HomeMy WebLinkAboutBuilding plans1.1.1 PROJECT NOTES: 1 1.1.2 THIS PHOTOVOLTAIC iEVI SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE (NEC) ARTICLE 69C ALL MANUFACTURERS S LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTION'S (AHJ) APPLICABLE CODES. 1.13 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION 1.1A ALL PV SYSTEM COMPONENTS; MODULES, UTIL1TY-INTERACTIVE INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS 2 REQUIRED BY NEC OJA 8 NEC AOSO: PV MODULES'. UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929.519 COMBINER BOX(EB): UL 1703OR UL 1741 ACCESSORY 1,15 NEC 690.35 REFERS SPECIFICALLY TO 'UNGROUNDED' PV SYSTEMS ALSO DESIGNATED AS 'TRANSFORMERLESSBY INVERTER MANUFACTURERS AND "NONISOLATEO• BY UNDERWRITERS LABORATORY. 1.1.6 INVERTERIS) USED IN UNGROUNDED SYSTEM SHALL BE LISTED FOR THIS USE [NEC 690.35 (G)I. 1.1.7 AS SPECIFIED BY THE AHJ, EQUIPMENT USED IN UNGROUNDED SYSTEMS LABELED ACCORDING TO NEC 690,35 (F). 1.7 8 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED 3 TEMP COEFFICIENT FOR VON. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO NEC 690.7. 1.1,9 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS. AND SOURCE CIRCUIT COMBIG-RS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4(D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING NEC 110.31. 1.1.10 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE, IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AN,'. 1.2.1 SCOPE OF WORK: 4 1,22 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THE GRID -TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIOR ROOF MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT. 131 WORK INCLUDES: 1.3.2 PV ROOF ATTACHMENTS IRONRIDGEFIABHFOOT2 1.3.3 PV RACKING SYSTEM INSTALLATION-IRONRIDGE XR100 1.3.4 PV MODULE AND INVERTER INSTALLATION - CANADIAN. SOLAR CS6K-275M I SOLAR EDGE SE760OA-US 124M 1.15 PV EQUIPMENT GROUNDING 5 1.3.6 PV SYSTEM WIRING TO ROOF -MOUNTED JUNCTION BOX 7.37 PV LOAD CENTERS (IF LOCILUDEDI 1.3.8 PV METERINGIMONITORING(IF INCLUDED) 1.3.9 PV DISCONNECTS 1.3.10 PV FINAL COMMISSIONING 1.3.11 LEI ELECTRICAL EQUIPMENT RETROFIT FOR PV 1.3.12 SIGNAGE PLACED IN ACCORDA.NCE'WITH LOCAL BUILDING CODE SCOPEOFWORK SYSTEM SIZE: STC:27x275=7425kW PTC 27 x 249.2=6728MV OC (27) CANADIAN SOLAR C56K-275M 6 (1) SOLAR EDGE SE7600A'US(24OV) ATTACHMENT TYPE: PORRIDGE FLASHFOOT2 MSP UPGRA.DE'. NO SHEET LIST TABLE NEW PV SYSTEM. 7.425 kWp TITLE vf n�lasun FF FILE T-00 jI� ER PAGE FITZNER RESIDENCE N ES G002 SYSTEM NOTES 6103 BALSAM DR A-'°' SITE PLAN' CONTRACTOR A-102 ELECTRICAL PLAN FORT PIERCE FL 34982 SOLAR AGRAGHMENTPAN VI440951NGDRP f E-601 E501 LINE DIAGRAM PHONE: 5614409515 #: 340261005290000 602 DESIGN TABLES ADDRESS: STREETSUITE ASSESSOR'S 6603 PLACARDS LORIUA01 WEST PALM BEACN FLORIOA WEST 33401 5301 ASSEMBLY DETAILS LIC,NO.: CVC56967 R001 RESOURCE DOCUMENT HIC.NO.: R-002 RESOURCE DOCUMENT ELE.NO.: UTAUTxoarz_uUseoms R1% _VIFUiSUI DFexR43 RESOURCE DOCUMENT R 004 RESOURCE DOCUMENT 11=1191NOFfl0A00M1TRl HTTO LAWS Us.CTTO GMLLaws vIG)bILL E PNOWILLBESORSEi0CML aaNAGE9NUD NROSECMiIONS. RA05 RESOURCE DOCUMENT R B RESOURCE DOCUMENT NEW PV SYSTEM: 7.425 kWp n; R-DON RESOURCE DOCUMENT FITZNER R-008 RESOURCE DOCUMENT R-009 RESOURCE DOCUMENT RESIDENCE R-010 RESOURCE DOCUMENT 6103 BALSAM DR R011 RESOURCE DOCUMENT FORT PIERCE, FL 34982 API: 340261005290000 O AERIAL �� c(} ln��' VDLNC 01 3jMTON NOT TO SCALE 1 �VVED FOR LIANCE REVU,'RTiDT ! PROJECT INFORMATION ENGI �RJA� IGNER DATE • \\\\� d//// OWNER OWNER rLA,NSAlcO EiiMITMiiSTmEICe� ®NB®�"'E ROERiaEL BENFIT<NER .\\ a ••• ..0,'; f OR NO MS EC 'ION WII,I, BE MADE. PROJECT MINAGEA ' NAME P14]4B l'J611NNOY6AAOi S6t4409611 �• � -p C. >•' �_ CONTAACTOR • U C56967 0 _ ¢ NAME. 9INYASUN CARD �'J 0 = '•, g PHONE E6144G3515 �N / — AUTHORITIES HAVING JURISDICTION t SIZE Il' li:ff e1, _C '•,_(.� G\—/•�; I 3UILDING ZONING FGRiHEN:E FGRIEEP.CE i // �/• C•OVERPA UTILITY . F10RIDA POWER8LIG4T sox a \\\ / J \ - - — - DESIGN SPECIFICATIONS DATE: 4. A1I ! I 1 1 OCCUPANCY'. II . CONSTRUCTION: ZONING... SINGFFA4;RY AEE7`ffIAL DESIGN BY: D.T. GROUND SNOW CAG Wb4D EZFosuRe. 0Pa CHECKED BY: M.M. PLAT MAP N 'LLN0 PEED'. I6OMPH APPHCABLECOOES &STANDARDS BUILDING. FPC N14 FEE 2014 REVISIONS 02 n E L NOT TO SCALE EVECTRi L EIRE NET M4 EEEC2a14 T-001.00 (SUE,) 2.1.1 2.1.2 1 2.1.3 2.1A 2.1.5 2.1.6 2 2.2.1 2.2.2 2.3 �.2.3 2Z 4 2.2S 2.2.6 3 2.3.1 2.3.2 2.3.3 2.3.4 4 2.3.5 2.3.6 2.4.6 2.4.7 2.4 0 SITE NOTES' A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110,26. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE. EQUIPMENT LOCATIONS ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 590.31 (A),(C) AND NEC TABLES 310.15 (8)(2)(A) AND 310.15 (B)(3)(C). JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC 690,34. ADDITIONAL AC DISCONNECTS) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. STRUCTURAL NOTES: RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE -COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAYISUBARRAY, ACCORDING TO RAIL MANUFACTURER'S INSTRUCTIONS. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF ROOF -PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WI APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR, ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. GROUNDING NOTES: GROUNDING SYSTEM COMPONENTS SHALL DE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. AS IN CONVENTIONAL PV SYSTEMS, UNGROUNDED PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL ELECTRICAL EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN ACCORDANCE WITH 260.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE 250.122. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(AI. EACH MODULE WILL BE G90UNDEO USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF N4 AWG OR LARGER [NEC 250.1191 2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 ANDAHJ. 2.4.10 ACCORDING TO NEC 690,47 (C)(3), UNGROUNDED SYSTEMS INVERTER MAY SIZE DC p 78 GEC ACCORDING TO EGC REQUIREMENTS OF NEC 250,122. HOWEVER, DC GEC TO BE UNSPLICED OR IRREVERSIBLY SPLICED. 2AL11 IN UNGROUNDED INVERTERS, GROUND FAULT PROTECTION IS PROVIDED BY "ISOLATION MONITOR INTERRUPTORAND GROUND FAULT DETECTION PERFORMED BY "RESIDUAL -CURRENT DETECTOR" 2.5.1 INTERCONNECTION NOTES: 2.5.2 LOAD -SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 690,64 (8)) 2.5.3 THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120%OF BUSBAR RATING [NEC 705.12(D)(2)(3)). 2.5.4 WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE COED [NEC 705.12(D)(2)(3)]. 25.5 AT MULTIPLE INVERTERS OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (13)(2)(3)(C). 2.5.6 FEEDER TAP INTERCONECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (D)(2)(1) 2.5.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705,12 (A) WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230,42 2.5.8 BACKFEEDING BREAKER FOR UTILITY -INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [NEC 705.12 (D)(5)I. 2.6.1 DISCONNECTION AND OVER -CURRENT PROTECTION NOTES: 2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED "LINE SIDE" (TYPICALLY THE UPPER TERMINALS). 2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE -BREAK SWITCH. 