HomeMy WebLinkAboutEnergy Calculation Form & Manual J's (2) FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 96
The lower the EnergyPerformance Index,the more efficient the home.
8280 GERMANY CANAL RD, PORT ST LUCIE, FL,
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=11.0 1728.00 ft2
b.N/A R= ft
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 4 d.NIA R= ft2
5. Is this a worst case? Yes 10.Ceiling Types Insulation Area a.Under Attic(Vented) R=33.0 2597.00 ft2
-6. Conditioned floor area(ft2) 2597 b.N/A R= ft2
7. Windows"* Description Area c.NIA R= ft2
a. U-Factor: Dbl,U=0.30 291.33 ft2 11.Ducts R ft2
SHGC: SHGC=0.29 a.Sup:Attic,Ret:Main,AH:Main 6 519.4
b. U-Factor: N/A ft2
SHGC: 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 60.0 SEER:15.00
SHGC:
d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency
SHGC: a.Electric Heat Pump 60.0 HSPF:8.70
Area Weighted Average Overhang Depth: 0.963 ft.
Area Weighted Average SHGC: 0.290
8. Floor Types Insulation Area 14.Hot water systems
a.Crawlspace R=11.0 2597.00 ft2 a. Electric Cap:50 gallons
EF:0.95
b.N/A R= ft2
c. N/A R= ft2 b. Conservation features
None
15.Credits CF,Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building �zKE STAT
Construction through the above energy saving features which will be installed (or exceeded) = Fo
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
o
Builder Signature: Date:
Address of New Home: _ -� - —,`— — City/FL Zip:
WE
*Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient
-mortgage (EEM)incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
5/11/2017 9:06 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
Residential System Sizing Calculation
Summary
CROUCH Project Title:
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL
5/11/2017
Location for weather data: Fort Pierce, FL -Defaults: Latitude(27.48) Altitude(25 ft.) Temp Range(L)
Humidity data: Interior RH 50% Outdoor wet bulb 7817 Humidity difference 62 r.
Winter design temperature(TMY3 99%) 40 F Summer design temperature(TMY3 99%) 91 F
Winter setpoint 70 F Summer setpoint 75 F
Winter temperature difference 30 F Summer temperature difference 16 F
Total heating load calculation 21337 Btuh Total cooling load calculation 34602 Btuh
Submitted heating capacity % of caic Btuh Submitted cooling capacity % of calc Btuh
Total (Electric Heat Pump) 281.2 60000 Sensible (SHR= 0.75) 179.1 45000
Heat Pump + Auxiliary(O.OkW) 281.2 60000 Latent 158.3 15000
Total Electric Heat Pump) 173.4 60000
WINTER CALCULATIONS
Winter Heating Load for 2597 s ft
Load component Load
Window total 291 sqft 2622 Btuh
Wall total 1377 sqft 3918 Btuh Walls(18.4%) Ceilings(10.6%)
Door total 60 sqft 630 Btuh
Ceiling total 2597 sqft 2265 Btuh W4ndows(12.3°/°)
Floor total 2597 sqft 4109 Btuh
Infiltration 103 cfm 3389 Btuh Floors(19.3%)
Duct loss 4404 Btuh
Subtotal 21337 Btuh , Ducts(20.6%)
Ventilation 0 cfm 0 Btuh Ooors(3.0%)
TOTAL HEAT LOSS 21337 Btuh Infil.(15.9%)
SUMMER CALCULATIONS
Summer Cooling Load for 2597 s ft
Load component Load
Window total 291 sqft 6748 Btuh
N Wall total 1377 sqft 3801 Btuh
Door total 60 sqft 651 Btuh
Ceiling total 2597 sqft 3397 Btuh ° Ceilings(9.8%)
Floor total 2202 Btuh Walls(11.0/o)
Infiltration 77 cfm 1356 Btuh Windows(19.5%)
Internal gain 2350 Btuh Floors(6.4%}
Duct gain 4625 Btuh Doors(1.9%)
Sens,Ventilation 0 cfm 0 Btuh
Blower Load 0 Btuh M.
