99. Min. 15/32-inch plywood Polyglass G2 Base,
Elastobase, Elastobase P Simplex MAXX Cap
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -75.0
W-100. Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
None APP-TA -75.0
W-101. Min. 15/32-inch plywood Polyglass G2 Base,
Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -90.0
W-102. Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows None APP-TA -90.0
W-103. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two
(2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -90.0
W-104. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails.
4-inch o.c. in 4-inch lap and 4-inch o.c. in four
(4), equally spaced, staggered center rows None SBS-SA, APP-SA -97.5
W-105. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -105.0
W-106. Min. 19/32-inch plywood Elastobase, Elastobase P or
Elastovent
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
6-inch o.c. in 4-inch lap and 6-inch o.c. in four
(4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -112.5
W-107. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails. Note: Tin
caps are to be primed with PG100 or
ASTM D41 primer.
6-inch o.c. in 4-inch lap and 6-inch o.c. in four
(4), equally spaced, staggered center rows None SBS-SA, APP-SA -112.5
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 23 of 83
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-108. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two
(2), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-45.0*
W-109. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-52.5
W-110.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Elastobase (sanded top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-AA, SBS-TA,
APP-TA -60.0
W-111.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Elastobase (poly-film top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-TA SBS-TA, APP-TA -60.0
W-112.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Polyglass Base Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
APP-TA APP-TA -60.0
W-113. Min. 19/32-inch plywood
Elastobase, Elastobase P,
Elastovent, Polyglass G2
Base, CertainTeed Glasbase,
Firestone MB Base, JM
Perma-Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in three
(3), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-60.0
W-114. Min. 15/32-inch plywood
Polyglass G2 Base,
Elastobase, Elastobase P or
Elastovent
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in four
(4), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-67.5
W-115. Min. 15/32-inch plywood Polyglass Base 32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in four
(4), equally spaced, staggered center rows APP-TA APP-TA -67.5
W-116. Min. 15/32-inch plywood Polyglass G2 Base,
Elastobase, Elastobase P Simplex MAXX Cap
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-75.0
W-117. Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
APP-TA APP-TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 24 of 83
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-118. Min. 15/32-inch plywood Polyglass G2 Base,
Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-119. Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows APP-TA APP-TA -90.0
W-120. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two
(2), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-121. Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-105.0
W-122. Min. 19/32-inch plywood Elastobase, Elastobase P or
Elastovent
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
6-inch o.c. in 4-inch lap and 6-inch o.c. in four
(3), equally spaced, staggered center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-112.5
SELF-ADHERING BASE PLY:
W-123.
Min. 15/32-inch
(existing) or min. 19/32-
inch (new) APA rated
plywood
Elastobase (poly-film top)
Simplex MAXX Cap
Note: MAXX Caps are to be primed with
PG100 or ASTM D41 primer
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -60.0
W-124. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in three
(3), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -60.0
W-125. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails.
4-inch o.c. in 4-inch lap and 4-inch o.c. in four
(4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -97.5
W-126. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails. Note: Tin
caps are to be primed with PG100 or
ASTM D41 primer.
6-inch o.c. in 4-inch lap and 6-inch o.c. in four
(4), equally spaced, staggered center rows
Elastoflex SA V Plus,
Elastoflex SA V Plus
FR
SBS-SA, APP-SA,
SBS-TA, APP-TA -112.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-127. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. in 4-inch lap and 8-inch o.c. in three
(3), equally spaced, staggered center rows APP-SA-H APP-TA -60.0
W-128. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails.
4-inch o.c. in 4-inch lap and 4-inch o.c. in four
(4), equally spaced, staggered center rows APP-SA-H APP-TA -97.5
W-129. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails. Note: Tin
caps are to be primed with PG100 or
ASTM D41 primer.
6-inch o.c. in 4-inch lap and 6-inch o.c. in four
(4), equally spaced, staggered center rows APP-SA-H APP-TA -112.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 25 of 83
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-130. Min. 15/32” APA rated
plywood Elastobase (poly-film top)
Simplex MAXX Cap
Note: MAXX Caps are to be primed with
PG100 or ASTM D41 primer
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -60.0
W-131. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -60.0
W-132. Min. 19/32-inch plywood Elastobase, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with
11 ga. annular ring shank nails.
4-inch o.c. at min. 4-inch lap and 4-inch o.c. at
four (4), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -97.5
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
NO BASE PLY:
W-133. Min. 19/32-inch
plywood
Elastobase, Elastobase P,
Elastovent, Polyglass G2
Base, CertainTeed
Glasbase, Firestone MB
Base, JM Perma-Ply 28 or
GAFGLAS #75
OMG Flat Bottom Plates (square) with Roofgrip
#14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -52.5
W-134. Min. 19/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -60.0
W-135.
Min. 19/32-inch
APA rated
plywood
Elastobase, Elastobase P
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-136.
Min. 19/32-inch
APA rated
plywood
Elastobase, Elastobase P
(poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
None SBS-SA, APP-SA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 26 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-137.
Min. 19/32-inch
APA rated
plywood
Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
None APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF)
W-138. Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase P
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -75.0
W-139. Min. 15/32-inch
plywood Polyglass Base
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
None APP-TA -75.0
W-140.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Elastobase, Elastobase P
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c. at
two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 159 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-141.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c. at
two (2), equally spaced, staggered center rows None APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 159 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-142. Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase P
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 27 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-143. Min. 15/32-inch
plywood Polyglass Base
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows None APP-TA -90.0
W-144. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows None SBS-AA -90.0
W-145. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows None SBS-AA, SBS-TA or
APP-TA -90.0
W-146. Min. 15/32-inch
plywood Polyglass Base
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows None APP-TA -90.0
W-147.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Elastobase, Elastobase P
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 103 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-148.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
three (3), equally spaced, staggered center
rows
None APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-149. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in five
(5), equally spaced, staggered center rows None SBS-AA -120.0
W-150. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in five
(5), equally spaced, staggered center rows None SBS-AA, SBS-TA or
APP-TA -120.0
W-151. Min. 15/32-inch
plywood Polyglass Base
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in five
(5), equally spaced, staggered center rows None APP-TA -120.0
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 28 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-152. Min. 19/32-inch
plywood
Elastobase, Elastobase P,
Elastovent, Polyglass G2
Base, CertainTeed
Glasbase, Firestone MB
Base, JM Perma-Ply 28 or
GAFGLAS #75
OMG Flat Bottom Plates (square) with Roofgrip
#14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-52.5
W-153. Min. 19/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-60.0
W-154.
Min. 19/32-inch
APA rated
plywood
Elastobase, Elastobase P
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-155.
Min. 19/32-inch
APA rated
plywood
Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
APP-TA APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-156. Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase P
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-75.0
W-157. Min. 15/32-inch
plywood Polyglass Base
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
10-inch o.c. in 4-inch lap and 10-inch o.c. in
three (3), equally spaced, staggered center
rows
APP-TA APP-TA -75.0
W-158.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Elastobase, Elastobase P
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c. at
two (2), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 29 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 159 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-159.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c. at
two (2), equally spaced, staggered center rows APP-TA APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-160. Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase, Elastobase P
or Elastovent
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-161. Min. 15/32-inch
plywood Polyglass Base
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14, OMG 3” Round Metal Plate with
OMG HD, OMG Flat Bottom Plate (Accutrac) with
Roofgrip #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD.
9-inch o.c. in 4-inch lap and 9-inch o.c. in four
(4), equally spaced, staggered center rows APP-TA APP-TA -90.0
W-162. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows BP-AA or SBS-AA SBS-AA -90.0
W-163. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty (min. 1-5/8-inch long) with OMG 3” Round
Metal Plates or OMG Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-164. Min. 15/32-inch
plywood Polyglass Base
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
(3), equally spaced, staggered center rows APP-TA APP-TA -90.0
W-165.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Elastobase, Elastobase P
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 30 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-166.
Min. 15/32-inch
(existing) or min.
19/32-inch (new)
APA rated
plywood
Polyglass Base
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
three (3), equally spaced, staggered center
rows
APP-TA APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 103 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-167. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in five
(5), equally spaced, staggered center rows BP-AA or SBS-AA SBS-AA -120.0
W-168. Min. 15/32-inch
plywood
Elastobase, Elastobase P
or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in five
(5), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-120.0
W-169. Min. 15/32-inch
plywood Polyglass Base
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at 4-inch lap and 6-inch o.c. in five
(5), equally spaced, staggered center rows APP-TA APP-TA -120.0
W-170.
Min. 19/32-inch
APA rated
plywood
Elastobase (sanded top)
or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-AA, SBS-TA,
APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
W-171.
Min. 19/32-inch
APA rated
plywood
Elastobase (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced center rows SBS-TA SBS-TA, APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
W-172.
Min. 19/32-inch
APA rated
plywood
Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced center rows APP-TA APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
SELF-ADHERING BASE PLY:
W-173. Min. 19/32-inch
plywood
Elastobase, Elastobase P
(poly-film top)
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -52.5*
W-174. Min. 19/32-inch
plywood
Elastobase, Elastobase P
(poly-film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -60.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 31 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-175.
Min. 19/32-inch
APA rated
plywood
Elastobase, Elastobase P
(poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-176.