2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED. THEREFORE BOTH MUST OPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13. 2.6.5 DC DISCONNECT INTEGRATED INTO ROOFTOP DC COMBINER OR INSTALLED WITHIN 6 FT, ACCORDING TO NEC690.15 (C). 2.6.6 RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS 530V AND 5240VA [NEC 690.121, LOCATION OF LABEL ACCORDING TO ANN. 2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240, 2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED, THEREFORE BOTH REQUIRE OVER -CURRENT PROTECTION.. ACCORDING TO NEC 240.21. (SEE EXCEPTION IN NEC 690.9) 2.6.9 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC -FAULT CIRCUIT PROTECTION ACCORDING TO NEC 690.11 AND ULi6998. 2.7.1 WIRING & CONDUIT NOTES: 2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP -SIZING. 2.7.3 ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7. 2.7.4 EXPOSED UNGROUNDED PV SOURCE AND OUTPUT CIRCUITS SHALL USE WIRE LISTED AND IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.35 (D)]. PV MODULES WIRE LEADS SHALL BE LISTED FOR USE WITH UNGROUNDED SYSTEMS, ACCORDING TO NEC 690.35 0)(3). 2.7.5 PV WIRE BLACK WIRE MAY BE FIELD -MARKED WHITE (NEC 200.6(A)(6)). 2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY. 2Y.7 ACCORDING TO NEC 2007, UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKED AS FOLLOWS, DC POSITIVE- RED, OR OTHER COLOR EXCLUDING WHITE, GREY AND GREEN DC NEGATIVE -BLACK, OR OTHER COLOR EXCLUDING WHITE, GREY AND GREEN AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L7- BLACK PHASE B OR 1_2-RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR 1_3-BLUE, YELLOW, ORANGE', OR OTHER CONVENTION NEUTRAL- WHITE OR GREY - IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [NEC 110.151. CONTRACTOR AWASUNCORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH FLORIDA 33401 UQ NO.: CVC 56967 HIC.NO.: ELE. NO.: UWUTHORLED USE OF THIS ORA'AING SETVIRHOUTWRITTEN PERMISSION FROMCONTRACTOR IF IN VIOLATION OF U.S. COPYRIGM V315 ANOWILL BE SUBffGTID CNIL OAS.AGE6 AND PROS CUTIONS NEW PV SYSTEM: 7.425 k1Np FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 V = 69V i�' '• a G+E sI f,;r•t_(aus\r01 red So\M&kg' A77711111111\\ DATE: 4,10.2017 DESIGN BY: D.T. CHECKEDBY: M.M. REVISIONS G-001,00 15HEET 21 viny sun 7,425 WATT UTILITY INTERACTIVE RESIDENTIAL PHOTOVOLTAIC SYSTEM NO BATTERY BACK UP LOADS CONTRACTOR VINYASUN CORP The system is a grid -tied photovoltaic system consisting of 27 275 Watt DC Canadian Solar PV Modules. Each module is connected to a single PHONE: 5614409515 DC Power Optimizer which are connected in series. The Modules and Optimizer strings are connected to a single inverter Solar Edge Inverter. ADDRESS: 313 DATURA STREET SUITE 101 The PV Supply side of the power conditioning device is then connected to the building through either a single breaker located within the main 33401 PALM BEACH,FLORIDA PP Y P 9 9 9 33401 distribution panel, a sub panel or through a Supply Side Service Connection per NEC 690.64(a). Point of connection is diagramed on the LIC, NO.: CVC 56967 electrical diagram. HIC.NO.: FBC 2014 107.3.4.2 Certifications by contactors authorized under the provisions of Section 489.115(4)(b), Florida Statutes, shall be considered equivalent to sealed plans and specifications by a person licensed under Chapter 471 Florida Statutes or Chapter 481 Florida / / / by local enforcement agencies for plans reviewing for permitting purposes relating to compliance with wind -resistance provisions of the code or alternate methodologies approved by the Florida Building Commission for one- and two-family dwellings. Local enforcement UNs'JTROR¢EO USE OF I HIS BRIXNINO SET WITHOUT WRITTEN PER ISSIDN FROM CONTRACTOR 0 IN NOTATION OF US. COPSROHTb4S OAA&OES AH..FBIJAI. IUDWILL BE SUBJECT TO CIVILStatutes, NEW PV SYSTEM: 7,425 kWp agencies may rely upon such certification by contractors that the plans and specifications submitted conform to the requirements of the code FITZNER for wind resistance. Upon good cause shown local government code enforcement agencies may accept or reject plans sealed by persons licensed under Chapter 471, 481 or 489, Florida Statutes. RESIDENCE 6103 BALSAM DR HOW IT WORKS FORT PIERCE, FL 34982 APN:340261005290000 4 When sunlight is available, The PV array generates DC power which is then fed to the inverters and converted to AC power synchronized with AA%T,i,I,TT/ the AC power supplied by the utility. The inverters meet the requirements of IEEE 1547 and UL 1741. This means that if they detect a loss of \��y4�R utility power, they will automatically disconnect from the utility company. When utility voltage is restored, the inverters automatically �5.:�$eRE;l-Rr9. reconnect to the utility grid after verifying utility voltage and frequency stability. �: �.<° �'> . ; N OD This system, when installed in accordance with the information contained in this package, and as per the installation manuals supplied by the 5 67 equipment manufacturers, meets all requirements of the latest editions of the National Electric Code Article 690. am: m` s of The Contractor shall be fully cognizant of the latest edition of the 2014 FBC, 2014 NEC and all local codes, ordinances of the authority having / F .�• jurisdiction and perform all work in accordance with the intent and requirements of these codes, ordinances and authorities T;V - ;\tA SYS'V*I9 M�� NOTES The design of this system is based on information gathered at the site and existing conditions. All measurements and locations should be field I DATE: 4.102017 verified prior to the start of installation. DESICNBY:D.T. CHECKEDBY: M.M. REVISIONS G-002.00 2 3 4 5 6 METER AC DISCONNECT INVERTER I I I I 20'-10" E,7�SITE PLAN N wE ® s GENERALNOTES 1. FIELD VERIFY ALL MEASUREMENTS v,nyasun 2. ITEMS BELOW MAY NOT BE ON THIS PAGE ------- PROPERTYLINE CONTRACTOR VINYASUN CORP PHONE: 5611.409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH,FLORIDA 33401 LIC.%: CVC56MC HIC. NO.: ELE. NO.: JNAu UCUIZED USE 0f IHIS D.12-T-� UTWRITT=N PERLIISSIOH FROMCONTRACTOR IS IN AND WHOLES SUBJECT TOIDIRL1Yl5 HM1'04W.dESUWECTTOCMI phIAADe3AND 110SEC`JiID11Y. NEW PV SYSTEM: 7,425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 OVJC56967 o 2 U — m' cp DATE: 4.10.2017 DESIGN BY: D.T. CHECKED BY: M.M. REVISIONS A-101.00 (SHEETd) F 2 3 ARRAY I-4.675 kW I%17) (N) MODULES TILT'15 DEGREES ROOF PITCH: 3'12 AZIMUTH: 270 DEGREES 4 INTERIOR PV EQUIPMENT (E) (N MAIN ELECTRICAL PANEL EXTERIOR PV EQUIPMENT (E)(NMETER (N)(1) AO DISCONNECT IN) (1) INVERTER REES I01 PN)rdODULEs TILT: 15 DEGREES ROOF PITCH312 AZIMUTH. 160 DEGREES GENERALNOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE O MODULE STRINGING O MODULE STRINGING CONTRACTOR VINYASUN CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH FLORIDA 33401 LIC.NO.: CVC56967 HIS. NO.: ELE. NO.: UNAU LORDED USE 0E IBIS E.IIG SELWRHOUT'Y BAFEN PER1119510NERONCENTRACTOR IGIN VIOIAil9ll04 U fl COPVRIE"I AVENEL BE MEET10 CNIi DA MGES AIID PROSECUTIGI IS, NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 ' 56967 o CD U 3'-3" I _ I N MODULE: AL PLAN CANADIAN SOLAR ELECTRICME 5's' CS6K-275M 01 °® 1 275 WATTS E 1 VAAY lot I ltj JIXI /�A Ylh11V DATE: 4.10.2017 DESIGN BY: D T. CHECKEDBY: M.M. REVISIONS A-102.00 ,EREETB 3 T 4 5 19'-51, 6I ATTACHMENT PLAN N H_S�OLAI E o® H GENERAL NOTES A:. 