Total sensible gain 25129 Btuh Infil.(13.3%) Latent int(12.7%)
Latent gain(ducts) 1825 Btuh
Latent gain(infiltration) 3248 Btuh Int.Gain{6.8°io}
Latent gain(ventilation) 0 Btuh Ducts(18.6%)
Latent gain(internal/occupants/other) 4400 Btuh
Total latent gain 9473 Btuh
TOTAL HEAT GAIN 34602 Btuh
EnergyGauge®System Sizing
8th Edition PREPARED BY: Gp
DATE: 5-11-17
EnergyGauge®/USRCZB v5.1
System Sizing Calculations - Winter
Residential Load - Whole House Component Details
CROUCH Project Title:
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL Building Type: User
5/11/2017
Reference City: Fort Pierce, FL (Defaults) Winter Temperature Difference: 30.0 F(TMY3 99%)
This calculation is for Worst Case.The house has been rotated 90 degrees.
Component Loads for Whole House
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
1 2, NFRC 0.29 Vinyl 0.30 E 17.5 9.0 158 Btuh
2 2, NFRC 0.29 Vinyl 0.30 E 60.0 9.0 540 Btuh
3 2, NFRC 0.29 Vinyl 0.30 E 15.0 9.0 135 Btuh
4 2, NFRC 0.29 Vinyl 0.30 W 87.5 9.0 788 Btuh
5 2, NFRC 0.29 Vinyl 0.30 W 40.0 9.0 360 Btuh
6 2, NFRC 0.29 Vinyl 0.30 W 15.0 9.0 135 Btuh
7 2, NFRC 0.29 Vinyl 0.30 W 15.0 9.0 135 Btuh
8 2, NFRC 0.29 Vinyl 0.30 N 30.0 9.0 270 Btuh
9 2, NFRC 0.29 Vinyl 0.30 N 7.5 9.0 68 Btuh
10 2, NFRC 0.29 Vinyl 0.30 N 3.8 9.0 34 Btuh
Window Total 291.3 s ft 2622 Btuh
Walls Type Ornt. Ueff. R-Value Area X HTM= Load
(Cav/Sh)
1 Frame-Wood - Ext (0.095) 11.0/0.0 355 2.85 1009 Btuh
2 Frame-Wood - Ext (0.095) 11.0/0.0 77 2.85 219 Btuh
3 Frame-Wood -Ext (0.095) 11.0/0.0 300 2.85 854 Btuh
4 Frame-Wood -Ext (0.095) 11.0/0.0 367 2.85 1043 Btuh
5 Frame-Wood - Ext (0.095) 11.0/0.0 279 2.85 793 Btuh
Wall Total 1377 s ft 3918 Btuh
Doors Type Storm Ueff. Area X HTM= Load
1 Wood - Exterior, n (0.350) 20 10.5 210 Btuh
2 Wood -Exterior, n (0.350) 20 10.5 210 Btuh
3 Insulated -Exterior, n (0.350) 20 10.5 210 Btuh
Door Total 60 s ft 63013tuh
Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load
1 Vented Attic/L/Shing (0.029) 33.0/0.0 2597 0.9 2265 Btuh
= .Ceiling Total 2597 s ft 226513tuh
Floors Type Ueff, R-Value Size X HTM= Load
1 Stem/Crawisp(Tile)(v) (0.075) 11.0/0.0 2597.0 sqft 1.6 4109 Btuh
Floor Total 2597 s ft 4109 Btuh
Envelope Subtotal: 13544 Btuh
Infiltration Type Wholehouse ACH Volume(cuft) Wall Ratio CFM=
Natural 0.30 20776 1.00 102.8 3389 Btuh
Duct load Average sealed, R6.0, Supply(Att), Return(Con) (DLM of 0.260) 4404 Btuh
All Zones Sensible Subtotal All Zones 21337 Btuh
EnergyGauge®/USRCZB v5.1 Page 1
Manual J Winter Calculations
Residential Load - Component [details (continued)
CROUCH Project Title:
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL Building Type: User
5/11/2017
HOLE.HOUSE TOTALS
I
Subtotal Sensible Heat Loss 21337 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 21337 Btuh
EQUIPMENT
1. Electric Heat Pump # 60000 Btuh
Key:Window types-NFRC(Requires U-Factor and Shading coefficient(SHGC)of glass as numerical values)
or-Glass as'Clear'or'Tint'(Uses U-Factor and SHGC defaults)
U-(Window U-Factor) ,
HTM-(ManualJ Heat Transfer Multiplier)
Version 8
EnergyGauge®/USRCZB v5.1 Page 2
System S"Min g Calculations - Summer
Residential Load - Whole House Component Details
CROUCH Project Title:
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL
5/11/2017
Reference City: Fort Pierce, FL Temperature Difference: 16.OF(TMY3 99%) Humidity difference: 62gr.
