RESPONSE TO COMMENTS INSPECTION (REFERENCE TO 1 /11 /2021) INSP. ID.237
PERMIT #
FBC107. 4 POST TO CONCRETE AND POST TO BEAM ATTACHMENT NOT PER PLAN. MISSING
DOUBLE JOISTS AT FAN LOCATIONS AND HUS210—2 HANGERS, MISSING HUS210—4 CONCEALED
FLANGE HANGERS. FRONT BEAM IS NOT CONNECTED TOGETHER PER THE PLAN, A LETTER
FROM THE ENGINEER APPROVING THIS ATTACHMENT.
BALCONY DECK ...............ONE LAYER 1X6 VJOINT AND ONE LAYER 3/4" CDX IS INSTALLED. PLAN
CALLS FOR 2 LAYERS CDX, LETTER FROM ENGINEER REQUIRED TO ELIMINATE ONE LAYER CDX.
LETTER OF RESPONSE TO USE COMPATIBLE AND COMPARABLE SIMPSON STRONG -TIE JOIST
HANGERS, IN REFERENCE TO THE HANGERS THAT WERE INSTALLED ARE EQUAL AND AS GOOD
AS WHAT WAS SPECIFIED ON THE DRAWING.
THE REPLACED ITEMS USED ARE AS NOTED: FOR THE POST CAP
THE REPLACED ITEM USED IS BC6Z- R - PRODUCT APPROVAL FL#10860.5 FOR THE POST BASE
THE REPLACED ITEM USED IS ABA66Z - PRODUCT APPROVAL FL#10860.1 FOR THE JOIST
HANGERS
THE REPLACED ITEM USED IS LUS21OZ- PRODUCT APPROVAL FL#10531.16
THE DOUBLE JOIST AT FAN IS NOT NEEDED, AFTER ADJUSTNG THE FAN
LOCATION THE DOUBLE JOIST WAS ELIMINATED. IT HAS NO EFFECT TO THE STRUCTURE.
THE CONCEALED FLANGE HANGERS WERE REPLACED WITH LUS21O FLANGE HANGERS. NO
EFFECT TO THE STRUCTURE.
BALCONY DECK CALLS FOR 2 LAYERS OF CDX. AFTER INSTALLING ONE LAYER 3/4“CDX WITH
WATERPROOF MEMBRANE, THE SECOND LAYER CDX WAS NOT NEEDED.
THANK YOU
ENGINEER OF RECORD
JOSEPH SIMMONS, III, P.E.
FL P.E. # 52101