1. FIELD VERIFY ALL MEASUREMENTS vinyasun 2. ITEMS BELOW MAY NOT BE ON THIS PAGE ROOF TRUSSES CONTRACTOR VINYASUN CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH,FLORIDA 33401 LIC. NO.: CVC56967 HIC. NO.: E.E. NO.: UYAUTHORREV USE OE IT S C2INING SETWHHOUTPIRIREN PERM16510N FROM CONTRACTOR IS IN VIIXATI@I Oi U.S. COPYRIGHT"$ ANDVIILL BE SUWEGT TO CIVIL 04AL43ES AIIDPRGRECllilO'IS, NEW PV SYSTEM: 7.425 kWp FLUSH MOUNTED SOLAR MODULES FITZN E R ATTACHED TO ROOF SURFACE (SEE SHEET 5-501 FOR MOUNTING DETAILS) RESIDENCE ROOF MATERIAL S i LAYER 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 .AT n)mi ppv /rwgirm;P _ m ; VC56967 4, o r�Q p 1�>f �QOENT PLAN 3T-3" DATE: 4,102017 J MODULE: DESIGN BY: D.T. CHECKEDBY: M.M. 5 CANADIAN SOLAR CS6K-275M REVISIONS A-103.00 275 WATTS r y ISHEET51 A R C 0 F F G H I 2 I 3 I 4 I 5 CONDUCTOR AND CONDUIT SCHEDULE WIELECTRICAL CALCULATIONS IDTYPICAL CONDUCTOR CONDUIT CURRENT -CARRYING CONOUCTORS COED EGC TEMP.CORR. FACTOR CONDUIT FILL FACTOR CONT.CURRENT MAX. CURRENT(125%) BASEAMP. DERATEDAMP. TERM. TEMP. RATING AMP. 7�iER(AINAL NCONDwr 01 2 12 AWG PV WIRE, COPPER FREEAIR 4 NIA 6 AWG BARE, COPPER 0J6(55°C) to 15A 18.75 1 40A I 30AA ]5°C 35A 021 1 1 BAWGTHWN-2, COPPER 0.75'DIA. EMT 2 NIA 6AWG THWN-2, COPPER 0.96(33°C) 1.0 32A 40A 55A 52,8A 75°C 50A 031 1 1 6ANIGTHWN-2, COPPER H75"01A.EMT 2 40A 6 AWG THAW, COPPER 0.96(33°C) 1.0 32A 40A 75A 72A 75°C 66A AC SERVICE DISCONNECT SHOULD BE LOCATED NEAR MAIN J z DISCONNECTING MEANS WHEN POSSIBLE THOUGH PER 690.64(A) ARTICLE } J xo a M o 240.21(B) DOES NOT APPLY TO SUPPLY SIDE PV SERVICE CONNECTIONS. IF = o THE DISCONNECTING MEANS IS NOT VISIBLE FROM MAIN DISCONNECT A o � v PLACARD DIRECTING TO THE PV DISCONNECT SHALL BE APPLIED TO THE o BID On MAIN DISCONNECT. A A A d o a SUPPLY SIDE CONNECTION FROM THE PV SUPPLY SIDE OF THE POWER ' � N � CONDITIONING DEVICE SHOULD BE MADE WITH POLARIS OR EQUAL J INSULATED SINGLE ENTRY SPLICE. ALL ENCLOSURES RATED NEMA 3R J > �z� 0 m3r W�� �w Q o � <z W �W� Wow o 0� 00 o BUDa—OD 0= O Q u� W ¢ U O CDW �o Q� OZI. CiZZ Z cYv < 0 a o But � w ¢ i----� C z o x o z o z =O S •�• N Z W T N' <[ W W iu I joo �s i 5 I , I •�• O m Z I I I A — S — C — U — h vinydsun CONTRACTOR VINYASUN CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH,FLORIDA 33401 LIC.NO.: CVC56967 HIC. NO.: ELE. NO.: UNAUTHOREEU USE OF THIS 21VING SETWITHOUT WRITTEN vEaNLsSION""I CGNT"' Ew VWTION OF US. CO1.R HT IVSS ANDLYILL BE SUBJECT TO G%IL FEW49ES AND PRW SCUT Ions. NEW PV SYSTEM: 7.425 KIND FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 AA\�Nqjf&@�� 665JGNER VC56967 s ate' �`Qr A�. •..aPP ftslx: ti ,�T B�� PP7j1111A 11Y(�GRAM DATE: 4.10.2017 DESIGN BY: D.T. 1 CHECKED BY: M.M. REVISIONS E-601.00 (SHEET7) POWER OPTIMIZERS I REF. IMTY.j MODEL RATED INPUT POWER MAX OUIPUT CURRENT MAX IITPUFISC MAX DC VOLTAGE WEIGHTED EFFICIENCY P01-27 27 SOLAR EDGE PIN MOIST I5 910A I 43V 98.6% INVERTERS QTy RATED MAX GUTPUT MAX INPUT MAXINPUT CEO WEIGHTED REF. MAKE AND MODEL AC VOLTAGE GROUND MAXOCPD RATING POWER CURRENT CURRENT VOLTAGE EFFICIENCY 11 1 SOLAR EDGE SE7600A-US (240141 24P1 FLOATING 40A 83WW 32A 24A 500V 975% DESIGN TEMPERATURES DISCONNECTS OCPDS ASHRAE EXTREME LO'N 0°C(32°F), SOURCE ' VERO BEACH MUNICIPAL AIRPORT (KVRB)27,66°. 00.47 REE.QTV. MAKE AND MODEL RATEOCURRENT MAX RATED VOLTAGE REF. QTV. RATED CURRENT M1IAXVOLTAGE ASHRAE 2%HIGH ECU FE°Fj,SOURCE. VERO BEACH MUNICIPAL AIRPORT(KVR5) 27.66 A0.42° S'Nt 1 SQUARED02221JRB MODEL GNA 240VAC Fi-Z 1 2 4OA 2GOVAC BILL OF MATERIALS CATEGORY MAKE MODEL NUMBER SEE QTY UNIT QTVIUNIT DESCRIPTION 1ODULE CANADIAN SOLAR CS6K-2751A PIAI-27 27 PIECES i ]APIADIAN SOLAR C66K275110 CELLS, MONQCRYSTALLINE SILICON IJVERTER SOLAR EDGE SE600.A-US 11 1 PIECE 1 301FAR EDGE SE7600A US B35OVI IIJVERTER gODULE CPTIMUSER SOLAR EDGE P300 POI-27 27 PIECES 1 30LAR EDGE PEGS OPTIMIZER(REQUIRED PART OF INVERTER DISTRIBUTED DC ARCHITECTURE) ISCONNEGT SQUARED D22214RB SON 1 PIECE 1 QUARE D D222NRB, 2POLE, BOA, 240VAC, OR EQUIVALENT NIRING GEN-b-AWGRARECU WRi 90 FEE i 3 AWG BARE, COPPER (GROUND) NIRING GEN-I2-AVVG-PV-WIRECU WR1 350 FEET 1 2AWG PV WIRE, COPPER JPOSITIVE AND PIEGAIIVE) AIRING GEN9 A'NG-THWIJ-2CU OR WR23 35 FEE 1 3 A'NG THWN-2, COPPER, GREEN (GROUND) NIRING GEN,&AWO-THI CU-BLK WR2 25 FEE i 3AVVG THWN 2 COPPER, BLACK(LIFE 1) AIRING GEN-8 AWG4HWN 2CU-RO WR2 25 FEET 1 AWGTH'NN-$COPPER, RED(LINI AIRING OEN-&AWGTHWPI-2-CNWH WR2 25 FEET 1 A'NOTHVIN-2, COPPER, WHITE(NEUTRAL) GErF6ANGTHWNC WR3 1 10 1 FEE i AWG THWN-2, COPPER, WHITE (NEUTRAL)G NIIRRIIInJIG H2ELGWTN- COPP(LINE 2) NIPING GEN5.AWGT9WN.2CU-BLK WR3 10 FEET 1 A4VG THWIJ-2. COPPER. BLACK(LINE 1j NIRE'NAY GEN EMLO 75DIA WW23 35 FEET 1 MT CONONi, Ol5 DIA CPD I GENERIC MANUFACTURER GEN-FU 40A-240VAC Fi-2 2 PIECES 1 USE, GOA, 240VAG _CD CONTRACTOR VINYASUN CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SMITE 101 WEST PALM BEACT LLORIDA 33401 LIC,NO,: CVC56967 HIC. HO.: ELE, NO.: UNAU HORSED USE OF IHI5 PW'NING SST VIHNOUT WRITTEN PERY15MOO FROM CONTRACTOR I IN VIOIATE'l O4 US."0PMIGHT LOOS AIJDM L6E SUCTECT TO CIVIL OUCII ND PROSECUTIONS. NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 �5ic SAC f i 7 VC56967 @ _ 7 T 11111111\\\A DATE: 4,10.2017 DESIGN BY: O.T. CHECKED BY: M.M. REVISIONS E-602.00 ISHEETG F OTOVOLTAICHaPpa ` DISCONNECT ORRENT: 52A ACLTAGE: 2<O/FC PLACARD LABEL2 LABEL LASEL4 AT EACH JUNCTION, COMBINER, DISCONNECT AT EACH DISCONNECTING MEANS FOR AT EACH DC DISCONNECTING MEANS AT POINT OF INTERCONNECTION, MARKED AND DEVICE WHERE ENERGIZED PHOTOVOLTAIC EQUIPMENT [NEC 690.531 AT DISCONNECTING MEANS UNGROUNDED CONDUCTORS MAY BE [NEC 690,17] [NEC 690.541 EXPOSED DURING SERVICE DIRECTORY INEC 690,35(F)I PERMANENT PLAQUE OR 1 1 INTERACTIVE PHOTOVOLTAIC SYSTEM DIRECTORY PROVIDING CAUTION THE LOCATION OF THE O O O CONNECTED O SERVICE PHOTOVOLTAIC SYSTEM PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED DISCONNECTING MEAN'S CIRCUIT IS BACKFED NORTH SIDE OF THE GARAGE AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING LABEL LABEL6 PLAQUE MEANS IF NOT IN THE AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY SAME LOCATION PHOTOVOLTAIC SYSTEM [NEC 690.56(B)l (NEC 705.12(D)(4)I INHERE THE INVERTERS ARE REMOTELY LOCATED • • • ' FROM EACH OTHER.A O INTERACTIVE PHOTOVOLTAIC SYSTEM O O PHOTOVOLTAIC O • , DIRECTORY IN CONNECTED DC DISCONNECT ACCORDANCE WITH 705.10 �• BHALL BE INSTALLED AT LASEL7 LABEL LABEL DISCONNECTING MEANS, AT AT UTILITY METER AT EACH DC DISCONNECTING MEANS AT RAPID SHUTDOWN SWITCH EACH AC DISCONNECTING [NEC 690.56(B)l INEC690.13(B)) [NEC 690.56(8)1, MEANS, AND AT THE MAIN LETTERS AT LEAST 318 INCH; WHITE ON RED SERVICE DISCONNECTING BACKGROUND; REFLECTIVE MEANS SHOWING THE [IFC 60S11.1.13 LOCATION OF ALL AC AND DC PV SYSTEM DISCONNECTING MEANS IN WARNING:PHOTOVOLTAIC o PHOTOVOLTAIC a THE BUILDING. •• • AC DISCONNECT [NEC 690.4(H)I LABEL IO LABEL 11 LABEL 12 AT EXPOSED RACEWAYS. CABLE TRAYS, AND OTHER WIRING AT EACH AC DISCONNECTING MEANS AT POINT OF INTERCONNECTION METHODS; SPACED AT MAXIMUM IO FT SECTION OR WHERE [NEC69D.13(B)1 OVERCURRENT DEVICE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, LABELING NOTES [NEC 705.12(D)(7)I OR FLOORS. 