Min. 19/32-inch
APA rated
plywood
Elastobase (poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
Note: Versa-Fast Plates shall be primed with
PG100 or ASTM D41 primer.
9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-177. Min. 19/32-inch
plywood
Elastobase, Elastobase P
(poly-film top)
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows APP-SA-H APP-TA -52.5*
W-178. Min. 19/32-inch
plywood
Elastobase, Elastobase P
(poly-film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
(2), equally spaced, staggered center rows APP-SA-H APP-TA -60.0*
W-179.
Min. 19/32-inch
APA rated
plywood
Elastobase, Elastobase P
(poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
APP-SA-H APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-180. Min. 19/32-inch
plywood
Elastobase, Elastobase P
(poly-film top)
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with
Dekfast #14 or Trufast 3” Metal Insulation Plate
with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -52.5*
W-181. Min. 19/32-inch
plywood
Elastobase, Elastobase P
(poly-film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -60.0*
W-182.
Min. 19/32-inch
APA rated
plywood
Elastobase, Elastobase P
(poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 32 of 83
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 199 lbf. Additional Versa -Fast Fasteners within each Versa-Fast Plate may be utilized to
produce Minimum Characteristic Resistance Force (MCRF).
W-183.
Min. 19/32-inch
APA rated
plywood
Elastobase (poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
Note: Versa-Fast Plates shall be primed with
PG100 or ASTM D41 primer.
9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced center rows SBS-SA-H SBS-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield MCRF > 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 33 of 83
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
SC-1.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 1.5-inch Polytherm,
ACFoam II, ENRGY 3, H-
Shield or Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast
#14 HD or OMG 3-inch Galv Plate
with OMD HD
1 per
2.0 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
SC-2.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3, H-
Shield or Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast
#14 HD or OMG 3-inch Galv Plate
with OMD HD
1 per
4.0 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
SC-3.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 1.5-inch ENRGY 3,
H-Shield or Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14 or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.3 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-90.0
SC-4.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 1.5-inch ENRGY 3,
H-Shield or Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14 or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.3 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
BP-AA, SBS-
AA (Top
surface
primed
with PG100
primer)
SBS-SA, SBS-TA or
APP-TA
SBS-SA,
APP-SA,
SBS-TA or
APP-TA
-90.0
SC-5.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
D-IS
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
SC-6.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-
Fiber Roof Board or SECUROCK
Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof
Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA or
M-PG1
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 34 of 83
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
SC-7.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
OB500
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
SC-8.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
SELF-ADHERING BASE PLY:
SC-9.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
D-IS SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
SC-10.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck, Dens
Deck Prime, SECUROCK
Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof
Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-
inch SECUROCK Cement Roof
Board
PRIMER: POLYBRITE 745 or
WB3000
M-OSFA or
M-PG1 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
SC-11.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
OB500 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 35 of 83
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
SC-12.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
CR-20 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
COLD-APPLIED BASE PLY:
SC-13.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck
Prime, DEXcell FA Glass Mat
Roof Board or SECUROCK
Gypsum-Fiber Roof Board
D-IS SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
SC-14.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck, Dens
Deck Prime, DEXcell FA Glass
Mat Roof Board, SECUROCK
Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof
Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-
inch SECUROCK Cement Roof
Board
M-OSFA or
M-PG1
SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
SC-15.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck
Prime, DEXcell FA Glass Mat
Roof Board or SECUROCK
Gypsum-Fiber Roof Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
SC-16.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #14, OMG 3”
Galvalume Ribbons Plates with
OMG #14 Roofgrip or Trufast 3”
Metal Insulation Plate with Trufast
#14 HD
1 per
1.6 ft2
Min. 0.25-inch Dens Deck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 36 of 83
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
SC-17.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.75-inch JM Fesco
Board (homogeneous) or
min. 1.5-inch JM Fesco
Board (laminated)
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka,
Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel
only) or Trufast #14 HD
1 per
2.0 ft2
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
SC-18.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.5-inch Structodek
High Density Fiberboard
Roof Insulation
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka,
Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel
only) or Trufast #14 HD
1 per
4.0 ft2
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
SC-19.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka,
Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel
only) or Trufast #14 HD
1 per
4.0 ft2
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
SC-20.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 2-inch H-Shield WF
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka,
Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel
only) or Trufast #14 HD
1 per
4.0 ft2
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
SC-21.
Min. 22 ga., type B,
Grade 40 steel; 6 ft
span; 5/8” puddle
welds, 6” o.c.
One or more layers,
any combination,
min. 1.5” thick, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF-#12-PH3, DF-
#14-PH3 or DF-#15-PH3 fasteners or OMG 3 in. Galvalume Steel
Plate, 3 in. Ribbed Galvalume Plate (Flat) or AccuTrac Flat Bottom
Plate with OMG #12 Roofgrip, #14 Roofgrip or OMG #15 Roofgrip
fasteners or Trufast 3” Metal Insulation Plate with Trufast #12 DP,
Trufast #14 HD or Trufast #15 EHD fasteners
1 per
2.0 ft2
SBS-TA or
APP-TA
(Optional) SBS-
TA or APP-TA
SBS-TA
or APP-
TA
-52.5
SC-22.
Min. 22 ga., type B,
Grade 40 steel; 6 ft
span; 5/8” puddle
welds, 6” o.c.
One or more layers,
any combination,
min. 1.5” thick, loose
laid
Min. 0.25-inch DensDeck
Prime
Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF-#12-PH3, DF-
#14-PH3 or DF-#15-PH3 fasteners or OMG 3 in. Galvalume Steel
Plate, 3 in. Ribbed Galvalume Plate (Flat) or AccuTrac Flat Bottom
Plate with OMG #12 Roofgrip, #14 Roofgrip or OMG #15 Roofgrip
fasteners or Trufast 3” Metal Insulation Plate with Trufast #12 DP,
Trufast #14 HD or Trufast #15 EHD fasteners
1 per
2.0 ft2
SBS-TA or
APP-TA
(Optional) SBS-
TA or APP-TA
SBS-TA
or APP-
TA
-60.0
SC-23.
Min. 22 ga., type B,
Grade 40 steel; 6 ft
span; 5/8” puddle
welds, 6” o.c.
One or more layers,
any combination,
min. 1.5” thick, loose
laid
Min. 0.25-inch DensDeck
Prime or SECUROCK
Gypsum-Fiber Roof Board
Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF-#12-PH3, DF-
#14-PH3 or DF-#15-PH3 fasteners or OMG 3 in. Galvalume Steel
Plate, 3 in. Ribbed Galvalume Plate (Flat) or AccuTrac Flat Bottom
Plate with OMG #12 Roofgrip, #14 Roofgrip or OMG #15 Roofgrip
fasteners or Trufast 3” Metal Insulation Plate with Trufast #12 DP,
Trufast #14 HD or Trufast #15 EHD fasteners
1 per
1.6 ft2
SBS-TA or
APP-TA
(Optional) SBS-
TA or APP-TA
SBS-TA
or APP-
TA
-67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 37 of 83
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
SC-24.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch SECUROCK
Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per
1.8 ft2
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-75.0
SC-25.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.5-inch Structodek
High Density Fiberboard
Roof Insulation or min.
0.25-inch Dens Deck, Dens
Deck Prime or SECUROCK
Gypsum-Fiber Roof Board
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 (steel only)
or #14 or Trufast 3” Metal Insulation Plate with Trufast DP (steel
only) or HD
1 per
1.3 ft2
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-82.5
SELF-ADHERING BASE PLY:
SC-26.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm
OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or
OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-45.0*
SC-27.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3”
Galvalume Ribbed Plates with OMG #14 RoofGrip or Trufast 3”
Metal Insulation Plates with Trufast #14 HD Fasteners
1 per
2.0 ft2 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0*
SC-28.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14
HD
1 per
2.0 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA or
APP-TA
SBS-SA,
APP-SA,
SBS-TA
or APP-
TA
-45.0*
SC-29.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round
(aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round
Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac
Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.0 ft2 SBS-SA None SBS-SA -45.0
SC-30.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch Dens Deck
Prime optionally primed
with POLYBRITE 745 or
WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in.
Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.0 ft2 SBS-SA None SBS-SA -45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 38 of 83
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
SC-31.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-
#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG
#14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or
Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA
or APP-
TA
-45.0
SC-32.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch Dens Deck
Prime optionally primed
with POLYBRITE 745 or
WB3000
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal
Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3”
Metal Insulation Plate
1 per
1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA
or APP-
TA
-45.0
SC-33.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel
only) or Dekfast #14
1 per
2.0 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
SC-34.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14
HD
1 per
1.6 ft2 SBS-SA (Optional) SBS-
TA or APP-TA
SBS-TA
or APP-
TA
-60.0
SC-35.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II,
ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3,
ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL,
Multi-Max FA3, Polytherm
or Ultra-Max optionally
primed with POLYBRITE 745
or WB3000
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel
3” Round Insulation Plate (aka, Dekfast PLT-R-3) with Dekfast #12
(steel only) or Dekfast #14, OMG 3 in. Galvalume Plate (non-ribbed)
or OMG AccuTrac Plate with #12 Roofgrip (steel only) or OMG #14
Heavy Duty or Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
1.3 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-67.5*
SC-36.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14
HD
1 per
1.3 ft2 SBS-SA (Optional) SBS-
TA or APP-TA
SBS-TA
or APP-
TA
-72.5
SC-37.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch SECUROCK
Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per
1.8 ft2 SBS-SA (Optional) SBS-
TA SBS-TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 39 of 83
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
SC-38.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-
#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG
#14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or
Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.0 ft2 SBS-SA (Optional) SBS-
TA, APP-TA
SBS-TA,
APP-TA -90.0
SC-39.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch Dens Deck
Prime optionally primed
with POLYBRITE 745 or
WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-
#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG
#14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or
Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
1.0 ft2 SBS-SA (Optional) SBS-
TA, APP-TA
SBS-TA,
APP-TA -97.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
SC-40.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm
OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or
OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2 APP-SA-H (Optional) APP-
TA APP-TA -45.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
SC-41.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm H
OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or
OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0*
SC-42.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round
(aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round
Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac
Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0
SC-43.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch Dens Deck
Prime optionally primed
with POLYBRITE 745 or
WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in.
Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0
SC-44.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm optionally
primed with POLYBRITE 745
or WB3000
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel
only) or Dekfast #14
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -60.0
SC-45.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14
HD
1 per
1.6 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 40 of 83
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
SC-46.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II,
ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3,
ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL,
Multi-Max FA3, Polytherm
or Ultra-Max optionally
primed with POLYBRITE 745
or WB3000
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel
3” Round Insulation Plate (aka, Dekfast PLT-R-3) with Dekfast #12
(steel only) or Dekfast #14, OMG 3 in. Galvalume Plate (non-ribbed)
or OMG AccuTrac Plate with #12 Roofgrip (steel only) or OMG #14
Heavy Duty or Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
1.3 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -67.5*
SC-47.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-
7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14
HD
1 per
1.3 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -72.5
SC-48.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch SECUROCK
Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per
1.8 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -75.0
SC-49.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-
#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG
#14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or
Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -90.0
SC-50.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch Dens Deck
Prime optionally primed
with POLYBRITE 745 or
WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-
#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG
#14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or
Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
1.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -97.5
COLD-APPLIED BASE PLY:
SC-51.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch Dens Deck
Prime or SECUROCK
Gypsum-Fiber Roof Board
Dekfast Galvalume Steel Hex with Dekfast #14, OMG 3” Galvalume
Ribbed Plates with OMG #14 RoofGrip or Trufast 3” Metal Insulation
Plates with Trufast #14 HD Fasteners
1 per
2.0 ft2
SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 41 of 83
TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
SC-52.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase,
Elastobase P,
Elastovent or JM
Perma-Ply 28
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Trufast #14
HD with Trufast 3” Metal Insulation Plate
12-inch o.c. at 4-inch lap and
18-inch o.c. at two, equally
spaced, staggered center
rows
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -45.0*
SC-53.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase,
Elastobase P,
Elastovent, Polyglass
G2 Base, CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Trufast #14
HD with Trufast 3” Metal Insulation Plate
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -52.5
SC-54.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase,
Elastobase P or
Elastovent
Roofgrip #12 (steel only) or #14 with OMG
Flat Bottom Plates (square)
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -60.0
SC-55.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached Polybond, Polyflex
Dekfast #14 with Dekfast Hex (aka, Dekfast
PLT-H-2-7/8) or OMG Roofgrip #14 OMG
Flat Bottom Plates
12-inch o.c. at the 4-inch lap
and 18-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -112.5
SELF-ADHERING BASE PLY:
SC-56.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase or
Elastobase P with
poly top surface
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Trufast #14
HD with Trufast 3” Metal Insulation Plate
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA or
APP-TA
-52.5*
SC-57.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase or
Elastobase P with
poly top surface
Roofgrip #12 (steel only) or #14 with OMG
Flat Bottom Plates (square)
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA or
APP-TA
-60.0*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
SC-58.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase or
Elastobase P with
poly top surface
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Trufast #14
HD with Trufast 3” Metal Insulation Plate
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
APP-SA-H APP-TA -52.5*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 42 of 83
TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf)
Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
SC-59.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase or
Elastobase P with
poly top surface
Roofgrip #12 (steel only) or #14 with OMG
Flat Bottom Plates (square)
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
APP-SA-H APP-TA -60.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
SC-60.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase or
Elastobase P with
poly top surface
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast Hex
(aka, Dekfast PLT-H-2-7/8) or Trufast #14
HD with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
SBS-SA-H SBS-TA -52.5*
SC-61.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase or
Elastobase P with
poly top surface
Roofgrip #12 (steel only) or #14 with OMG
Flat Bottom Plates (square)
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
SBS-SA-H SBS-TA -60.0*
COLD-APPLIED BASE PLY:
SC-62.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Loose
laid Elastobase Trufast #12 DP (steel only), #14 HD or #15
EHD with Trufast 3” Metal Insulation Plate
12-inch o.c. at 4-inch lap and
12-inch o.c. at one staggered
center row
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -45.0*
SC-63.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Loose
laid Elastovent Trufast #12 DP (steel only), #14 HD or #15
EHD with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at one
staggered center row
(Optional) SBS-CA1 SBS-CA1, APP-
CA1 -45.0*
SC-64.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Loose
laid Elastobase Trufast #12 DP (steel only), #14 HD or #15
EHD with Trufast 3” Metal Insulation Plate
12-inch o.c. at 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center
rows
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -67.5
SC-65.
Min. 22 ga., type B, Grade
33 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Loose
laid Elastovent Trufast #12 DP (steel only), #14 HD or #15
EHD with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) SBS-CA1 SBS-CA1, APP-
CA1 -67.5
SC-66.
Min. 22 ga., type B, Grade
40 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Loose-
laid Elastoflex S6
Trufast #12 DP (steel only) or Trufast #14
HD (steel or concrete) with Trufast 3”
Metal Insulation Plate
6-inch o.c. at min. 4-inch lap
and 6-inch o.c. at one
staggered center row
(Optional) Elastoflex
S6 applied in PG350
at 1.5-2.0 gal/square
SBS-CA1 -75.0*
SC-67.
Min. 22 ga., type B, Grade
40 steel or min. 2,500 psi
structural concrete
One or more
layers, any
combination
Loose-
laid Elastoflex S6
Trufast #12 DP (steel only) or Trufast #14
HD (steel or concrete) with Trufast 3”
Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) Elastoflex
S6 applied in PG350
at 1.5-2.0 gal/square
SBS-CA1 -90.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 43 of 83
TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
SC-68.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4” Scoop Seam Plates or Trufast 2.75”
Barbed Metal Seam Plates
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA SBS-TA -45.0
SC-69.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.75” Barbed Metal Seam Plates
6-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA SBS-TA -60.0
SC-70.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.75” Barbed Metal Seam Plates
18-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -60.0
SC-71.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.75” Barbed Metal Seam Plates
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -82.5
SC-72.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoshield HT
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast
2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal
Seam Plates or Dekfast #15 with Dekfast Galvalume Steel
1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-
3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round
Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B)
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -82.5
SC-73. Min. 22 ga., type B,
Grade 80 steel
One or more
layers, any
combination
Prelim.
Attached Polyflex Dekfast #15 HS with Dekfast Galvalume Steel 2-3/8”
Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B)
12-inch o.c. within the 5-inch
wide, torch-sealed side lap
(Optional)
APP-TA
SBS-TA, APP-
TA -82.5
SC-74.
Min. 22 ga., type B,
Grade 80 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Polybond or
Polyflex
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4 in. Barbed Seam Plates
12-inch o.c. within the 6-inch
wide, torch-sealed side lap
(Optional)
APP-TA
SBS-TA, APP-
TA -82.5
SC-75.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoshield HT
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast
2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal
Seam Plates or Dekfast #15 with Dekfast Galvalume Steel
1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-
3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round
Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B)
6-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -97.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 44 of 83
TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
SC-76.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.75” Barbed Metal Seam Plates
6-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -135.0
COLD-APPLIED BASE PLY:
SC-77.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.75” Barbed Metal Seam Plates
18-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
Elastoflex S6
applied in
PG350 at 1.5-
2.0 gal/square
SBS-CA1 -60.0
Note: When extrapolating base sheet attachment for this system for elevated pressure zones, any additional fastener rows installed in the center of the sheet shall be stripped-in with
minimum 6-inch wide strips of torch-applied, sand-top-surfaced, Polyglass SBS modified bitumen membrane prior to placement of subsequent Base Ply or Cap Ply membranes in
PG350 adhesive.
SC-78.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.75” Barbed Metal Seam Plates
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
Elastoflex S6
applied in
PG350 at 1.5-
2.0 gal/square
SBS-CA1 -82.5
Note: When extrapolating base sheet attachment for this system for elevated pressure zones, any additional fastener rows installed in the center of the sheet shall be stripped-in with
minimum 6-inch wide strips of torch-applied, sand-top-surfaced, Polyglass SBS modified bitumen membrane prior to placement of subsequent Base Ply or Cap Ply membranes in
PG350 adhesive.
