Review Type Status Reviewed By Date Started Date Completed Date Released
FRONT COUNTER REVIEW COMPLETE Ellen Vaughn 1/15/2021 1/15/2021 1/15/2021
Comment:
NOTIFIED FOR PICK UP PENDING
Comment:
PLANS EXAMINER REVIEW INCOMPLETE Jpi, Inc-Andrew 1/20/2021
1/20/2021
Comment: 1) THE PRODUCT PRESSURE DOES NOT MEET THE REQUIRED DESIGN PRESSURE. (R301).
SEE PAGE 2, NOTE 9 FOR MECHANICALLY ATTACHED COMPONENTS OR PARTIALLY-BONDED
INSULATION, THE MAXIMUM DESIGN PRESSURE FOR THE SELECTED ASSEMBLY SHALL MEET OR EXCEED
AT LEAST THE ZONE 1 PRIME DESIGN PRESSURE DETERMINED IN
ACCORDANCE WITH FBC CHAPTER 16. ELEVATED PRESSURE ZONES SHALL EMPLOY AN ATTACHMENT
DENSITY DESIGNED BY A QUALIFIED DESIGN PROFESSIONAL TO RESIST THE ELEVATED PRESSURE
CRITERIA. COMMONLY USED METHODS ARE
ANSI/SPRI WD1, FM LOSS PREVENTION DATA SHEET 1-29, ROOFING APPLICATION STANDARD RAS 117
AND ROOFING APPLICATION STANDARD RAS 137. ASSEMBLIES MARKED WITH AN ASTERISK* CARRY THE
LIMITATIONS SET FORTH IN
SECTION 2.2.10.1 OF FM LOSS PREVENTION DATA SHEET 1-29 (FEBRUARY 2020) FOR ZONE 2/3
ENHANCEMENTS
1/20/2021
Comment: 2) SEE PAGE 3, NOTE 11 FOR MECHANICALLY ATTACHED COMPONENTS OVER EXISTING DECKS,
FASTENERS SHALL BE TESTED IN THE EXISTING DECK FOR WITHDRAWAL RESISTANCE. A QUALIFIED
DESIGN PROFESSIONAL SHALL REVIEW THE DATA FOR COMPARISON TO THE MINIMUM REQUIREMENTS
FOR THE SYSTEM. TESTING AND ANALYSIS SHALL BE IN ACCORDANCE WITH ANSI/SPRI FX-1 OR TESTING
APPLICATION STANDARD TAS 105. ([A]107.2.1)
Email:Adamryckman@Alliancegro
upllc.Com;Ap@Alliancegrou
pllc.Com
REVIEW COMMENTS