This calculation Is for Worst Case,The house has been rotated 90 degrees.
"s,f6r Whole,House.
Type* Overhang r--Window-Area-(-s-q-ft)---"'- HT _�Load
Window Panes SHGG U InSh IS Ornt Len Hgt Gross Shaded Unshade Shaded U'�ns�haded *_ -J
1 2 NFRC 0.29,0.30 B-L No E 0.5ft. 0.7ft. 17.5- 0.0 17.5 8 23 406 Btuh
2 2 NFRC 0.29,0.30 B-L No E 0.5ft. 0.7ft. 60,0 0.0 60.0 8 23 1391 Btuh
3 2 NFRC 0.29,0.30 B-L No E 9.5ft. 0.7ft. 15.0 15.0 0.0 8 23 116 Btuh
4 2 NFRC 0.29,0.30 B-L No W 0.5ft. 0.7ft. 87.5 0.0 87.5 8 23 2028 Btuh
5 2 NFRC 0.29,0.30 B-L No W 0.511. 0.7ft. 40.0 0.0 40.0 8 23 927 Btuh
6 12 NFRC 0.29,0.30 B-L No W 0.5ft. 0.7ft. 15.0 0.0 15.0 8 23 348 Btuh
7 2 NFRC 0.29.0.30 B-L No W 0.5ft. 0.7ft. 15.0 0.0 15.0 8 23 348 Btuh
8 2 NFRC 0.29,0.30 B-L No N 0.5ft. 3.Oft. 30.0 0.0 30.0 8 8 231 Btuh
9 2 NFRC 0.29,0.30 B-L No N 0.5ft. 3.Oft. 7.5 0.0 7.5 8 8 58 Btuh
10 2 NFRC 0.29,0.30 B-L No N 0.5ft. 2.Oft. 3.8 0.0 3.8 8 8 30 Btuh
Excursion 867 Btuh
Window Total 29�1 (sqft)_ 6748 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
I Frame-Wood-Ext 0.09 11.0/0.0 354.5 2.8 979 Btuh
2 Frame-Wood-Ext 0.09 11.0/0.0 77.0 2.8 213 Btuh
3 Frame-Wood-Ext 0.09 11.0/0.0 300.0 2.8 828 Btuh
4 Frame-Wood-Ext 0.09 11.0/0.0 366.5 2.8 1012 Btuh
5 Frame-Wood-Ext 0.09 11.0/0.0 278.7 2.8 769 Btuh
Wall Total 1377 (sqft) 3801 Btuh
Doors Type T Area (sqft) HTM Load
I Wood-Exterior 20.0 10.8 217 Btuh
2 Wood-Exterior 20.0 10.8 217 Btuh
3 Insulated-Exterior 20.0 10.8 217 Btuh
sq
____ Door Total 60 (sl
ft) 651 Btuh
Ceilings Type/Color/Surface U-Value R-Value Area(sqft) HTM V Load
I Vented Attic/Light/Shingle 0.029 33.0/0.0 2597.0 1.31 3397 Btuh
Ceiling Total 2597 (sqft) 3397 Btuh
Floors Type R-Value Size HTM Load
I Stem/Crawlsp(v) 11.0 2597(sqft) 0.8 2202 Btuh
Floor Total 2597.0 (sqft) 2202 Btuh
Envelope Subtotal: 16799 Btuh
Infiltration Type y Average ACH Volume(cuft)Wall Ratio CFM= Load
Natural 0.22 20776 1 77.1 1356 Btuh
Internal Occupants Btuh/occupant Appliance Load
-gain 5 X 230 + 1200 2350 Btuh Sensible Envelope Load: 20504 Btuh
EnergyGauge@/USRCZB v5.1 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
CROUCH Project Title: Climate:FL VERO_BEACH_MUNICIPAL_A
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL
5/11/2017
Duct load Average sealed,Supply(R6.0_Attic),Retum(R6.0-Condi) -_ (DGM of 0.226) 4625 StUh
Sensible Load All Zones 25129 Btuh
a
EnergyGauge®/USRCZB v5.1 Page 2
Manual J Summer Calculations
Residential Load - Component Details (continued)
CROUCH Project Title: Climate:FL VERO_BEACH_MUNICIPAL A
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL
5/11/2017
` WHOLE HOUSE TOTALS - -