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 45 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
C-1 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0
C-2 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS Min. 0.25-inch Dens Deck
Prime D-IS SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-3 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
D-IS SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-4 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0
C-5 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch Dens Deck
Prime OB500 SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-6 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
OB500 SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-7 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
M-OSFA or
M-PG1 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0
C-8 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch Dens Deck
Prime
M-OSFA or
M-PG1
SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-9 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
M-OSFA or
M-PG1
SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-10 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or
min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 46 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-11 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or
min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5
C-12 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch Dens Deck
Prime CR-20 SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-13 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
CR-20 SBS-TA, APP-
TA
(Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-14 Structural
concrete None (Optional) Min. 2-inch Polytherm, ACFoam
II, Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0
C-15 Structural
concrete None (Optional) Min. 2-inch Polytherm, ACFoam
II, Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
APP-TA (Optional) APP-TA APP-TA -232.5
C-16 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0
C-17 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt APP-TA (Optional) APP-TA APP-TA -232.5
C-18 Structural
concrete PG100 Min. 0.75-inch Fesco Board
(homogeneous) Hot asphalt None N/A
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -277.5
C-19 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.75-inch Fesco Board
(homogeneous) Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -290.0
C-20 Structural
concrete PG100 Min. 0.5-inch Structodek High Density
Fiberboard Roof Insulation Hot asphalt None N/A
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -285.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 47 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-21 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt
Min. 0.5-inch Structodek
High Density Fiberboard Roof
Insulation
Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -480.0
C-22 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch Dens Deck
Prime Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -480.0
C-23 Structural
concrete PG100 Min. 0.25-inch Dens Deck Prime Hot asphalt None N/A
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -510.0
SELF-ADHERING BASE PLY TO INSULATION:
C-24 Structural
concrete
(Optiona
l) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional
layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
C-25 Structural
concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional
layers(s) of base insulation D-IS SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -122.5
C-26 Structural
concrete
(Optiona
l) PG100
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS (Optional) additional
layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -135.0
C-27 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers
of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -120.0
C-28 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional
layers(s) of base insulation OB500 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -122.5
C-29 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional
layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -127.5
C-30 Structural
concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional
layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -150.0
C-31 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
M-OSFA or
M-PG1
(Optional) additional
layers(s) of base insulation
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -122.5
C-32 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional
layers(s) of base insulation M-OSFA SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 48 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-33 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax.
M-OSFA or
M-PG1
(Optional) additional
layers(s) of base insulation,
optionally primed with
POLYBRITE 745 or WB3000
M-OSFA or
M-PG1 SBS-SA None SBS-CA1, SBS-
CA2 -290.0
C-34 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
Polytherm H, H-Shield CR-20 (Optional) additional
layers(s) of base insulation CR-20 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -122.5
C-35 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers
of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -240.0
C-36 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
(Optional) additional
layers(s) of base insulation
OB Classic
(full-
coverage)
SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -270.0
C-37 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt (Optional) additional
layers(s) of base insulation Hot asphalt SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -480.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY TO INSULATION:
C-38 Structural
concrete
(Optiona
l) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional
layers(s) of base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5
C-39 Structural
concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional
layers(s) of base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -122.5
C-40 Structural
concrete
(Optiona
l) PG100
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS (Optional) additional
layers(s) of base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -135.0
C-41 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional
layers(s) of base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -122.5
C-42 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional
layers(s) of base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5
C-43 Structural
concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional
layers(s) of base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -150.0
C-44 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
M-OSFA or
M-PG1
(Optional) additional
layers(s) of base insulation
M-OSFA or
M-PG1 APP-SA-H (Optional) APP-TA APP-TA -122.5
C-45 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional
layers(s) of base insulation M-OSFA APP-SA-H (Optional) APP-TA APP-TA -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 49 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-46 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
Polytherm H, H-Shield CR-20 (Optional) additional
layers(s) of base insulation CR-20 APP-SA-H (Optional) APP-TA APP-TA -122.5
C-47 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
(Optional) additional
layers(s) of base insulation
OB Classic
(full-
coverage)
APP-SA-H (Optional) APP-TA APP-TA -270.0
C-48 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt (Optional) additional
layers(s) of base insulation Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -480.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY TO INSULATION:
C-49 Structural
concrete
(Optiona
l) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional
layers(s) of base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5
C-50 Structural
concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional
layers(s) of base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-51 Structural
concrete
(Optiona
l) PG100
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS (Optional) additional
layers(s) of base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -135.0
C-52 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional
layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-53 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional
layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5
C-54 Structural
concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional
layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -150.0
C-55 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
M-OSFA or
M-PG1
(Optional) additional
layers(s) of base insulation
M-OSFA or
M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-56 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional
layers(s) of base insulation M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -232.5
C-57 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
Polytherm H, H-Shield CR-20 (Optional) additional
layers(s) of base insulation CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-58 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
(Optional) additional
layers(s) of base insulation
OB Classic
(full-
coverage)
SBS-SA-H (Optional) SBS-TA SBS-TA -270.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 50 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-59 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt (Optional) additional
layers(s) of base insulation Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -480.0
SELF-ADHERING BASE PLY TO COVERBOARD:
C-60 Structural
concrete None Min. 1.5-inch Multi-Max FA3 D-IS
Min. 0.25-inch Dens Deck
Prime or SECUROCK Gypsum-
Fiber Roof Board
D-IS SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
C-61 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam,
Polytherm, ACFoam II, ENRGY 3, Polytherm
H or H-Shield
D-IS Min. 0.25-inch Dens Deck
Prime D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-62 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck,
Dens Deck Prime D-IS SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -120.0
C-63 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch Dens Deck
Prime optionally primed with
POLYBRITE 745 or WB3000
D-IS SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-64 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS Min. 0.25-inch DEXcell FA
Glass Mat Roof Board D-IS SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-65 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
D-IS SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-66 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck
Prime OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-67 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch Dens Deck,
Dens Deck Prime OB500 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -127.5
C-68 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II, H-
Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck,
Dens Deck Prime OB500 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -150.0
C-69 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch Dens Deck
Prime OB500 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 51 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-70 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch DEXcell FA
Glass Mat Roof Board OB500 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-71 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OB500 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-72 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck
Prime M-OSFA SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-73 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -232.5
C-74 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch Dens Deck
Prime
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-75 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch DEXcell FA
Glass Mat Roof Board
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-76 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-77 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min.
2-inch Polytherm, ACFoam II, min. 1.5-inch
Ultra-Max or Multi-Max FA-3, min. 1.3-inch
Polytherm G, ACFoam III or min. 1.0-inch
ISO 95+GL, Polytherm H, H-Shield, H-Shield
CG or ENRGY 3
CR-20 Min. 0.25-inch Dens Deck,
Dens Deck Prime CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-78 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min.
1.5-inch Ultra-Max or Multi-Max FA-3, min.
1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield,
H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch Dens Deck,
Dens Deck Prime CR-20 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 52 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-79 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or
min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
C-80 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch Dens Deck
Prime CR-20 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -282.5
C-81 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch or DEXcell FA
Glass Mat Roof Board CR-20 SBS-SA (Optional) SBS-TA, APP-
TA SBS-TA, APP-TA -322.5
C-82 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
CR-20 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-83 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -350.0
C-84 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -350.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY TO COVERBOARD:
C-85 Structural
concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5
C-86 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck,
Dens Deck Prime D-IS APP-SA-H (Optional) APP-TA APP-TA -120.0
C-87 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000 or
DEXcell FA Glass Mat Roof Board
D-IS APP-SA-H (Optional) APP-TA APP-TA -322.5
C-88 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch Dens Deck,
Dens Deck Prime OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5
C-89 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II, H-
Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck,
Dens Deck Prime OB500 APP-SA-H (Optional) APP-TA APP-TA -150.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 53 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-90 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
OB500 APP-SA-H (Optional) APP-TA APP-TA -322.5
C-91 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
M-OSFA or
M-PG1 APP-SA-H (Optional) APP-TA APP-TA -322.5
C-92 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min.
1.5-inch Ultra-Max or Multi-Max FA-3, min.
1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield,
H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch Dens Deck,
Dens Deck Prime CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
C-93 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or
min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
C-94 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -322.5
C-95 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
APP-SA-H (Optional) APP-TA APP-TA -350.0
C-96 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -350.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY TO COVERBOARD:
C-97 Structural
concrete None Min. 1.5-inch Multi-Max FA3 D-IS
Min. 0.25-inch Dens Deck
Prime or SECUROCK Gypsum-
Fiber Roof Board
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5
C-98 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck,
Dens Deck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 54 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-99 Structural
concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-
3, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-100 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch Dens Deck
Prime optionally primed with
POLYBRITE 745 or WB3000
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-101 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000 or
DEXcell FA Glass Mat Roof Board
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
C-102 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch Dens Deck,
Dens Deck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5
C-103 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II, H-
Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck,
Dens Deck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -150.0
C-104 Structural
concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-
3, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-105 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch Dens Deck
Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-106 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
C-107 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -232.5
C-108 Structural
concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-
3, Polytherm H or H-Shield M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-109 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch Dens Deck
Prime
M-OSFA or
M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-110 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
M-OSFA or
M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 55 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-111 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min.
1.5-inch Ultra-Max or Multi-Max FA-3, min.