1.1 LABELING REQUIREMENTS BASED ON THE 2014 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605,11, OSHA [NEC690.31(G)l STANDARD 1910J45, ANSI Z635 LETTERS AT LEAST 318 INCH; WHITE ON RED BACKGROUND', 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. REFLECTIVE 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. [IFC 605.11.1.11 1A LABELS TO BE A MINIMUM LETTER HEIGHT OF SIT AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. "DANGER" WILL HAVE RED BACKGROUND; "WARNING` WILL HAVE ORANGE BACKGROUND: 'CAUTION "WILL HAVE YELLOW BACKGROUND, [ANSI Z5351 ° !CAUTION! ` POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: PV ARRAY BACK N NTE 6 GRADE PVARRAY IN)INVERTER SLt 5„ TO MEP x CONTRACTOR MAIN DISTRIBUTION UTILITY DISCONNECT VINYASUN CORP PHONE: 6614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH FLORIDA 33401 LIC, NO.: CVC 56967 FRONT HIC. NO.: ELE. NO.: UNAUTH01F. USE OF TNA RWWING SET WRHOUTA'RIREN PERNISSION FR011 CONTFPCIDR IS IN o V IZRON OF U.S. COPYRIGHT LAW AND MLL SE SU W EC! TO OWI L DAMAGES ANO PROSECUTIONS. NEW PV SYSTEM: 7.425 kWp ° FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN: 340261005290000 111111111//// XXKAT ti\�'CN61N E l'G (%NER -(E)UTILITY ete ost N N r C56967 � ' CD (E) METER (fl, m ' Do . Ln `a : t ;s •'fate of F\O C ' • ......•''r�.` / 77 V ARDS — (E) UTILITY DATE: 4,10.2017 DESIGN BY: D.T. EEQUIPMENT ELEVATION NOTTOSCALE CHECKEDBY: W.M. REVISIONS E-603.00 (SHEET9, n RACKING DETAIL (TRANSVERSE) DI NOT TO SCALE /� 9 \a 0 4 (TI. RACKING DETAIL (LONGITUDINAL) UL NOT TO SCALE RACKING DETAIL (TOP) D3NDT TO SCALE 4 IN 6 DETAIL (TRANSVERSE) (7 DETAIL (LONGITUDINAL) D4NOTToscALE U� NQr7oscaLE GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 0 SHEET KEYNOTES ROOF MATERIAL: ASPHALT SHINGLE 2. ROOF STRUCTURE: TRUSS 3. ATTACHMENT TYPE: IRONRIDGE FLASHFOOT2 4. MODULE MANUFACTURER: CANADIAN SOLAR 5. N10DULE MODEL: CS6K-275M 6. MODULE LENGTH: FLA' 7, MODU[LEWIDTH: 3'-3' 0, MODULE WEIGHT: 40.0 LBS. 9. SEE SHEET A-2 FOR DIMENSION(S) 10. MIN. FIRE OFFSET: NO FIRE CODE ENFORCED H. TRUSS SPACING: 241N, O.C. 12. TRUSS SIZE ZX6 NOMINAL 13. LAG BOLT DIAMETER: 51161N. 14, LAG BOLT EMBEDMENT: 31N, 15. TOTAL k OF ATTACHMENTS: 54 i6. TOTAL AREA: 476.53 SO, FT. 17. TOTAL WEIGHT: 1256.35 LBS. 18. WEIGHT PER ATTACHMENT, 2327 LBS. 19, DISTRIBUTED LOAD: 2.64 PST. 20, MAX. HORIZONTAL STANDOFF: 481N. 21. MAX. VERTICAL STANDOFF: LANDSCAPE 26IN., PORTRAIT: 321IT 22. STANDOFF STAGGERING: YES 23. RAIL MANUFACTURER(OR EQUIR)'. IRONRIDGE 24. RAIL MODEL (OR EQUIVALENT): NET 00 25. RAIL WEIGHT: 0.68 ELF, 26. MAX. TRUSS SPAN: 6 FT. 27, MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX. Lo kp 6 RISK CATEGORY: II EXPOSURE CATEGORY: C VULT:160MPH vinyasun CONTRACTOR VINYASUN CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACHYLORIDA 33401 LIC.NO.: CV056967 HIC,NO.: ELE. NO.: UNALFHORIZED USE OF THIS DW ONG SETvnDl0UT IR17EN PERMISSION FIRMS CONTRACTOR [SIN MULLEN OF US. COPYRIGHT V.19S NND N'ILL BE SUBJECT TO CNIL OA[AABES A IDPHOSECUTIONi NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 A33{i-1+4+4t f�1,D)ESIGNER 9, CVC56967 : ° m� 447� •' � ., .SOAP "01I J` F* �Y7 j40� ,L\PbETA LI S DATE: AIDS017 DESIGN BY: D.T. 1 — CHECKEDBY: M.M. REVISIONS S-501.00 SNEET IT, 2 4 a H r# ALL -BLACK C 16K.M modules are equipped with dark mono -crystalline cells, dark colored backsheet and a black frame to enhance the aesthetic appearance of our standard mono modules. This product can Improve the aesthetics of a rooftop. kEY FEATURES oExcellent module efficiency of up m 17.11% Outstanding lowirradiance performance: 96.5% OIP671unction box for longterm weatherendurance ♦ } Heavy snow load up to 5400 Pa, wind load up to 24M Pa �'19 r CanadianSolar r25 linear power output warranty YN �10 Product warranty on materials year, and workmanship MANAGEMENT SYSTEM CERTIFICATES^ Is090gI:2C0e/opals, management eystem ISOrt516969RCa9/Tim aummoWe ndom, quality managementwohm '50 14al:Wa4/S4ndaNa 1.11rommments managementnorn o1HsA51Min 207 / m[ernatlaml4an&nJx hr ocw,firal health and satey PRODUCT CERTIFICATES' IEC 612S/1EC61wO:VOEICE[MCSICE[,kU UL 1703/RC 61215.0ormanw:CEC"anHUs) UL into: Cif/Take e'way ROW roware dleerw[ [ertiMatlon rtqulrtmm¢ In trMxeM meM1ep plwe wnett a�rleareauowur:al-..PreSemarM[ar NeePeuW,emn,.r.,aPPuwaew me Proiumin Neryloninwl:khmel:rWunsarewMm.a CANADIAN SOLAR INC. Is committed to providing high quality salar produce, solarsyitem solutions and services to customers around the word. Asa leading PV project developer and manufacturer ofsolar module, with over 15 GW deployed around thewmldsin sZ001,CavedIan Solar Inc(NASDAQ:CSIQ)isaneof them As nkablewo rcompaniesworldWde. CANADIAN SOLAR INC. SAS Speedvale Avenue West, Guelph, Ontario N19 IE6, Canada, www.canadiansolancom, suppor@Canadiansoll ENGINEERING DRAWING Imm) Rea View f me Cross Section AA ji a M it H.I. 4 ca ELECTRICAL DATA I SIC* All -Black CS6K 210M Z75M 280M. ELECTRICAL DATA I NOCTe All -Black CS6K uWer PERFORMANCE AT LOW IRRADIANCE Outstanding performance at low irradlance, average relative efficienry, of96.5% from an irradlance of l AGO W/ma to 20) W(ma (AM 1.5, 25-C). me,P+uMalanane Yey rea[M 4,Nt MrmMarmzyYi SgMN mmon" ero�CPoamlwW,a:�nottm�n,:hm:r',nre�anr�tp�1Pwfb,.alre�ea<�,lssali�::aemaalo"riM1 atnowi�ercI�xuh�n:rvV�n"n�,airnaN�rannecealrmm'mgeMnaRMwdertle�anitrretlwe'gn¢.'aeoyen'rJ" rmW¢PMlw-.xrvY9_.themawoenepuww�luxV:en,o—smrrwpeewYy—n,arew utt,a kme reanrnesa,etyan WENYtlon:nA:2tanahehre w:gNe:n::Wlev CS6 W280M / I V CURVES ;I n m F,m es e4 r, nut to � ce A n a MECHANICAL DATA Specification Data Cell Type Mono crystalline 6lnch Cell Arrangement 60(6 x10) Dimensions 1660+992aa0mm(65.0.39.1at571n) Weight Front Cover 3.2 mm tempered glass Frame Material Anodized aluminium alloy JBax IP673diodes _. Cable 4 non' HECI ar4 Ann' &12 AWG 1 g0GV(UL), 1000 Ran (394in) Connectors T4-t000V Or PV2seres Per Pallet 26pldces, 520 kg H 146411m) _. Per Container (40' H(d 729 pieces _ _- TEMPERATURE CHARACTERISTICS specification Data Temperature Coefficient (Pmax) -041%PC Te pera[ure COeffcient(VOc) ___ 031%i-C _ Temperature C_oef(nen[(Isq _ 0053111/'C_. _ Nominal Operating Cell Temperature 45E2'C _ PARTNER SECTION CANADIAN SOLAR INC. July 2016. NI rights reserved, PV Module Product Datasheet V5.51 EN vinyasun CONTRACTOR MNYASUNCORP PHONE: 604409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH,FLORIDA 33401 LIC.NO.: CVC56967 HIC. NO.: ELE. NO.: DusEOFTITS MWNGMTUBfW PERMISSION Ang" CONAKHITCIMIR WIS9W HUTK)NOF NCN1LLBESURIECTTOCML pMAOEeAN0PR09ECUIXIk3. NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 rVC56967 =�°CD°' // ��I�I`•x IT�IBI $17U12C OCUMENT DATE: 4.102017 DESIGN BY: D.T. CtD:CNEOBY: M.M. PENSIONS R-001,00 19HFEr111 Single Phase Inverters for North America solar- SE3000A-US I SE380OA-US I SE500DA-US / SE600GA-US solar =@@ 0 SE7600A-USjSE10000A-US/SEI1400A US 2 apoi-as So u. j7i�' Imam SE -- - --- - ATUS] Snar !I.", ounm N-1-1 AC P-1 .111n roo n. T A SolarEdge Single Phase Inverters 1111 an ES; EO Pu� -1— 1 1 Al P—r Cut,11 SES, . .VA . . . For North America "I - a - �Iu SE3000A-US SE380OA-US / SE500OA-US / SE600OA-US�z uu"'a 311 a 11.1� EP� S E760OA-US 8 El OOOOA- U S SET I 40OA- US ' ."S nw. W n Lla'hIEUE.0 Is INPUT Spa' 'sn' w- RO. N.. rr"vU'. I S"a,"RER'S. Vi.' US�60,38 PI EEPTAW c u r.