Sensible Envelope Load All Zones 20504 Btuh
Sensible Duct Load 4625 Btuh
Total Sensible Zone Loads 25129 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 25129 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 3248 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 1825 Btuh
Latent occupant gain(5.0 people @ 200 Btuh per person) 1000 Btuh
Latent other gain 3400 Btuh
Latent total gain 9473 Btuh
TOTAL GAIN 34602 Btuh
EQUIPMENT
1. Central Unit # 60000 Btuh
'Key: Window types(Panes-Number and type of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value)
(U-Window U-Factor)
(InSh-Interior shading device:none(No),Blinds(B),Draperies(D)or Roller Shades(R))
- For Blinds:Assume medium color,half closed
For Draperies:Assume medium weave,half closed
For Roller shades:Assume translucent,half closed ,: w
(IS-Insect screen:none(N),Full(F)or Half(%)) "
(Omt-compass orientation)
Version 8
EnergyGaugeO/USRCZB v5.1 Page 3
System Sizing Calculations - Winter
Residential Load - Room by Room Component Details
CROUCH Project Title:
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL Building Type: User
5/11/2017
Reference City: Fort Pierce, FL (Defaults) Winter Temperature Difference: 30.0 F (TMY3 99%)
This calculation is for Worst Case.The house has been rotated 90 degrees.
Component Loads f®r Room#1 ;Main j �: f _
Window Panes/Type Frame U Orientation Area(sqft) X HTM= Load
1 2, NFRC 0.29 Vinyl 0.30 E 17.5 9.0 158 Btuh
2 2, NFRC 0.29 Vinyl 0.30 E 60.0 9.0 540 Btuh
3 2, NFRC 0.29 Vinyl 0.30 E 15.0 9.0 135 Btuh
4 2, NFRC 0.29 Vinyl 0.30 W 87.5 9.0 788 Btuh
5 2, NFRC 0.29 Vinyl 0.30 W 40.0 9.0 360 Btuh
6 2, NFRC 0.29 Vinyl 0.30 W 15.0 9.0 135 Btuh
7 2, NFRC 0.29 Vinyl 0.30 W 15.0 9.0 135 Btuh
8 2, NFRC 0.29 Vinyl 0.30 N 30.0 9.0 270 Btuh
9 2, NFRC 0.29 Vinyl 0.30 N 7.5 9.0 68 Btuh
10 2, NFRC 0.29 Vinyl 0.30 N 3.8 9.0 34 Btuh
Window Total 291.3(sqft) 2622 Btuh
Walls Type Ornt. Ueff. R-Value Area X HTM= Load
(Cav/Sh)
I Frame-Wood -Ext (0.095) 11.0/0.0 355 2.85 1009 Btuh
2 Frame-Wood -Ext (0.095) 11.0/0.0 77 2.85 219 Btuh
3 Frame-Wood -Ext (0.095) 11.0/0.0 300 2.85 854 Btuh
4 Frame-Wood -Ext (0.095) 11.0/0.0 367 2.85 1043 Btuh
5 Frame-Wood -Ext (0.096) 11.010.0 279 2.85 793 Btuh
Wall Total 1377(sqft) 3918 Btuh
Doors Type Storm Ueff. Area X HTM= Load
1 Wood- Exterior, n (0.350) 20 10.5 210 Btuh
2 Wood -Exterior, n (0.350) 20 10.5 210 Btuh
3 Insulated-Exterior, n (0.350) 20 10.5 210 Btuh
Door Total 60(sqft) 63013tuh
Callings Type/Color/Surface Ueff. R-Value Area X HTM= Load
I Vented Aftic/L/Shlng (0.029) 33.0/0.0 2597 0.9 2265 Btuh
CeilingTotal 2597(sqft) 226513tuh
Floors Type Ueff. R-Value Size X HTM= Load