1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield,
H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch Dens Deck,
Dens Deck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
C-112 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or
min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
C-113 Structural
concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-
3, Polytherm H or H-Shield CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-114 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch Dens Deck
Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-115 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof
Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
C-116 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
SBS-SA-H (Optional) SBS-TA SBS-TA -350.0
C-117 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -350.0
COLD-APPLIED BASE PLY:
C-118 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H or H-Shield
D-IS
Min. 0.25-inch Dens Deck
Prime, DEXcell FA Glass Mat
Roof Board or SECUROCK
Gypsum-Fiber Roof Board
D-IS SBS-CA1, SBS-
CA2
(Optional) SBS-CA1, SBS-
CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-119 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H or
H-Shield
D-IS
Min. 0.25-inch Dens Deck
Prime or DEXcell FA Glass
Mat Roof Board
D-IS SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 56 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-120 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H or
H-Shield
D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-121 Structural
concrete None Min. 1-inch ENRGY 3, Polytherm H or H-
Shield D-IS
Min. 0.25-inch Dens Deck
Prime or SECUROCK Gypsum-
Fiber Roof Board
D-IS SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
C-122 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA, M-
PG1
Min. 0.25-inch Dens Deck, Dens
Deck Prime, DEXcell FA Glass Mat
Roof Board, SECUROCK Gypsum-
Fiber Roof Board or SECUROCK
Glass-Mat Roof Board, min. 7/16-
inch DEXcell Cement Roof Board
or min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA or
M-PG1
SBS-CA1, SBS-
CA2
(Optional) SBS-CA1, SBS-
CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-123 Structural
concrete None
Min. 1-inch Polytherm or ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA, M-
PG1
Min. 0.25-inch Dens Deck
Prime or DEXcell FA Glass
Mat Roof Board, min. 7/16-
inch DEXcell Cement Roof
Board or min. 0.5-inch
SECUROCK Cement Roof
Board
M-OSFA, M-
PG1 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-124 Structural
concrete None
Min. 1-inch Polytherm or ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA, M-
PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
M-OSFA, M-
PG1
SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-125 Structural
concrete None
Min. 1-inch Polytherm or ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA, M-
PG1
Min. 0.25-inch Dens Deck, Dens
Deck Prime, DEXcell FA Glass Mat
Roof Board, SECUROCK Gypsum-
Fiber Roof Board or SECUROCK
Glass-Mat Roof Board, min. 7/16-
inch DEXcell Cement Roof Board
or min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA, M-
PG1
SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 57 of 83
TABLE 3A: STRUCTURAL CONCRETE DECKS; MIN. 2,500 PSI – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TO NOTE 16 FOR VAPOR BARRIER OPTIONS
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-126 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
OB500
Min. 0.25-inch Dens Deck
Prime, DEXcell FA Glass Mat
Roof Board or SECUROCK
Gypsum-Fiber Roof Board
OB500 SBS-CA1, SBS-
CA2
(Optional) SBS-CA1, SBS-
CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-127 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
OB500
Min. 0.25-inch Dens Deck
Prime or DEXcell FA Glass
Mat Roof Board
OB500 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-128 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-129 Structural
concrete None Min. 1-inch Polytherm, ACFoam II, ENRGY
3 or Multi-Max FA3 OB500
Min. 0.25-inch Dens Deck
Prime, DEXcell FA Glass Mat
Roof Board or SECUROCK
Gypsum-Fiber Roof Board
OB500 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
C-130 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
CR-20
Min. 0.25-inch Dens Deck
Prime or SECUROCK Gypsum-
Fiber Roof Board
CR-20 SBS-CA1, SBS-
CA2
(Optional) SBS-CA1, SBS-
CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-131 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
CR-20
Min. 0.25-inch Dens Deck
Prime or DEXcell FA Glass
Mat Roof Board
CR-20 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-132 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-133 Structural
concrete None Min. 1-inch ENRGY 3, Polytherm H, H-
Shield, Multi-Max FA3 CR-20
Min. 0.25-inch Dens Deck
Prime or SECUROCK Gypsum-
Fiber Roof Board
CR-20 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 58 of 83
TABLE 3B: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE F: NON-INSULATED, BONDED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1) Primer Roof Cover (Note 15) *MDP
(psf) Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
C-134 Structural concrete PG100 (Optional) SBS-TA (Optional) SBS-TA SBS-TA -495.0
C-135 Structural concrete PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA,
SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -622.5
SELF-ADHERING BASE PLY:
C-136 Structural concrete PG100 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -315.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
C-137 Structural concrete PG100 APP-SA-H (Optional) APP-TA APP-TA -315.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
C-138 Structural concrete PG100 SBS-SA-H (Optional) SBS-TA SBS-TA -315.0
COLD-APPLIED BASE PLY:
C-139 Structural concrete None SBS-CA1 None SBS-CA1, SBS-CA2, APP-CA1 -105.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 59 of 83
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CELCORE (NOA 13-0307.02):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-1 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -222.5
SELF-ADHERING BASE PLY:
LWC-2 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -222.5
LWC-3 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
LWC-4 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-5 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
LWC-6 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-7 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
LWC-8 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 60 of 83
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ELASTIZELL (NOA 18-0208.03):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-9 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -225.0
LWC-10 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -180.0
SELF-ADHERING BASE PLY:
LWC-11 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
(Optional)
Additional layers of
base insulation
OB500 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -120.0
LWC-12 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-120.0
LWC-13 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
(Optional)
Additional layers of
base insulation
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-225.0
LWC-14 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-225.0
LWC-15 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -180.0
LWC-16 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-180.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 61 of 83
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-17 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-180.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-18 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 APP-SA-H (Optional) APP-
TA APP-TA -120.0
LWC-19 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
(Optional)
Additional layers of
base insulation
OB500 APP-SA-H (Optional) APP-
TA APP-TA -225.0
LWC-20 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 APP-SA-H (Optional) APP-
TA APP-TA -225.0
LWC-21 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -180.0
LWC-22 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -180.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-23 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA-H (Optional) SBS-
TA SBS-TA -120.0
LWC-24 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
(Optional)
Additional layers of
base insulation
OB500 SBS-SA-H (Optional) SBS-
TA SBS-TA -225.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 62 of 83
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-25 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA-H (Optional) SBS-
TA SBS-TA -225.0
LWC-26 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -180.0
LWC-27 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -180.0
MEARLCRETE (NOA 13-1007.09):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-28 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -222.5
SELF-ADHERING BASE PLY:
LWC-29 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -222.5
LWC-30 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
LWC-31 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-32 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 63 of 83
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-33 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-34 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
LWC-35 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 64 of 83
TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
‡Deck
(Note 1)
Lightweight Concrete
(Note 14)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-36
Min. 22
ga., Type B,
vented
steel at
max. 5 ft
spans
Min. 300 psi, min. 2-inch
Celcore Cellular
Concrete, Elastizell
Lightweight Insulating
Concrete or Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
4-inch lap
and 7-inch
o.c. in two,
equally
spaced
center rows
(Optional) Min.
1.5-inch
Polytherm,
ACFoam II,
Polytherm H, H-
Shield, Multi-
Max FA3 or
Polytherm
HA
Min. 1.5-inch Thermaroof
Composite, Polytherm
Composite, or min. 0.5-
inch Structodek High
Density Fiberboard Roof
Insulation or min. 0.75-
inch Fesco Board
(homogeneous)
HA
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA
Base) BP-
AA, SBS-AA,
SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
LWC-37
Min. 22
ga., Type B,
vented
steel at
max. 5 ft
spans
Min. 300 psi, min. 2-inch
Celcore Cellular
Concrete, Elastizell
Lightweight Insulating
Concrete or Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
4-inch lap
and 7-inch
o.c. in two,
equally
spaced
center rows
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H, H-
Shield, Multi-
Max FA3 or
Polytherm
HA None N/A SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-45.0
LWC-38
Min. 22
ga., Type B,
vented
steel at
max. 5 ft
spans
Min. 300 psi, min. 2-inch
Celcore Cellular
Concrete, Elastizell
Lightweight Insulating
Concrete or Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
4-inch lap
and 7-inch
o.c. in two,
equally
spaced
center rows
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H, H-
Shield, Multi-
Max FA3 or
Polytherm
HA None N/A APP-SA-H (Optional)
APP-TA APP-TA -45.0
LWC-39
Min. 22
ga., Type B,
vented
steel at
max. 5 ft
spans
Min. 300 psi, min. 2-inch
Celcore Cellular
Concrete, Elastizell
Lightweight Insulating
Concrete or Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
min. 4-inch
lap and 7-
inch o.c. at
two, equally
spaced
center rows
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H, H-
Shield, Multi-
Max FA3 or
Polytherm
HA None N/A SBS-SA-H (Optional)
SBS-TA SBS-TA -45.0
‡ NOTE: For steel deck application where specific deck attachment is not referenced, tested attachment was 5/8” puddle welds with weld-washers or Tek/5 screws spaced 6” o.c.