—r EuL." I'l Ot t 9nal E. SI..Vl _5 ' a, "E 'IE I j E101.1 uS R r,. 171 11 REE111— C.S.T.S11.11 -u A[RUITIONALFRATINI "no— rraar plol ANN, STANDARD COM PLUAIM ....... ..... .. - - - - - - - - uumFuu T K ROSE,, 4 x� -Nd w INMI AIATION - - - - - - - - 11,C S.—/d IAIL. I a a. RJ ; . . . 775 EA,1 M, SA'E.Itd, 2 n S I 'E.' IS k., the 00A engibU it, co"A' -4phicourad-inq ran I At'lon'. SLZ..' So. Pwot "J Internet contain. through Ethroaft a tawpol. Outdoor and indoor In'toll.til R I, Find Vollor forte erg DC/AC Munition only Pre-aunnabled Safin, Swurb for finta, Installation Optional - rvienne guide data, ANSI C12.1 USA GERELIANY-TEALY FRANCE IAAAN-CIIINA AUSTRAM THENETHERIANDS Uk ISRAEL www.5olaredge,us 19 vinyasun CONTRACTOR VINYASUN CORP PHONE: 504409515 ADDRESS: 39 DATURA STREET SUITE 101 WEST PALM BEACH.FLORIDA 33401 UC.NO.: CVC56MI HI:. NO.: ELE. NO.: K�m FROM fAkIIMCrm IS IN NEW PV SYSTEM: 7.425 kWp FITZNER 6103 BALSAM DR FORT PIERCE, FL 34982 j� !Ni84026jqq5290000 05 Ui. 1//' CVC56967 0:: 6 Olt of 0(y 1/// 1CLEETV, RESOURCE DOCUMENT OAR: k102017 DESIGN ft O.T. CHIECKI M.M. REMKINS R-002.00 (MW12) solar =@o & S 0'ar Solar =pq SolarEdge Power Optimizer Module Add -On for North America P300 P320 / P400 / P405 2 Optimizer SolarEdge Power Optimizer Power 0 pt� 7 _320" MIND ------- P405 P n For North America, Module Add -On For North America 0 INPUT Pa I. P 390 0 00 P 5 P300 P320 P400 P405 — Ab.. ER.—mm'u, 4E ICE US Au, 13,75 G 01�'RNCV, Came, ... . ............ .. OPERATIN"ONAREINHE INVERTING IS Ad, OUTPUT DURING STANDBY ROWNERUPTIM121HR DISCONNECTED FPOM501AREDGE1NtlERTER ORBDIpPEDGEINVERTEP 0"____ .G, cuu,", vKh" Pa,P.'a" I I .' Next .NatRG L.IBUBnan.PaVa .NLES-fieval numftcadug fity USA CANPGA GERMANY ITALY FRANCE MEAN CHINA ADSTRIALIA THE NFYHEPLAND5 UK ISRAEL www.solaredge.US 6 11 ... 5,aIE" SEK' ,I ; . I�_ aa/m , iR .0.95 00' F"'NYm "aHx1mMPNU.GT'. TVSYSTIM DESIGN USING A SOftAREOGEINVER11AA SINGLE PHASE THREE PHASE MY THREE PHASE 481 - - --------- T- U. -I N GI maximum rmurp END Po (U.PANIma 4 vinyasun CONTRACTOR MNYASUNCORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACH.FLONDA 33401 LICAO.; GVGMI HICAW ELE. NO.: UNURNICHIMUSECATHS MNN09UVTHmWgrtB1 NEW PV SYSTEM: 7A25 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FI. 34982 APN: 340261005290000 le L a 1 .k\r z 'a" CIA Ip [ 'V : 0 56967 (D Z7 "I'llifill"I" DATE: 4.102017 DESIGN BY. O.T. CHEONED11r. M.M. REVISIONS R-003.00 SUGBYrI3) AAIRONRIDGE 3 EM Roof Mount System Built for solai's toughest roofs. IronRidge builds the strongest roof mounting system in solar. Every component has been tested to the limit and proven in extreme environments. 4 Our rigorous approach has led to unique structural features, such as curved rails and reinforced flashings, and is also why our products are fully certified, code compliant and backed by a 20-year warranty. Strength Tested All components evaluated for superior structural performance. Class A Fire Rating Certified to maintain the fire resistance rating of the existing roof. 5 Integrated Grounding UL 2703 system eliminates separate module grounding components. PEi CertifiedPre-stamped engineering letters available in most states. MDesign Software fib Online tool generates a complete bill of materials in minutes. 20 Year Warranty Twice the protection offered by competitors. XR Rails XRI0 Rail A low -profile mounting rail for regions will light snow. • (reasoning capability • Moderate load capability • Clear anodlzetl finish Attachments ------ FlashFoot XR100 Rail im- The ultimate residential solar mounting roll. • 8' spanning capability • Heavy load capability • Clear & black (nod. finish Stoned L-Feet XRt000 Rail Internal Splines (D A heavyweight mounting All rails use internal splices rail for commercial projects. for seamless connections. • 12'spanningcapability Self -tapping screw. • Extreme load capability, Varying versions for rails • Clear anodized finish Grounding Straps offered Standoffs Tilt Legs Anchor, flash, and mount Orop-in design for rapid rail Raise flush or tilted Tilt assembly to desired With all -in -one attachments. attachment, systems to various heights. angle, up to $5 degrees. • Ships with all hardware High -friction scanted face Works with vent flashing • Attachesdlreelly to rail • IBC & IRC compliant Heavy-duty profile shape Ships pre -assembled Ships with all hardware Certified with XR Rails Clear & black (nod. finish Lengths from 3" to 9' Fixed and adjustable Clearps & Grounding End Clamps Grounding Mid Clamps :' T-Bolt Grounding Lugs t=) Accessories a Slide In clamps and secure Attach and ground modules modules at ends of rills. in the middle of the rail. • Mill finish & black and. Parallel boning T-bolt • Sizes from 1.22" to 2.3" Reusable up to 10 times • Optional Under Clamps MOD & black stainless Free Resources -- — Design Assiabat Go from rough layout to fully engineered system. For Vee. Go to IronHidgeco�Nrrn Ground system using the Provide a finished and mil'stopslot, organized look for ails. • Easy top -slot mounting Snap -in Wire Clips • Eliminates pre -drilling Perfected End Caps • Swivels in any direction UV -protected polymer y,Ad NABCEPORr ,.dm fallg c v Earn tree continuing ¢ducat on credAs n while learning more about our systems. T d Go to Ire Rid9s.cu nRrmning X"fr�47" - av; ..x.. ; xr1s...,. r'`t"•,c i.,.�." a >x. __s"?.= -: ,, r"r 3�.,s ,. s..,us s t Y.b. ♦4 <.F ."�v.°4y�,'s!`v�a£=_..n�;.♦�� S vinyasun CONTRACTOR VINYASUN CORP PHONE: 5614109515 ADDRESS: 313DATURASTREETSURE101 WEST PALM BEACH,FLORIDA 33401 UCNO.: GV0507 ND. NO.: ELE. NO.: uruunaa®useavlxe paMNG9alrWNrtEN PERMISSION10N FRONT FRaAI CUrtR WTOR I6 N VMPEIONU S CCFMCMrlAW9 M(wILL6EeL9JEEWm 9, 0.NNf E60Na PaaBECUMMB. NEW PV SYSTEM: 7A25 kWp FITZNER 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 \\\'`FitIllffElj! 