1 Stem/Crawisp(Tile)(v) (0.075) 11.0/0.0 2597.0 sqft 1.6 4109 Btuh
Floor Total 2597 sqft 4109 Btuh
Room Envelope Subtotal: 13544 Btuh
Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM=
Natural 0.30 20776 1.00 102.8 3389 Btuh
Duct load Average sealed,Supply(RU-Attic),Retum(RU-Cond.) (DLM of 0.260) 4404 Btuh
Room#1 Sensible Room Subtotal 21337 Btuh
EnergyGauge@ USRCZB v5.1 Pagel
V
Manual J Summer Calculations
Residential Load - Component Details (continued)
CROUCH Project Title: Climate:FL_VERO_BEACH_MUNICIPAL A
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL
5/11/2017
w
.WHOLE.HOUSE TOTALS
Sensible Envelope Load All Zones 20504 Btuh
Sensible Duct Load 4625 Btuh
Total Sensible Zone Loads 25129 Btuh
Sensible ventilation 0 Btuh
y Blower 0 Btuh
Whole House Total sensible gain 25129 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 3248 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 1825 Btuh
Latent occupant gain(5.0 people @ 200 Btuh per person) 1000 Btuh
Latent other gain 3400 Btuh
Latent total gain 9473 Btuh
TOTAL GAIN 34602 Btuh
EQUIPMENT
1. Central Unit # 60000 Btuh
*Key: Window types(Panes-Number and type of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value)
(U-Window U-Factor)
(lnSh-Interior shading device:none(No),Blinds(B),Drapedes(D)or Roller Shades(R))
- For Blinds:Assume medium color,half closed
For Draperies:Assume medium weave,half closed
For Roller shades:Assume translucent,half closed
(IS-Insect screen:none(N),Full(F)or Half(%))
(Omt-compass orientation)
Version 8
EnergyGauge®/USRCZB v5.1 Page 3
Residential Window Diversity
MidSummer
CROUCH Project Title:
8280 GERMANY CANAL RD CROUCH
PORT ST LUCIE, FL
5/11/2017
W
Summer design temperature 91 F Average window load for July 2837 Btuh
Cooling setpoint 75 F Peak window load for July 4556 Btuh
Summer temperature difference 16 F Excusion limit(130%of Ave.) 3689 Btuh
Latitude 27.48 North Window excursion (July) 867 Btuh
WINDOW Average and Peak Loads
4,500
4,000
----------------------- ------------ -----------
3,500 IT
3,000
2,500
2,000 All
1,500
8 10 12 14 16 18 20
Window Load (Btull) Limit for excursion
12 Hour Average
Total July Window Load(Radiation and conduction)
This application has glass areas that produce large heat gains for part of the day. Variable air volume devices
are required to overcome spikes in solar gain for one or more rooms. Install a zoned system or provide zone
control for problem rooms. Single speed equipment may not be suitable for the application.
EnergyGauge@ System Sizing for Florida residences only
PREPARED BY: GANNON BQGGS III
DATE: 5-11-17
EnergyGauge@/USRCZ13 v5.1