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 65 of 83
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. ‡Deck (Note 1) Lightweight Concrete (Note 14)
Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Base Ply Cap Ply
PRE-EXISTENT CELLULAR LIGHTWEIGHT INSULATING CONCRETE:
LWC-40
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick pre-
existent cellular LWC. Note: To
qualify the LWIC under this
assembly, an OMG CR BPF shall
achieve an average withdrawal of
53 lbf when tested per TAS 105 or
ANSI/SPRI FX-1
B3 or B11 OMG CR BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
(Optional)
BP-AA, SBS-
AA
SBS-AA, APP-
TA -45.0
CELCORE (NOA 13-0307.02):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-41
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick
Celcore B1 through B11
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA SBS-AA -45.0
LWC-42
Min. 26 ga., type HF steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF
B1, B2, B3, B4,
B7, B8, B10 or
B11
OMG CR BPF
9-inch o.c. in a 3-inch lap and 9-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA SBS-AA -45.0
LWC-43
Min. 22 ga., type B steel at max
6 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF
B1, B2, B3, B4,
B7, B8, B10 or
B11
OMG CR BPF
7-inch o.c. in a 3-inch lap and 14-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA SBS-AA -45.0
LWC-44
Min. 22 ga., type B steel at max
6 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF
B1, B2, B3, B4,
B7, B8, B10 or
B11
OMG CR BPF
9-inch o.c. in a 3-inch lap and 9-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA SBS-AA -45.0
LWC-45
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF B1, B2 or B11 Trufast Twin
Loc-Nail
9-inch o.c. in a 4-inch lap and 18-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-45.0
LWC-46
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore MF B2 or B11 Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three
equally spaced, staggered center rows
BP-AA, SBS-
AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-60.0
LWC-47
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore MF
B2 (with poly-
film top surface) Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three
equally spaced, staggered center rows
SBS-TA or
APP-TA
SBS-TA or
APP-TA -60.0
LWC-48
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore B1 through B11
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA, APP-
TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 66 of 83
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. ‡Deck (Note 1) Lightweight Concrete (Note 14)
Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Base Ply Cap Ply
LWC-49
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore MF Elastobase P Trufast FM-
290
10-inch o.c. in a 4-inch lap and 10-inch o.c. in three
equally spaced, staggered center rows
(Optional)
BP-AA, SBS-
AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -90.0
SELF-ADHERING BASE PLY:
LWC-50
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nail
9-inch o.c. in a 4-inch lap and 18-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-45.0
LWC-51
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore MF
B2 (with poly-
film top surface) Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three
equally spaced, staggered center rows SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-52
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nail
9-inch o.c. in a 4-inch lap and 18-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
APP-SA-H APP-TA -45.0
LWC-53
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore MF
B2 (with poly-
film top surface) Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three
equally spaced, staggered center rows APP-SA-H APP-TA -60.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-54
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick
Celcore MF Cellular Concrete with
Celcore HS Rheology Modifying
Admixture
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nail
9-inch o.c. at a min. 4-inch lap and 18-inch o.c. at
two, equally spaced, staggered rows in the field of
the sheet
SBS-SA-H SBS-TA -45.0
LWC-55
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Celcore MF Cellular Concrete with
Celcore HS Rheology Modifying
Admixture
B2 (with poly-
film top surface) Trufast FM-90 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at
three equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0
ELASTIZELL (NOA 18-0208.03):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-56
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick
Elastizell Range II B1 through B11
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA, SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-45.0
LWC-57
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick
Elastizell Range II
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 67 of 83
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. ‡Deck (Note 1) Lightweight Concrete (Note 14)
Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Base Ply Cap Ply
LWC-58
Min. 22 ga., type B vented
steel at max 5 ft spans or
structural concrete
Min. 350 psi, min. 2-inch thick
Elastizell with Zell-Crete Fibers,
supplemental attached with
Roofgrip #21 and 3-inch plates at 1
per 8 ft2
Elastobase P
(with poly-film
top surface)
Trufast FM-
290
8-inch o.c. in a 4-inch lap and 8-inch o.c. in three,
equally spaced, staggered rows in the field of the
sheet
(Optional)
BP-AA, SBS-
AA, SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-52.5
LWC-59
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick
Elastizell with Zell-Crete Fibers,
supplemental attached with
Roofgrip #21 and 3-inch plates at 1
per 8 ft2
B2 or B11
Trufast Twin
Loc-Nails
(min. 1.8-inch)
6-inch o.c. in a 4-inch lap and 6-inch o.c. in three,
equally spaced, staggered rows in the field of the
sheet
BP-AA or
SBS-AA
SBS-AA, SBS-
TA, SBS-SA,
APP-TA or
APP-SA
-60.0
LWC-60
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick
Elastizell with Zell-Crete Fibers,
supplemental attached with
Roofgrip #21 and 3-inch plates at 1
per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nails
(min. 1.8-inch)
6-inch o.c. in a 4-inch lap and 6-inch o.c. in three,
equally spaced, staggered rows in the field of the
sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -60.0
SELF-ADHERING BASE PLY:
LWC-61
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick
Elastizell Range II
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-45.0
LWC-62
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick
Elastizell with Zell-Crete Fibers,
supplemental attached with
Roofgrip #21 and 3-inch plates at 1
per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nails
(min. 1.8-inch)
6-inch o.c. in a 4-inch lap and 6-inch o.c. in three,
equally spaced, staggered rows in the field of the
sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-63
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick
Elastizell Range II
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 3-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
APP-SA-H APP-TA -45.0
LWC-64
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick
Elastizell with Zell-Crete Fibers,
supplemental attached with
Roofgrip #21 and 3-inch plates at 1
per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nails
(min. 1.8-inch)
6-inch o.c. in a 4-inch lap and 6-inch o.c. in three,
equally spaced, staggered rows in the field of the
sheet
APP-SA-H APP-TA -60.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 68 of 83
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. ‡Deck (Note 1) Lightweight Concrete (Note 14)
Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Base Ply Cap Ply
LWC-65
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick
Range II Elastizell Lightweight
Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two,
equally spaced, staggered rows in the field of the
sheet
SBS-SA-H SBS-TA -45.0
LWC-66
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick
Elastizell with Zell-Crete Fibers,
supplemental attached with
Roofgrip #21 and 3-inch plates at 1
per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin
Loc-Nails
(min. 1.8-inch)
6-inch o.c. at a min. 4-inch lap and 6-inch o.c. at
three, equally spaced, staggered rows in the field of
the sheet
SBS-SA-H SBS-TA -60.0
MEARLCRETE (NOA 13-1007.09):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-67
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Mearlcrete
B1, B2, B3, B7 or
B11
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 4-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
BP-AA, SBS-
AA, SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-52.5
LWC-68
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Mearlcrete
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 4-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -52.5
SELF-ADHERING BASE PLY:
LWC-69
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Mearlcrete
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 4-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-52.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-70
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Mearlcrete
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. in a 4-inch lap and 7-inch o.c. in two,
equally spaced, staggered rows in the field of the
sheet
APP-SA-H APP-TA -52.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-71
Min. 22 ga., type B steel at max
5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick
Mearlcrete
B2 (with poly-
film top surface)
Trufast FM-90
or OMG CR
BPF
7-inch o.c. at a min. 4-inch lap and 7-inch o.c. at two,
equally spaced, staggered rows in the field of the
sheet
SBS-SA-H SBS-TA -52.5
‡ NOTE: For steel deck application where specific deck attachment is not referenced, tested attachment was 5/8” puddle welds with weld-washers or Tek/5 screws spaced 6” o.c. See Note 1.
A. Base Sheets options in Table 4C are coded as follows:
➢ B1: Polyglass G2 Base; B2: Elastobase or Elastobase P; B3: GAFGLAS #75; B4: GAFGLAS Stratavent Nailable Venting Base Sheet; B5: GAFGLAS Ply 4; B6: GAFGLAS FlexPly 6; B7: JM Perma Ply No. 28; B8: JM
Vensulation; B9: JM GlasPly IV; B10: JM GlasPly Premier; B11: Elastovent
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 69 of 83
TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No. Deck (Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
CWF-1 Existing Min. 2.5-inch Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board or min. 0.5-inch Structodek High
Density Fiberboard Roof Insulation
D-IS or
OB500
BP-AA,
SBS-AA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -45.0
CWF-2 Existing Min. 2.5-inch Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or
OB500
SBS-TA
or APP-
TA
(Optional) SBS-
TA or APP-TA
SBS-TA, APP-
TA -45.0
CWF-3
Existing Min. 2-inch Tectum Plank or
Tectum LS Plank; 2 ft span; three (3)
evenly spaced #15 screws with 2”
diameter plates per joist
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board or min. 0.5-inch Structodek High
Density Fiberboard Roof Insulation
CR-20 BP-AA,
SBS-AA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -52.5
CWF-4
Existing Min. 2-inch Tectum Plank or
Tectum LS Plank; 2 ft span; three (3)
evenly spaced #15 screws with 2”
diameter plates per joist
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20
SBS-TA
or APP-
TA
(Optional) SBS-
TA or APP-TA
SBS-TA, APP-
TA -52.5
SELF-ADHERING BASE PLY:
CWF-5 Existing Min. 2.5-inch Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA or
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-45.0
CWF-6
Existing Min. 2-inch Tectum Plank or
Tectum LS Plank; 2 ft span; three (3)
evenly spaced #15 screws with 2”
diameter plates per joist
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA or
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-52.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
CWF-7 Existing Min. 2.5-inch Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or
OB500
APP-SA-
H
(Optional) APP-
TA APP-TA -45.0
CWF-8
Existing Min. 2-inch Tectum Plank or
Tectum LS Plank; 2 ft span; three (3)
evenly spaced #15 screws with 2”
diameter plates per joist
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 APP-SA-
H
(Optional) APP-
TA APP-TA -52.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 70 of 83
TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No. Deck (Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CWF-9 Existing Min. 2.5-inch Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or
OB500
SBS-SA-
H
(Optional) SBS-
TA SBS-TA -45.0
CWF-10
Existing Min. 2-inch Tectum Plank or
Tectum LS Plank; 2 ft span; three (3)
evenly spaced #15 screws with 2”
diameter plates per joist
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch Dens Deck, Dens Deck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-SA-
H
(Optional) SBS-
TA SBS-TA -52.5
TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
CWF-11
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase,
Elastobase
P,
Elastovent
or Polyglass
G2 Base
Trufast
Twin
Loc-Nail
9-inch o.c. in 4-inch
lap and 18-inch o.c.