51CyNER do �N C56967 - Dm : (V i •1eAMSIS'flr.1TgIFFeJ\\ 0OI ENT DATE: 4.102017 OESDN BY: D.T. CHECHEDBY: M.M. REVISIONS R-004.00 (6NE£T1„ SR -Starling Madison Lofquist, Inc. C onso NlnY Structval and ro,ensic ingrne am 1 5224 South 39" Street, Phoenix, Arizona 85040 tel: (602) 438-2500 tan: (602) 438-2505 ROC#291316.w rale,.com IronRidge March 14, 2016 1495 Zephyr Ave Page 1 of 20 Hayward, CA 94W Attn: Mr. David F. Taggart, Vice President Products Subject: IronRidge XR100 Rail, Roof Flush Mounting System - Structural Analysis Dear Sir: We have analyzed the IronRidge XR100 Rail for the subject solar module support system and determined that, for the configurations and criteria described below, it is in compliance with the applicable sections of the following Reference Documents: Codes: ASCE/SEI 7-10 Min. Design Loads for Buildings & Other Structures Florida Building Code 2014 Edition Other: AC428, Acceptance Criteria for Modular Framing Systems Used to Support PV Modules, dated Effective November 1, 2012 by ICC-ES Alumimmm Design Manual, 2010 Edition The IronRidge XR100 Rail is an extruded aluminum section with an overall depth of 2.438 in. and a net area of 0.583 sq.m. The rails are used to support solar modules, typically, on the roof of a building. See Exhibit 0011- attached. The modules are clamped to the mils by the IronRidge Module Mounting Clamps as shown in the attached Exhibit. The rails are attached to the L-Foot aluminum angle brackets that are either attached directly to the roof framing or attached to a stand that is screwed to the roof framing. The mils are mounted across the slope with a small clearance (flush mounting) to the underlying roof structure. The installed solar modules are at the same slope as the underlying roof structure. All loads are transferred to the roof framing through the angle brackets by simple bi-axial flexure of the mils. The maximum span of the mils is governed by either the mid -span flexural stresses or the deflection requirement that the mil not come into contact with the roof. The effect of seismic loads (for all design categories A-F) have been determined to be less than the effect due to wind loads in all load conditions and combinations. Therefore, the maximum allowable spans for common load cases are shown in the tables below. Tables IA-9A are for modules with a maximum long dimension of 67.5 inches and Tables IB-9B are for modules with a maximum long dimension of 78.5 inches. Starling Madison t-ofquisy Inc. Consulting Structural and Forensic Eaghreera IronRidge March 14, 2016 Mr. David F. Taggart Page 4 of 20 IronRidge XR100 Rail, Roof Flush Mounting System - Structural Analysis Table 3A - MAXIMUM SPANS (in) - Roof Slope 0'to 6` - Wind Zone 3 (67.5" Max Module Length) XRLOD Rail Wind Speed Ground Snow Load Exposure mph 0 pef 10 st 2sf0 30sf 40 sf 50 I Psf 60 I PIT 70 Pat 80 I Pat 90 I Pat 100 87 87 87 82 61 56 53 50 105 83 83 83 62 61 56 53 50 110 79 79 79 79 61 56 53 50 120 72 72 72 72 61 56 53 50 CntB 'y 130 67 67 67 67 61 56 53 50 S 140 62 62 62 62 61 56 53 50 150 8 58 58 58 M 58 56 53 50 760 64 54 54 64 54 54 53 50 170 51 51 51 51 51 51 51 50 160— 3 73 73 73 61 56 53 50 105 70 70 70 70 61 56 53 50 110 87 87 67 67 61 56 53 50 120 61 61 61 61 61 61 61 66 53 50 CaleCgary 130 56 56 56 56 56 1 56 56 56 53 50 140 52 52 52 52 52 52 52 52 52 50 160 49 49 49 49 49 49 49 49 49 49 160 46 46 46 46 46 46 46 46 46 46 170 43 43 43 43 43 43 43 43 43 43 100 67 67 67 67 67 66 61 56 53 50 105 64 64 64 64 64 64 61 56 53 50 110 61 61 61 61 61 61 61 56 53 50 120 56 56 56 56 56 56 56 56 53 50 CateDgory 130 52 52 52 52 52 52 52 52 52 50 140 46 48 1 48 48 48 48 48 48 48 1 48 ISO 45 45 45 1 45 1 45 45 45 45 46 45 160 42 42 1 42 1 42 1 42 42 42 42 42 42 170 40 40 1 40 1 40 1 40 40 40 40 40 40 Notes -see page 20 Starting Madison Lnfquiey Inc. Consulting Stmetural and Forensic Engineers .4. CONTRACTOR VINYASON CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SURE ill WEST PALM BEACH,FLORIDA 33401 LIC.NO.: CVC56967 HIC. NO.: ELE NO.: GNaffHORUEDGRE arnle uumxa sErtmxaurwslrml PE.iA9ssIGN FlpN tlYnR.iCrd1151N ANDWUREM WPINGHr UWB NIDVGESMDMSE 3CNs DuwDESAsolwosEcmloxa. NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 a t/0 �ar (b N C56967 : 0 _� : U- ' '• / PAPERSUE ll•vl�llSfR ` DA7Er lk1P?•g1i 1 \ \ \ • . DESIGN BY: D.T. CHECNEDBY: M.M. REVISIONS R-005,00 (aaEl q ImnRidge March 14, 2016 IronRidge March 14, 2016 Mr. David F. Taggart Page 7 of 20 Mr. David F. Taggart Page 20 of 20 IronRidge XR100 Rail, Roof Flush Mounting System - Structural Analysis IronRidge XRI00 Rail, Roof Flush Mounting System - Structural Analysis Table 6A - MAXIMUM SPANS lin] - Roof Slope 7° w 27' -Wind Zone 3 (67.5" Max Module Length) Wind Speed Ground Snow Load mph 0 psi 10 sf 20 sf 30 s( 40 sf 50 e( 60 IA 70 sf 80 sf 90 f 100 87 87 83 72 64 58 53 49 46 43 FCateg 105 83 83 83 72 64 58 53 49 46 43 110 80 BO 80 72 64 58 53 49 46 43 120 73 73 73 72 64 58 53 49 46 43 130 68 68 68 58 53 49 46 43 740 63 63 63 58 53 49 46 43 59 59 58 53 49 46 43 160 56 56 58 56 53 49 46 43 170 52 52 52 52 52 49 46 43 100 74 74 74 #6454 58 53 49 46 43 105 71 71 71 58 53 49 48 43 110 68 68 BB 58 53 49 46 43 120 82 62 82 58 53 49 46 43 CeteCgory 130 56 58 58 58 53 49 46 43 140 54 54 54 54 53 49 46 43 150 50 50 50 50 50 50 50 49 46 43 160 47 47 47 47 47 47 47 47 46 43 170 44 44 44 44 44 44 44 44 44 43 100 68 68 68 68 64 58 53 49 46 43 105 65 65 65 65 64 58 53 49 46 43 110 62 62 62 62 62 58 53 49 46 43 120 57 57 57 57 57 57 53 49 46 43 Category 130 53 53 53 53 53 53 53 49 46 43 G 140 49 49 49 49 49 49 49 49 46 43 150 46 48 46 46 46 46 46 46 48 43 160 43 43 43 43 43 43 43 43 43 43 170 41 41 41 41 41 41 41 41 41 41 Notes - see page 20 Starting Madison Le4quist, Inc. Consulting Structural and Forensic Engineers -7- Notes- Tabulated values we based on the following criteria: 1. Building mean roof height = 30 ft 2. Risk Category I 3. Solar maximum module long dimension is 67.5 inches for Tables IA-9A and 78.5 inches for Tables 1131-911. 4. Provide 2 in. clear between roof and mil 5. End cantilever span (max) = OAO x maximum span (Lour) from above tables. See Figure A 6. No mil splices in outer 213 of end spans, or the middle 1/3 of interior spans based on the installed attachment spacing (Lassen). See Figure A 7. Single simple span(s). Spans listed in the tables above may be multiplied by 1.09 for continuous rails of 3 or more spans. 8. Module Mounting Mid Clamps shall not be installed less than 20 inches from Roof Zone 3 where wind speeds arc marked with an' in Tables 3B and 6B. End Span Interior Span End Spar 0.4 La, J I L. I YF 1 1/3 L-= Maximum attachment spacing provided in the tables above for the project design criteria I. = Actual installed attachment spacing = Indicates region of the tell where splice may be installed Our analysis assumes that the rails, including the connections and associated hardware, ere installed in a workmanlike manner in accordance with the "IronRidge Flush Meant Installation Manuel" by IranRidge and generally accepted standards of construction practice. Additional information is available at the IronRidge web site, IronRidge.com. Verification of PV Module capacity to support the loads associated with the given way shall be the responsibility of the Contractor or Owner and not IrortRidge or Starling Madison Lofquist. I The adequacy of the supporting roof framing is to be determined by others. Please feel free to contact me at your convenience if you have any questions. Respectfully yours, Tres Woman, P.E. `"`flv .......... Design Division Manager Starting Madison lafquist,Inc. Consulting Structural and Fenced. Engineers 20 - li5 vinyasun CONTRACTOR VINYASUN CCRP PHONE: 5614409515 ADDRESS: 313DATURASTREETSURE101 WEST PALM BEACH,FLORIDA 33401 UC.ND.: CVC56W HIC. NO.: ELE NO.: uwaraoamume've rUWIN08ETNnNpR Wfllflm rraMssiox rsom caxrancroa ie w wxalwn or ua wrraiaxr wws ANal59LL BE 9i1aE4nmCML msucEeaxoraasrcaoxs. NEW PV SYSTEM: 7A25 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 ,,111111111Ir, DATE: 4.102017 DESION BY: D.T. CHECNEDBY: M.M. REVISIONS R-006,00 is MIG) 2 ,ac��—OR ir,,, IRONRIDGE FlashFoot2 ITEM NO. DESCRIPTION Oty In KH I BOLT LAG 5116 X 4.75" 4 2 ASSY, FLASHING 4 3 ASSY, CAPFOOi 4 4 WASHER, EPDM BACKED 4 FLNSHFOOT2 Pad Number_ Deecdpfion FM-FF2-001 Kit 4pc% FlashFo02lMilll FM-FF2-WI-B Kit, 4pcs. HashP00121Blockl 1) Bolt, Lag 5116 x 4.75 5/16THD on 6" Heatl—d.JS� Properly Value Matetlal 3005edes Stainless Steel Finish Clear ��ri' s ItFL3 2) Assy, Flashing 9.0 O I.o 29 —I 12.0 J1� P� 3) Assly, IICapfoot -III 4) Washer, EPDM Backed 1.66 0.35 ��IIy���I-IIIITjIIII�—.14 3.3 W O 0.75 vLo Property Value Mafedal Aluminum Finifi Mill/Block hoperty Value Material Alaminum Finish MBI/Black Properly Value Motedal 3W 5edes Stainless Steel Fnish Clear I'mPt2ei`s s d s as i V]rL r 1 :rs 3 ] sari `.n sues' tx FCC ' } s s 3 ,{ a'>5`r*s 4ry�`v e i!i TyF't'." ]C. -�. s fe iF4 3 J ref: -r„'*. -5�'7 z'dWP' Arsa `" 'a t r? „v�uf �... .. ,.a v.J.wu �, w....a u�bF..u. „v �v .,. .,,.... s..:�1,x ..