HomeMy WebLinkAboutCOMMENT LETTER2/1/2021 RESPONSE TO COMMENTS INSPECTION (REFERENCE TO 1 /11 /2021) INSP. ID.237 PERMIT # FBC107. 4 POST TO CONCRETE AND POST TO BEAM ATTACHMENT NOT PER PLAN. MISSING DOUBLE JOISTS AT FAN LOCATIONS AND HUS210—2 HANGERS, MISSING HUS210—4 CONCEALED FLANGE HANGERS. FRONT BEAM IS NOT CONNECTED TOGETHER PER THE PLAN, A LETTER FROM THE ENGINEER APPROVING THIS ATTACHMENT. BALCONY DECK ...............ONE LAYER 1X6 VJOINT AND ONE LAYER 3/4" CDX IS INSTALLED. PLAN CALLS FOR 2 LAYERS CDX, LETTER FROM ENGINEER REQUIRED TO ELIMINATE ONE LAYER CDX. LETTER OF RESPONSE TO USE COMPATIBLE AND COMPARABLE SIMPSON STRONG -TIE JOIST HANGERS, IN REFERENCE TO THE HANGERS THAT WERE INSTALLED ARE EQUAL AND AS GOOD AS WHAT WAS SPECIFIED ON THE DRAWING. THE REPLACED ITEMS USED ARE AS NOTED: FOR THE POST CAP THE REPLACED ITEM USED IS BC6Z- R - PRODUCT APPROVAL FL#10860.5 FOR THE POST BASE THE REPLACED ITEM USED IS ABA66Z - PRODUCT APPROVAL FL#10860.1 FOR THE JOIST HANGERS THE REPLACED ITEM USED IS LUS21OZ- PRODUCT APPROVAL FL#10531.16 THE DOUBLE JOIST AT FAN IS NOT NEEDED, AFTER ADJUSTNG THE FAN LOCATION THE DOUBLE JOIST WAS ELIMINATED. IT HAS NO EFFECT TO THE STRUCTURE. THE CONCEALED FLANGE HANGERS WERE REPLACED WITH LUS21O FLANGE HANGERS. NO EFFECT TO THE STRUCTURE. BALCONY DECK CALLS FOR 2 LAYERS OF CDX. AFTER INSTALLING ONE LAYER 3/4“CDX WITH WATERPROOF MEMBRANE, THE SECOND LAYER CDX WAS NOT NEEDED. THANK YOU ENGINEER OF RECORD JOSEPH SIMMONS, III, P.E. FL P.E. # 52101