in two, equally
spaced, staggered
center rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max FA3,
Hot asphalt
Min. 0.25-inch Dens Deck,
Dens Deck Prime, SECUROCK
Gypsum-Fiber Roof Board,
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-
inch Structodek High Density
Fiberboard Roof Insulation
Hot asphalt BP-AA,
SBS-AA
(Optional)
BP-AA, SBS-
AA, SBS-TA
or APP-TA
SBS-
AA,
SBS-TA,
APP-TA
-45.0*
CWF-12
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase,
Elastobase
P,
Elastovent
or Polyglass
G2 Base
Trufast
Twin
Loc-Nail
9-inch o.c. in 4-inch
lap and 18-inch o.c.
in two, equally
spaced, staggered
center rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max FA3,
Hot asphalt
Min. 0.25-inch Dens Deck,
Dens Deck Prime,
SECUROCK Gypsum-Fiber
Roof Board
Hot asphalt
SBS-TA
or APP-
TA
(Optional)
SBS-TA,
SBS-SA or
APP-TA
SBS-TA,
SBS-SA,
APP-
TA,
APP-SA
-45.0*
SELF-ADHERING BASE PLY:
CWF-13
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase,
Elastobase
P,
Elastovent
or Polyglass
G2 Base
Trufast
Twin
Loc-Nail
9-inch o.c. in 4-inch
lap and 18-inch o.c.
in two, equally
spaced, staggered
center rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max FA3,
Hot asphalt
Min. 0.25-inch Dens Deck,
Dens Deck Prime,
SECUROCK Gypsum-Fiber
Roof Board
Hot asphalt SBS-SA
(Optional)
SBS-TA,
SBS-SA or
APP-TA
SBS-TA,
SBS-SA,
APP-
TA,
APP-SA
-45.0*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 71 of 83
TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CWF-14
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase,
Elastobase
P,
Elastovent
or Polyglass
G2 Base
Trufast
Twin
Loc-Nail
9-inch o.c. in 4-inch
lap and 18-inch o.c.
in two, equally
spaced, staggered
center rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max FA3,
Hot asphalt
Min. 0.25-inch Dens Deck,
Dens Deck Prime,
SECUROCK Gypsum-Fiber
Roof Board
Hot asphalt APP-SA-
H
(Optional)
APP-TA APP-TA -45.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
CWF-15
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase,
Elastobase
P,
Elastovent
or Polyglass
G2 Base
Trufast
Twin
Loc-Nail
9-inch o.c. at min. 4-
inch lap and 18-inch
o.c. at two, equally
spaced, staggered
center rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max FA3,
Hot asphalt
Min. 0.25-inch Dens Deck,
Dens Deck Prime,
SECUROCK Gypsum-Fiber
Roof Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -45.0*
TABLE 5C: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15)
MDP (psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CWF-16
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 2-inch H-
Shield or
Polytherm H
OMG Polymer GypTec Plate
with Polymer GypTec or Trufast
TL 3 in. Plate with TL Fastener
1 per
4.0 ft2
Min. 0.5-inch Structodek
High Density Fiberboard
Roof Insulation
Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 72 of 83
TABLE 5D: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
CWF-17
Existing Min. 2.5-
inch Tectum
Plank or Tectum
LS Plank
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch Dens Deck, Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board or min. 0.5-
inch Structodek High Density Fiberboard Roof
Insulation
Trufast Twin Loc-
Nails (min. 1-inch
embedment)
1 per
2.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 5E: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
CWF-18
Existing Min. 2.5-inch
Tectum Plank or Tectum
LS Plank
Elastobase, Elastobase P, Polyglass
G2 Base Trufast Twin Loc-Nails 9-inch o.c. in 4-inch lap and 18-inch o.c. in
two, equally spaced, staggered center rows
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 73 of 83
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No. Deck (Notes 1&12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
G-1
Existing, sound
poured gypsum or
gypsum plank deck
Min. 0.25-inch Dens Deck, Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board CR-20 None N/A
(Optional
if using
AA Ply)
BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-245.0
SELF-ADHERING BASE PLY:
G-2
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-72.5
G-3
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch min. 2.0 pcf, Insulfoam OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA,
APP-SA -112.5
G-4
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-112.5
G-5
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-112.5
G-6
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-72.5
G-7
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of
base insulation and/or min. 0.25-
inch SECUROCK Gypsum-Fiber Roof
Board
M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-202.5
G-8
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch, min. 2.0 pcf Insulfoam, Polytherm,
ACFoam II, Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or Multi-Max
FA3
CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-72.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 74 of 83
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No. Deck (Notes 1&12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-9
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of base
insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0
G-10
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-240.0
G-11
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-
Shield CG or Multi-Max FA3
CR-20
(Optional) additional layers(s) of
base insulation and/or min. 0.25-
inch SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-257.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
G-12
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -112.5
G-13
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 APP-SA-H (Optional) APP-TA APP-TA -112.5
G-14
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of
base insulation and/or min. 0.25-
inch SECUROCK Gypsum-Fiber Roof
Board
M-OSFA APP-SA-H (Optional) APP-TA APP-TA -202.5
G-15
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
G-16
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1.5-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-
Shield CG or Multi-Max FA3
CR-20
(Optional) additional layers(s) of
base insulation and/or min. 0.25-
inch SECUROCK Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -257.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
G-17
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
G-18
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -112.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 75 of 83
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No. Deck (Notes 1&12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-19
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -112.5
G-20
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
G-21
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of
base insulation and/or min. 0.25-
inch SECUROCK Gypsum-Fiber Roof
Board
M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -202.5
G-22
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch, min. 2.0 pcf EPS insulation board,
Polytherm, ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
G-23
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
G-24
Existing, sound
poured gypsum or
gypsum plank
Min. 1.5-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-
Shield CG or Multi-Max FA3
CR-20
(Optional) additional layers(s) of
base insulation and/or min. 0.25-
inch SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -257.5
COLD APPLIED BASE PLY:
G-25
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield ISO 95+ GL, Multi-Max
FA3, RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA
Min. 0.25-inch Dens Deck, Dens Deck
Prime, DEXcell FA Glass Mat Roof Board,
SECUROCK Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK Cement Roof
Board
M-OSFA SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-120.0
G-26
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm or ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max
FA3, RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA
Min. 0.25-inch Dens Deck Prime or
DEXcell FA Glass Mat Roof Board,
min. 7/16-inch DEXcell Cement Roof
Board or min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA SBS-CA1 None
SBS-CA1,
SBS-CA2,
APP-CA1
-127.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 76 of 83
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No. Deck (Notes 1&12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-27
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm or ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max
FA3, RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board M-OSFA SBS-CA1,
SBS-CA2 None
SBS-CA1,
SBS-CA2,
APP-CA1
-127.5
G-28
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm or ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max
FA3, RESISTA or UltraMax or min. 2-inch
DECKMATE Plus or DECKMATE Plus FA
M-OSFA
Min. 0.25-inch Dens Deck, Dens Deck
Prime, DEXcell FA Glass Mat Roof Board,
SECUROCK Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK Cement Roof
Board
M-OSFA SBS-CA1,
SBS-CA2 None SBS-CA1,
SBS-CA2 -202.5
G-29
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
OB500
Min. 0.25-inch Dens Deck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof
Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-112.5
G-30
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20
Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-120.0
G-31
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20 Min. 0.25-inch Dens Deck Prime or
DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None
SBS-CA1,
SBS-CA2,
APP-CA1
-127.5
G-32
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2 None
SBS-CA1,
SBS-CA2,
APP-CA1
-127.5
G-33
Existing, sound
poured gypsum or
gypsum plank deck
Min. 1-inch ENRGY 3, Polytherm H, H-Shield, Multi-
Max FA3 CR-20
Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1,
SBS-CA2 -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 77 of 83
TABLE 6B: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten
(Note 11) Attach Type
Attach
(Notes
6,7,8)
Type
Attach
(Notes
6,7,8)
Base Ply Ply Cap Ply
G-34
Existing,
sound poured
gypsum or
gypsum plank
deck
Elastobase,
Elastobase
P,
Elastovent
or Polyglass
G2 Base
Trufast FM-75
or FM-90 or
Twin Loc-Nails
9-inch o.c. in 4-
inch lap and 18-
inch o.c. in two,
equally spaced,
staggered
center rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3, Polytherm or
Multi-Max FA3
Hot
asphalt
Min. 0.25-inch Dens Deck, Dens
Deck Prime, SECUROCK Gypsum-
Fiber Roof Board, Min. 0.75-inch
Fesco Board (homogeneous) or
min. 0.5-inch Structodek High
Density Fiberboard Roof Insulation
Hot
asphalt
BP-AA,
SBS-AA
(Optional)
BP-AA, SBS-
AA, SBS-TA
or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 6C: GYPSUM DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
G-35
Existing sound
poured gypsum or
gypsum plank deck
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch Dens Deck, Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board or min. 0.5-
inch Structodek High Density Fiberboard Roof
Insulation
Trufast Twin Loc-
Nails (min. 1-inch
embedment)
1 per
2.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 6D: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
G-36
Existing sound poured
gypsum or gypsum plank
deck
Elastobase, Elastobase P,
Elastovent or Polyglass G2
Base
Trufast FM-75 or FM-
90 or Twin Loc-Nails
9-inch o.c. in 4-inch lap and 18-inch o.c.