^.,e3`5 ��..�...m 2. �.. .. ,k I _, 1+4....'src,.. .A�'. .z Sre. >v .n.. �i ....� a.�. _ .>.� �. S. �.. v`v a , e. 4, .,.n � S . sr iilfl@/aSUtI CONTRACTOR VINYASIMCORP PHONE: 5614409515 ADDRESS: 313 DATDRASTREETSMRE iD1 WEST PALM BEACH,FLORIDA 33401 LIC. NO.: CVC 56987 HIC, NO.: ELE. NO.: ux4u,xcalITnueEwTBD pMWINa BEi WI1BfNRWRInFN pEMnNspx F aw camucTBR Is m W BIALDN OF V e. CBPmDM uW9 NAMLLBE8116EmipcML pAMAGEBRNUPMASECUfIONB.lp NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34962 APN:340261005290000 _`\\11111111 ///4. C 56967 • m� m; �••' tea' � � ,J7y RE IRCE b CLIMENT DATE: 4.102017 DESIGN BY: D.T. CHECKED BY: M.M. RENSIONS R-007.00 1. SYSTEM DESIGN CALCULATIONS REPORT (NON -CODE) 1.1. PV SOURCE CIRCUIT VOLTAGE RANGE TEST THIS TEST CONFIRMS THAT THE VOLTAGE OF THE PV SOURCE CIRCUIT WILL ALWAYS REMAIN WITHIN THE DC INPUT VOLTAGE WINDOW OF THE SYSTEMS INVERTER, MICROINVERTERS, OR POWER OPTIMIZERS. 1.1.1. (1) CSBK-275M (276M IN SERIES nC13`ITi^,17d. 3Fii'3:3 DESCRIPTION 1 G86X475M 1275M IN SERIES CONNECTED DEVICE SOLAR EDGE MOO CONNECTEDDEVICETYPE POWER OPTIMNER DESIGNLOWTEMP. O-C DESIGN HIGH TEMPT 33'C MODULE C56K-275M 275 MODULE VMP SIN MODULE VOC M13V POWER OPTIMIZER MIN. INPUT VOLTAGE BY POWER OPTIMIZER MAX. INPUT VOLTAGE 48V MOUNTINGMETHOD ITILTEDROOFMOUNT TEMP. COEFFICIENTVOC -0.59VIC VOLTAGE LOSS WETO DEGRADATION OERATE GO VOLTAGE LOSS DUE TO TOLERANCEDERATE O.G CMmietlone A. STRING VOC AT LOW 41.27V TEMPERATURE THE MOWLE VOC (38.3V) WILL INCREASE TO 41.2NAT THE DESIGN LOW TEMPERATURE O-G). (0-0 - 25-0) X -0.119VIC + 3 S 3V = 41 XV THE TOTAL VOC FOR THE STRING 15412M 412NX i =41.27V B.STRING VMP AT HIGH 26.75V TEMPERA ESTIMATED CELL TEMPERATURE EQUALS THE DESIGN HIGH TEMPERATURE(33-C) PLUS SOT (THE ESTIMATED DIFFERENCE BETWEEN AMBIENT TEMPERATURES AND THE CELL TEMPERATURE FOR A ROOF MOUNT WITH TILT). 33-C+N-C=WC THE MODULE VMP (31.3V) WILL DROP TO 28.78V AT THE DESIGN HIGH TEMPERATURE M3'CL (63-C - 25-C) X -0.11 O VIC I SIN = 28.76V THE TOTAL VMP FOR THE STRING IS 26.78V. 28.78V X 1=28.78V 7+.w+a+IW,reearsawoary,rmw- VAUDATIONTESTS THE MINIMUM VMP MUST EXCEED THE PASS MINIMUM INPUT VOLTAGE OF THE CONNECTED DEVICE 26.78V, 8V=TRUE THE MAXIMUM VOC MUST NOT EXCEED THE PASS MAX INPUT VOLTAGE OF THE CONNECTED DEVICE 41.27V�48V=TRUE 2. NEC CODE COMPLIANCE REPORT XL1. MAXIMUM SYSTEM VOLTAGE TEST 2.1.1. SOLAR EDGE INVERTER INW CANADIAN SOLAR CBSK475M (275W)S ARRAY PROPERTIES ARRAYTYPE DISTRIBUTEDMPPTSYSTEM 1NVERTERARRAY SYSTEM DESCRIPTION SOLAR EDGE INVERTER WR7 CANADIAN SOLAR CSSK-ZMM 27M S MODULE CM-275M 275 HIGHEST NUMBER OF MODULES 1 INSERIESINANSOURCE CIRCUIT DESIGNLOWTEMP. 0•C MODULEVOC S8.3V TEMP. COEFFICIENT VOC -0.119VIC NECCo86CaI IRBwo A. MAXIMUM VOLTAGE OF PV 41.27V SOURCE CIRCUIT NEC ARTICLE 690] REQUIRES T R4T IF T HE FV MODULE MANUFACTURER PROWDES AWMPERATURE COEFHCIEW OF OPEN -CIRCUIT VOLTAGE, IT MUST BE USED TOCALCULATE THE PV ARRAYS MAXIMUM SYSTEM VOLTAGE. IT INCLUDES AN INFORMATION NOTE RECOMMENDING ME USE OF NE ASHRAE 'EXTREME ANNUAL MEAN MINIMUM DESIGN DRY BULB TEMPERATURE AS THE DESIGN LOW TEMPERATURE. USING THESE VALUES, THE MODULE VOC(38.3V) WILL INCREASE TO 41.2N AT THE DESIGN LOW TEMPERATURE (O-Q. (0•C-25•C) X-0.119VIC+3S.3V- 412TV TH E TOTAL VOC FOR THE STRING IS 41.2N. 41.27VX 1=41.2N B. MAXIMUM VOLTAGE OF DC OUTPUT 350V CIRCUIT NEC ARTICLE 690.T(B) REQUIRES THAT ALL PV CIRCUITS HAVE A VOLTAGE THAT DOES NOT EXCEED B W V. THIS SYSTEM DC OUTPUT CIRCUITS ARE FED BY SOLAR EDGE MOO DPTOCC CONVERTER OPTIMIZATION DEVICES. EACH DEVICE IS CONNECTED TO A SINGLE CS8K-275M (275W) PV MODULE. THE VOLTAGE OF THIS CIRCUIT IS REGULATED BY THE INVERTER AT A CONSTANT 33K NEC CODE VAUDATIDN TESTS PV SOURCE CIRCUIT MAXIMUM VOC MUST PASS NOT EXCEED 600V 412N,OMV=TRUE DC OUTPUT CIRCUIT VOLTAGE MUST NOT PASS EXCEED 600V 35OV<BOOV=TRUE CONTRACTOR VINYASUN CORP PHONE: 6614409515 ADDRESS: 313 DATURA STREET SURE 101 WEST PALM BEACH,FLORI DA 33401 UCNO: CV056957 HIC. NO.: ELE NO.: uN4uDKn®La mwm mmNo SJOmmourwF PEPMSSIONFH061CprtXhCrONISIN VXXATONOFUACC WTIAWS ANOAS,SESLMSETDCML UW.WGES INC FflOSECIliNM15. NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM OR FORT PIERCE, FL 34982 APN:340261005290000 ��' FYX��MFFILI.'11}-NIGNEPB U L C56967 0 Q — of R bfWE UMENT DATE: 4.1020V DESIGN BY: D.T. CHECKEDBY: M.M. REMSIONS R-008.00 (sxEEr,R 22. WIRE, CONDUIT, AND OCPD CODE COMPLIANCE VALIDATION 22.1. 1: DC CIRCUITCIRCUIT: SERIES STRING OUTPUTTO INVERTER CONDUCTOR 12AWG PV WIRE COPPER EQUIPMENTGROUND CONDUCTOR EGC 6 AWG BARE, COPPER OCP[XSj NIA RACEWAY TREE AIR LOWEST TERMINAL %MPERATURERARNG 751C MAXIMUM WIRE TEMPERATURE 55-C POWER SOURCE DESCRIPTION STRING OF 14 SOLAR EDGE Pam POWER OPTIMIZERS, EACH CONNECTED TO A CS6K-275M (275M PV MODULE CURRENT 15A VOLTAGE 350V MODULE SERIES FUSE RATING 15A TOTAL NUMBER OF SERIES STRINGS 2 NEC CC* C*MIO fi A. CONTINUOUS CURRENT 15A THE CONTINUOUS CURRENT OF THIS SERIES STRING OF POWER OPTIMIZERS 15 EQUAL TO THE RATED MAXIMUM OUTPUT CURRENT OF THE OPTIMIZER. RATED MAX OUTPUT CURRENT OF OPTIMIZER IS 15A B. BASE AMPACITY 40A BASE AMPACRY(M) FORA COPPER CONDUCTOR WITH WC INSULATION IN FREE AIR IS 40A C. CONDITIONS OF USE AMPACITY 30AA THE TEMPERATURE FACTOR FOR WO INSULATION AT XVC IS 0.76. THE FILL FACTOR FOR CONDUCTORS IN FREE AIR IS 1. THE AMPACITY DEMTED FOR CONDITIONS OF USE IS THE PRODUCT OF THE BASE AMPACITY (40A) MULTIPLIED BY THE TEM PERATURE FACTOR (0A6) AND BY THE CONDUIT FILL FAOTORD), 40A X D.76 Xi=30.4A D. AMPACITY AT TERMINAL RATING 35A THE LOWEST TERMINAL TEMPERATURE MTINO FOR THIS SEGMENTIS75°C. THE BASE AMPACITY OF THIS CONDUCTOR AT 75°C IS 35A. E. MINIMUM REQUIRED EGC SIZE 12 AWG THE SMALLEST EGC SIZE ALLOWED BY TABLE 250.122IS 12 AWG R{ Ngvla atSdaAesgnTOd NEC CODE VADDATION TESTS SYSTEM MUST MEET REQUIREMENTS FOR PASS NOT HAVING SERIES FUSE CONDITIONS OF USE AMPACITY MUST BE PASS GREATER THAN OR EQUAL TO THE CONTINUOUS CURRENT 304A>=16A=TRUE BASEAMPACITY MUST BEAT LEAST 125%OF PASS CONTINUOUS CURRENT 40A> 16.75A=TRUE . BASE CONDUCTOR AMPAUTY ATTHE PASS TERMINAL TEMPERATURE RATING MUST EXCEED 125%OF THE CONTINUOUS CURRENT. 35A>=15AX1.25 =TRUE EGCMUSTMEETNECREQUIREMENTS FOR PASS MINIMUM SIZE 6AWG>=12 AWG=TRUE EGC MUST MEET NEC REQUIREMENTS FOR PASS PHYSICAL PROTECTION BAWG>=BAWG=TRUE 22.2. 