in two, equally spaced, staggered center
rows
(Optional) BP-AA, SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-TA,
APP-TA -45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 78 of 83
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
R-1 Existing asphaltic
roof Min. 1.5-inch Multi-Max FA3 D-IS
Min. 0.25-inch Dens Deck, Dens Deck
Prime or SECUROCK Gypsum-Fiber Roof
Board
D-IS
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA
or APP-TA -67.5
R-2 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 or min. 2.0 pcf Insulfoam D-IS
Min. 0.25-inch Dens Deck, Dens Deck
Prime or SECUROCK Gypsum-Fiber Roof
Board
D-IS
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA,
or APP-TA -90.0
R-3 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or ISO 95+GL OB500
Min. 0.25-inch Dens Deck, Dens Deck
Prime or SECUROCK Gypsum-Fiber Roof
Board
OB500
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA,
or APP-TA -127.5
R-4 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board M-OSFA
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA,
or APP-TA -157.5
R-5 Existing asphaltic
roof
Min. 1.5-inch Ultra-Max or Multi-Max
FA-3, min. 1.3-inch Polytherm G,
ACFoam III or min. 1.0-inch ISO 95+GL,
Polytherm H, H-Shield, H-Shield CG or
ENRGY 3 or min. 2.0 pcf Insulfoam
CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board CR-20 BP-AA, SBS-
AA
(Optional) BP-AA, SBS-
AA SBS-AA -225.0
R-6 Existing asphaltic
roof
Min. 1.5-inch Ultra-Max or Multi-Max
FA-3, min. 1.3-inch Polytherm G,
ACFoam III or min. 1.0-inch ISO 95+GL,
Polytherm H, H-Shield, H-Shield CG or
ENRGY 3 or min. 2.0 pcf Insulfoam
CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5
SELF-ADHERING BASE PLY:
R-7 Existing asphaltic
roof Min. 1.5-inch Multi-Max FA3 D-IS
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board or
Dens Deck Prime
D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
R-8 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3 or Multi-Max FA3 or min. 2.0
pcf Insulfoam
D-IS Min. 0.25-inch Dens Deck Prime D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-9 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS (Optional) additional layers(s) of base
insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA -90.0
R-10 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 79 of 83
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-11 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -90.0
R-12 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield or
min. 2.0 pcf Insulfoam
OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-13 Existing asphaltic
roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base
insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA -120.0
R-14 Existing asphaltic
roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -120.0
R-15 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield OB500
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -127.5
R-16 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-17 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -157.5
R-18 Existing asphaltic
roof
Min. 1.5-inch min. 2.0 pcf Insulfoam,
Min. 2-inch Polytherm, ACFoam II, min.
1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm
H, H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-19 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers(s) of base
insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0
R-20 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
R-21 Existing asphaltic
roof
(Optional if Top Layer Insulation
installed) Min. 1.5-inch Ultra-Max or
Multi-Max FA-3, min. 1.3-inch
Polytherm G, ACFoam III or min. 1.0-
inch ISO 95+GL, Polytherm H, H-Shield,
H-Shield CG or ENRGY 3
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 80 of 83
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-22 Existing asphaltic
roof
(Optional if Top Layer Insulation
installed) Min. 2-inch Polytherm,
ACFoam II, ENRGY-3, Polytherm H or H-
Shield
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -247.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
R-23 Existing asphaltic
roof Min. 1.5-inch Multi-Max FA3 D-IS
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board or
Dens Deck Prime
D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5
R-24 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -90.0
R-25 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
D-IS APP-SA-H (Optional) APP-TA APP-TA -90.0
R-26 Existing asphaltic
roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board OB500 APP-SA-H (Optional) APP-TA APP-TA -120.0
R-27 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield OB500
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5
R-28 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
M-OSFA APP-SA-H (Optional) APP-TA APP-TA -157.5
R-29 Existing asphaltic
roof
Min. 1.5-inch Ultra-Max or Multi-Max
FA-3, min. 1.3-inch Polytherm G,
ACFoam III or min. 1.0-inch ISO 95+GL,
Polytherm H, H-Shield, H-Shield CG or
ENRGY 3
CR-20
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
R-30 Existing asphaltic
roof
Min. 2-inch Polytherm, ACFoam II,
ENRGY-3, Polytherm H or H-Shield CR-20
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -247.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
R-31 Existing asphaltic
roof Min. 1.5-inch Multi-Max FA3 D-IS
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board or
Dens Deck Prime
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 81 of 83
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-32 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3 or Multi-Max FA3 or min. 2.0
pcf Insulfoam
D-IS Min. 0.25-inch Dens Deck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-33 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -90.0
R-34 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -90.0
R-35 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield or
min. 2.0 pcf Insulfoam
OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-36 Existing asphaltic
roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -120.0
R-37 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield OB500
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5
R-38 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-39 Existing asphaltic
roof
Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -157.5
R-40 Existing asphaltic
roof
Min. 1.5-inch min. 2.0 pcf Insulfoam,
Min. 2-inch Polytherm, ACFoam II, min.
1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm
H, H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-41 Existing asphaltic
roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
R-42 Existing asphaltic
roof
Min. 1.5-inch Ultra-Max or Multi-Max
FA-3, min. 1.3-inch Polytherm G,
ACFoam III or min. 1.0-inch ISO 95+GL,
Polytherm H, H-Shield, H-Shield CG or
ENRGY 3
CR-20
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 82 of 83
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-43 Existing asphaltic
roof
Min. 2-inch Polytherm, ACFoam II,
ENRGY-3, Polytherm H or H-Shield CR-20
(Optional) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
COLD APPLIED BASE PLY:
R-44 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H or H-Shield
D-IS
Min. 0.25-inch Dens Deck Prime, DEXcell
FA Glass Mat Roof Board or SECUROCK
Gypsum-Fiber Roof Board
D-IS SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -90.0
R-45 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or
min. 2-inch DECKMATE Plus or
DECKMATE Plus FA
M-OSFA,
M-PG1
Min. 0.25-inch Dens Deck, Dens Deck
Prime, DEXcell FA Glass Mat Roof Board,
SECUROCK Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK Cement Roof
Board
M-OSFA or
M-PG1
SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
R-46 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm or
ACFoam II, Polytherm G, ACFoam III,
EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield, ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or
min. 2-inch DECKMATE Plus or
DECKMATE Plus FA
M-OSFA,
M-PG1
Min. 0.25-inch Dens Deck Prime or
DEXcell FA Glass Mat Roof Board, min.
7/16-inch DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK Cement Roof
Board
M-OSFA, M-
PG1 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-47 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm or
ACFoam II, Polytherm G, ACFoam III,
EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield, ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or
min. 2-inch DECKMATE Plus or
DECKMATE Plus FA
M-OSFA,
M-PG1
Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board
M-OSFA, M-
PG1
SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-48 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm or
ACFoam II, Polytherm G, ACFoam III,
EnergyGuard Polyiso Insulation, ENRGY
3, Polytherm H, H-Shield, ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or
min. 2-inch DECKMATE Plus or
DECKMATE Plus FA
M-OSFA,
M-PG1
Min. 0.25-inch Dens Deck, Dens Deck
Prime, DEXcell FA Glass Mat Roof Board,
SECUROCK Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK Cement Roof
Board
M-OSFA, M-
PG1
SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2 -157.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P40690.12.13-1-R11 for FL16717-R10
Certificate of Authorization #32455 7TH EDITION (2020) FBC HVHZ EVALUATION Revision 11: 10/01/2020
©2018, NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 83 of 83
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) *MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-49 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
OB500
Min. 0.25-inch Dens Deck Prime, DEXcell
FA Glass Mat Roof Board or SECUROCK
Gypsum-Fiber Roof Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
R-50 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
OB500 Min. 0.25-inch Dens Deck Prime or
DEXcell FA Glass Mat Roof Board OB500 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-51 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board OB500 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-52 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20 Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
R-53 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20 Min. 0.25-inch Dens Deck Prime or
DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-54 Existing asphaltic
roof
(Optional) Min. 1-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber
Roof Board CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-55 Existing asphaltic
roof
(Optional) Min. 1-inch ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or
SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2 -232.5
TABLE 7B: RECOVER APPLICATIONS
SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER
System No. Substrate
(Notes 1 & 12) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply
R-56 Existing fully-adhered, granule-
surfaced modified bitumen None Polyflex, torch-applied (Optional) Polyflex, torch-applied APP-TA -362.5
R-57 Existing fully-adhered, granule-
surfaced modified bitumen PG100 Polyflex, torch-applied (Optional) Polyflex, torch-applied APP-TA -445.0