02: INVERTER OUTPUT: INVERTER TO UTILITY DISCONNECT CIRCURSEDDON PROPERTIES CONDUCTOR BAWG THWN2 COPPER EQUIPMENT GROUND CONDUCTOR EGC 6 AWG THWN2, COPPER OCP S 40A RACEWAY CITY DIA. EMT LOWESTTERMINAL TEMPERATURE RATING 75°C MAXIMUM WIRE TEMPERATURE 33°C POWER SOURCE DESCRIPTION SOUR EDGE SET6WA41S 836OW INVERTER CURRENT 32A VOLTAGE 240V INVERTER MAX OCPD RATING 40A NEC CodeCakuWma A. CONTINUOUS CURRENT 32A EQUIPMENT MAXIMUM RATED OUTPUT CURRENT IS i X 30A=32A B. BASE AMPACITY 55A BASE AMPACITY (30-C) FOR A COPPER CONDUCTOR WITH WC INSULATION IN CONDUIT IS SM. C. CONDITIONS OF USE AMPACITY 52.8A THE TEMPERATURE FACTOR FOR WC INSULATION AT 3M IS OBE. THE FILL FACTOR FOR A CONDUIT THAT RAS 2 WIRES IS 1. THE AMPACITY DEBATED FOR CONDITIONS OF USE IS THE PROD LOT OF THE BASE AMPACIT Y (SSA) MULTIPLIED BY THE TEMPERATURE FACTOR (ON) AND BY THE CONDUIT FILL FACTOR (1). SSA X 0.0X 1=528A D. AMPACITY AT TERMINAL RATING 50A THE LOWEST TERMINAL TEMPERATURE RATING FOR THIS SEGMENT IS 75-C, THE BASE AMPACITY OF THIS CONDUCTOR AT 75°C IS 50A E. MINIMUM ALLOWED OCPD RATING 40A NEC CODE REQUIRES THAT THE OCPD BE RATED FOR NO LESS THAN 125 TIMES THE CONTINUOUS CURRENT OF THE CIRCUIT. 32AX1.25=40A F. MINIMUM REQUIRED EGC SIZE 10 AWG THE SMALLEST EGC SME ALLOWED BY TABLE 250.1221E 10 AWG G. MINIMUM RECOMMENDED 0.75°dia. CONDUIT SIZE THE TOTAL AREA OF ALL CONDUCTORS IS 0.1451 N'. WITH A MAXIMUM FILL RATE OF 0.A THE RECOMMENDED CONDUIT DIAMETER IS 0]5. OT Y DESCRIPTION SIZE TYPE AREA TOTAL AREA 2 CONDUCTOR BAWG THW14.2 a.W531N' 007VIN, I NEUTRAL 10 AWO Tm4&2 OM111N' aD2111N' 1 EQUIPMENT GROUND BAWG THWN3 005D11N' 0AMRIf 0.1451N' 0.1451N'10.4= 0.36251N'(CORRESPONDING TO A DIAMETER OF 0.75') NEC CODE VALIDATION TESTS OCPD RATING MUST BE AT LEAST 125%OF PASS CONTINUOUS CURRENT 40A>=32A%1.25=TRUE CONDITIONS OF USE AMPACITY MUST BE PASS GREATER THAN OCPD RATING.OR RATING OF NEXT SMALLER OCPD 52BA>=40A(OCPD RATING) =TRUE CONDITIONS OF USE AMPACITY MUST BE PASB GREATER THAN OR EQUAL TO THE CONTINUOUS CURRENT 52.BA>=32A=TRUE BASE AMPACITY MUST BE AT LEAST 125%OF PASS CONTINUOUS CURRENT SSA>40A=TRUE BASE CONDUCTOR AMPACRY AT THE PASS TERMINAL TEMPERATURE RATING MUST EXCEED 125%OF THE CONTINUOUS CURRENT. 50A>=32AX 1.25 =TRUE EGC MUST MEET NEC REQUIREMENTS FOR PASB MINIMUM SIZE 6AWG>=10AWG=TRUE CONDUIT MUST MEET NEC PASS RECOMMENDATION FOR MINIMUM SIZE 0.]51N.>=0.]51N. =TRUE CONTRACTOR AWASUN CORP PHONE: 5614409515 ADDRESS: 313 DATURA STREET SUITE 101 WEST PALM BEACKFLORIDA 33401 LIC.NQ: CVC56S67 BIG NO.: ELE NO.: URAUIHORIZED USE OF TN I9 MMOSETWDHOUTWRrtFcN PWI PNF CmIMCTIXII6W WXAMN OP U.S. COPYMGHT IAWB AND W U-BE SUSJELT TO GML OMNOES AND PTNBEGJTIONS. NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 . II II I I . . DATE: 4.102017 DESIGN BY: D.T. CHECNEDBY: M.M. REVISIONS R-009.00 (6NEETIN i i 225. ft. UTILITY DISCONNECT OUTPUT: UTILITY DISCONNECT TO CIRCUIT SECTION PROPERTIES CONDUCTOR 6AWGTHWN-2 COPPER EQUIPMENTGROUND CONDUCTOREGO) 6AWGTHWN-2, COPPER OCPD S 40A RACEWAY 0.75'DIA. EMT LOWESTTERMINAL TEMPERATURE RATING 75°C MAXIMUM WIRETEMPERATURE 33'C POWER SOURCE DESCRIPTION SOLAR EDGE SE760DA-US 835OW INVERTER CURRENT 32A VOLTAGE 240V NEC CockCekuMlow A. CONTINUOUS CURRENT 32A EQUIPMENT MAXIMUM RATED OUTPUT CURRENT IS 1 X 30A= 32A B. BASE AMPACITY 75A BASE AMPACITY (30.0) FOR ACOPPER CONDUCTOR WITH 9)'C INSULATION IN CONDUIT IS 75A C. CONDITIONS OF USE AMPACITY 72A THE TEMPERATURE FACTOR FOR 90'C INSULATION AT 33=C IS 0.96. THE FILL FACTOR FORA CONDUIT THAT HAS 2 WIRES IS 1. THE AMPACITY DERATED FOR CONDITIONS OF USE 118 THE PRODUCT OF THE BASE AMPACITY (75A) MULTIPLIED BY THE TEMPERATURE FACTOR (0.96) AND BY THE CONDUIT FILL FACTOR (1). 75AX 0.96X I.72A D.AMPACITY ATTERMINALRATING 65A THE LOWEST TERMINAL TEMPERATURE RATING FOR THIS SEGMENT IS 75°C. THE BASE AMPACITY OF THIS CONDUCTOR AT 7VC IS 65A, ------------ E. MINIMUM ALLOWED OCPD RATING 4 AA NEC CODE REQUIRES THAT THE OCPO BE RATED FOR NO LESS THAN 1.25 TIMES THE CONTINUOUS CURRENT OF THE CIRCUIT. 32A X 1.25=40A F. MINIMUM REQUIRED EGC SIZE 8 AWG WHERE CONDUCTORS ARE OVERSIZED, THE EGO MUST BE OVERSIZED BY THE SAME RATE. TABLE 260,122, GIVES A MINIMUM EGC SIZE OF 10 AWG. MULTIPLIED BY THE OVERSIZE RATE, THIS YIELDS 16.49735KCMIL CORRESPONDING TO BAWG. (2624KCMIL 116.51 KCMIL) X 10.38KCMIL=16.49735KCMIL RepafSenereWKSd ,DWTa .. G. MINIMUM RECOMMENDED 0.75" dla. CONDUIT SIZE THE TOTAL AREA OF ALL CONDUCTORS IS 0.18B71N'. WITH A MAXIMUM FILL RATE OF 0.4, THE RECOMMENDED CONDUIT DIAMETERIS0.75. OT DESCRIPTION 012E TYPE AREA TOTAL AREA 2 CONDUCTOR BAWG iHWN2 0.05071N' 0.1D1411f 1 NEUTRAL BAWG iHWN-2 0.11MIN' 0.03661W 1 EQUIPMENT GROUND 6AWG THWN-2 0.05071W 0.05071NI 4 0.10071W 0.18871NN 0.4= 0A7101W (CORRESPONDING TO DIAMETER OF 0.7V) NEC OCPD RATING MUST BEAT LEAST 125%OF PASS CONTINUOUS CURRENT 400=32AX 125=TRUE CONDITIONS OF USE AMPACITY MUST BE PASS GREATER THAN OCPD RATING, OR RATING OF NEXT SMALLER OCPD 72A>= 40A(DCPD RATING) =TRUE CONDITIONS OF USE AMPACITY MUST BE PASS GREATER THAN OR EQUAL TO THE CONTINUOUS CURRENT 72A >= 32A = TRUE BASE AMPACITY MUST BE AT LEAST 125%OF PASS CONTINUOUS CURRENT 76A>40A=TRUE BASE CONDUCTOR AMPACITY AT THE PASS TERMINAL TEMPERATURE RATING MUST EXCEED 1251%OF THE CONTINUOUS CURRENT. 65A>=32AX 1.25 =TRUE F EGG MUST MEET NEC REQUIREMENTS FOR PASS MINIMUM SIZE 6 AWG>= 10 AWG = TRUE CONDUIT MUST MEET NEC PASS RECOMMENDATION FOR MINIMUM SIZE 0.751 N. >= 0.751N. = TRUE IV vinyasun CONTRACTOR VNYASUNCORP PHONE: 56144005% ADDRESS: 313 DATURASTREETSURE 101 NEST PALM BEACH,FLORIDA 33401 UC.NO.: CVCH987 HIC.NO.: ELE. NO.: UWWI IZWWEa Vl$ WMNGSEFW OUTMITF pFP Nl0NFIWMWNMCi IBW VICIAToN0FU3.f IMTIAWS MDWUBE SU9IECTTOCML 6 E5MDIWXKUIICNS. NEW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 ` >:--PFpx RD _ ;u : C 56967 L0 V — LO. •• ate•: fay , ` sr' / o`er' I. l fc D CUMENT l )11) DATE: 4.10.2017 DESIGN BY: D.T. CHECKED BY: M.M. RENSIONS R-010.00 u ISINET m) A B C D E F G H I 4R DARE 135893 1952EPHR AVCHAWAXD, CA 94944 PITCHED ROOF Project Details NAME 135893 DATE 2017-04-10 LOCATION Fort Pierce, FL, 34982 TOTAL MODULES 27 MODULE Canadian Solar:CS6K-275M(40mm) TOTAL WATTS 7,425 DIMENSIONS 65.0"x39.1"x 1.6"(1 m m x 992mm x 40mm) ATTACHMENT PIS 48 Load Assumptions Building Details WIND EXPOSURE C ROOF SLOPE 15 deg I WIND SPEED 160 mph BUILDING HEIGHT 15ft GROUND SNOW LOAD 0 psf RISK CATEGORY II ATTACHMENT SPACING 4.0ft Engineering 1 XR100 SPAN DETAILS MAXIMUM REACTION FORCES Roof Zone Down Uplift Lateral 1 217.00-313.00 9.00 2 218.00-608.00 9.00 — =m 3 213.00-921.00 9.00 to s System Weight TOTAL WEIGHT 12361bs WEIGHT/ATTACHMENT 25.8 Ibs DISTRIBUTED WEIGHT 2.6 psf RACKING WEIGHT 153.4lbs i A R C D E F G H Max Span Max Cantilever CONTRACTOR VINYASUN CORP 'NONE; 5614409616 NDRES9: 313 DATURA STREET SURE 101 WEST PALM BEACH,FLORIDA 33401 LIC.NO.: CVC50961 HIC.NO.: ELE NO.: UxWfXM.WE0 vz 0anvnxOSErvmxourwxmei Paaxusiu+PXaa+c9xmxcax i6 ix of oulwn aP u.s. coPms'rt uwa XN9 ESMDUNEET DNL DIAUpE80.NU PRPSEgIfIUXB. 1EW PV SYSTEM: 7.425 kWp FITZNER RESIDENCE 6103 BALSAM DR FORT PIERCE, FL 34982 APN:340261005290000 111uuIT11Y// >a1N>: • rs'st�N�w ALL, TD � VC56967 s b �`tr f� rdfe of RESOb6MENT DATE: 4.101017 DESIGNSY; D.T. CHECNEDBY: M.M. REVISIONS R-011.00 laxaarnl